Aprilaire 8465, 8466, 8463, 8448, 8446 Install Instructions

Page 1
8400 Series Thermostats
Safety &
Installation
Instructions
READ AND SAVE THESE INSTRUCTIONS
61000652D 8400 Tstat Install.indd 1 7/9/13 9:03 AM
Page 2
INSTALLATION
Installation location recommendations................................................................3
Outdoor temperature sensor (optional) ................................................................4
Thermostat mounting..............................................................................5
Power & reset options.............................................................................5
Wiring terminal ..................................................................................6
Wiring diagrams .................................................................................7
SETUP & TESTING
System setup instructions .........................................................................11
System test mode ...............................................................................16
REFERENCES
Quick reference to controls & display
 •Non-programmablemodels(8444,8446,8448).....................................................22
 •Programmablemodels(8463,8465,8466).........................................................23
Thermostat features .............................................................................24
Troubleshooting .................................................................................25
Specifications...................................................................................27
2
61000652D 8400 Tstat Install.indd 2 7/9/13 9:03 AM
Page 3
INSTALLATION
INSTALLATION LOCATION RECOMMENDATIONS
Thermostat should be mounted:
•Onaninteriorwall,inafrequentlyoccupiedspace.
•Approximately5‘abovefloor.
•Atleast18”fromoutsidewall.
•Thermostatcanbemountedtoaverticaljunctionbox.
Do not mount thermostat:
•Behinddoors,incorners,orotherdeadairspaces.
•Indirectsunlight,nearlightingfixtures,orother appliancesthatgiveoffheat.
•Onanoutsideorunconditionedareawall.
•Intheflowofasupplyregister,instairwells,ornear
outside doors.
•Onawallwithconcealedpipesorductwork.
3
61000652D 8400 Tstat Install.indd 3 7/9/13 9:03 AM
Page 4
INSTALLATION
OUTDOOR TEMPERATURE SENSOR (OPTIONAL)
Outdoortemperaturecanbemeasuredbyattachingan 8052sensortotheS1andS2terminals.Systemsetting #05(Remotesensor)isusedtoenablesensor.
Heat pump models can use the outdoor temperature to
effectivelyutilizetheheatpump:
•WhentheoutdoortemperatureislessthantheLow BalancePoint,theheatpumpwillbelockedoutand onlyauxiliaryheatingwillbeused.
•WhentheoutdoortemperatureishigherthantheHigh BalancePoint,theauxiliaryheatingwillbelockedout andonlytheheatpumpwillbeusedtoprovideheating.
4
•Installonsideofbuildingoutofdirectsunlight (north side recommended).
•Mountabovesnowline.
•Mountatleast3’awayfromexhaustventsand
condensing lines.
•Maximumwirelengthis300’.
•Donotroutewiresalong120VAClines.
G
S1
C
RC
W
Y
R
S2
L
W2
O/B
Y2
61000652D 8400 Tstat Install.indd 4 7/9/13 9:03 AM
Page 5
INSTALLATION
THERMOSTAT MOUNTING
1.Removethebackofthethermostat,bypressingthe tabonthebottomoftheunit.
2.Pullwiresthroughtheopeningonthebackofthe
thermostat.
3.Positionandlevelthebackofthethermostatonwall
and mark the hole locations with a pencil.
4.Drill1/4”holes&insertsuppliedanchors(drywallonly).
5.Placebackoveranchors,insertandtightenscrews.
6.Sealwireentryholestopreventdraftsaffecting
temperature readings.
61000652D 8400 Tstat Install.indd 5 7/9/13 9:03 AM
POWER & RESET OPTIONS
Thethermostatisdualpower.ItcaneitherbeACor batterypowered,orboth(toprovidebackuppowerfor theclock).Batteriesareoptionalifthethermostatwas connectedtoACpowerwheninstalled.
