Tab. 1 Connecting terminals (overview) 11
Tab. 2 Operating display of the bus module 13
Tab. 3 Interpretation of the master setpoint for Thyro-S 15
Tab. 4 Cyclic input and output data for Thyro-S…H1 15
Tab. 5 Cyclic input and output data for Thyro-S…HRL1 15
Tab. 5b Thyro-S Status / Faults 15
Tab. 6 Cyclic input and output data for Thyro-A 1A…H1 16
Tab. 7 Cyclic input and output data for Thyro-A 1A…HRL1 16
Tab. 8 Cyclic input and output data for Thyro-A 1A…HRLP1 17
Tab. 9 Cyclic input and output data for Thyro-A 2A…H1 17
Tab. 10 Cyclic input and output data for Thyro-A 2A…HRL1 17
Tab. 11 Cyclic input and output data for Thyro-A 2A…HRLP1 18
Tab. 12 Cyclic input and output data for Thyro-A 3A…H1 18
Tab. 13 Cyclic input and output data for Thyro-A 3A…HRL1 19
Tab. 14 Cyclic input and output data for Thyro-A 3A…HRLP1 19
Tab. 14b Thyro-A Status / Fault 20
Tab. 15 Cyclic input and output data for Thyro-A 1A…C01 21
Tab. 16 Cyclic input and output data for Thyro-A 1A…C02 21
Tab. 17 Cyclic input and output data for Thyro-A 1A…C03 21
Tab. 18 Cyclic input and output data for Thyro-A 1A…C05 22
Tab. 19 Cyclic input and output data for Thyro-A 1A…C07 22
Tab. 20 Supported operating modes 22
Tab. 21 Cyclic input and output data TPM automatic mode 23
Tab. 22 Cyclic input and output data TPM manual mode 23
Tab. 23 Cyclic input and output data TSC mode 24
Tab. 24 Cyclic input and output data TIO mode 24
Tab. 25 Cyclic input and output data TMU mode 25
Tab. 25b TPM, TSC, TIO,TMU Status / Faults 25
3
Contact
Technical queries
Do you have any technical queries regarding the subjects dealt with in these operating instructions?
If so, please get in touch with our team for power controllers:
Tel. +49(0)2902 763-520 or +49(0)2902 763-290
Commercial queries
Do you have any commercial queries on power controllers? If so, please get in touch with our team for
power controllers.
Tel. +49 (0)2902 763-591 or +49 (0)2902 763-558
Service-Hotline
Our team is at your service on the following hotline:
AEG Power Solutions GmbH
Emil-Siepmann-Strase 32
D-59581 Warstein
Tel. +49 (0)2902 763-100
http://www.aegps.de
Copyright
No part of these operating instructions may be transmitted, reproduced and/or copied by any electronic or
mechanical means without the express prior written permission of AEG Power Solutions.
Thyro- is an international registered trademark of AEG Power Solutions GmbH.
Windows and Windows NT are registered trademarks of the Microsoft Corporation.
All other company and product names are (registered) trademarks of the respective owners.
4
1. Introduction
The operating instructions below serve only as an addition to be used in conjunction with the operating
instructions of the AEG Power Solutions Thyro-A power controller, Thyro-S power switch, and ThyroPower Manager in the versions of the types indicated on the covering page. The safety instructions contained therein are to be observed in particular.
1.1 General
The Ethernet bus module can connect up to 8 power controllers of type Thyro-A and type Thyro-S with a
master in any desired order.
Several bus modules can be used on one system.
The power supply of the bus module comes from an external 24V DC voltage source (150mA), which is to
be fed in (reverse polarity protected) at X11.1 (+) and X11.2 (ground). Several modules can be operated
from one power supply.
As short a ground connection as possible is needed at terminal X11.3 for EMC reasons.
1.2 Special features
• The Ethernet bus module connects the devices with several Ethernet bus systems. By setting the
“Protocol” switch to 0, the Ethernet bus module becomes a ProfiNet IO-device.
