Copyright 2011 AMETEK Programmable Power. Rev C, January 2012.
2 CSW Series
User Manual California Instruments
About AMETEK
AMETEK Programmable Power, Inc., a Division of AMETEK, Inc., is a global leader in the design
and manufacture of precision, programmable power supplies for R&D, test and measurement,
process control, power bus simulation and power conditioning applications across diverse industrial
segments. From bench top supplies to rack-mounted industrial power subsystems, AMETEK
Programmable Power is the proud manufacturer of Elgar, Sorensen, California Instruments and
Power Ten brand power supplies.
AMETEK, Inc. is a leading global manufacturer of electronic instruments and electromechanical
devices with annualized sales of $2.5 billion. The Company has over 11,000 colleagues working at
more than 80 manufacturing facilities and more than 80 sales and service centers in the United
States and around the world.
Trademarks
AMETEK is a registered trademark of AMETEK, Inc. California Instruments is a trademark owned by
AMETEK, Inc. Other trademarks, registered trademarks, and product names are the property of their
respective owners and are used herein for identification purposes only.
UNLESS SPECIFICALLY AGREED TO IN WRITING, AMETEK PROGRAMMABLE POWER, INC. (“AMETEK”):
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMA GES, COSTS OR EXPENSES,
WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT
ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL
BE ENTIRELY AT THE USER’S RISK, AND
(c) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH,
ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION,
THE ACCURACY CANNOT BE GUARANTEED. APPROVED AMETEK CONTENT IS CONTAINED
WITH THE ENGLISH LANGUAGE VERSION, WHICH IS POSTED AT
WWW.PROGRAMMABLEPOWER.COM.
Date and Revision
January 2014 Revision F
Part Number
M162084
Contact Information
Telephone: 800 733 5427 (toll free in North America)
858 450 0085 (direct)
Before applying power to the system, verify that your product is configured properly for your
particular application.
WARNING
WARNING
Only qualified personnel who deal with attendant hazards in power supplies, are allowed to perform
installation and servicing.
Ensure that the AC power line ground is connected properly to the Power Rack input connector or
chassis. Similarly, other power ground lines including those to application and maintenance equipment
must be grounded properly for both personnel and equipment safety.
Always ensure that facility AC input power is de-energized prior to connecting or disconnecting any
cable.
In normal operation, the operator does not have access to hazardous voltages within the chassis.
However, depending on the user’s application configuration, HIGH VOLTAGES HAZARDOUS TO HUMAN SAFETY may be normally generated on the output terminals. The customer/user must ensure
that the output power lines are labeled properly as to the safety hazards and that any inadvertent
contact with hazardous voltages is eliminated.
Guard against risks of electrical shock during open cover checks by not touching any portion of the
electrical circuits. Even when power is off, capacitors may retain an electrical charge. Use safety
glasses during open cover checks to avoid personal injury by any sudden component failure.
Neither AMETEK Programmable Power Inc., San Diego, California, USA, nor any of the subsidiary
sales organizations can accept any responsibility for personnel, material or inconsequential injury, loss
or damage that results from improper use of the equipment and accessories.
Hazardous voltages may be present when covers are removed. Qualified
personnel must use extreme caution when servicing this equipment.
Circuit boards, test points, and output voltages also may be floating above
(below) chassis ground.
The equipment used contains ESD sensitive parts. When installing
equipment, follow ESD Safety Procedures. Electrostatic discharges might
cause damage to the equipment.
SAFETY SYMBOLS
4 CSW Series
User Manual California Instruments
CSW Series 5
User Manual California Instruments
Product Family: CSW Series Power Source
Warranty Period: 1 Year
WARRANTY TERMS
AMETEK Programmable Power, Inc. (“AMETEK”), provides this written warranty covering the
Product stated above, and if the Buyer discovers and notifies AMETEK in writing of any defect in
material or workmanship within the applicable warranty period stated above, then AMETEK may, at
its option: repair or replace the Product; or issue a credit note for the defective Product; or provide
the Buyer with replacement parts for the Product.