Forheatpumpmodels(8446and8465)anduniversal models(8448and8466)usedinheatpumpapplications 24VACmustbeconnectedinorderforthesystemfault
and emergency heat indicators to operate.
Thethermostathasamemorybackupthatsavesthe thermostat’ssettingsincaseofapowerinterruption.
Theresetbuttonlocatedunderthebatterycovercanbe usedtoresetthethermostatbacktofactorydefaults. Thesystemsettingswillalsoberesetbacktodefaults.
5
Page 6
INSTALLATION
WIRING TERMINAL
Wire specifications
18-24gaugethermostatwire
Installation notes
•EnsurepowerattheHVACequipmentisoff.
•Loosenscrewterminals,insertstrippedwire andre-tighten.
•Pushtheexcesswirebackintotheopening andplugthewallopeningtopreventdrafts.
RC
R
6
RC–24VACsupplycooling* R–24VACsupplyheating* W–1ststageheat/auxiliary Y–1ststagecooling/compressor G – Fan C–RC24VACcommon(optionalwhenpoweredbybatteries) S1 & S2 – outdoor temperature sensor (optional) O/B–Reversingvalve L – System fault indicator W2–2ndstageheat/auxiliary Y2–2ndstagecooling/compressor
* Jumper between RC & R is used in single transformer systems
(see wiring diagrams).
G
S1
C
W
Y
S2
O/B
Y2
L
W2
61000652D 8400 Tstat Install.indd 6 7/9/13 9:03 AM
Page 7
INSTALLATION
TRANSFORMER
TRANSFORMER
COOLING
WIRING – MODEL 8463 & 8444 SINGLE TRANSFORMER (USE JUMPER WIRE)
FAN
HEATING
COOLING
RC
JUMPER
R
G
W
Y
61000652D 8400 Tstat Install.indd 7 7/9/13 9:03 AM
S1
C
SENSOR
OUTDOOR TEMP
S2
WIRING – MODEL 8463 & 8444 TWO TRANSFORMERS (REMOVE JUMPER WIRE)
HEATING
TRANSFORMER
FAN
HEATING
COOLING
G
RC
W
R
C
Y
SENSOR
OUTDOOR TEMP
S1
S2
7
Page 8
INSTALLATION
TRANSFORMER
HEAT PUMP
WIRING – MODEL 8465 & 8446 SINGLE TRANSFORMER (USE JUMPER WIRE)
RC
JUMPER
W
R
AUX HEATING
COMPRESSOR
G
Y
FAN
S1
C
SENSOR
OUTDOOR TEMP
S2
O/B
REVERSE VALVE
FAULT DETECT
L
WIRING – MODEL 8465 & 8446 TWO TRANSFORMERS (REMOVE JUMPER WIRE)
AUX HEATING
TRANSFORMER
TRANSFORMER
FAN
AUX HEATING
COMPRESSOR
G
S1
RC
W
R
C
Y
8
61000652D 8400 Tstat Install.indd 8 7/9/13 9:03 AM
SENSOR
OUTDOOR TEMP
REVERSE VALVE
S2
L
O/B
FAULT DETECT
Page 9
INSTALLATION
TRANSFORMER
HEATING
COOLING
WIRING – MODEL 8466 & 8448 SINGLE TRANSFORMER (USE JUMPER WIRE) FOR HEAT/COOL SYSTEM
FAN
1st HEATING
JUMPER
R
W
1st COOLING
G
Y
61000652D 8400 Tstat Install.indd 9 7/9/13 9:03 AM
RC
S1
C
SENSOR
OUTDOOR TEMP
NOT USED
S2
L
O/B
2nd HEATING
NOT USED
W2
Y2
WIRING – MODEL 8466 & 8448 TWO TRANSFORMERS (REMOVE JUMPER WIRE) FOR HEAT/COOL SYSTEM
TRANSFORMER
FAN
2nd COOLING
TRANSFORMER
RC
1st HEATING
1st COOLING
G
W
Y
R
S1
C
SENSOR
OUTDOOR TEMP
S2
O/B
NOT USED
NOT USED
L
2nd HEATING
W2
2nd COOLING
Y2
9
Page 10
INSTALLATION
HEAT PUMP
HEATING
HEAT PUMP
WIRING – MODEL 8466 & 8448 SINGLE TRANSFORMER (USE JUMPER WIRE) FOR HEAT PUMP SYSTEM
TRANSFORMER
RC
JUMPER
W
R
FAN
1st AUX HEATING
1st COMPRESSOR
G
Y
S1
C
SENSOR
OUTDOOR TEMP
REVERSE VALVE
S2
O/B
FAULT DETECT
L
W2
2nd AUX HEATING
Y2
WIRING – MODEL 8466 & 8448 TWO TRANSFORMERS (REMOVE JUMPER WIRE) FOR HEAT PUMP SYSTEM