• function control via LED
• 8 free application outputs X1 to X8 in each case terminal 5
• C-rail assembly
1.3 Type designation
Ethernet bus module ProfiNet order-no. 2000 000 846
1.4 Abbreviations
AEG PS AEG Power Solutions GmbH
TPM Thyro – Power Manager
TSC Thyro – Step Controller
TMU Thyro – Measurement Unit
TIO Thyro Input / Output Unit
1.5 Warranty
In the event of any claims in connection with the Ethernet bus module, please contact us quoting:
• type designation
• fabrication number / serial number
• reason for the complaint
• environmental conditions of the device
• operating mode
• period of use
Goods and services are subject to the general conditions of supply for products of the electrical industry,
and our general sales conditions. Claims in connection with supplied goods must be submitted within
one week of receipt, along with the delivery note. AEG PS will rescind all obligations such as warranty
agreements, service contracts, etc. entered into by AEG PS or its representatives without prior notice
if maintenance and repair work is carried out using anything other than original AEG PS spare parts or
spare parts purchased from AEG PS.
5
2. Safety
2.1 Identification in the operating instructions
In these operating instructions, there are warnings before dangerous actions. These warnings are divided
into the following danger categories:
DANGER
Dangers that can lead to serious injuries or fatal injuries.
WARNING
Dangers that can lead to serious injuries or considerable damage to property.
CAUTION
Dangers that can lead to injuries and damage to property.
CAUTION
Dangers that can lead to minor damage to property.
The warnings can also be supplemented with a special danger symbol (e.g. „Electric current“ or
„Hot parts“) , e.g.
risk of electric current or
risk of burns
In addition to the warnings, there is also a general note for useful information.
NOTE
Content of note
2.2 General danger information
DANGER
Not adhering to the safety stipulations in the operating instructions of the power controllers
used can lead to danger of injury / danger of damaging the device or system.
> Adhere to all safety stipulations in the chapter “Safety” of the operating instructions of the
power controllers being used.
DANGER
Electric current
Risk of injury from current carrying parts / danger of damaging the bus module.
> Never operate the device without the covering.
> Undertake settings and wiring without current being supplied
CAUTION
Danger of damaging the bus module
The current at terminals X1.5 to X8.5 must not exceed 120 mA.
> Check the connection information of the preceding relay.
6
NOTE
Communication errors
To avoid communication errors please note the following points:
> Use shielded cables.
> Undertake grounding of the bus module (X1.7 to X8.7). Do not ground additionally at the
power controller.
2.3 Operator requirements
The operator must ensure the following:
- The safety regulations of the operating instructions are observed.
- The accident prevention regulations valid in the respective country of use and the general safety
regulations are observed.
- All safety devices (covers, warning signs etc.) are present, in perfect condition and are used correctly.
- The national and regional safety regulations are observed.
- The personnel has access to the operating instructions and safety regulations at all times.
- The operating conditions and restrictions resulting from the technical data are observed.
- Should abnormal voltages, noises, increased temperatures, vibration or similar occur, the device is
immediately put out of operation and the maintenance personnel is informed
2.4 Personnel requirements
Only qualified electro-technical personnel who are familiar with the pertinent safety and installation regulations may perform the following:
- transport
- installation
- connection
- commissioning
- maintenance
- testing
- operation
These operating instructions must be read carefully by all persons working with or on the equipment prior
to installation and initial start-up
2.5 Intended use
The device may only be used for the purpose for which it was intended, as persons may otherwise be
exposed to dangers (e.g. electric shock, burns) and plants also (e. g. overload). The user must therefore
observe the following points:
- It is not permitted to make any unauthorized modifications to the unit or to use any spare parts or
replacement parts not approved by AEG PS, or to use the unit for any other purpose.
- The warranty obligations of the manufacturer are only applicable if these operating instructions are
observed and complied with.
- The device is a component that cannot function alone.
- Project planning must account for the proper use of the device.
2.6 Use of the device
2.6.1 Operation
- Only switch on the mains voltage at the device when there is no danger to persons, system or load.
- Protect the device against dust and damp.
- Ensure that the ventilation openings are not blocked.
7
2.6.2 Prior to installation / commissioning
- If stored in a cold environment: ensure that the device is absolutely dry. (Allow the device a period of at
least two hours to acclimatize before commissioning)
- Ensure sufficient ventilation of the cabinet if mounted in a cabinet.
- Observe minimum spacing.
- Ensure that the device cannot be heated up by heat sources below it. (see page 33, Technical data).
- Ground the device in accordance with local regulations.
- Connect the device in accordance with the connection diagrams.
2.6.3 Maintenance, service, faults
In order to avoid personal and material damages, the user must observe the following:
- Before all work:
> Disconnect the device from all external voltage sources.
> Secure the device against accidentally being switched back on.
> Use suitable measuring instruments and check that there is no voltage present.
