Read this manual before installing. This product must be installed by qualified HVAC and electrical contractors and in
compliance with local, state, federal, and governing codes. Improper installation can cause property damage, severe personal
injury, or death as a result of electric shock, burns, or fire.
Read all cautions and instructions.
Read this manual before performing service or maintenance procedures on any part of the system. Failure to follow all cautions
and instructions could produce the hazardous situations described, resulting in property damage, personal injury, or death.
Failure to follow the instructions in this manual can cause moisture to accumulate, which can cause damage to structure and
furnishings.
HOT SURFACES AND HOT WATER
This steam humidification system has extremely hot surfaces. Water in steam canister, steam pipes, and dispersion tube can
be as hot as 212°F (100°C). Discharged steam is not visible. Contact with hot surfaces, discharged hot water, or air into which
steam has been discharged can cause severe personal injury. To avoid severe burns, follow procedures in this manual when
performing service or maintenance procedures on any part of the system.
DISCONNECT ELECTRICAL POWER
Disconnect electrical power before installing supply wiring or performing service or maintenance procedures on any part of
the humidification system. Failure to disconnect electrical power could result in fire, electrical shock, and other hazardous
conditions. These hazardous conditions could cause property damage, personal injury, or death.
Contact with energized circuits can cause property damage, severe personal injury, or death as a result of electrical shock or
fire. Do not remove access panels unless electrical power is disconnected.
Follow the shutdown procedure in this manual before performing service or maintenance procedures on any part of the system.
ELECTRICAL SHOCK HAZARD
If the humidifier starts up responding to a call for humidity during maintenance, severe injury or death from electrical shock could
occur. Follow the procedures in this manual before performing service or maintenance procedures on this humidifier.
EXCESSIVE SUPPLY WATER PRESSURE
Supply water pressure greater than 120 psi may cause the humidifier to overflow.
SHARP EDGES
Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling ductwork.
EXCESS HUMIDITY
Do not set humidity higher than recommended. Condensation may cause damage to structure and furnishings.
2
MATERIALS LIST
MODEL 800/800LCMODEL 801
MATERIALS FURNISHED
Humidifier
Model 62 Automatic Digital Humidifier Control
Dispersion tube
Steam hose (6 feet)
7/8” I.D. drain tubing (10 feet)
Hose clamps
Saddle valve
Mounting screws
NOT FURNISHED
Main power disconnect switch
Wiring
1/4” O.D. supply water tubing
Boards for mounting (if required)
Model 63 Automatic Digital Modulating Control
Main power disconnect switch
Wiring
1/4” O.D. supply water tubing
Boards for mounting (if required)
3
PRINCIPLES & SEQUENCE OF OPERATION
ube
Drain
Inlet
Fill V
2% PROPORTIONAL BAND SETTING
5% PROPORTIONAL BAND SETTING (DEF
10% PROPORTIONAL BAND SETTING
The Aprilaire® Steam Humidifier delivers humidity in the
form of steam to the conditioned space via the HVAC
system duct or the Fan Pack. The humidifier generates
steam by energizing two electrodes that extend into a
canister of water. Current flowing between the electrodes
causes the water to boil, creating steam. Water is
introduced to the humidifier through a fill valve to a fill
cup located in the top of the cabinet. The fill cup serves
as an overflow reservoir and provides an air gap between
the humidifier and water source. The steam canister is
filled from the bottom. The canister is seated in a drain
cup assembly which includes a drain valve. The drain and
fill valves work together to maintain water level in the
canister to deliver the rated steam capacity based on the
electrical conductivity of the water and to temper drain
water. See Figure 1 for representation of fill and drain
system and canister.
To control the Steam Humidifier as part of the HVAC
system, the Model 62 Automatic Digital Humidifier Control
(ADHC) is installed to detect the RH level in the duct.
When the ADHC detects RH below the set point, and the
humidifier and HVAC system blower are operating, the
humidifier energizes the electrodes to provide steam.
Steam is delivered into the duct work via the steam hose
and through the dispersion tube. The dispersion tube is
fitted with “Tubelets™.” The design of the dispersion tube and Tubelets distribute steam over a wide area in the duct and direct any condensed
moisture back into the steam hose. The blower activation function on the ADHC allows the control to turn on the HVAC system blower to
maintain the proper RH level even when the furnace or air handler is in stand-by mode. See ADHC installation manual.
