Altronix ACMS8CB, ACMS8CBK1, ACMS8K1 Installation Guide

0 (0)

ACMS8 Series

Sub-Assembly

Access Power Controllers

Installation Guide

Models Include:

ACMS8

- Eight (8) Fuse Protected Outputs

ACMS8CB

- Eight (8) PTC Protected Outputs

 

 

 

 

 

 

 

 

 

 

 

 

Rev. 090518

More than just power.TM

Overview:

Altronix ACMS8(CB) Access Power Controller’s dual input design allows power to be steered from two (2) independent low voltage 12 or 24VDC power sources to eight (8) independently controlled fuse (ACMS8) or PTC (ACMS8CB) protected outputs. Power outputs of ACMS8(CB) can be converted to dry form “C” contacts. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. ACMS8(CB) will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power to multiple ACMS8(CB) modules. This feature allows you to distribute the power over more outputs for larger systems.

Specifications:

Power Supply Input Options:

Input 1 and Input 2 voltage range:

ACMS8: 5VDC to 24VDC, up to 10A each, 20A total input.

ACMS8CB: 5VDC to 24VDC up to 10A each, 16A total input.

Eight (8) trigger inputs:

a)Normally open (NO) inputs.

b)Normally closed (NC) inputs.

c)Open collector sink inputs.

d)Wet Input (5VDC - 24VDC) with 10K resistor

e)Any combination of the above.

Outputs:

ACMS8:

Fuse protected outputs rated @ 2.5A

 

per output, non power-limited.

 

Total output 20A max.

 

Do not exceed the individual

power supply ratings. ACMS8CB: PTC protected outputs rated @ 2A

per output, Class 2 power-limited. Total output 16A max.

Do not exceed the individual power supply ratings.

Total output current should not exceed max. current rating of the power supplies employed on each input. See Maximum Output of Altronix Power Supplies.

Eight (8) selectable independently controlled outputs or eight (8) indepently controlled Form “C” relay outputs (see below for ratings):

a)Fail-Safe and/or Fail-Secure power outputs.

b)Form “C” relays rated @ 2.5A.

c)Auxiliary power outputs (unswitched).

d)Any combination of the above.

Individual outputs may be set to OFF position for servicing (output jumper set to middle position). Does not apply to Dry Contact applications.

Outputs (cont’d):

Any of the eight (8) fuse/PTC protected power outputs are selectable to follow power Input 1 or Input 2. Output voltage of each output is the same as the input voltage of the input selected.

Surge suppression.

Fire Alarm Disconnect:

Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the

eight (8) outputs.

Fire Alarm disconnect input options:

a)Normally open [NO] or normally closed [NC] dry contact input. Polarity reversal input from FACP signaling circuit.

FACP output relay [NC] contact or provides 10k resistance with [EOL JMP] intact.

Outputs Ratings:

ACMS8: Fuses are rated 2.5A each.

ACMS8CB: PTCs are rated 2A each.

Fuse Ratings:

Main input fuses rated @ 10A/32V each.

LED Indicators:

Red LEDs indicate outputs are triggered.

Blue LED indicates FACP disconnect is triggered.

Individual voltage LED indicates 12VDC (Green) or 24VDC (Red/Green).

Environmental:

Operating temperature: 0ºC to 49ºC ambient.

Humidity: 20 to 93%, non-condensing.

Mechanical:

Board Dimensions (W x L x H approximate): 7.65” x 4.125” x 1.25”

(194.3mm x 104.8mm x 31.8mm).

Product weight (approx.): 0.7 lb. (0.32 kg).

Shipping weight (approx.): 0.95 lb. (0.43 kg).

- 2 -

ACMS8/CB Sub-Assembly

Altronix ACMS8CB, ACMS8CBK1, ACMS8K1 Installation Guide

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code NFPA 70/NFPA 72/ ANSI / Canadian Electrical Code / CAN/ULC-S524/ULC-S527/ULC-S537, and with all local codes and authorities having jurisdiction. Product is intended for indoor dry use only.

1. Refer to Sub-Assembly Installation Instruction for mounting Rev. MS050913.

Carefully review:

 

 

Terminal Identification Table

(pg. 4)

Typical Application Diagram

LED Diagnostics

(pg. 4)

Hook-up Diagrams

2.Ensure all output jumpers [OUT1] - [OUT8] are placed in the OFF (center) position.

3.Connect low voltage DC power supplies to terminals marked [+ PWR1 –], [+ PWR2 –]

4.Set each output [OUT1] - [OUT8] to route power from power supply 1 or 2

(Fig. 1, pg. 3).

Note: Measure output voltage before connecting devices. This helps avoiding potential damage.

5.Turn power off before connecting devices.

6.Output options: The ACMS8(CB) will provide up to eight (8) switched power outputs or eight (8) dry form “C” outputs, or any combination of both switched power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.

Switched Power outputs:

Connect the negative (–) input of the device being powered to the terminal marked [COM].