> Ground and short circuit the device.
> Provide protection by covers or barriers for any neighboring live parts.
- The device may only be serviced and repaired by trained electro-technical personnel.
2.6.4 Transport
- Only transport the device in the original packaging.
- Protect the device against damage, caused by jolts, knocks and contamination, for instance.
8
3. Functions
3.1 Processing the setpoint Thyro-S
Only local setpoints, no bus setpoint
Switching signal (24DC) at the control terminal X22.1 of the Thyro-S
> No wiring of the terminal point X22.4 at the power controller
- The bus module is fully functional. The analog signal from the control terminal X22.1 is used as setpoint
(on/off).
Setpoint from the bus module (X22.3), no local setpoint
> Connect the ground to terminal X22.4 of the power controller.
- The master setpoint of the bus module is used. For this purpose the setpoint is interpreted as the operating mode.
Bus setpoint, switching over to „local“ in case of bus fault
Only use the setpoint of the bus module if there is an IO connection.
> Connect terminal X22.4 of the power controller to one of the terminals X1.1 to X8.1 of the bus module.
- If there is an IO connection the master set point is used.
If not then the analog signal from the control terminal X22.1 is used as setpoint (on/off).
Switching over to bus / local setpoint switchable for each controller in operation
Individual setpoint from the bus module for each power controller.
> Connect terminal X22.4 of the power controller to one of the terminals X1.5 to X 8.5 of the bus
module.
- The power controllers can be switched over individually (targeted) via the bus between master setpoint
and terminal X22.1
3.2 Processing the setpoint Thyro-A
Only local setpoints, no bus setpoint
Analog input at control terminal X2.4 of Thyro-A
> Do not connect anything to terminal X22.1 of the power controller.
- The bus module is fully functional. The analog signal from the control terminal X2.4 is used as setpoint
(on/off).
Setpoint from the bus module (X22.3), no local setpoint
> Connect the ground to terminal X22.1 of the power controller.
- The master setpoint of the bus module is used.
Bus setpoint, switching over to “local” in case of bus fault
Only use the setpoint of the bus module if there is an IO connection.
> Connect terminal X22.1 of the power controller to one of the terminals X1.1 to X8.1 of the bus module.
- If there is an IO connection the master setpoint is used. If there is no IO connection then the analog
signal from the control terminal X2.4 is used as setpoint.
Switching over to bus / local setpoint switchable for each controller in operation
Individual setpoint from the bus module for each power controller.
> Connect terminal X22.1 of the power controller to one of the terminals X1.5 to X8.5 of the bus module.
- The power controllers can be switched over individually (targeted) via the bus between master setpoint
and terminal X2.4.
9
3.3 Processing the setpoint Thyro-Step Controller
Only local setpoints, no bus setpoint
Analog input at control terminal X6.1 or X6.4 (depending on X6.7) of the TSC
> Do not connect anything to terminal X2.1 of the power controller.
- The bus module is fully functional. The analog signal from the control terminal X6.1 or X6.4 is used as
setpoint.
Setpoint from the bus module (X22.3), no local setpoint
> Connect the ground to terminal X2.1 of the TSC.
- The master setpoint of the Ethernet bus module is used.
Bus setpoint, switching over to “local” in case of bus fault
Only use the setpoint of the bus module if there is an IO connection.
> Connect terminal X2.1 of the TSC to one of the terminals X1.1 to X8.1 of the bus module.
- If there is an IO connection the master setpoint is used. If there is no IO connection then the analog
setpoint is used.
Switching over to bus / local setpoint value switchable for each controller in operation
Individual setpoint from the bus module for each power controller.
> Connect terminal X2.1 of the power controller to one of the terminals X1.5 to X8.5 of the bus module.
- The power controllers can be switched over individually (targeted) via the bus between master setpoint
and the analog setpoint.
3.4 Freely addressable digital outputs
> As long as the terminals X1.5 to X8.5 of the bus module are not being used for switching over the set-
point, these can be used as switch outputs.
> Connect the relay to a 24 V DC coil voltage for free use. The idle circuit is integrated. The actuating
current is a maximum 120 mA per output. As a result it is possible to switch over, for example, the room
ventilators, anti-condensation heating, circuit breakers or control lamps via the bus.
Relais Control
10
4. Installation
DANGER
Dangers during Installation
Risk of injury / Risk of damage to the device or plant
Observe all safety regulations in the chapter “Safety”.
