Altronix AL400ULXB2 Installation Instructions

0 (0)
Altronix AL400ULXB2 Installation Instructions

AL400ULXB2

UL Recognized Power Supply/Charger

Overview:

The AL400ULXB2 is a power supply/charger that converts a 115VAC 60Hz input into a Class 2 Rated power-limited 12VDC or 24VDC output (see specifications).

Specifications:

Agency Listings:

 

Battery Backup:

 

• UL Recognized component for: Access Control

 

• Built-in charger for sealed lead acid or gel type batteries.

System Units (UL 294), Power Supplies for use with

 

• Maximum charge current 0.7 amp.

Burglar-Alarm Systems (UL 603), Hospital Signaling

 

• Automatic switch over to stand-by battery when AC fails.

and Nurse Call Equipment (UL 1069), Power Supplies

 

• Zero voltage drop when switched over to battery backup.

for Fire Protective Signaling Systems (UL 1481).

 

Visual Indicators:

Input Rating:

 

• AC input, DC output and Battery LED indicators.

• Input 115VAC 60Hz, 3.5 amp.

 

Supervision:

Output Rating:

 

• AC fail supervision (form “C” contacts).

• Class 2 Rated power-limited output.

 

• Low battery and battery presence supervision

• 12VDC or 24VDC selectable output.

 

(form “C” contacts).

• 12VDC @ 4 amp or 24VDC @ 3 amp continuous

 

Additional Features:

supply current.

 

• Short circuit and thermal overload protection.

• Filtered and electronically regulated output.

 

Board Dimensions (W x L x H approximate):

 

 

4.5” x 7.1” x 1.44” (114mm x 180mm x 37mm)

 

 

Power Supply Voltage Output Selections:

Output

Switch Position

 

 

12VDC

SW1 - CLOSED (Fig. 1, on the right)

 

 

24VDC

SW1 - OPEN (Fig. 1, on the right)

 

 

 

Fig. 1

 

Switch Detail

Opened - 24V

SW1

 

Closed - 12V

 

 

OPEN SWITCH

 

 

CLOSED SWITCH

 

 

Stand-by Specifications:

Output

4 hr. of Stand-by &

24 hr. of Stand-by &

60 hr. of Stand-by &

5 Minutes of Alarm

5 Minutes of Alarm

5 Minutes of Alarm

 

12VDC / 40AH Battery

Stand-by = 4.0 amp

Stand-by = 1.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

Alarm = 4.0 amp

Alarm = 4.0 amp

 

24VDC / 12AH Battery

--------

Stand-by = 200mA

--------

Alarm = 3.0 amp

 

 

 

24VDC / 40AH Battery

Stand-by = 3.0 amp

Stand-by = 1.0 amp

Stand-by = 300mA

Alarm = 3.0 amp

Alarm = 3.0 amp

Alarm = 3.0 amp

 

Installation Instructions:

The AL400ULXB2 should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes.

1.Mount the AL400ULXB2 in the desired location/enclosure.

2.Set the AL400ULXB2 to the desired DC output voltage by setting SW1 (Fig. 2, pg.­2) to the appropriate position (refer to Power Supply Voltage Output Selections chart).

3.Connect AC power (115VAC 60Hz) to the terminals marked [L, G, N] (Fig. 2, pg.­2). Use 18 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits

(AC Fail/Low Battery reporting).

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.

4.Connect devices to be powered to the terminals marked [+ DC –] (Fig. 2, pg.­2).

5.Measure output voltage before connecting devices. This helps avoiding potential damage.

6.For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

Connect battery to the terminals marked [+ BAT –] (Fig. 2, pg.­2). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included).