TRANSFORMER
TRANSFORMER
FAN
1st AUX HEATING
R
1st COMPRESSOR
W
Y
G
2nd COMPRESSOR
RC
SENSOR
OUTDOOR TEMP
S1
C
S2
O/B
10
61000652D 8400 Tstat Install.indd 10 7/9/13 9:03 AM
REVERSE VALVE
FAULT DETECT
L
W2
2nd AUX HEATING
2nd COMPRESSOR
Y2
Page 11
SETUP & TESTING
SYSTEM SETUP INSTRUCTIONS
Thefollowinginstructionsshowhowtoenterthesystemsetupmenuandchangesettings.Thetableonthe followingpagesliststhesettingsandtheirdetails.Defaultsettingsareshowninbold. Some settings are only availabletocertainmodels,andsomearespecifictothermostatssettoheatpumpmode.
How to enter the system setup menu to change system settings
Press
Press and hold
repeatedly until system is set to OFF.
and for three seconds.
Thescreenofthefirstsettingwillbedisplayed.
Press or to change the setting.
Press
Press
tochangetothenextoption.
afterthelastsetting.“DONE”willbe
displayed.
ThethermostatwillsavechangesandreturntoNormal modeifnokeyispressedfor20seconds.
Toresetallsystemsettingsbacktodefault,pressthe RESETbuttonlocatedunderthebatterydoor.
SETTINGVALUE
SYSTEMSETTINGNUMBER
11
61000652D 8400 Tstat Install.indd 11 7/9/13 9:03 AM
Page 12
SETUP & TESTING
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
Thermostatmodels8448&8466havetheoptionofbeingusedinheatpumporheat/coolsystems.Theequipment typeswitchlocatedonthebackofthethermostat’sfaceisusedtoselectthis.Systemsettingnumber00willonlybe shownonthesemodelstodisplaythepositionoftheequipmenttypeswitch.
EQUIPMENT
TYPE SWITCH
HEATPUMP HEAT/COOL
12
61000652D 8400 Tstat Install.indd 12 7/9/13 9:03 AM
Page 13
SETUP & TESTING
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
System setting Setting range, default in bold
00Equipmenttype(8466,8448)
(Set by the equipment type switch)
01 Temperature scale
02Heat/Cool:Fancontrolinheating
HeatPump:Auxiliaryequipmenttype
03 Offset temperature for internal sensor
04Autochangeovermode
05 Outdoor temperature sensor
06Compressorminimumofftime
07 Heating minimum off time
08Equipmentminimumontime
0:heat/cool 1:heatpump
0 : Fahrenheit
1:Celsius
0 : Gas or oil furnace (Equipment controls fan)
Note:UsedforDualFuelapplications
1:Electric(Thermostatcontrolsfan)
0° : No offset applied
–4°Fto+4°F(–2°Cto+2°C)
0 : Auto changeover mode is disabled
1:Autochangeovermodeisenabled
0 : No outdoor temperature sensor attached
1:Outdoortemperaturesensorattached
5 minutes
1 to 5 minutes in 1 minute steps
2 minutes
1 to 5 minutes in 1 minute steps
2 minutes
1 to 5 minutes in 1 minute steps
13
61000652D 8400 Tstat Install.indd 13 7/9/13 9:03 AM
Page 14
SETUP & TESTING
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
System setting Setting range, default in bold
09 1st stage differential
102ndstagedifferential(8448,8466)
113rdand4thstagedifferential(8448HP,8466HP)
12Reversevalve(8446,8448HP,8465,8466HP)
13Stagerate*
14Deadband(automode)
15Progressiverecovery(8463,8465,8466)
*Accumulationofequipmentruntimeinequipmentstagingdetermination.