4.1 Connection terminals (overview)
Tab.1 Connecting terminals (overview)
TerminalDescription
X11.124V (+)
.224V (ground)
.3grounding, carry out as short as possible
X1 - X8.1jointly switchable ground potential
.2RxD
.3TxD
.4ground
.5separately switchable ground potential
.6ground
.7ground potential for shield connection
Connection diagram see page 30.
4.2 Connecting a 24 V power supply
> Switch off the main power supply including the external 24 V power source and make sure these cannot
be accidentally switched back on again.
> Connect the external 24 V voltage supply (150 mA) to X11.1 (+) and X11.2 (-) (reverse polarity protec-
tion).
> Ground the X11.3 terminal by as short a route as possible (for EMC reasons).
REMARK
24 V DC power source
Several bus modules can be operated with one power supply.
> In cases of SELV (safety extra low voltages) do not ground the 24 V power source.
4.3 Connecting the power controller to X1-X8
> Switch off the main power supply including the external 24 V power source and make sure these cannot
be accidentally switched back on again.
> Connect the interfaces X1 to X8 of the bus module to the system interfaces of the power controller
(shielded four-wire cable)
Attention: To control all parameters by ProfiNet we recommend closing the Thyro-A switches S1.3, S1.4,
S1.5 (Thyro-Tool Mode).
4.4 Connecting the Ethernet bus module to the master
The Ethernet bus module has two Ethernet ports which are equipped with a switch functionality which
allows a line topology to be constructed.
A standard patch cable is required for connecting with a switch. For a direct connection (line topology) a
cross-over cable is required.
11
5. Settings
5.1 Setting the protocol
The Ethernet bus module supports various real time Ethernet bus systems. The desired system can be
selected using the rotary switch “Protocol”. For ProfiNet this needs to be set to 0.
5.2 Setting the number of slots
The number of devices which are connected to the Ethernet bus module is set with the rotary switch
“Slots”. After switching on, the Ethernet bus module reads all the parameters of the device. Following this
it starts communicating.
Attention: To change the number of slots when switched on, the switch “Slots” must first be turned to 0.
Communication with the master is then interrupted. Following this the desired number can be set. After
leaving the position 0 you have about 2 seconds time for this.
5.3 Setting the device name
Every IO device is identified by its device name. The setting of the device name can be undertaken using,
for example, the program “Step 7 – HW Config” in the menu “Target system / Ethernet / Edit Ethernet
participant…”
Fig. 1 Configuration & LED displays
1 Terminal X110 Terminal X11
2 Terminal X211 SYS LED
3 Terminal X312 COM0 (BF) LED
4 Terminal X413 COM1 (SF) LED
5 Terminal X514 Fault LED
6 Terminal X615 Switch Slots
7 Terminal X716 Switch Protocol
8 Terminal X8
9 Ethernet Port
12
5.4 Operating display of the bus module
Table 2 Operating display of the bus module
LEDColorStatusMeaning
SYSGreenOnOperating system running
RedFlashing with 1HzError in boot process
RedOnWaiting for boot process (check position of
OffNo supply voltage
COM0 (BF)RedOnNo physical connection
RedFlashing with 2HzNo data exchange
OffThe device is exchanging data with the ProfiNet IO
COM1 (SF)RedOnWatchdog time out or system error
OffNo error
FaultRedOnHardware error
Operating status of the Ethernet bus module
“Protocol” switch)
Controller
LEDColorStatusMeaning
LinkGreenOnThere is an Ethernet connection
ActivityYellowOnData are being exchanged via Ethernet
Status LED of the Ethernet Ports
13
6. Operation
6.1 Start configuration (parameterization)
Via the parameterization (in step 7 – HW Config, double-click on slot 0 of the bus module, parameter tab)
the following settings can be undertaken.
No connection (slot 1-8):
Here you can set what should happen with the output data of the devices if the connection to the master
is interrupted.
Hold last values The output data are not changed.
Outputs = 0 The output data are set to 0
No connection (slot 9):
Here you can set what should happen with the output data of the bus module if the connection to the
master is interrupted.
Hold last value The digital outputs are not changed.
Outputs = 0 The digital outputs are set to 0.
Averaging of the measured values:
Here you can enter the number of actual values which flow into the averaging. A new value is calculated
once a second. Values from 0-20 can be entered, whereby 0 or 1 deactivates this function.