The Buyer will, at its expense, return the defective Product or parts thereof to AMETEK in
accordance with the return procedure specified below. AMETEK will, at its expense, deliver the
repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the
Buyer is in default under the Purchase Order Agreement or where the Product or any part thereof:
is damaged by misuse, accident, negligence or failure to maintain the same as
specified or required by AMETEK;
is damaged by modifications, alterations or attachments thereto which are not
authorized by AMETEK;
is installed or operated contrary to the instructions of AMETEK;
is opened, modified or disassembled in any way without AMETEK’s consent; or
is used in combination with items, articles or materials not authorized by AMETEK.
The Buyer may not assert any claim that the Products are not in conformity with any warranty until
the Buyer has made all payments to AMETEK provided for in the Purchase Order Agreement.
PRODUCT RETURN PROCEDURE
Request a Return Material Authorization (RMA) number from the repair facility (must be done in
the country in which it was purchased):
In the USA, contact the AMETEK Repair Department prior to the return of the
product to AMETEK for repair:
Telephone: 800-733-5427, ext. 2295 or ext. 2463 (toll free North America)
858-450-0085, ext. 2295 or ext. 2463 (direct)
Outside the United States, contact the nearest Authorized Service Center (ASC). A
full listing can be found either through your local distributor or our website,
www.programmablepower.com, by clicking Support and going to the Service Centers
tab.
When requesting an RMA, have the following information ready:
Model number
Serial number
Description of the problem
NOTE: Unauthorized returns will not be accepted and will be returned at the shipper’s expense.
NOTE: A returned product found upon inspection by AMETEK, to be in specification is subject to an
1.1 General Description ............................................................................................................................. 12
3.2 Power Requirements ........................................................................................................................... 28
3.7 Single-Phase and Three Phase Multiple Box System Configurations ................................................. 36
3.8 Output Voltage Ranges ....................................................................................................................... 37
3.9 Functional Test .................................................................................................................................... 37
3.10Tour of the Front Panel ........................................................................................................................ 43
4. Principle of Operation ............................................................................................................. 104
4.1 General .............................................................................................................................................. 104
6. Service ...................................................................................................................................... 118
6.2 General .............................................................................................................................................. 118
7. Top Assembly Replaceable Parts .......................................................................................... 121
CSW Series 7
User Manual California Instruments
7.1 Sub assemblies ................................................................................................................................. 121
10. Index .......................................................................................................................................... 180
8 CSW Series
User Manual California Instruments
List of Figures
Figure 1-1 California Instruments CSW5550 (With Rack Mount Ears) ................................................................ 12
Figure 2-1: CSW5550 – Typical Current De-Rating Chart for 156v AC Range ................................................... 17
Figure 2-2: CSW5550 – Typical Current De-Rating Chart for 312v AC Range ................................................... 18
Figure 3-8: FUNCTION keypad .......................................................................................................................... 45
Figure 3-9: Entering value from decimal keypad ................................................................................................ 46
Figure 3-10: Cursor UP key movement .............................................................................................................. 47
Figure 3-11: Cursor DOWN key movement ........................................................................................................ 47
Figure 3-12: Main Menu 1 screen ....................................................................................................................... 48
Figure 3-13: Menu 1 through 3 ........................................................................................................................... 49
Figure 3-14: PROGRAM Menu ........................................................................................................................... 53
Figure 3-15: MEASUREMENTS Screen, single phase and three phase modes ................................................ 55
Figure 8-1: Application Menu ............................................................................................................................. 124
Figure 8-2: DO160 Main Menu .......................................................................................................................... 124
Figure 8-3: Normal state .................................................................................................................................... 125
Figure 8-4: Voltage Modulation ......................................................................................................................... 127
Figure 8-5: Frequency Modulation ..................................................................................................................... 128
CSW Series 9
User Manual California Instruments
Figure 8-6: Power Interrupt ............................................................................................................................... 129
Figure 8-7: Power Interrupt for Group 2 and 3 .................................................................................................. 130
Figure 8-10: DO-160 DC Main Menu ................................................................................................................ 135
Figure 8-11: Normal State ................................................................................................................................. 135