1=morerapidstagingofequipment(comfort). 5=slowerstagingofequipment(economy).
14
1°F (0.5°C)
1°Fto4°F(0.5°Cto2°C)
1°F (0.5°C)
1°Fto4°F(0.5°Cto2°C)
1°F (0.5°C)
1°Fto4°F(0.5°Cto2°C)
0 – O/B energized in cooling (O)
1–O/Benergizedinheating(B)
4
1to5or“OFF”todisable
3°F (2°C)
2°Fto5°F(1°Cto3°C)
0:Progressiverecoveryisdisabled
1 : Progressive recovery is enabled
61000652D 8400 Tstat Install.indd 14 7/9/13 9:03 AM
Page 15
SETUP & TESTING
SYSTEM SETUP INSTRUCTIONS (CONTINUED)
System setting Setting range, default in bold
16LowBalancePt.(8446,8448HP,8465,8466HP)
Systemsetting05mustbeenabled
17HighBalancePt.(8446,8448HP,8465,8466HP)
Systemsetting05mustbeenabled
19Programformat(8463,8465,8466)
20Changeairfilter
21Changewaterpanel**
Setnumberofmonthsuntilreminderisrequired
22Humidifiertype**
23Servicedehumidifier
24ServiceHVAC
**IfhumidifiertypeissettoDrain-less,thenthefirstreminderisbasedonthesystemsetting21,secondreminder
willactivate3monthslater.IfhumidifiertypeissettoFlowthrough,thenthefirstreminderisbasedonsystem setting21,secondreminderwillactivate12monthslater.
20°F (–7°C)
1°Fto35°F(–17°Cto1°C)or“OFF”todisable
60°F (16°C)
40°Fto80°F(4°Cto27°C)or“OFF“todisable
0 – 5/2 program (Weekdays and Weekends)
1–5/1/1program(Weekdays,Sat.andSun.)
OFF
1,3,6,12monthsor“OFF”todisable
OFF
1to12monthsor“OFF”todisable
0 : Flow through type humidifier (1 reminder per season)
1:Drain-lesstypehumidifier(2 reminders per season)
OFF
1to12monthsor“OFF”todisable
OFF
1to12monthsor“OFF”todisable
15
61000652D 8400 Tstat Install.indd 15 7/9/13 9:03 AM
Page 16
SETUP & TESTING
SYSTEM TEST MODE
Thesystemtestmodeisusedtotestasystemafterinstallation.Theoutputsofthethermostatcanbemanually activatedoneatatimetotesttheirfunction.Thefollowinginstructionsshowhowtoenterthetestmodeandturn
outputs on and off. The charts on the following pages show all of the options for each model.
The test steps are:
Test
Number
50 Heating (W) (W2) AuxHeating(W)(W2)
51 Cooling(Y)(Y2) CompressorCooling(Y)(Y2)
52 Fan(G) CompressorHeating(Y)(Y2)
53 Fan(G)
16
61000652D 8400 Tstat Install.indd 16 7/9/13 9:03 AM
Heat/Cool Models
8444, 8463, 8448HC, 8466HC
Heat Pump Models
8446, 8465, 8448HP, 8466HP
Page 17
SETUP & TESTING
SYSTEM TEST MODE (CONTINUED)
How to enter the system test menu
Press
Press and hold
Thescreenofthefirstteststep#50isdisplayed:
repeatedly until system is set to OFF.
and for three seconds.