Remove device when it is switched off:
Not all devices are equipped with a 24 V supply connection. When switching off the Thyro mains supply
and the control voltage supply (24V) the Thyro no longer communicates with the bus modules. A switched
off device will normally be displayed as pull. This display can be suppressed here.
DeactivateDevices which are no longer accessible (no communication) will continue to
be displayed as plug.
Activate Devices which are no longer accessible will be displayed as pull.
Use output data:
The suppression of certain output data can be activated here.
Always New output data are transferred immediately.
Only when Bit is set New output data are only transferred, if the Bit 0 is set in the output
“Functions”
6.2 Cyclical data transmission (configuration)
The configuration of the cyclical data traffic is undertaken by adding modules.
The input and output data depend on the device types. The following tables show the input and output
data available for each of the devices.
6.3 Input and output data Thyro-S
With the Thyro-S the setpoint is interpreted as operating mode.
14
Tab. 3 Interpretation of the master setpoint with Thyro-S
Tab. 18 Cyclic input and output data with Thyro-A 1A...C05
OffsetInput data, actual valuesData typeSizeUnit
0Load voltage phase 1float4[V]
4Load current phase 1float4[A]
8Load current phase 2float 4[A]
12Total load current float 4[A]
16Power phase 1float 4[W]
20Power phase 2float 4[W]
24Total power float 4[W]
28Mains voltage L1integer2[V]
30Switch-on angle alpha phase 1integer2[0.01 °el]
32Total setpoint integer 24096=100%
34Fault (see table 14b)integer2-
36Status (see table 14b)integer 2-
OffsetOutput data, setpoint Data typeSizeUnit
0Master setpointinteger24096=100%
Tab. 19 Cyclic input and output data with Thyro-A 1A...C07
OffsetInput data, actual valuesData typeSizeUnit
0Load voltage L1float4[V]
4Load current L1float 4[A]
8Power L1float 4[W]
12Mains voltage L1integer 2[V]
14Load temperatureinteger2[°C]
16Switch-on angle alphainteger2[0.01 °el]
18Total setpoint integer 24096=100%
20Fault (see table 14b)integer2-
22Status (see table 14b)integer 2-
OffsetOutput data, setpoint Data typeSizeUnit
0Master setpointinteger24096=100%
Supported operating modes TPM; TSC; TMU
With the Thyro-Power Manager, Thyro-Step Controller and Thyro-Measurement Unit the input and output
data are depend on the operating mode. The following table shows which operating mode the devices
support.
Tab. 20 Supported operating modes
TPMTSCTIOTMU
automaticmanual
Thyro-Power ManagerXXXXX
Thyro-Step Controller--XXX
Thyro-Measurement Unit---XX
22
6.5 Input and output data Thyro-Power Manager
Tab. 21 Cyclic input and output data TPM automatic mode
OffsetInput data, actual valuesData typeSizeUnit
0AC input 1float4[A],[V]
4AC input 2float 4[A],[V]
8AC input 3float 4[A],[V]
12Power float 4[W]
16Energyfloat4[kWh]
20DC input 1integer24096=100%
22DC input 2integer24096=100%
24DC input 3integer24096=100%
26Mains voltageinteger2[V]
28Period durationinteger 2[μs]
30Temperature integer 2[°C]
32Fault (see table 25b)integer2-
34Status (see table 25b)integer 2-
Tab. 22 Cyclic input and output data TPM manual mode
OffsetInput data, actual valuesData typeSizeUnit
0AC input 1float4[A],[V]
4AC input 2float 4[A],[V]
8AC input 3float 4[A],[V]
12Power float 4[W]
16Energyfloat4[kWh]
20DC input 1integer24096=100%
22DC input 2integer24096=100%
24DC input 3integer24096=100%
26Mains voltageinteger2[V]
28Period durationinteger 2[μs]
30Temperature integer 2[°C]
32Fault (see table 25b)integer2-
34Status (see table 25b)integer 2-
23
6.6 Input and output data Thyro-Step Controller
Tab. 23 Cyclic input and output data TSC mode
OffsetInput data, actual valuesData typeSizeUnit
0AC input 1float4[A],[V]
4AC input 2float 4[A],[V]
8AC input 3float 4[A],[V]
12Power float 4[W]
16Energyfloat4[kWh]
20DC input 1integer24096=100%
22DC input 2integer24096=100%
24DC input 3integer24096=100%