Figure 8-12: Abnormal State ............................................................................................................................. 137
Figure 8-13: Application menu .......................................................................................................................... 141
Figure 8-14: IEC1000-4-11 Menu ...................................................................................................................... 141
Figure 8-15: IEC Dips and Interrupts ................................................................................................................. 142
Figure 8-16: Voltage Variation screen ............................................................................................................... 144
Figure 8-17: EN 61000-4-11 Voltage Variation specification- Edition 1.0 .......................................................... 145
Figure 8-18: EN 61000-4-11 Voltage Variation specification- Edition 2.0 .......................................................... 145
Figure 8-32: Application Menu .......................................................................................................................... 161
Figure 8-33: MIL704 Menu ............................................................................................................................... 161
Figure 8-34: Steady State Menu ....................................................................................................................... 161
Figure 8-35: Transient Menu ............................................................................................................................. 164
Figure 8-36: Emergency Menu ......................................................................................................................... 165
Figure 8-38: MIL704 DC Menu .......................................................................................................................... 167
Figure 8-39: Steady State DC .......................................................................................................................... 167
Figure 8-40: Transient Menu ............................................................................................................................ 168
Figure 8-41: Abnormal Test Screen .................................................................................................................. 169
Figure 8-42: Emergency Test ............................................................................................................................ 170
Table 7-1: Replaceable Parts ........................................................................................................................... 121
Table 8-1: Normal Voltage and Frequency minimum ........................................................................................ 125
Table 8-2: Normal Voltage and Frequency Maximum ........................................................................................ 125
Table 8-3: Normal Voltage Unbalance ............................................................................................................... 126
Table 8-4: Normal VoltageSurge Sequence ...................................................................................................... 130
Table 8-5: Normal Frequency Transient Sequence ........................................................................................... 131
Table 8-6: Normal Frequency Variation Sequence ............................................................................................ 131
Table 8-7: Emergency Voltage and Frequency Minimum .................................................................................. 132
Table 8-8: Emergency Voltage and Frequency Maximum ................................................................................. 132
Table 8-9: Emergency Voltage Unbalance ........................................................................................................ 132
Table 8-10: Abnormal Voltage Minimum ........................................................................................................... 133
Table 8-11: Abnormal Voltage Maximum .......................................................................................................... 133
Table 8-12: Abnormal Frequency Transient ...................................................................................................... 134
Table 8-13: Normal Voltage Minimum ............................................................................................................... 135
Table 8-14: Normal Voltage Maximum .............................................................................................................. 136
Table 8-15: Voltage Surge ................................................................................................................................. 136
Table 8-16: Abnormal Voltage Surge ................................................................................................................ 138
This instruction manual contains information on the installation, operation, calibration and
maintenance of all power systems that use the CSW5550.
This user manual also covers higher power configurations consisting of multiple units of the
CSW5550 operated in parallel. Such models are the CSW11100, CSW16650, CSW22200,
CSW27750, CSW33300, CSW38850 and CSW44400.
Figure 1-1 California Instruments CSW5550 (With Rack Mount Ears)
1.1 General Description
The CSW5550 is a high efficiency, lightweight AC power source that provides a precise output
with low distortion. The CSW Series offers a 0-156/0-312 AC or DC voltage range. Full power
is available from 115/230V to full-scale voltage using a constant power mode of operation.
Two to eight CSW5550 units can be connected in parallel as a single-phase or 3-phase power
system for an output of up to 44.4 KVA. They can be operated with AC or DC output.
The CSW5550 Series also offers AC+DC output mode.
Remote Interfaces
The CSW5550 has the standard GPIB, RS232 and USB remote interfaces. The LAN (Ethernet)
interface is offered as an option. With the LAN interface the RS232 interface will not be
functional.
AC Line Input Options
PFC USA = C
PFC International = G
Hardware Options
No Option = X
LKM = J
LKS = K
LF = H
LF & LKM = A
Firmware Options CODE
None 0 0 0 0
-RTCA/DO160 1 0 0 0
-IEC61000-4-11 0 4 0 0
-Mil Std 704 0 2 0 0
-704F 0 1 0 0
-A350 0 0 8 0
-ABD 0 0 4 0
-ABL 0 0 2 0
-AMD 0 0 0 8
-B787 0 0 0 4
-WHM 0 0 0 1
For multiple options use the HEX sum. For example A350 and ABD would be
00D0
Sum of 0 –9 = HEX 0 –9. Sum of 10 – 15 = HEX A - F
CSW Series 13
User Manual California Instruments
2. Specifications
All specifications are for a single CSW5550 unit and 25 5C sine wave output with a resistive
load unless noted otherwise.