Press toturnontheoutput(01).Formultistage output,press
Press
Press
Press
againtoturnonthe2ndstage(02).
toturnofftheoutput(00).
tochangetothenextteststep.
afterthelastteststep.“DONE”willbe
displayed.
ThethermostatwillreturntoNormalmodeifnokeyis pressedin20seconds.
SYSTEMTEST NUMBER
OUTPUTSTATUS
61000652D 8400 Tstat Install.indd 17 7/9/13 9:03 AM
FLASHESIF24VAC ISNOTPRESENT
MODE(SW1SETTING 8448&8466ONLY)
17
Page 18
SETUP & TESTING
Step Key Input
#50Heat
#51Cool
#52 Fan
18
Test steps for 8444 & 8463
System Setting Display (Output)
#2
0:Gas ON
[UP]
1:Elec ON ON
[DOWN]
[UP] ON ON
[DOWN]
[UP] ON
[DOWN]
01
HEATING
ON (W)
01
COOLING
ON (Y)
01
FAN ON
(G)
61000652D 8400 Tstat Install.indd 18 7/9/13 9:03 AM
Page 19
SETUP & TESTING
Step Key Input
1st[UP]
#50Heat
#51Cool
#52 Fan
2nd[UP]
[DOWN] 1st[UP] 2nd[UP] ON ON ON [DOWN]
[UP] ON
[DOWN]
Test steps for 8448HC & 8466HC
System Setting Display (Output)
#2
0:Gas ON 1:Elec ON ON 0:Gas ON ON 1:Elec ON ON ON
ON ON
01
HEATING
ON (W)
02
HEATING
ON (W2)
01
COOLING
ON (Y)
02
COOLING
ON (Y2)
01
FAN ON
(G)
19
61000652D 8400 Tstat Install.indd 19 7/9/13 9:03 AM
Page 20
SETUP & TESTING
Step Key Input
#50Aux
#51Cool
#52 Heat
#53 Fan
20
Test steps for 8446 & 8465
System Setting Display (Output)
#2 #12
0:Gas
[UP]
1:Elec ON ON
[DOWN]
[UP]
[DOWN]
[UP]
[DOWN]
[UP] ON
[DOWN]
01 AUX
HEATING
ON (W)
ON
0:O ON ON ON 1:B ON ON 0:O ON 1:B 0:O ON ON 1:B ON ON ON 0:O 1:B ON
01
COOL/HEAT
ON (Y)
01
FAN ON
(G)
O/B
61000652D 8400 Tstat Install.indd 20 7/9/13 9:03 AM
Page 21
SETUP & TESTING
Step Key Input
1st[UP]
#50Aux
#51Cool
#52 Heat
#53 Fan
2nd[UP]
[DOWN]
1st[UP]
2nd[UP]
[DOWN]
1st[UP]
2nd[UP]
[DOWN]
[UP] ON
[DOWN]
Test steps for 8448HP & 8466HP
System Setting Display (Output)
#2 #12
0:Gas 1:Elec ON ON 0:Gas 1:Elec ON ON ON
01 AUX
HEATING
ON (W)
0:O ON ON ON 1:B ON ON 0:O ON ON ON ON 1:B ON ON ON 0:O ON 1:B 0:O ON ON 1:B ON ON ON 0:O ON ON ON 1:B ON ON ON ON 0:O 1:B ON
ON
ON ON
02 AUX
HEATING
ON (W2)
01
COOL/HEAT
ON (Y)
02
COOL/HEAT
ON (Y2)
01
FAN ON
(G)
O/B
21
61000652D 8400 Tstat Install.indd 21 7/9/13 9:03 AM
Page 22
QUICK REFERENCE TO CONTROLS & DISPLAY
NON-PROGRAMMABLE MODELS (8444, 8446, 8448)
CURRENTINDOORTEMPERATURE
SYSTEMMODE SETTING
OUTDOORTEMPERATURE(OPTIONAL)
TEMPERATURESETTING
EQUIPMENTSTATUS
SYSTEMMODE
FANSETTING
FANSETTING
BATTERYDOOR
MESSAGECENTER LOWBATTERYWARNING
22
61000652D 8400 Tstat Install.indd 22 7/9/13 9:03 AM
NOTE:BACKLIGHTISACTIVATEDWITHFIRSTBUTTONPRESSANDAUTOMATICALLYTURNSOFF.