26Mains voltageinteger2[V]
28Period durationinteger 2[μs]
30Temperature integer 2[°C]
32Fault (see table 25b)integer2-
34Status (see table 25b)integer 2-
36Analog output 4integer 24096=100%
38Stepsinteger 2-
40Total setpoint Integer24096=100%
OffsetOutput data, setpoint Data typeSizeUnit
0Master setpointinteger24096=100%
6.7 Input and output data Thyro Input/Output Unit
Tab. 24 Cyclic input and output data TIO mode
OffsetInput data, actual valuesData typeSizeUnit
0AC input 1float4[A],[V]
4AC input 2float 4[A],[V]
8AC input 3float 4[A],[V]
12Power float 4[W]
16Energyfloat4[kWh]
20DC input 1integer24096=100%
22DC input 2integer24096=100%
24DC input 3integer24096=100%
26Mains voltageinteger2[V]
28Period durationinteger 2[μs]
30Temperature integer 2[°C]
32Fault (see table 25b)integer2-
34Status (see table 25b)integer 2-
OffsetOutput data, setpoint Data typeSizeUnit
0Digital outputinteger2-
2Analog output 1integer24096=100%
4Analog output 2integer24096=100%
6Analog output 3integer24096=100%
8Analog output 4integer24096=100%
10Analog output 5integer24096=100%
12Analog output 6integer24096=100%
24
6.8 Input and output data Thyro-Measurement Unit
Tab. 25 Cyclic input and output data TMU mode
OffsetInput data, actual valuesData typeSizeUnit
0AC input 1float4[A],[V]
4AC input 2float 4[A],[V]
8AC input 3float 4[A],[V]
12Power float 4[W]
16Energyfloat4[kWh]
20DC input 1integer24096=100%
22DC input 2integer24096=100%
24DC input 3integer24096=100%
26Mains voltageinteger2[V]
28Period durationinteger 2[μs]
30Temperature integer 2[°C]
32Fault (see table 25b)integer2-
34Status (see table 25b)integer 2-
Tab. 25b Status TPM, TSC, TIO, TMU
DescriptionBitFault LED, fault output*
Frequency measurement outside of 47Hz to 63HzBit 0on
SYNC error, no cero crossing within the gateBit 1on
Temperature max. limit has been exceededBit 2on
Temperature min. limit has been exceededBit 3on
One or more parameters outside the limitsBit 4on
Mains voltage lower than lower voltage limitBit 5 on
Tab. 25b Fault TPM, TSC, TIO, TMU
DescriptionBitAlarm LED, alarm output*
Mains frequency is 60HzBit 2off
Transformer 1 fallen below min. limitBit 3on
Transformer 1 exceeded max. limitBit 4on
Transformer 2 fallen below min. limitBit 5on
Transformer 2 exceeded max. limitBit 6on
Transformer 3 fallen below min. limitBit 7 on
Transformer 3 exceeded max. limitBit 8on
Device switched offBit 9--
Wrong deviceBit 10--
Bus module active (0=no bus module / 1=bus module
active)
Bit 11off
* Default setting can be parameterized.
25
6.9 Acyclic data transmission (parameterization)
Via the acyclic parameter data transmission, parameters of the devices can be changed or selected.
Cyclical and acyclical services can be used in the network simultaneously.
Read data record “RDREC”:
For reading access to a data record, the slot, index and length of the data record must be entered. At step
7 and when using the SFB 52 the Logical Address of the slot is to be entered instead of the slot. As such
the device at slot X1 is to be activated as the device at slot 1.
Error codeMeaning
DE80B000The unit does not recognize the parameter (invalid index)
DE80B100The length entry of the parameter is incorrect
DE80B200The projected slot is not occupied
DE80B300The actual unit type does not match the set unit type
Write data record “WRREC”:
For writing access to a data record, the slot, index, length of the data record and the new value must be
entered. At step 7 and when using the SFB 53 the Logical Address of the slot is to be entered instead of
the slot.
Error codeMeaning
DF80B000The unit does not recognize the parameter (invalid index)
DF80B100The length entry of the parameter is incorrect
DF80B200The projected slot is not occupied
DF80B300The actual unit type does not match the set unit type
DF80B600The parameter cannot be changed
DF80B700Invalid range of values of a parameter
You will find the parameter tables (acyclic) of each of the device types in Appendix 17 (A).