(pg. 7) (pg. 8-9)

Fig. 1

PWR1

PWR2

OFF

For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC].

For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].

Form “C” outputs:

When form “C” outputs are desired, the corresponding jumper (1-8) must be placed in the OFF position (Fig. 1, pg. 3). Alternatively, the corresponding output fuse (1-8) can be removed (ACMS8 only). Connect negative (–) of the power supply directly to the locking device.

Connect the positive (+) of the power supply to the terminal marked [C].

For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked [NC].

For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].

Dry contacts rated @ 3A.

Auxiliary Power outputs (unswitched):

Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.

7.Turn main power on after all devices are connected

8.Input Trigger options:

Note: If Fire Alarm disconnect is not used, connect a 10K ohm resistor to terminals marked [GND and EOL], plus connect a jumper to terminals marked [GND, RST].

Normally Open (NO) Input:

 

 

 

Fig. 2

Slide input control logic DIP switch into the ON position for [Switch 1-8]

 

 

 

INP Logic

 

(Fig. 2, on right). Connect your wires to terminals marked

 

[+ INP1 –] to [+ INP8 –].

NO <-- > NC

Normally Closed (NC) Input:

 

 

 

1

 

 

 

Slide input control logic DIP switch into the OFF position for [Switch 1-8]

 

 

 

2

 

 

 

 

 

 

(Fig. 2, on right). Connect your wires to terminals marked

ON

 

 

3

 

 

 

 

[+ INP1 –] to [+ INP8 –].

 

 

4

 

 

Open Collector Sink Input:

 

 

 

 

Connect the open collector sink input to the terminal marked

 

 

 

 

[+ INP1 –] to [+ INP8 –].

 

 

 

 

Wet (Voltage) Input Configuration:

 

 

 

 

Carefully observing polarity, connect the voltage input trigger wires and the supplied 10K resistor to

 

terminals marked [+ INP1 –] to [+ INP8 –].

 

 

 

 

If applying voltage to trigger input - set the corresponding INP Logic switch to the “OFF” position

 

If removing voltage to trigger input - set the corresponding INP Logic switch to the “ON” position.

 

ACMS8/CB Sub-Assembly

- 3 -

9. Fire Alarm Interface options:

Fig. 3

A normally closed [NC], normally open [NO] input or polarity reversal input from

FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding DIP switch [SW1-SW8] ON.

To disable FACP disconnect for an output turn the corresponding DIP switch [SW1-SW8] OFF. Switch is located directly to the left of the

Fire Alarm Interface Terminals.

Normally Open Input:

Wire your FACP relay and 10K resistor in parallel on terminals marked

FACP

EN <-- > DIS

 

 

 

1

 

 

 

 

 

 

2

 

 

 

ON

 

 

3

 

 

 

 

4

 

 

 

[GND] and [EOL].

Normally Closed Input:

Wire your FACP relay and 10K resistor in series on terminals marked [GND] and [EOL].

FACP Signaling Circuit input trigger:

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked [+ FACP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm condition).

Non-Latching Fire Alarm Disconnect:

Connect a jumper to the terminals marked [GND, RST].

Latching Fire Alarm Disconnect:

Connect a NO normally open reset switch to terminals marked [GND, RST].

10.FACP Dry NC output:

Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NC] and [C]. When [EOL JMP] is kept intact, the output is of 0 Ohm resistance in a normal condition.

When [EOL JMP] is clipped, a 10k resistance will be passed to next device when in a normal condition.

LED Diagnostics:

ACMS8 and ACMS8CB Access Power Controller

LED

ON

OFF

LED 1- LED 8 (Red)

Output relay(s) de-energized.

Output relay(s) energized.

FACP

FACP input triggered (alarm condition).

FACP normal (non-alarm condition).

Green Output 1-8

12VDC

------

Red/Green Output 1-8

24VDC

------

 

Terminal Identification Table:

ACMS8 and ACMS8CB Access Power Controller

 

 

Terminal Legend

Function/Description

+ PWR1 –

5-24VDC input from Power Supply.

+ PWR2 –

5-24VDC input from Power Supply.

+ INP1 – through

Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),

+ INP8 –

Open Collector Sink or Wet Input Triggers.

C, NC

FACP Dry NC output.

With EOL JMP intact, will provide 10k resistance in a normal condition.

 

GND, RST

FACP interface latching or non-latching

GND, EOL

EOL Supervised FACP Input terminals

– F, + F, – R, + R

FACP Signaling Circuit Input and Return terminals

Output 1 through

Eight (8) selectable 5VDC-24VDC independently controlled outputs [Fail-Safe (NC) or

Output 8

Fail-Secure (NO)] and eight (8) independently controlled Form “C” Relay outputs.

NO, C, NC, COM

Fuses are rated 2.5A each (ACMS8). PTCs are rated 2A each (ACMS8CB).

 

 

- 4 -