FIGURE 1 – Fill and Drain System and Canister
Steam Hose
alve
Overflow
Fill
Supply
Water
Steam
Outlet
High Water Level Sensor
Electrodes
Canister
Drain Valve
Drain Cup
Tubelets
Dispersion T
in Duct
90-1522
Humidity can be distributed directly into the living space via the Fan Pack. When the Model 65 Manual Digital Humidistat detects RH below the
set point, the humidifier energizes the electrodes to provide steam via the steam manifold at the bottom of the Fan Pack. Steam is dispersed by
the fan located behind the grille above the steam manifold. The fan will operate for two minutes after the call for humidity ends, to disperse any
residual steam.
To provide precise control to the Modulating Steam
Humidifier, the Automatic Digital Modulating Control
FIGURE 2 – Humidifier Output for ADMC Signal
(ADMC) should be installed in the living space. The ADMC
will vary the Modulating Steam Humidifier output based
on the difference between set point and actual RH. The
ADMC sends a proportional signal to the Modulating
100%
PROPORTIONAL BAND
AULT)
Steam Humidifier providing precise control of living space
humidity. See Figure 2 for Steam Humidifier output vs RH
demand. The ADMC can be used in place of the ADHC
and Manual Digital Humidistat to provide On/Off control
to the Steam Humidifier not equipped with the modulating
feature. See the ADMC installation and operating manual
for details.
HUMIDIFIER OUTPUT (%)
20%
HUMIDIFIER OFF
-2%-5%-10%
RH DIFFERENCE FROM SETPOINT (%)
90-2008
4
SPECIFICATIONS & DIMENSIONS
This humidifier is able to produce steam at various capacities depending on the voltage and current applied. The unit can be wired to use an
input voltage of 120, 208 or 240 Volts and input amperage can be set to 11.5 or 16.0 amps by changing a dip switch on the control circuit board
(see the Electrical Power Wiring & Shut Off Switch section on page 13). Configure the unit appropriately for the application (see Table 1 for
capacity specifications).
TABLE 1 – Humidifier Capacities and Recommended Home Sizes
2
*
AmperageVoltage
120V11.52,500 sq ft1,500 sq ft1,000 sq ft
Maximum steam
capacity (gal/day)
Maximum recommended home size in ft
TightAverageLoose
11.5
208V20.5
4,500 sq ft2,500 sq ft1,500 sq ft
240V23.3
120V16.03,500 sq ft2,000 sq ft1,500 sq ft
16.0
208V30.0
6,000 sq ft4,000 sq ft2,500 sq ft
240V34.6
* Assumes 8 ft ceiling height, adjust as necessary for higher ceilings. For homes with multiple furnaces/air handlers a humidifier should be installed on each.
Model 800 Series Shipping Weight: 28 lbs
Model 865 Shipping Weight: 39 lbs
Humidifier Operating Weight: 23 lbs**
** As minerals precipitate, unit weight can increase to approximately 30 lbs.
5
SPECIFICATIONS & DIMENSIONS (CONTINUED)
FIGURE 3 – Humidifier Dimensions (inches)
8-7/8
7-7/8
3-3/8
3-3/8
TOP VIEW
10-1/8
Fill Cup
1-5/8
Electrical Knockouts
Dispersion Outlet
20-7/8
4-1/4
5-3/4
7-1/8
Steam Dispersion Tube
3 sq
3 sq
90-1518
Mounting
Holes
2 sq
2 sq
1-3/4
8-1/4
8-1/4
1-3/4
1 dia
1 dia
4
1
12
3-3/8
3-3/8
FRONT VIEW
Drain
6-5/8
7-7/8
9-1/8
BOTTOM VIEW
Water
Fill Line
Connection
1-7/8
Electrical
Knockouts
4
SIDE VIEW
2
BACK VIEW
6
90-1518
SPECIFICATIONS & DIMENSIONS (CONTINUED)
WATER QUALITY
Minerals that are naturally found in water contribute to water’s electrical conductivity; water conductivity is measured in microsiemens per
centimeter (uS/cm). Mineral content, also described as “water hardness” is usually measured in grains per gallon. Variation is found among
water samples but generally the higher the mineral content, the higher the conductivity.