UP
DOWN
HEAT PUMP MODELS ONLY
EMERGENCYHEAT(RED)
SYSTEMFAULT(YELLOW)
INDICATORSHOWSTHROUGHHOUSING
QUICKREFERENCECARD
Page 23
QUICK REFERENCE TO CONTROLS & DISPLAY
PROGRAMMABLE MODELS (8463, 8465, 8466)
SYSTEMMODE SETTING
FANSETTING
SYSTEMMODE
FANSETTING
PROGRAM
CURRENT SCHEDULE PERIOD
BATTERYDOOR
CURRENTINDOORTEMPERATURE
MESSAGECENTER LOWBATTERYWARNING
CURRENTTIME
OUTDOORTEMPERATURE(OPTIONAL)
TEMPERATURESETTING
EQUIPMENTSTATUS
UP
DOWN
HOLD
HEAT PUMP MODELS ONLY
EMERGENCYHEAT(RED)
SYSTEMFAULT(YELLOW)
INDICATORSHOWSTHROUGHHOUSING
QUICKREFERENCECARD
NOTE:BACKLIGHTISACTIVATEDWITHFIRSTBUTTONPRESSANDAUTOMATICALLYTURNSOFF.
61000652D 8400 Tstat Install.indd 23 7/9/13 9:03 AM
23
Page 24
THERMOSTAT FEATURES
ALL 8400 SERIES THERMOSTATS
•Large,clear,backlitdisplayiseasytoread–even
in the dark.
•Displaysroomtemperature,temperaturesetting,and
optional outdoor temperature.
•Dualpoweroption(Batteryor24VAC).
•Frontbatterydooraccessforfast,easyreplacement.
•Builtincompressorprotection.
•Circulationfanmodeforaircleaning.
•Waterpanel,dehumidifier,airfilter,andHVAC serviceindicators.
•Systemtestmode.
24
61000652D 8400 Tstat Install.indd 24 7/9/13 9:03 AM
PROGRAMMABLE MODELS ONLY (8463, 8465, 8466)
•Separatelyprogrammableweekday/weekend
schedules.
•Easytousetemperaturecontrolcanoverride
program schedule at any time.
•Progressiverecovery.ProgressiveRecoveryfeature allowsthethermostattoactivatetheheatingand coolingequipmentpriortoaneventinordertoreach thedesiredtemperatureatthestartofthenext scheduledevent.
Page 25
TROUBLESHOOTING
DISPLAY IS BLANK
•Checkcircuitbreakerandresetifnecessary.
•Makesurepowerswitchatheating&cooling
system is on.
•Makesurefurnacedoorisclosedsecurely.
•Ifthermostatisbatterypowered,makesurefreshAA alkalinebatteriesarecorrectlyinstalled.
TEMPERATURE SETTINGS DO NOT CHANGE
Makesureheatingandcoolingtemperaturesaresetto acceptableranges:
• Heat:45°to90°F(7°to32°C).
• Cool:50°to99°F(10°to37°C).
