APC ACSC101, ACSC100 User Manual

Operation
InRow® SC
ACSC100 ACSC101
This manual is available in English on the enclosed CD.
Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.
Deze handleiding staat in het Nederlands op de bijgevoegde cd.
Ce manuel est disponible en français sur le CD-ROM ci-inclus.
Questo manuale è disponibile in italiano nel CD-ROM allegato.
本マニュアルの日本語版は同梱の CD-ROM からご覧になれます。
Instrukcja Obs
O manual em Português está disponível no CD-ROM em anexo.
Данное руководство на русском языке имеется на прилагаемом компакт-диске.
您可以从包含的 CD 上获得本手册的中文版本。
您可以从付属的CD上获得本手册的中文版本。
ługi w jezyku polskim jest dostepna na CD.
동봉된 CD 안에 한국어 매뉴얼이 있습니다 .
Contents
General Information........................................................ 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Commissioning ............................................................... 3
Inspection Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Initial inspection checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical inspection checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mechanical inspection checklist . . . . . . . . . . . . . . . . . . . . . . . . . . 4
User interface inspection checklist . . . . . . . . . . . . . . . . . . . . . . . 5
Start-up inspection checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Final inspection checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Operation ......................................................................... 6
Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Using the Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Scrolling status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Main menu screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Navigating the main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Navigating the sub-menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Using the Path statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Password entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Start the cooling unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Stop the cooling unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling Group Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Configure the cooling group . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Identify the cooling unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Configure Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
InRow SC Operation
i
Control the Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Run hours . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Service intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Display Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Password & time-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Override the password time-out and require password entry immediately.
Date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Configure display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Display units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
. . . . . . . . . . . . . . . . . . . . .18
Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
View Status Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Scrolling status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Cooling unit status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Cooling group status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
About the cooling unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Respond to Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
View alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Clear active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Alarm messages and suggested actions . . . . . . . . . . . . . . . . . .24
Network Management Card .......................................... 27
Quick Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . . . . .27
APC Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . .28
.ini file utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
BOOTP & DHCP configuration . . . . . . . . . . . . . . . . . . . . . . . . . .28
Local access to the control console . . . . . . . . . . . . . . . . . . . . . .30
Remote access to the control console . . . . . . . . . . . . . . . . . . . .30
Control console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
ii
InRow SC Operation
Access a Configured Network Management Card . . . . . . . . . . . . . .32
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Web interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Telnet and SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Simple Network Management Protocol (SNMP) . . . . . . . . . . . . . 34
FTP/SCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Recover From a Lost Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Maintenance...................................................................36
Monthly Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Quarterly Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . .38
Semi-Annual Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . .39
Troubleshooting ............................................................40
Warranty .........................................................................42
InRow SC Operation
iii

American Power Conversion Legal Disclaimer

The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, American Power Conversion Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of evaluating data center design and construction. This Publication has been compiled in good faith by American Power Conversion Corporation. However, no representation is made or warranty given, either express or implied, as to the completeness or accuracy of the information this Publication contains.
IN NO EVENT SHALL AMERICAN POWER CONVERSION CORPORATION BE LIABLE FOR ANY DIRECT, INDIRECT, CONSEQUENTIAL, PUNITIVE, SPECIAL, OR INCIDENTAL DAMAGES (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS, CONTRACT, REVENUE, DATA, INFORMATION, OR BUSINESS INTERRUPTION) RESULTING FROM, ARISING OUT, OR IN CONNECTION WITH THE USE OF, OR INABILITY TO USE THIS PUBLICATION OR THE CONTENT, EVEN IF AMERICAN POWER CONVERSION CORPORATION HAS BEEN EXPRESSLY ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AMERICAN POWER CONVERSION CORPORATION RESERVES THE RIGHT TO MAKE CHANGES OR UPDATES WITH RESPECT TO OR IN THE CONTENT OF THE PUBLICATION OR THE FORMAT THEREOF AT ANY TIME WITHOUT NOTICE.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio, video, text, and photographs) rests with American Power Conversion Corporation or its licensors. All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to persons accessing this information.
iv
InRow SC Operation

General Information

Overview

Note the definitions for the icons here and be observant for them throughout this manual. They are intended to call attention to potential hazards and important information.