The Steam Humidifier is designed to operate on water with conductivity between 100 and 1,250 uS/cm. This correlates loosely with water
hardness between 3 and 36 grains/gallon. Water that is considered “hard” and softened water work well in the Steam Humidifier. The humidifier
makes steam when plumbed to low-conductivity water but it takes longer to reach nominal current.
Two canisters are available for use with the Steam Humidifier. The Model 80 canister is used in most installations and is optimized for “hard”
and softened water. The Model 80 typically works best when the Steam Humidifier is installed at 208 or 240 VAC. If the Steam Humidifier has
a yellow Steam light in the first two weeks of running with a new canister, the Steam Humidifier is taking a long time to reach its nominal
current; changing to the Model 80LC canister will prevent this from happening in the future.
The Model 80LC canister is optimized for use in areas where the water conductivity is less than 300 uS/cm or when the Steam Humidifier is
installed at 120VAC. The Model 80LC should not be used with softened water. If the Steam Humidifier is draining too frequently, the water
conductivity is too high; changing to the Model 80 canister will reduce the drain frequency.
As water in the canister boils and turns into steam, minerals are left behind. Minerals remaining in solution increase the conductivity of the
water. Minerals also deposit onto the submerged portions of the electrodes rendering those areas ineffective. As this occurs, the level of water
in the canister rises to expose uncoated electrode surface.
There are benefits and trade-offs to consider when the application allows a choice between hard and softened water:
Hard water: The benefit of hard water is less frequent draining and filling than with soft water, which results in better energy and water
efficiency and more consistent steam output. However, canister replacement could be more frequent with hard water, because mineral deposits
coat the electrodes. The harder the water, the more frequent the need for a new canister.
Softened water: The benefit of softened water is longer canister life (depending on water chemistry) than with hard water, because softened
water does not coat the electrodes nearly as much as hard water. However, softened water ions stay in solution to much higher concentrations
than hard water ions. This requires more frequent draining and filling, which results in lower energy efficiency, higher water consumption and
less consistent steam output.
above 1250above 36Extremely HardInstallation Not Recommended
Grains/GalHardness
120VAC208VAC240VAC
Installation Not
Recommended
Recommended Canister by Voltage
80LC80LC
Softened808080
7
INSTALLATION INSTRUCTIONS
CAUTION
Each humidifier requires its own steam hose and dispersion tube. Do not connect steam hoses from more than one humidifier
together. Back-pressure from one humidifier can lower the water level in the canister in the other humidifier and cause
operational problems.
Do not install the dispersion tube in a duct with greater than 2 in. wg static pressure. High duct pressure can cause backpressure in the canister which can result in unstable unit operation.
Do not mount humidifier in a location where operating ambient temperatures exceed 140°F or where freezing temperatures
may occur.
CHOOSING A LOCATION
DISPERSION TUBE LOCATION
When choosing a location for the dispersion tube three things must be considered: Location in duct, elevation with respect to the humidifier, and
distance from humidifier to dispersion tube.
Duct Location and Absorption Distance
Absorption distance, the unobstructed straight line distance needed for steam to be fully absorbed, is dependent on air velocity, air temperature
and relative humidity in the duct. Determine absorption distance based on the lowest duct temperature, lowest air velocity and highest humidity that the system will see. The dispersion tube must be located in a straight section of duct far enough upstream of any
obstructions or bends in the duct. Use Table 3 to determine the appropriate absorption distance.
Operation during AC calls is not recommended because of the potential for condensation in the ductwork. Configure controls to lock out the
humidifier during AC calls and use the blower activation feature on the ADHC to allow the humidifier to run with the blower only. Call Aprilaire
Tech Support at 1-800-334-6011 for additional information on steam absorption.
The dispersion tube must be mounted with the plate on a vertical surface with the tube angled up as shown in Figure 4. The steam tubelets
must face up regardless of the airflow direction in the duct. The plate is labeled “UP”to indicate proper orientation. On horizontal duct runs
install the dispersion tube low in the duct, on vertical runs center the tube on the duct.
If the dispersion tube is mounted on insulated ductwork, make sure insulation is not more than 2” thick at tube location to prevent insulation
from blocking first steam outlet.
