Aprilaire 700a Installation Instruction

This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.
This product must be installed in compliance with all local, state and federal codes.
ATTENTION INSTALLER:
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING
AUTOMATIC HUMIDIFIER MODEL 700
P.O. BOX 1467 • MADISON, WI 53701-1467 • CALL 800/334-6011 • FAX 608/257-4357
INSTALLATION OPTIONS
Typical Installation Alternate Installation
COOLING COILS IN
WARM AIR PLENUM
Aprilaire to be installed as shown in relation to cooling coils.
WIRING DIAGRAM
(SEE STEP 7 ON BACK AND “HUMIDIFIER CONTROL SAFETY AND INSTALLATION INSTRUCTIONS” FOR DETAILED WIRING INSTRUCTIONS)
90-1099
90-922
90-921
RETURN
RETURN
HOT WATER
SUPPLY
SUPPLY
Orientation of Aprilaire Model 700
to Cooling Coils
WARNING
1. ELECTRICAL SHOCK HAZARD.
Disconnect electrical power to the furnace before starting installation. Failure to do so could result in serious injury from electrical shock.
2.
SHARP EDGES HAZARD. Sharp
edges may cause serious injury from cuts. Use care when making plenum openings and handling ductwork.
3.
RISK OF SCALDING. Water
temperature over 125°F can cause severe burns and scald instantly. Shut off the hot water supply before disconnecting or tapping into any hot water supply line.
SPECIFICATIONS
HUMIDIFIER DIMENSIONS
Width 15
29
32
Height
(including solenoid valve
and drain spud)
18”
Depth 10
11
32
PLENUM OPENING
14
3
4”W x 145⁄16”H
WATER FEED RATE
6 gph
ELECTRICAL DATA
120 VAC-60 Hz, 0.8 AMP
CAUTION
1. Do not install humidifier where freezing temperatures could occur. The water line could freeze and crack causing water damage to the home.
2. Do not install humidifier on the furnace jacket.
3. Do not install humidifier on a plenum face where the blanked off ends of the cooling coil will restrict air movement through the humidifier.
4. Do not set humidity level above recommended or to recommended level if condensation exists on inside windows of any unheated space, as condensation damage may result. Excess humidity can cause moisture accumulation which can allow the possibility for mold growth in the home.
5. Do not connect the Model 700 power cord to multi-speed furnace blower motors or blower motors other than 120 VAC. Premature component failure may result. Use Research Products Corporation Model 50 Current Sensing Relay.
6. When installing Aprilaire Humidifier Control on a downflow furnace, ensure blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Control.
7. Do not install humidifier where water pressure exceeds 125 psi, since damage to the humidifier may result. Follow codes in effect concerning pressure reduction.
8. Do not install humidifier on the supply plenum where static pressure exceeds 0.4 in. wg.
RISK OF PROPERTY AND EQUIPMENT DAMAGE.
BLANKED OFF
END OF COIL
NOTES
1. The Model 700 is not suitable for installation on ducts with horizontal airflow. Performance will be reduced.
2. When installing Aprilaire humidifier on a heat pump system, use hot water. The heated water supplements the reduced supply air temperature as added heat for evaporation.
NOTE:
FOR INSTALLATION IN MANUAL MODE, REPLACE OUTDOOR TEMPERATURE SENSOR WITH PLASTIC RESISTOR CASE AND ATTACH MANUAL FACE PLATE. SEE “HUMIDIFIER CONTROL SAFETY AND INSTALLATION INSTRUCTIONS” INCLUDED WITH EACH HUMIDIFIER.
COMMUNICATION
TERMINALS FOR 8570
THERMOSTAT
24 VAC FURNACE ACCESSORY TERMINALS
(2 VA MINIMUM) OR
24 VAC TRANSFORMER (2 VA MINIMUM)
SHUT-OFF
(SADDLE VALVE)
WATER SUPPLY
120 VAC OUTLET
CONNECT DRAIN
LINE HERE
R
I+
C
24V
ODT
NORTH, EAST
OR WEST SIDE
OF HOME
OUTDOOR
TEMPERATURE
SENSOR
ABOVE EXPECTED
SNOW LINE
BROWN WIRES
COMMON
FURNACE
BLOWER
MODEL 50 CURRENT SENSING RELAY (NOT SUPPLIED) REQUIRED IF 120 VOLT POWER SOURCE FOR HUMIDIFIER AND 24 VOLT POWER SOURCE FOR CONTROL ARE POWERED CONTINUOUSLY.
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING
TEMPLATE MUST BE LEVEL
– TOP –
READ REVERSE SIDE FIRST! READ REVERSE SIDE FIRST!
Figure 1
10006916 B2204052A 04.06
90-923 90-924 90-925 90-926
Figure 2 Figure 3 Figure 4
6
5
7
1
3
9
11
13
12
14
15
8
10
4
2
16
17
90-888
1. Place the humidifier on a flat surface.
Unlatch humidifier cover assembly from base assembly at the bottom of the cover, lift and set aside. Pull out the Water Panel
®
evaporator assembly by grasping at the top and tipping out. (See Figure 1)
2. Using a level, position this template at
least 11⁄ 2 inches above the furnace housing or cooling coil if applicable, for clearance of the drain line. Trace around template edges. When there is insufficient space on the supply plenum, the humidifier can be installed on the return duct provided the humidifier is supplied with hot water. Remove the template and accurately cut the plenum opening 14
3
4”W x 145⁄16“H, being careful to
avoid injury from sharp edges.