26
7. External connections
7.1 Power supply
+24V to X11, current consumption approx. 150mA
bridge (contact)
Thyro-S: see chapter 3.1
Thyro-a: see chapter 3.2
TPM: see chapter 3.3
X1 - X8 to the power controllers
supply
24V DC (approx. 150mA)
The foregoing circuit diagram shows the connection of the bus module
27
7.2 Operating elements and terminal blocks
This chapter describes the available terminal blocks, plug connectors and operating elements.
Configuration of the 7 pin connector of slots X1 to X8:
1 Switched ground potential. All pins 1 of slots X1 – X8 are connected.
2 RxD
3 TxD
4 Ground
5 Switchable ground potential. The slots X1 – X8 can be switched as desired.
6 Ground
7 Ground potential for shield connection
Configuration of the 3 pin connector X11:
X11: +24V
X11: 24V - ground
X11: Grounding, carry out by as short a route as possible.
28
8. Interfaces
8.1 System interface
The bus module is connected with the relevant system interfaces of the power controllers via X1 to X8
(four-wire, 2x2 twisted, shared shielding).
The transmission rate is 38,400 Bd.
The asynchronous characters are transferred with 8bit, no parity, one stop bit. The protocol begins with
STX, followed by an identifier, the data, and is concluded with a check sum. Defective protocols are
ignored.
8.2 Ethernet interfaces
Communication medium CAT 5e
Network topology tree, star and line
Maximum cable length 100m
ProfiNET-participants restricted to the maximum supported number of devices by the con-
troller used
PNO identification number0x0188
Device ID 0x0001
Transmission rate 100 Mbit/s
29
9. Connection diagrams Thyro-A
Fig. 2 Connection diagram Thyro-A
bus setpoint/
analog input
setpoint 1
bus setpoint is
active
bus setpoint/
analog input
setpoint 2
analog input is
active
setpoint
*blank
bus setpoint/
analog input
setpoint 8
group switching
bus setpoint/
analog input
setpoint 1
selective switching
bus setpoint/analog input
bus setpoint/
analog input
setpoint 2
bus setpoint/analog input
bus setpoint/
analog input
setpoint 8
30
10. Connection diagrams Thyro-S
Fig. 3 Connection diagram Thyro-S
bus setpoint/
analog input
setpoint 1
ON/OFF
bus setpoint is
active
bus setpoint/
analog input
setpoint 2
ON/OFF
analog input is
active
setpoint
*blank
bus setpoint/
analog input
setpoint 8
ON/OFF
group switching
bus setpoint/
analog input
setpoint 1
ON/OFF
selective switching
bus setpoint/analog input
bus setpoint/
analog input
setpoint 2
ON/OFF
bus setpoint/analog input
bus setpoint/
analog input
setpoint 8
ON/OFF
31
11. Connection diagrams TSC
Fig. 4 Connection diagram TSC
bus setpoint/
analog input
setpoint 1setpoint 2setpoint 8
bus setpoint is
active
bus setpoint/
analog input
analog input is
active
setpoint
*blank
bus setpoint/
analog input
group switching
bus setpoint/
analog input
setpoint 1setpoint 2setpoint 8
selective switching
bus setpoint/analog input
bus setpoint/
analog input
bus setpoint/analog input
bus setpoint/
analog input
32
12. Specific notes
12.1 Installation
The bus modules can be installed in any desired order.
12.2 Service
The devices supplied have been produced in accordance with the quality standard ISO 9001. Should there
be faults in spite of this, our 24 hour service hotline is on hand, tel.: +49 (0)2902 763-100.
13. Technical Data
Power supply 24V DC 150mA
Connection options for up to 8 AEG power controllers of series Thyro-S, Thyro-A and the TPM
series
Function control LED
Assembly DIN rail
Ambient temperature maximum 55°C
Dimensions (WxDxH): 150 x 60 x 95 mm
Weight circa: 0.35 kg
33
14. Dimension drawings
55 mm height
incl. cover
15. Accessories and options
Ready-made bus module-side shielded cable.
A set of cable consists of 4 connection cables for connecting 4 power controllers.