2.1 Electrical
2.1.1 Input
Function Specification
Input Power
Input Power Factor 0.99
Input Frequency Range 47 to 440 Hz
Efficiency 70% minimum at full-load
Ride-through or hold-up 10 mSec, minimum
Input Current See Table below
Input Turn-on Current
Surge
MAXIMUM LINE
CURRENT
USA 27A RMS Not Required 40A RMS
INTL 14A RMS 14A RMS 20A RMS
Standard: 208 to 240V
option: 380 to 415V
±10%, 3, 3 wire or
L-L
±10%, 3, 4 wire
L-L
Limited to less than peak value of RMS listed
in Tables below
MAXIMUM
NEUTRAL
CURRENT
Input Currents for 3-Phase Input Power
RECOMMENDED
CIRCUIT BREAKER
RATING (MAX.)
REQ’D INPUT
TERMINAL JUMPER
CONNECTIONS
USA ØA to ØB ØA, ØC
INTL
ØA to ØB,
ØB to ØC
CONNECT 1-
PHASE INPUT
POWER TO
ØA, Neutral
VOLTAGE
187-264
VRMS, L-L
187-264
VRMS, L-N
MAXIMUM
INPUT
CURRENT
RECOMMENDED
CIRCUIT BREAKER
RATING (MAX.)
30A RMS 40A RMS
45A RMS 40A RMS
* Only Phase A and Phase B are present at the output.
Single-Phase Input Configurations
14 CSW Series
User Manual California Instruments
2.1.2 Output
(ALL SPECIFICATIONS ARE FOR AC AND DC UNLESS NOTED OTHERWISE)
Function Specification
Calibration Interval
Power Factor of Load 0 lagging to 0 leading
AC or DC Output
Voltage
Output Current Per
Phase
Crest Factor 3.25 (peak output current to RMS output current).
Output Frequency DC, or 40 Hz to 5 kHz
Frequency Resolution
( Without CLock/Lock
option enabled)
Frequency Accuracy: ±0.01% at 25ºC ±0.001%/ºC
Output Power 1850 VA, maximum, per phase
AC Noise Level >60 dB RMS below full output (sine wave, 40 to 500 Hz).
Voltage Program and
Measurement
Accuracy
Voltage Program
resolution
Voltage Stability
Voltage Distortion 0.25% maximum, 40 to 100 Hz; 0.5% maximum to 500 Hz; and 1% maximum
Load Regulation ±0.025% of full scale voltage for a full resistive load to no load; above 1 kHz,
Line Regulation ±0.025% of full scale for a ±10% input line change.
Phase Accuracy
Resistive Load
Phase Program
Resolution
External Amplitude
Mod
External Direct Input 0 to 5 VRMS (DC to 5 kHz) for 0 to full-scale output (±2% of full scale output to
DFI output Contact closure to indicate: Loss of AC line and indication of various Status
1 year
0 to 156 VRMS L-N range ; 0 to 312 VRMS L-N range
16A to 115V in 156V range; 8.0A to 230V in 312V range (1850 VA maximum).
Multiply current by the number of sources in a multiple power source system
±0.1% of range. Above 1 kHz, add 0.2%/kHz. Add ±0.1% of full scale for "AC
PLUS DC" mode. Valid for 5 to 156 VRMS and 10 to 312 VRMS at 25°C
(77°F), sense leads connected. Temperature coefficient less than 50 ppm/°C
0.1 V from Front Panel
0.01 V from remote programming
±0.1% of full scale over 24 hours at constant line, load and temperature.
(Measured at Remote Sense point)
to 1 kHz plus 1%/kHz to 5 kHz (Full linear load or No load)
add ±0.015%/kHz
±1º, 40 to 1 kHz plus ±1º/kHz above 1 kHz
±0.1º
0 to 5 VRMS provides 0 to 20%(±2% of full scale output)
3 kHz. ±2% from 3 kHz to 5 kHz). Limited to ±7.25 Vpeak
that can be remotely programmed.