Note: If dispersion tubes for two humidifiers are installed in one duct, double the dispersion distances. If three dispersion tubes are installed,
triple the dispersion distance. Position dispersion tubes so one does not discharge directly onto another.
8
INSTALLATION INSTRUCTIONS (CONTINUED)
Steam hose or pipe.
Insulate pipe with 1” fiberglass
TABLE 3 – Absorption Distance (Minimum distance from dispersion tube downstream to any obstruction or bend in duct)
*Velocity in feet per minute = Duct airflow volume in cubic feet per minute / duct area in square feet.
Example: 1,200 cfm through 16” x 12” duct = 1,200/(12 x 16/144 sq. in./sq ft.) = 1,200/1.333 = 900 fpm
The preferred location for the dispersion tube is higher than the
humidifier so that the steam hose has a constant downward slope of at
least 2” per foot from the dispersion tube to the humidifier. If hard pipe
is used, the slope can be 1/4” per foot. With the constant downward
slope, any condensation that forms in the steam hose will drain back
to reduce steam loss.
90° long sweep
or two 45° elbows
into the steam canister. See Figure 4.
Setpoint
5” minimum
Pitch*
45°F & 45% RH
Setpoint
Duct
Dispersion
tube
* Pitch steam hose down
from dispersion tube to
humidifier:
2”/ft (15%) minimum
when using steam hose.
1/4”/ft when using
hard pipe.
90-1521
9
INSTALLATION INSTRUCTIONS (CONTINUED)
Drip tee installation for
piping over obstruction,
or if dispersion tube is
lower than humidifier
Reducing Coupling
To Steam
Dispersion
Hose Clamp
ube
NOTICE
CONTROL CONDENSATE FLOW AND COLLECTION.
Failure to follow steam hose recommendations in this
manual can result in reduced or erratic performance,
increased noise and condensate in the duct.
If the dispersion tube must be mounted below the humidifier
or if the steam hose needs to run up and over an obstruction, a
drip tee with drain trap, Part #4028, must be installed as shown
in Figure 5. When using the Fan Pack, install Part #4028 close
to the humidifier outlet to help prevent noise from gurgling as
shown in Figure 6.
DISTANCE FROM HUMIDIFIER TO
DISPERSION TUBE/FAN PACK
The capacity of the humidifier is reduced by the length of
the steam hose or pipe due to condensation. The maximum
recommended length of steam hose is 6 feet. Use hard pipe
insulated with 1” thick insulation rated for 212°F or higher
for lengths greater than 6 feet. Table 4 provides humidifier
capacity with various lengths of steam hose and pipe. If 6-foot
steam hose does not reach from humidifier to dispersion tube,
splice in 1” copper pipe using 3/4” x 1” reducing couplings as
shown in Figure 7.
Do not mount humidifier in a location where operating
ambient temperature exceeds 140°F or where freezing
temperatures may occur. Extreme temperatures may cause the
humidifier to leak which can damage furnishings or structure.
Mount humidifier in a location that allows access for servicing, and
clearance to remove front panel for replacing the canister and side
panel for access to the electrical components during installation.
See Figure 8 for minimum clearances around humidifier.
The humidifier should be mounted as close to the dispersion
tube as possible. Table 4 shows how capacity is reduced as the
distance between the humidifier and dispersion tube increases. If
the humidifier is mounted on the duct directly below the dispersion
tube, allow space for a bend in the steam hose. Allow a minimum
of 2” of steam hose to extend straight out of the humidifier before
beginning any bends; this will help ensure a tight connection with
the top of the canister.
The humidifier can be mounted to a wood surface, or to sheet metal
ductwork if it is structurally stable. Do not mount humidifier to fiber
duct board. Sound isolation may be desired when mounting to sheet
metal ductwork.
120 Volts208 Volts240 Volts
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
Pipe
Steam
Hose
Insulated
FIGURE 8 – Clearances
FRONT VIEW
16" for
4"
90-1519
Electrical
Access
16"
for Drain
Pipe
Steam
Hose
16" for
Steam
Hose
30" for
Service
Access
SIDE VIEW
Insulated
Pipe
The humidifier must be mounted to a vertical surface and must be
mounted level in the upright position.
