This Uninterruptible Power Supply (UPS) prevents blackouts,
brownouts, sags and surges from reaching your computer and
other valuable electronic equipment, filters out utility line
fluctuations, and isolates your equipment from disturbances by
actively controlling voltage to loads, and supplying power
from its batteries when required.
While running on battery, an internal alarm will sound
(periodic beeps). The mute button may be pressed to silence
the UPS alarm.
If the utility power does not return, the UPS will continue
supplying power to the connected equipment until exhausted.
A continuous beeping will sound two minutes before the
UPS’s final low battery shutdown. If using a computer, you
must manually save your files and power down before the UPS
turns itself off, unless you are using PowerChute interface
software that provides automatic, unattended shutdown.
Installation and Setup
1. Install UPS
•The Smart-UPS DP must be installed by a local
authorized electrician.
• National and local electrical regulations must be adhered
to during installation and operation.
2. Turn on UPS
• Switch on the mains fuse on the rear of the
UPS. The Smart-UPS DP will perform a
i
n
s
a
M
1
0
0
F
3. Install PowerChute
•For additional computer system security, install
PowerChute
automatic unattended shutdown capabilities on most
major network operating systems. See the SoftwareInstallation: Instruction Sheet for details.
self-check ending with the LED display
showing red/yellow/green, indicating the
unit is functioning properly. The unit
performs a self-test automatically when
turned on, and every two weeks thereafter.
• Turn the on/off switch on the front of the
Smart-UPS DP to 1 (up). The acoustic
alarm will give a short beep when output
power is available.
•The UPS charges its battery whenever it is
connected to utility power and the on/off
switch on the front of the unit is turned on
(1 or up). The battery charges fully during
the first 4 hours of normal operation. Do
not expect full runtime during this initial
charge period.
®
®
UPS monitoring software. It provides
Troubleshooting
Use the chart below to solve minor UPS installation problems.
Contact APC Technical Support Staff for assistance with
complex UPS problems. See APC Contact Information, page
18, for a location near you.
Problem and
Possible Cause
UPS will not turn on.
• On/off switch turned to off
(0 or down).
• Fuse switch turned to off
(down).
• On/off switch needs to be
cycled on and off
• UPS not connected to AC
power supply.
• UPS input circuit breaker
tripped.
• Very low or no utility
voltage.
UPS will not turn off.
• Internal UPS fault.
UPS operates on-battery although normal line voltage exists.
• UPS input circuit breaker
tripped.
• Very high, low, or distorted
line voltage. Inexpensive
fuel powered generators can
distort the voltage.
UPS beeps occasionally.
• Normal UPS operation.
UPS does not provide expected backup time.
• The UPS’s battery is weak
due to recent outage or is
near the end of its service
life.
• The UPS is overloaded.
Front panel indicators off.
• The UPS has been shut
down by remote control.
All indicators are lit constant red and UPS emits a constant beeping.
• Overload
• Internal UPS fault.
All indicators are off and UPS is connected to the AC power.
• The UPS is shut down and
the battery is discharged
from an extended outage.
All indicators are flashing yellow.
• Weak batteries.
• Replacement batteries not
connected properly.
Turn the switch to 1 (up) to power the UPS
and the load.
Turn the switch up.
Switching the on/off switch to off (0 or
down) and on again (1 or up).
Check that the power cable from the UPS to
the power supply is securely connected at
both ends.
Reduce the load on the UPS by unplugging
equipment and reset the fuse switch (on
back of UPS) by switching it up.
Check the circuit breakers to the AC power
supply.
Have the UPS serviced immediately.
Reduce the load on the UPS by unplugging
equipment and reset the fuse switch (on
back of UPS) by switching it up if
necessary.
Move the UPS to a different circuit.
Test the input voltage using PowerChute.
None. The UPS is protecting the load.
Charge the battery. Batteries require
recharging after extended outages. Also,
they wear faster when put into service often
or when operated at elevated temperatures.
If the battery is near the end of its service
life, consider replacing the battery.
Check the UPS’s load using PowerChute.
Unplug less needed equipment, such as
printers.
None. The UPS will restart automatically
when utility power returns.
Reduce the load on the UPS by unplugging
equipment and reset the fuse switch (on
back of UPS) by switching it up if
necessary.
Have the UPS serviced immediately.
None. The UPS will return to normal
operation when the power is restored and
the battery has a sufficient charge.