CSW Series 15
User Manual California Instruments
Function Specification
External Gain Control, RPV 0 to +7.07 VDC for 0 to programmed output. 0 to full-scale output for CSW.
(±2% of full scale output
External Input Impedance 40K for each of the three inputs.
XLOAD The CSW5550 is guaranteed to be stable for power factors from 0 leading to 0
lagging. The most difficult load for most amplifiers is driving large capacitive
loads (10-10,000F).Though stable with its normal loop compensation, the
CSW can provide additional phase/gain margin with these unusual loads by
selecting XLOAD On. This significantly improves the transient response of the
amplifier.
X-Load should only be used for reactive loads, and with programmed
frequencies of less than 1000 Hz.
Output current for which specifications apply is de-rated for frequencies above 400Hz as a function of
voltage, and for maximum power of 1850 VA per phase, as shown in Figure 2-1 and Figure 2-2.
16 CSW Series
User Manual California Instruments
OUTPUTCURRENTDE‐RATINGFROM45HzTO5kHz
Current
(RMS)
16
14
12
10
8
6
4
2
0
10
03570105140
156
Figure 2-1: CSW5550 – Typical Current De-Rating Chart for 156v AC Range
per Phase
<400Hz
1KHz
2KHz
3KHz
4KHz
5KHz
Voltage (RMS)
CSW Series 17
User Manual California Instruments
OUTPUTCURRENTDE‐RATINGFROM45HzTO5kHz
Current
(RMS)
8
7
6
5
4
3
2
1
0
070140210280
20
<400Hz
1Khz
2Khz
3KHz
4KHz
5KHz
312
Figure 2-2: CSW5550 – Typical Current De-Rating Chart for 312v AC Range
per Phase
Voltage (RMS)
18 CSW Series
User Manual California Instruments
Output Parameter CSW5550 (multiply current and power by the number of power
sources in multi-source power systems)
Current Limit
Range Programmable 0 to 100% of range for all ranges
Resolution 0.01 Arms
Accuracy ± 1% of Range. Add ±1.5%/kHz above 500 Hz
Frequency Range:
(Without Cloc/ Lock
option enabled)
Frequency Accuracy:
IEEE 488.2 and SCPI
Response time is 10 ms (typical)
RS232C Interface: Bi-directional serial interface
9 pin D-shell connector
Handshake: CTS, RTS
Data bits: 7, 8
Stop bits: 1,2
Baud rate: 9600, 19200, 38400 (Models without USB I/F)
Baud rate: 9600, 19200, 38400, 57600, 115200, 230400, 460800
IEEE 488.2 and SCPI.
Note: Disconnect any USB connection when using the RS232 interface.
USB Interface: Standard USB 1.1 peripheral.
Data transfer rate: 460,800 bps
Syntax: IEEE 488.2 and SCPI.
Note: Use of the USB port to control more than one power source
from a single PC is not recommended, as communication may not be
reliable. Use GPIB interface for multiple power source control.
LAN Interface: Option –LAN. When the LAN interface is installed, the RS232 interface is
disabled.
RJ45 Connector, 10BaseT, 100BaseT or 1000BaseT,
Data transfer rate: 460,800 bps
Protocol: TCP/IP.
Syntax: IEEE 488.2 and SCP
Note: Disconnect any USB connection when using the LAN interface.
Current Limit
Modes:
Two selectable modes of operation.
Constant current and constant voltage with hold-off time and trip.
22 CSW Series
User Manual California Instruments
System Specification (continued)
Parameter Specification
Front Panel Trigger,
BNC connector
Output available at the front panel BNC connector that provides a
negative going pulse for any programmed voltage or frequency
change. The trigger can be reassigned as an output when running list
transients.
Front Panel Phase
A, B and C, BNC
connectors
These three outputs are representative of the programmed output
waveform, magnitude and frequency. 0 to 4.86 Vrms represents 0 to a
full-scale output voltage. The output impedance is 100 ohms.