3. Position the two plastic hooks on the top
of base along the top edge of the plenum opening. Push base up to engage the two hooks and sheet metal along the top edge opening. Push base in and slide down so that the bottom four hooks engage the sheet metal at the bottom edge of the opening. Secure base to opening using top three screw holes in housing. An additional hole is provided at the bottom for securing the base to the plenum. (See Figure 2)
4. While pressing the base against the plenum,
reach through the center opening and turn left and right swing latches down to secure the base onto the plenum. (See Figure 3)
5. Reinstall the Water Panel
®
evaporator assembly into the base, with the bottom of the scale control insert (5) sitting firmly in the inside of the drain spud attached to the base. Push the Water Panel®evaporator assembly in at the top between the retaining ribs that hold the assembly in place in a vertical position. Reinstall cover assembly by hooking at the top of base assembly and latching at the bottom.
6. Install the Aprilaire Humidifier Control in
the return duct using the installation instructions enclosed (see Wiring Diagram, opposite side). For detailed installation and wiring instructions, see “Humidifier Control Safety and Installation Instructions” included with the humidifier.
7. The Model 700 humidifier power cord must
be plugged into a 120 VAC outlet. Do not use an extension cord. Do not power 120 VAC outlet from the furnace blower circuit. The Automatic Humidifier Control must be powered from a 24 VAC source connected to the “R” and “C” terminals on the control. The 24 VAC humidifier wires (brown) must be connected to the “H” terminals on the control.
CAUTION: Do not connect brown wires to “ACC” or “HUM” terminals on furnace or damage to the humidifier could result.
In order for the humidifier to turn on, the furnace blower must be operating and the control must be calling for humidity. The interface between the Model 700 Humidifier and the furnace to detect blower operation can be accomplished several different ways:
A. If the humidifier is plugged into a continuously powered 120 VAC outlet and the control is powered from 24 VAC “ACC” or “HUM” terminals on the furnace connected to the “R” and “C” terminals on the control, then the brown wires from the humidifier can be connected directly to the “H” terminals on the control.
B. If the humidifier is plugged into a 120 VAC outlet that is powered only when the furnace is on, then the humidifier control can be powered by a constant 24 VAC source connected to the “R” and “C” terminals on the control, and the brown wires from the humidifier can be connected directly to the “H” terminals on the control.
C. If the humidifier is plugged into a continuously powered 120 VAC outlet and the control is powered from a continuous 24 VAC source, then a Model 50 Current Sensing Relay (not included) must be installed in the humidifier circuit. (Brown wires connected to “H” terminals on control.)
8. Tap into water supply line with the saddle
valve furnished. See instructions on saddle valve package. The humidifier will function with cold, hot, softened or unsoftened water. The use of service hot water (140°F MAX.)
and constant blower operation will provide maximum evaporative capacity. When
installing humidifier on heat pump system, humidifier must be supplied with service hot water.
NOTE: The saddle valve is designed to be fully opened or closed. Do not use it to regulate water flow.
9. Connect tubing from the saddle valve to
the inlet side of the solenoid valve using 1⁄ 4” O.D. copper tubing (not furnished).
DOUBLE WRENCH TO PREVENT LEAKING! (See Figure 4)
10. Drain spud is designed to accept
1
2” I.D. plastic hose (not furnished). Run drain line from drain spud to floor drain. CAUTION: If
hose clamp is used, do not overtighten, drain spud could crack. Be sure drain line has continuous slope. NOTE: Do not sweat or directly attach metal drain line to fitting. Do not use solvent type adhesives when connecting plastic drain line, since damage to fitting could result.
11. Open saddle valve completely and turn
on furnace. Turn up humidifier control so that humidifier will turn on. Allow humidifier to run until water is observed coming out of the drain line. Check to see if humidifier and saddle valve are watertight. Check operation to make sure that all electrical components function properly by utilizing humidification system check-out section in the “Humidifier Control Safety and Installation Instructions”. Set humidifier control to recommended level.
FURNISHED ITEMS
Automatic Humidifier Control
Automatic Humidifier Control
Installation Sheet
Saddle Valve
Humidifier Installation Template
Mounting screws
(sheet metal screws)
Water supply line (1⁄4” copper)
Drain line (1⁄2” I.D. hose)
Low voltage wire
Model 50 Current Sensing Relay
(if required)
ITEMS NOT FURNISHED
IMPORTANT! Be sure owner’s manual containing instructions for operation
and warranty information is given to owner in order to avoid unnecessary calls. Warranty is void unless humidifier is installed by qualified heating and air conditioning contractor due to possible misapplication of product.
PARTS LIST
1. Front Cover
2. Base
3. Orifice Plate
4. Motor Mount Bridge
5. Scale Control Insert
6. Water Panel Evaporator
7. Water Distribution Tray
8. Fan Blade
9. Motor
10. Motor Mount Gasket
11. Circuit Board
12. Power Cord
13. Strain Relief Bushing
14. Solenoid Valve
15. Connector Plug
16. Feed Tube
17. Nozzle
NOTE: BEFORE LEAVING THE JOB SITE, MAKE SURE:
1. Saddle valve is fully open.
2. All plumbing connections are watertight.
3. Humidifier functions properly.