Do another self test to see if it clears
Confirm the battery connections.
Replacement and Recycling of Batteries ................................................................................................................................................1
Common Fault........................................................................................................................................................................................6
Computer Interface Port (Optional)........................................................................................................................................................6
Emergency Power Off (EPO) Remote Shut Down and Signal Relay Port (Optional) ............................................................................6
External Service Bypass Panel (SBP) ..................................................................................................................................................10
External Service Bypass Panel and Galvanic Isolation Transformer....................................................................................................11
External Run Battery Cabinet...............................................................................................................................................................12
Switching Off .......................................................................................................................................................................................13
Setting the Voltage ...............................................................................................................................................................................13
External Service Bypass Panel Operation ............................................................................................................................................13
Service .....................................................................................................................................................................................................15
APC Contact Information .....................................................................................................................................................................18
Latin America, South America .............................................................................................................................................................18
This Safety Guide contains important instructions that should be followed during installation and maintenance of the APC equipment and batteries.
It is intended for APC customers who setup, install, relocate, or maintain APC equipment.
Handling Safety
•Be careful. Do not lift heavy loads without assistance.
<18 kg (<40 lb.)
18-32 kg (40-70 lb.)
32-55 kg (70-120 lb.)
>55 kg (>120 lb.)
• Equipment with casters is built to move on a smooth surface without any obstacles.
• Do not use a ramp inclined at more than 10°.
• This equipment is intended for installation in a temperature-controlled indoor area (see the User's Manual for exact temperature range), free of
conductive contaminants.
Electrical Safety
• Do not work alone under hazardous conditions.
• High short circuit current through conductive materials could cause severe burns.
• A licensed electrician is required to install permanently wired equipment.
• Check that the power cord(s), plug(s), and sockets are in good condition.
• To reduce the risk of electric shock when grounding cannot be verified, disconnect the equipment from the AC power before installing or
connecting to other equipment. Reconnect only after all connections are made.
• Do not handle any kind of metallic connector before the power has been removed.
• Use one hand, whenever possible, to connect or disconnect signal cables to avoid a possible shock from touching two surfaces with different
electrical grounds.
•Connect the equipment to appropriate branch circuit/mains protection (fuse or circuit breaker). Connection to any other type of receptacle may
result in a shock hazard.
CAUTION!
• If the equipment has an internal energy source (the battery), the output may be energized when the unit is not connected to AC power.
• To deenergize permanently wired equipment: set the power switch to off (0 or down). Next set the AC circuit breaker to off (down). Then
disconnect the batteries (including any expansion units). Finally, disconnect the AC power from the building power supply.
•Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly effect its safety or effectiveness is not recommended.
Deenergizing Safety
WARNING!
•This equipment contains potentially hazardous voltages. Do not attempt to disassemble the unit. The unit contains no user serviceable parts.
Repairs are performed only by factory trained service personnel.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin and eyes.
• To avoid personal injury due to energy hazard, remove wrist watches and jewelry such as rings when replacing the batteries. Use tools with
insulated handles.
•Replace batteries with the same number and type of batteries as originally installed in the equipment.
Battery Safety
Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new
battery’s packing material. See the new battery instructions for more information.
Replacement and Recycling of Batteries
See your dealer or the Battery Replacement Section of this User’s Manual for information on replacement battery kits and battery recycling.
1
990-1007A, Revision 2 9/99
Initial Inspection
Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for
reuse or dispose of it properly.
Unpacking
Move the UPS, in its shipping package, as close to the desired location as possible. Then follow these instructions:
Use scissors or a knife to cut the
plastic straps and open the
package.
Unpack all visible foam pieces
and the wooden unloading
ramp.
Remove the carton liner.Unscrew the hold-down bolts
Pull out the two (2) metal bars
and set aside.
Insert the metal pallet brackets
into the holes on the unloading
ramp.
Refer to this User’s Manual
for safety information and
installation instructions.
Lift off the cardboard box that
covers the top and sides of the
package. A wooden pallet
forms the bottom of the box.
that secure the Smart-UPS DP
to the pallet.
Open the literature kit and
locate the two (2) metal pallet
brackets.
Attach the unloading ramp to
the pallet.
Have two (2) people, standing
on either side of the Smart-UPS
DP, wheel the unit down the
unloading ramp. Do not stand
in front of the UPS.
990-1007A, Revision 2 9/992
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.