External Signal Individual inputs for an external signal for each of the three phases. A 0
to 5.0 Vrms input provides a 0 to full-scale output voltage of the supplied
waveform
External Gain
Control (RPV)
Individual inputs for an external DC signal for each of the three phases. A
0 to ±7.07 VDC signal provides a 0 to full-scale output voltage.
/INHIBIT A logic Lo or contact closure input to inhibit the outputs
MOD An input for an amplitude modulation. 0 to 5 Vrms provides 0 to ≥20%
modulation for each of the three output phases
Trigger Input An input to trigger a function
External Synch A TTL input to frequency synchronize the outputs. The Phase A output
can be programmed relative to the external input.
2.1.6 Unit Protection
Parameter Specification
Input Overcurrent: Circuit breaker with current trip control.
Input Overvoltage: Automatic trip of input circuit breaker.
Input Overvoltage
Transients:
Output Overcurrent: Adjustable level constant current mode with a maximum set point
Output Short Circuit: Peak and rms current limit.
Overtemperature: Automatic shutdown.
Surge protection to withstand EN50082-1 (IEC 801-4, 5) levels.
between 0% and 10% above programmed value.
CSW Series 23
User Manual California Instruments
2.2 Mechanical
Parameter Specification
Dimensions: 19” (483 mm) wide x 8.75” (222 mm) high x 23.5” (597 mm) deep
chassis size which is available in a rack mount or stand-alone
configuration.
Unit Weight: 126.5 lb. (57.2 kg)
Material: Steel chassis and front panel, Aluminum top cover and rear panel.
Finish: Light textured painted external surfaces.
Front and rear panels semi-gloss polyurethane color no. 26440
(medium gray)
Top, bottom and sides semi-gloss polyurethane color no. 26622 (light
gray).
Cooling: Fan cooled with air intake on the sides and exhaust to the rear.
Internal
Construction:
Rear Panel
Connections:
2.3 Environmental
Parameter Specification
Operating Temp:
Storage Temp:
Altitude: < 2000 m
Modular sub assemblies.
(see section 3 for description of connections)
Input terminal block with cover
Output terminal block with cover
Remote voltage sense terminal block with cover
System interface (not for table top use, use only in rack enclosed
systems)
Clock and Lock (not for table top use, use only in rack enclosed
systems)
RS232, GPIB, USB, LAN (option)
0 to +45 C (32F to 113F)
-40 to +70C.
Relative Humidity:
Installation/Over voltage
Category:
Pollution Degree: 2
Indoor Use Only
Vibration: Designed to meet NSTA 1A transportation levels.
Shock: Designed to meet NSTA 1A transportation levels.
24 CSW Series
85% maximum at 25C decreasing linearly to 50% at 40C.
User Manual California Instruments
2.4 Regulatory
Electromagnetic
Emissions and Immunity:
Acoustic Noise: 65 dBA maximum at 0% to 50% load, 75 dBA maximum greater
Safety: Designed EN61010-1 European safety standards as required for
2.5 Front Panel Controls
Controls:
Shuttle knob: Allows continuous change of all values including output calibration
Decimal keypad: A conventional decimal keypad facilitates quick entry of numerical
Up/down arrow keys: A set of up and down arrow keys is used to move the cursor
Designed to meet EN50081-2 and EN50082-2 European
Emissions and Immunity standards as required for the “CE” mark.
than 50% load to 100% load. Measured at one meter.
the “CE” mark.
and range change.
values such as voltage, current limit, etc. The large blue enter
key will make the value you enter effective. Using the SET key
allows the user to preset all parameter values and update them all
at once by pressing the Enter key.
position in all menus. This allows quick selection of the desired
function or parameter.
Function keys: Measure key will display most measurement values. Program key
will show all program parameters. Output on/off key for output
relay control. Phase key will switch display to show program and
measured values for each phase.
Displays:
LCD graphics display: A large high contrast LCD display with backlight provides easy to
read guidance through all setup operations.
Status indicators: Large and bright status indicators inform the user of important
power source conditions. The Remote lamp informs the user that
the unit is under remote control. The Overload lamp indicates that
excessive current is being drawn at the output. The Over
temperature lamp illuminates when internal heat sink
temperatures are too high. The Hi Range indicator is lit any time
the unit is switched to high output voltage range. The Output
On/Off indicator is on when the power source output relays are
closed.