Symbols used in this manual

Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in
injury or death.
Danger:
death.
Warning: Indicates a hazard which, if not avoided, could result in personal injury or damage to product or other property.
Heavy: Indicates a heavy load that should not be lifted without assistance.
Caution: Indicates a potential hazard which, if not avoided, could result in damage to the
equipment or other property.
Tip Hazard:
moving.
Note: Indicates important information.
Indicates that more information is available on the same subject.
Indicates a hazard which, if not avoided, could result in severe personal injury or
This equipment is easily tipped. Use extreme caution when unpacking or

Cross-reference symbol used in this manual

See another section of this document or another document for more information on this subject.
1InRow SC Operation

Safety

Read and adhere to the following important safety considerations when working with this cooling unit.
®
Note: All work must be performed by American Power Conversion (APC personnel only.
Caution: Keep your hands, clothing, and jewelry away from moving parts. Check the equipment for foreign objects before closing the doors and starting the equipment.
Heavy: The equipment is heavy. For safety purposes, at least two people must be present when moving this equipment.
Tip Hazard: This equipment has a high center-of-gravity. Use extreme caution when moving.
) authorized
Electrical Hazard:
Warning: Before performing any service, properly de-energize and remove access to
the equipment (Lockout). Physically label the equipment as intentionally out of service (Tagout).
Do not wear jewelry when working near energized components.
InRow SC Operation2

Commissioning

Warning: APC authorized personnel must perform the following procedures.
Electrical Hazard: Perform Lockout/Tagout procedures on the cooling unit before
servicing the cooling unit. Failure to remove power before servicing this equipment could result in serious injury or death.
After installation is complete, verify that all components are working properly and that the cooling unit is ready to begin operation.

Inspection Checklists

Initial inspection checklist

The initial inspection ensures that the cooling unit has been properly installed, the location of the cooling unit has been properly prepared, and the cooling unit is free of damage.
Warning: The cooling unit operates under pressure. Take proper safety precautions when connecting gauges or servicing piping. Warning: Do not operate the cooling unit with any cover, guard, door, or panel removed unless the instructions indicate otherwise. Then, proceed with extreme caution. Warning: Do not run service utilities in front of the fan outlets.
unit is required for service access. To roll the cooling unit out of the row, there must be a minimum of 1200 mm (48 in) of clear floor space in front of or behind the cooling unit. Out-of-row service requires 760 mm (30 in) of side clearance in addition to the front and rear clearance.
Ensure that:
The installation procedure is complete according to the installation manual.
The walls, floor, and ceiling of the room where the cooling unit is located are sealed with a vapor barrier.
There is no evidence of damage to the cooling unit.
The cooling unit is level and joined to the adjacent racks or secured to the floor.
The clearance around the cooling unit is in accordance with local and national codes and regulations as well as the installation manual.
Caution: The vapor barrier minimizes moisture infiltration. Without a vapor barrier, it will be difficult to maintain the humidity in the room.
Caution: Do not introduce unconditioned outside air into the space.
Note: A minimum of 900 mm (36 in) of clear floor space in front of and behind the cooling
3InRow SC Operation

Electrical inspection checklist

The electrical inspection verifies that all electrical connections are secure and correct and that the cooling unit is properly grounded.
Electrical Hazard: All electrical wiring must comply with local and national codes and regulations. Electrical Hazard: The equipment must be grounded (do not use a water-pipe ground).
Ensure that the:
Incoming voltages match the phase and voltage listed on the nameplate.
Electrical wiring complies with local and national codes and regulations.
Cooling unit is properly grounded.
Electrical connections are tight, including contactors, terminal blocks, controllers, switches, relays, auxiliary devices, and field connections.

Mechanical inspection checklist

The mechanical inspection verifies that all mechanical components and connections are secure and tight and ready for start-up and system charging. The inspection ensures that field piping is properly installed to promote oil return to the compressor.
Caution: Improperly installed piping may result in improper operation and possible damage to the cooling unit or surrounding equipment.
Ensure that the:
Fans are turning freely and that the blades are not distorted or bent.
Condensate drain line is at least the size of the drain connection.
Mechanical connections are tight, including compressor and receiver connections.
Ceiling tile adapter is secured to the building structure with properly-sized safety wire.
Covers and guards are in place.
InRow SC Operation4

User interface inspection checklist

The user interface inspection verifies that the sensors and internal communications links of the cooling unit are installed properly.
Ensure that:
An A-Link bus is connected to each cooling unit in the group and a terminator is plugged into all unused A-Link connectors.
The input contacts and output relays are connected correctly.
The building management system (if used) is connected correctly.
The temperature sensor is properly routed and mounted on the front (entering air side) of the enclosure immediately to the left or right of the equipment (if InRow or RACS operating mode will be selected).
The network port is connected correctly and an IP address has been assigned to the equipment.