11
INSTALLATION INSTRUCTIONS (CONTINUED)
PREPARE HUMIDIFIER FOR MOUNTING
Unpack carton. Open front panel by removing screw and lifting panel up and away from humidifier. Disconnect three wires from top of canister
by pulling straight up. The two large wires are the electrode conductors. The smaller wire is connected to the high water level sensor. Remove
canister by pulling it up and out of drain assembly. Remove two screws on right side of humidifier and lift side panel off housing to expose
electrical compartment.
INSTALL STEAM DISPERSION TUBE
Make sure steam dispersion tube is mounted higher than the humidifier so that condensation that forms in the steam hose runs back into the
canister. If the dispersion tube cannot be mounted higher than the humidifier or if the steam hose must extend up from the humidifier then down
to the dispersion tube due to an obstruction, a drip tee and drain trap system (Part #4028) must be installed as shown in Figure 5.
Drill a 1-1/4” diameter hole in a vertical surface of the duct at the location chosen for the dispersion tube. Position the dispersion tube so it is
angled up, regardless of airflow direction. UP is stamped on the mounting bracket to aid in proper installation. Secure with four sheet metal
screws provided.
MOUNT HUMIDIFIER
Secure humidifier to a sturdy wall using screws provided, or to sheet metal duct. Humidifier initially weighs 23 lbs with a full canister, but will
increase in weight over time due to the precipitation of minerals inside the canister. Make sure mounting system will support weight. If mounting
to stud frame wall, install two spanner boards to studs and fasten humidifier to spanner boards. Make sure humidifier is mounted plumb.
INSTALL STEAM HOSE
Six feet of steam hose is provided with the humidifier. If the steam hose must be cut, use a hacksaw. If additional length is required, use
1” O.D. metal or copper pipe. Do not use PVC pipe for steam line. Insulate pipe with 1” thick insulation rated for 212°F or higher to reduce
steam loss. See Table 4 for humidifier capacity at various lengths of steam hose and pipe.
Use the steam hose provided. Other hoses may have impurities which can cause foaming in the canister. Foaming can cause water level
inaccuracies, reduced steam production and water sputtering into the duct. When using pipe, remove all traces of residual materials used to
connect the pipe to prevent foaming.
Verify that the O-ring is in place in the groove in the drain assembly. Dampen the O-ring with water (DO NOT use oil, grease,or any lubricant
besides water), then reinsert the canister with the caution label positioned toward the front of the unit.
Attach steam hose to dispersion tube and then to top of canister using hose clamps provided. Make sure steam hose has a constant slope of at
least 2” per foot between the dispersion tube and the humidifier. Any and every low spot in the steam hose or pipe must have a drip tee and drain
trap. Fill drain trap with water before making final connections. Support the steam hose in multiple locations over its span to prevent sagging.
Attach and fully seat the electrode conductors (interchangeable) and the high water level sensor wire to the top of the canister.
SUPPLY WATER
Plumb the humidifier to cold, hard or softened water. Do not use hot water because unheated supply water is used to cool water
draining from the humidifier. Do not use demineralized or reverse osmosis water. For proper operation, supply water pressure must be between
25 psi and 120 psi. Hard or softened water may be used provided it has conductivity between 125 microS/cm and 1250 microS/cm. See Table 2.
Supply water piping must be free of oils, lubricants, solder flux and other contaminants, which can cause foaming.
Follow local plumbing codes. An external backflow preventer may be needed.
Install the saddle valve according to the instructions printed on the bag. Run 1/4” copper tubing from the saddle valve to the humidifier. Connect
it to the fill valve. Double wrench to prevent leaking and damage to valve. Addition of a stainless steel braided water line can help reduce valve
noise.
Note: Adding an inline particulate filter can increase canister life in areas with high levels of suspended solids. DO NOT use filters that release
scale inhibitors, filters of this type can significantly decrease canister life.
12
INSTALLATION INSTRUCTIONS (CONTINUED)
DRAIN LINE
Attach the 7/8” I.D. drain tubing provided to the drain assembly at the bottom of the humidifier. Secure with the hose clamp provided. Do not
over tighten.
Make sure the drain line has a constant downward slope from the humidifier to the drain and is not kinked or blocked.
If floor drain is not available, use condensate pump (Part #4856) to route water to a suitable drain. Provide at least 16 inches for of drain line
between the Steam Humidifier and the condensate pump.
Note: The humidifier uses cold water to temper drain water to less than 140°F.