CSW Series 25
User Manual California Instruments
2.6 Special Features, Options and Accessories
Option Description
- 704 Mil Std 704D & E test firmware.
Mil Std 704A, B, C, & F test software (refer to Avionics Software Manual P/N
4994-971 for details).
Note: Requires use of CSWGui Windows application software provided on
CD ROM CIC496.
- 787 Boeing 787 Test software (refer to Avionics Software Manual P/N 4994-971
for details).
Note: Requires use of CSWGui Windows application software provided on
CD ROM CIC496.
- 160 RTCA/DO-160D test firmware
RTCA/DO-160E test software (refer to Avionics Software Manual P/N 4994971 for details)..
Note: Requires use of CSWGui Windows application software provided on
CD ROM CIC496.
- 411 IEC 1000-4-11 test firmware
- 413 IEC 1000-4-13 test hardware and firmware
-ABD Airbus ABD0100.1.8 Test software (refer to Avionics Software Manual P/N
4994-971 for details)..
Note: Requires use of CSWGui Windows application software provided on
CD ROM CIC496.
-AMD Airbus AMD24C Test software (refer to Avionics Software Manual P/N 4994971 for details)..
Note: Requires use of CSWGui Windows application software provided on
CD ROM CIC496.
-LAN Adds Ethernet interface (RJ45 connector) for local area network connection.
(Available on P/N 7000-485 and 7000-486 models only).
-LF Limits maximum output frequency to 500 Hz.
-FC Frequency accuracy is ± 0.15% of program value.
-LK Clock/ Lock Option. With this option enabled the programmed frequency
resolution is 1 Hz for all programmed values of frequency. If the upper
frequency limit is 819 Hz or less the standard program resolution applies.
26 CSW Series
User Manual California Instruments
V
2.7 Supplemental Specifications
Supplemental specifications are not warranted and generally reflect typical performance
characteristics. These characteristics have been checked on a type test basis only and are not
verified on each unit shipped. They are provided for reference only.
2.7.1 Output
Output Parameter
oltage:
Slew rate: > TBD V/micro sec
Stability: 0.25 % over 24 hour period at constant line, load and temperature.
Settling time: < 0.5 msec
Frequency:
Temperature
coefficient:
Stability:
5 ppm per degree C
15 ppm per year
CSW Series 27
User Manual California Instruments
3. Unpacking and Installation
3.1 Unpacking
Inspect the unit for any possible shipping damage immediately upon receipt. If damage is
evident, notify the carrier. DO NOT return an instrument to the factory without prior approval.
Do not destroy the packing container until the unit has been inspected for damage in shipment.
WARNING: This power source weighs 126.5 lb (57.2kg). Obtain adequate help when
moving or mounting the unit.
3.2 Power Requirements
The CSW5550 Power Source has been designed to operate from a 3-phase, 3-wire, 187 to 264
, AC line or a 3-phase, 4-wire, 342 to 457 V
V
L-L
CAUTION: Do not connect 400V into the 187-256V unit, the result could be a severely
damaged unit.
,AC line (option -400).
L-L
28 CSW Series
Figure 3-1:CSW5550
User Manual California Instruments
3.3 Mechanical Installation
The CSW series power sources are completely self-contained power sources. They may be
used free standing on a bench top or rack mounted using the rack mount/handle kit. The units
are fan cooled, drawing air in from the sides and exhausting at the rear. The sides of each unit
must be kept clear of obstruction and a 6” clearance must be maintained to the rear. Special
consideration of overall air flow characteristics and the resultant internal heat rise must be
allowed for with systems installed inside enclosed cabinets to avoid self heating and over
temperature problems.
Refer to Paragraph 2.2 for information on outline and mounting dimensions of the unit. Refer to
Figure 3-3, Paragraph 3.6 and sub-paragraphs for rear panel connector information.