Start-up inspection checklist

The start-up inspection ensures that the cooling unit is operating properly after the initial start-up. This inspection verifies that all modes of operation are working correctly and that the cooling unit is ready for normal operation.
While the cooling unit is operating, ensure that the:
Cooling unit is free from malfunctions, unusual vibrations, or other irregularities in each mode of operation.
Cool cycles engage.
Cooling configuration matches the application of the cooling unit.
Air filters are clean and free of debris. Replace air filters with APC part number 875-2013.
Clogged filter alarm is operating properly: Cover 1/3 of the filter area and monitor alarm performance.
Compressor suction and discharge pressures are recorded.

Final inspection checklist

The final inspection verifies that the system is clean and the start-up form has been sent to APC.
Ensure that:
The interior and exterior of the cooling unit is clean and free from debris.
Packaging materials have been disposed of properly.
The Start-up form was completed and sent to APC.
5InRow SC Operation

Operation

Display Interface

Item Function
Critical Alarm LED (red) When illuminated, a critical alarm condition exists that requires your
immediate attention.
Warning Alarm LED (yellow) When illuminated, a warning alarm condition exists. Failure to correct this
condition could cause a critical alarm.
Check Log LED (yellow) When illuminated, at least one new event has been logged since the last
Status LED (green) When illuminated, the cooling unit is receiving electrical power. When the
Liquid Crystal Display (LCD) View alarms, status data, context-sensitive help, and modify configurable
Up and down arrow keys Select menu items and access information.
ESC key Return to previous screen or cancel current operation.
Enter key Open menu items and input changes to the cooling unit settings.
Help key Display context-sensitive help. Press the help key for information about
time the log was checked. Only events that pertain to the operation of the cooling unit will activate this LED.
LED is flashing, the cooling unit is downloading firmware for the controller. This may take a few minutes.
items.
each option on the screen and for instructions on performing the tasks.
InRow SC Operation6

Using the Display Interface

On/Standby View Alarms
View Even t Log
na1636f
Set Date & Time Set Password
Service Intervals View Run Hou rs
Every time you apply power to the cooling unit, the display interface initializes, causing the LEDs to cycle and the alarm tone to activate.

Scrolling status screens

After start-up, the interface displays the firmware revision number of the display interface. The display interface then scrolls automatically and continuously through screens of status information.
Status Screen Name Status Information Displayed
APC InRow SC Status • On/Standby
• Cooling unit name
• Cooling unit location
Group • Alarms/No Alarms
• Cool Output kW
• Cool Setpoint °C (or °F)
• Max Rack (Maximum Rack Temperature) °C (or °F)
Unit • Alarms/No Alarms
• Cool Output kW
• Air Flow CFM (cubic feet per minute) or L/s (liters per second)
• Rack Inlet °C (or °F)

Main menu screens

Press the up or down arrow key to interrupt the automatic scrolling and view a specific status screen. Screens automatically begin to scroll after five seconds of inactivity. Press the
ENTER or ESC key to return
to the main menu screen.
On any top-level status screen, press the ENTER or ESC key to open the main menu screen.
Clear Alarms
Note: If the display interface is inactive for the time configured for the password time-out, it returns to the scrolling status screens.
For information on setting the password time-out, see page 18.
Note: Pressing the up arrow key from the top line of the top screen of the main menu will take you to the top line of the bottom screen.
Clear Event Log Configure Modbus
Set Display Units Configure Display Configure Network
About InRow SC Set Identification
Configure Unit Configure Group
Set Group Setpoi nts
Set Unit Th reshld s
View Group Status View Unit Status
7InRow SC Operation

Navigating the main menu

Time: 13 :15:23
Time: 13 :15:23
Selector arrows. Press the up or down arrow key to move the selector arrow
setting. Press the
Continue arrows. Continue arrows
ENTER key to view the selected screen or modify the setting.
indicate that additional options or settings are available on a
to a menu option or
menu or status screen. Press the up or down arrow key to view the additional items.