ELECTRICAL POWER WIRING & SHUT-OFF SWITCH
CAUTION
Only qualified electrical personnel should perform field wiring procedures. Improper wiring or contact with energized circuits
can cause property damage or severe personal injury.
All wiring must be installed in accordance with all governing electrical codes and with the wiring diagram provided inside the front panel.
Do not loop power wiring.
Do not use aluminum wire.
A safety grounding system that meets all governing electrical codes is required. The ground connection must be made with solid metal to metal
connections. Ground wire must be the same size as the power wiring.
With factory settings, the Steam Humidifier draws 11.5 amps +/- 10%. Use a minimum 20 amp dedicated circuit when installing to operate
at 11.5 amps. The Steam Humidifier can be set to draw 16.0 amps +/- 10% by repositioning dip switch #1 on the control circuit board (see
Figure 9). When set to 16 amps, use a minimum 25 amp dedicated circuit. For both applications, size wire according to local codes.
The Steam Humidifier is shipped from the factory wired for 240 VAC operation, but it can operate on 120, 208 or 240 VAC. If using 120V or
208V, move the black/white jumper wire to the proper tab on the control circuit board. See Figures 10, 11, 12.
WIRING INSTRUCTIONS
Install disconnect switch (not provided) between line power source and humidifier.
Knock-outs for power wiring and low voltage control circuit wiring are provided.
Connect power and ground wiring as shown in appropriate wiring diagram.
• 240 VAC – Figure 10
• 208 VAC – Figure 11
• 120 VAC – Figure 12
Do not run high voltage power lines over internal circuit boards.
13
INSTALLATION INSTRUCTIONS (CONTINUED)
FIGURE 9 – Control Circuit Board with Dip Switches
LED D8
Factory setting for
11.5 AMP nominal
operation.
Slide Dip Switch #1
to “ON” position
for 16.0 AMP
nominal operation.
90-1959
14
INSTALLATION INSTRUCTIONS (CONTINUED)
FIGURE 10 – 240 VAC Wiring Diagram
BLK
POWER
MAIN POWER BREAKER
(NOT PROVIDED)
GND
L2 / N
L1
DOOR SWITCH
ORANGE
TERMINAL
BLOCK
TRANSFORMER POWER
P7
J8
JUMPER WIRE
BLK/WHT
J10
BLK
J16
YEL
WATER LEVEL
PROBE
ELECTRODE
STEAM CANISTER
STEAM HUMIDIFIER IS SHIPPED FROM
THE FACTORY WIRED FOR 240 VOLTS.
ELECTRODE
HUMIDITY CONTROL
DRY
CONTACT
DISPLAY PANEL
(PROVIDED)
FAN PACK
(OPTIONAL)
RIBBON CABLE
HUMIDISTAT
1
2
FAN PACK
J2
10
1
J5J6
J11
120
VAC
SLOW BLOW FUSE
(5X20mm 5A)
CON1
BLK
YEL
J13
208
VAC
ORG
RED
BLK
WHT
P4
J14
240
VAC
P3
TRANSFORMER
BLUE
YEL
HIGH VOLTAGE WIRING
CONTROL CIRCUIT WIRING
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
90-1903
DRAIN
VALV E
FILL
VALV E
15
INSTALLATION INSTRUCTIONS (CONTINUED)
FIGURE 11 – 208 VAC Wiring Diagram
BLK
BLK
POWER
MAIN POWER BREAKER
(NOT PROVIDED)
GND
L2 / N
L1
DOOR SWITCH
ORANGE
TERMINAL
BLOCK
TRANSFORMER POWER
P7
J8
JUMPER WIRE
J10
BLK/WHT
J16
YEL
WATER LEVEL
PROBE
ELECTRODE
STEAM CANISTER
STEAM HUMIDIFIER IS SHIPPED FROM
THE FACTORY WIRED FOR 240 VOLTS.
MOVE THE JUMPER WIRE TO TERMINAL
J13 TO OPERATE AT 208VAC.