61000652D 8400 Tstat Install.indd 25 7/9/13 9:03 AM
HEATING SYSTEM DOES NOT RESPOND (“HEATING” APPEARS ON SCREEN)
•Checkfor24VACattheequipmentonthesecondary sideofthetransformerbetweenpowerand common.Ifvoltageisnotpresent,checktheheating equipmenttofindthecauseoftheproblem.
•Checkfor24VACbetweentheheatterminal(W) andthetransformercommon.If24VACispresent, thethermostatisfunctional.Checktheheating equipmenttofindthecauseoftheproblem.
•Checkforlooseorbrokenwiresbetweenthe thermostatandtheheatingequipment.
25
Page 26
TROUBLESHOOTING
COOLING SYSTEM DOES NOT RESPOND (“COOLING” APPEARS ON SCREEN)
•Checkfor24VACattheequipmentonthesecondary sideofthetransformerbetweenpowerand common.Ifvoltageisnotpresent,checkthecooling equipmenttofindthecauseoftheproblem.
•Checkfor24VACbetweenthecoolingterminal(Y) andthetransformercommon.If24VACispresent, thethermostatisfunctional.Checkthecooling systemtofindthecauseoftheproblem.
•Checkforlooseorbrokenwiresbetweenthe thermostatandthecoolingequipment.
FAN DOES NOT TURN ON IN A CALL FOR HEAT
•CheckSystemSetting#02(FanControl),tomake
sure the fan control is properly set to match the type of system (see page 11).
HEAT PUMP ISSUES COOL AIR IN HEAT MODE, OR WARM AIR IN COOL MODE
•CheckSystemSetting#12(ReversingValve),tomake
sure it is properly configured for your system (see page 11).
26
61000652D 8400 Tstat Install.indd 26 7/9/13 9:03 AM
HEAT/COOL BOTH ON AT SAME TIME
•CheckSW1(EquipmentType),tomakesureitisset tomatchtheinstalledheating/coolingequipment
(see page 12).
•Checktomakesureheatingandcoolingwiresare
not shorted together.
HEATING EQUIPMENT IS RUNNING IN COOL MODE
•CheckSW1(EquipmentType),tomakesureitisset tomatchtheinstalledheating/coolingequipment
(see page 12).
“HEATING” IS NOT DISPLAYED
•ChangetheSystemModetoHeat,andset thetemperaturelevelabovethecurrentroom
temperature.
“COOLING” IS NOT DISPLAYED
•ChangetheSystemModetoCool,andset thetemperaturelevelbelowthecurrentroom
temperature.
Page 27
SPECIFICATIONS
Environment
Temperature
Relativehumidity Operating:5%to90%R.H.(non-condensing)
Operatingvoltage 24VAC(18–30VAC)
Current
Power supply
Batterypower
Operating:32°to120°F(0°to48.9°C)
Shipping:-30°to140°F(-34.4°to60°C)
Electrical
Maximum:2.5A(total),1.0A(singleoutput)
Maximumsurgecurrent:5A
Dualpower.Canbebatteryor24VACpowered.
Whenboththesourcesareavailable,batterywillbeusedas backuppower.
Batterypower:AAsizealkalinebatteryx2
Batterylife:Approximately1year
27
61000652D 8400 Tstat Install.indd 27 7/9/13 9:03 AM
Page 28
SPECIFICATIONS
Thermal
Outdoor temperature sensor Maximumdistance:300feet
Roomtemperaturemeasurement Displayrange:32°to99°F(0°to40°C)
Outdoor temperature measurement Displayrange:-20°to130°F(-30°to55°C)
Temperature setting range
P.O.Box1467•Madison,WI53701-1467•Phone:800/334-6011 •Fax:608/257-4357
610006527.13 B2204777D ©2013Aprilaire–AdivisionofResearchProductsCorporation
28
Heat:45°to90°F(7°to32°C)
Cool:50°to99°F(10°to37°C)
www.aprilairepartners.com
61000652D 8400 Tstat Install.indd 28 7/9/13 9:03 AM
Loading...