Navigating the sub-menus

Selecting a main menu option displays the sub-menu screen for that option. Use the up or down arrow key to move the selector arrow to the setting that you wish to change, and press the
ENTER key.
Date: 29 -Jan-0 9 Format : dd-mmm -yy
na1623e
List of choices. If the setting is a list of choices, an input arrow is displayed next to the setting. Press the up or down arrow key to select the choice you want, and then press the the input mode and save the setting. Press the
ESC key to exit without saving.
ENTER key to exit
Numbers or text fields. If the setting is a number or text field, use the arrow keys to select the value of the first character, and press the the last character is set to exit the input mode and save the setting. Press the
ENTER key to move to the next. Press the ENTER key after
ESC key to exit
without saving. If an invalid value is entered, the display beeps and restores the previous valid value to the field.
Input arrows  next to a selected setting indicate that the setting can be modified by pressing the up or down arrow key. Press the
ENTER key to save the change or the ESC key to cancel the change.
Date: 29 -Jan-0 9 Format: dd-mmm-yy
na162 2b
InRow SC Operation8

Using the Path statement

Select the main- and sub-menu options specified in the path statement to view or configure a setting. The path statement lists the main- and sub-menu items you select to navigate to the item to view or modify. The parts of the path statement are defined below:
Path: Main > Set Password >Change Passwords
Main >
Set Password > Scroll to and select this option from the main menu.
Change Passwords > Scroll to and select this option from the sub-menu.
Your starting point is the main menu.
Subsequent options are listed and defined under the path statement.

Password entry

Path: Main Menu > Set Password > Change Passwords
The cooling unit has two levels of password protection:
Device password for users who need to change basic and environmental settings.
Admin password for users who need to modify settings that control the components in the cooling unit or change advanced options.
When you try to change any of the settings, the local display prompts you to enter your Admin password. The default value for both the Device and Admin passwords is apc (lower case). To enter your password, use the up or down arrow keys to scroll through the available character set. Press the
ENTER key to select
the current letter and move the cursor to the next letter position. After selecting the last letter of your password, press the
ENTER key once more to submit your password. If the Device and Admin passwords
have been configured to be unique, the Admin password can be entered for the Device password, and Admin privileges will be granted.
Once the password is entered, it remains in effect until the period of inactivity exceeds the Password Time-out setting.
See “Password & time-out” on page 18.
Note: Passwords are case-sensitive.
9InRow SC Operation

Start the cooling unit

na296 9a
Limit Access: Yes
Path: Main Menu > On/Standby
Limiting access by requiring a password: Selecting On/
Standby will display the Operate: On/Standby screen. The second line on the screen is Limit Access: Yes/No. Select Ye s to require a password in order to stop or start the unit. When the curser is on Operate: On/Standby and the
ENTER key is pressed, the screen will
display Enter Password. The password must then be entered in order to continue. If Limit Access: No is selected, a password is not required.
To start the cooling unit, change the setting to On by pressing the
ENTER key to toggle from Standby to On. At that point, the fans will
start or Unit startup in progress will appear if the Start-Up Delay option is set to restart multiple cooling units sequentially.
The cooling unit will run according to the configured settings.
Note: On/Standby only affects the local cooling unit. You must set the On/Standby option for each cooling unit in the cooling group. Note: To toggle between On and Standby from the scrolling status screens, press the key three times in rapid succession. This operation can only be done if Limit Access: Yes/No is set to No.

Stop the cooling unit

On/Standby View Alarms Clear Alarms View Event Log
Operate: On/Standby
Enter Password
********************
ENTER
Path: Main Menu > On/Standby
Note: The Limit Access: Yes/No information provided above is also applicable for shutting
down the unit.
Press the
ENTER key to change the setting to Standby. The cooling unit will enter the standby mode
Electrical Hazard: The Standby option does not remove power from the cooling unit. You must disconnect power at the mains to remove power from the cooling unit.
InRow SC Operation10
Loading...
+ 36 hidden pages