ELECTRODE
HUMIDITY CONTROL
DRY
CONTACT
DISPLAY PANEL
(PROVIDED)
FAN PACK
(OPTIONAL)
RIBBON CABLE
HUMIDISTAT
1
2
FAN PACK
J2
10
1
J5J6
J11
120
VAC
SLOW BLOW FUSE
(5X20mm 5A)
CON1
BLK
YEL
YEL
J13
208
VAC
VAC
ORG
RED
BLK
WHT
P4
J14
240
P3
TRANSFORMER
BLUE
YEL
HIGH VOLTAGE WIRING
CONTROL CIRCUIT WIRING
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
16
90-1904
DRAIN
VALV E
FILL
VALV E
INSTALLATION INSTRUCTIONS (CONTINUED)
FIGURE 12 – 120 VAC Wiring Diagram
BLK
BLK
POWER
MAIN POWER BREAKER
(NOT PROVIDED)
GND
L2 / N
L1
DOOR SWITCH
ORANGE
TERMINAL
BLOCK
TRANSFORMER POWER
P7
J8
JUMPER WIRE
BLK/WHT
J10
J16
YEL
WATER LEVEL
PROBE
ELECTRODE
STEAM CANISTER
STEAM HUMIDIFIER IS SHIPPED FROM
THE FACTORY WIRED FOR 240 VOLTS.
MOVE THE JUMPER WIRE TO TERMINAL
J11 TO OPERATE AT 120VAC.
ELECTRODE
HUMIDITY CONTROL
DRY
CONTACT
DISPLAY PANEL
(PROVIDED)
FAN PACK
(OPTIONAL)
RIBBON CABLE
HUMIDISTAT
1
2
FAN PACK
J2
10
1
J5J6
J11
120
VAC
SLOW BLOW FUSE
(5X20mm 5A)
CON1
BLK
YEL
J13
208
VAC
WHT
P4
J14
240
VAC
P3
ORG
RED
BLK
TRANSFORMER
BLUE
YEL
HIGH VOLTAGE WIRING
CONTROL CIRCUIT WIRING
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
90-1905
DRAIN
VALV E
FILL
VALV E
17
INSTALLATION INSTRUCTIONS (CONTINUED)
AUTOMATIC DIGITAL CONTROL & ACCESSORY WIRING (MODEL 800)
The control circuit operates on 24VAC.
The ADHC (Automatic Digital Humidifier Control) Model 62 must be mounted in the return air duct at least 6” upstream of any fresh air intake
ducts or sources of moisture and at least 12” upstream of the steam dispersion tube if it is mounted in the return. Follow instructions provided
with the control. Connect “H” terminals on ADHC to “HUMIDISTAT” terminals on humidifier circuit board. The “H” terminals on the Model 62
provide a dry contact switch to energize the humidifier.
If the application requires a wall-mounted humidistat in the conditioned space, use Manual Humidistat Part #4655, Digital Manual Humidistat
Part #65, Automatic Digital Modulating Humidistat Part #63 or any Aprilaire thermostat with integrated humidifier control functionality. Use
Blower Activation Relay Part #4851 with Aprilaire Manual and Digital Manual Humidistats in order to allow the humidifier to turn on the HVAC
system blower when humidity is required.
If protection from over-humidification is desired, install optional high humidity limit switch Part #4594 at least 4 feet downstream of the
dispersion tube. If airflow verification is desired, install optional airflow proving switch Part #4592 in duct. The high humidity limit switch and the
airflow proving switch are wired in series with the ADHC (humidistat) circuit. See Figure 13.
FIGURE 13 – Steam Humidifier Accessory Wiring
MODEL 62 DIGITAL HUMIDIFIER CONTROL
24V TERMINALS
24 VAC from HVAC
HGf RCAB ODTGWH
Equipment “R” & “C”
Communication with
Fan Signal to HVAC Equipment
Aprilaire 8570 Thermostat
Outdoor Temperature Sensor
C
Heat Signal from HVAC Equipment
NO
NC
Fan Signal from Thermostat or
Zone Panel Equipment Terminals
OPTIONAL:
FAN PACK HUMIDISTAT
AIR FLOW PROVING SWITCH #4592
Connect 1/4" plastic tubing from H (High) side
of proving switch to the airflow sensing probe
located 1.5 duct diameters downstream of
blower. Leave L (Low) side open to amosphere.
C
NC
NO
OPTIONAL:
HIGH HUMIDITY LIMIT SWITCH #4594
Switch breaks C to NO connection when
measured RH is above setpoint RH.
90-1544
18
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.