TYPE MANUFACTURER PART NUMBER
Mounting Kit (for slides) Jonathan BK-3
Slides Accuride C-3307-16D
Recommended Mounting Slide
3.4 Input Wiring – TB1
The input terminal block, TB1, is located at the rear of the unit. Ground (earth) wire must be
connected to the chassis of the AC power system. The mains source must have a current rating
equal to or greater than the input circuit breaker and the input wiring must be sized to satisfy the
applicable electrical codes. The input terminal block cover and strain relief must be installed in
table top applications to maintain protection against hazardous voltages.
CAUTION: Capacitors in the power source may hold a hazardous electrical charge
even if the power source has been disconnected from the mains supply. Allow
capacitors to discharge to a safe voltage before touching exposed pins of mains
supply connectors.
3.4.1 187 to 264 VRMS L–L 3-Phase Operation (3-Wire USA)
Connect the input wires to the phase A, B, and C input terminal block terminals
(no Neutral is required). Ensure that the chassis safety ground is also connected. Use cables with
ratings equal to or greater than the current rating listed on the unit or in Paragraph 3.5.1. Any phase
sequence of wiring can be used.
3.4.2 342 to 457 VRMS L–L 3-Phase Operation (4-Wire INTL)
It is essential that the Neutral connection is present when using the unit. Only units that are factory set at
this voltage will operate at this voltage.
Connect the input wires to phases A, B, C and Neutral of the input terminal block. Ensure that the chassis safety ground is also connected. Use cables with ratings equal to or greater than the current
rating listed on the unit or in paragraph 2.1.1.
CSW Series 29
User Manual California Instruments
3.4.3 Single-Phase Input Connections
The CSW system is designed for three-phase input power operation, either 3-wire (USA) or 4-wire
(EUR) plus a chassis safety ground. However, if only single-phase input power is available, the
configurations listed in paragraph 2.1.1 are possible.
3.5 Output Power Connections – TB2
The output terminal block, TB2, is located at the rear of the unit. Refer to Figure 3-3 for an illustration of
the power source rear panel and all terminal strips and connectors. The external sense inputs allow the
power system output voltages to be monitored directly at the load and must be connected either at TB2
or the load when the sense is programmed for external. The external sense input does not have to be
connected when Internal Sense is programmed. The external sense wires are to be connected to TB3
on the rear panel and should be run as a twisted pair for short lengths. Sense leads over three (3) feet
long should be run as a twisted shielded pair. Refer to Figure 3-4 for all connections. Included in the
power source ship-kit is a safety cover. This cover is used to cover the AC Line input, TB1, the Power
Output terminal block, TB2, and the External Sense terminal block, TB3. Strain reliefs are included with
the safety cover.
Note: The output of the power source is isolated from the input line and floating from
chassis ground. The Output Neutral must not float more than 20 volts or an error
will be reported and the output will shut down.
3.5.1 Wire Gauge Selection
The following guidelines assist in determining the optimum cable specification for
your power applications. These guidelines are equally applicable to both DC and low frequency AC (up
to 450 Hz) power cabling. The same engineering rules apply whether going into or out of an electrical
device. Thus, this guide applies equally to the input cable and output cable for this California Instrument
power source and application loads.
Power cables must be able to safely carry maximum load current without overheating or causing
insulation destruction. It is important to everyday performance to minimize IR (voltage drop) loss within
the cable. These losses have a direct effect on the quality of power delivered to and from instruments
and corresponding loads.
When specifying wire gauge, the operating temperature needs to be considered. Wire gauge current
capability and insulation performance drops with the increased temperature developed within a cable
bundle and with increased environmental temperature. Thus, short cables with generously derated
gauge and insulation properties are recommended for power source applications.
Avoid using published commercial utility wiring codes. These codes are designed for the internal wiring
of homes and buildings and accommodate the safety factors of wiring loss, heat, breakdown insulation,
aging, etc. However, these codes consider that up to 5% voltage drop is acceptable.
Such a loss directly detracts from the quality performance specifications of this power source.
Frequently, these codes do not consider bundles of wire within a cable arrangement.
In high performance applications, as in motor start-up and associated inrush/ transient currents,
additional consideration is required. The cable wire gauge must consider peak voltages and currents,
which may be up to ten times the average values. An underrated wire gauge adds losses, which alter
the inrush characteristics of the application and thus the expected performance. The following table
identifies popular ratings for DC and AC power source cable wire gauges.
30 CSW Series