Order number 2000 000 848 Bus module connection cable for 4 controllers, 2.5 m long
Order number 2000 000 849 Bus module connection cable for 4 controllers, 1.5 m long
16. Approvals and conformity
- Quality standard in acc. with EN ISO 9001
- CE conformity
- ProfiNet conformity
- RoHS compliant 5/6
- Directives
The CE mark on the device confirms compliance with the EC directives 2006 / 95 / EEC for low voltage
and 2004 / 108 / EEC for electromagnetic compatibility if the instructions on installation and commissioning described in the operating instructions are followed.
reserved, reserved, without regulation, temperature
38
unitR / WDefaultNoteIndex
Artype1
Vrtype2
WrtypeH RLP13
°elr/w *60°elR2017
periodr/w6 period9
periodr/w*50 periodR20110
periodr/w *3 periodR20111
periodr/w50 period12
periodr/w0 period13
°elr/w180°el14
°elr/w0°el15
0.1Vr/w *440VR202**21
0.1Ar/w *110AR20322
Wr/w *0R202**23
4096=100%r27
20/4096mAr/w *0mAS1.928
1/819r/w *1R20429
Vr/wtype30
Vr/w type31
100/4096%r/w *0%R20534
r/w *TAKTS1.1-26
r/w *8
r/w *Uload2S1.3-5 power only with
H RLP1
r/w2017
r/w6018
r/w1019
r/w20
r024
r/w *offR20532
r/w033
16
period/2r/w10036
20/4096mAr/w *0mAS1.638
20/4096mAr/w20mA39
°Cr84
20/4096mAr/w0mAS1.9110
1/819r/w1R204111
20/4096mAr/w0mAS1.9116
1/819r/w1R204117
0.1Vr/w119
0.1Vr/w120
0.1Ar/w121
0.1Ar/w122
Wr/w123
Wr/w124
r/w037
r/wtype41
r/w642
r44
r45
r46
r/woff48
r/w44749
r/woff50
r/w10056
r/w100109
r/w6112
r/w100115
r/w6118
39
3. Acyclic parameter table Thyro-Power Manager
Table C: TPM parameters slot 1-8
Controller parameter
SymbolNameData
Index
1W1_TYPType value transformer 1u161...65535
2W2_TYPType value transformer 2u161...65535
3W3_TYPType value transformer 3u161...65535
4W_CTRLTransformer settingu160...65535bit coded
5U_TYPType value U mainsu161…260
7T0u161…1500
8ANZNumber u162…10
9T011st time / phase 1u160…T0
10T022nd time / phase 2u160…T0
11T033rd time / phase 3u160…T0
12T044th time / phase 4u160…T0
13T055th time / phase 5u160…T0
14T066th time / phase 6u160…T0
15T077th time / phase 7u160…T0
16T088th time / phase 8u160…T0
17T099th time / phase 9u160…T0
18T1010th time / phase 10u160…T0
39DAC1_OFOffset 1u160…4095
40DAC1_FAScale end value 1u160…4096
41DAC1_CTRLOutput value 1u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
42DAC2_OFOffset 2u160…4095
43DAC2_FAScale end value 2u160…4096
44DAC2_CTRLOutput value 2u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
45DAC3_OFOffset 3u160…4095
46DAC3_FAScale end value 3u160…4096
47DAC3_CTRLOutput value 3u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
48DAC4_OFOffset 4u160…4095
49DAC4_FAScale end value 4u160…4096
50DAC4_CTRLOutput value 4u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
51DAC5_OFOffset 5u160…4095
52DAC5_FAScale end value 5u160…4096
53DAC5_CTRLOutput value 5u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
54DAC6_OFOffset 6u160…4095
55DAC6_FAScale end value 6u160…4096
56DAC6_CTRLOutput value 6u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
1W1_TYPType value transformer 1u161...65535
2W2_TYPType value transformer 2u161...65535
3W3_TYPType value transformer 3u161...65535
4W_CTRLTransformer settingu160...65535
5U_TYPType value U networku161…260bit coded
42 DAC2_OFOffset 2u160…4095
43 DAC2_FAScale end value 2u160…4096
44 DAC2_CTRLOutput value 2u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
45 DAC3_OFOffset 3u160…4095
46 DAC3_FAScale end value 3u160…4096
47 DAC3_CTRLOutput value 3u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
48 DAC4_OFOffset 4u160…4095
49 DAC4_FAScale end value 4u160…4096
50 DAC4_CTRLOutput value 4u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
52 DAC5_FAScale end value 5u160…4096
53 DAC5_CTRLOutput value 5u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
54 DAC6_OFOffset 6u160…4095
55 DAC6_FAScale end value 6u160…4096
56 DAC6_CTRLOutput value 6u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
1W1_TYPType value transformer 1u161...65535
2W2_TYPType value transformer 2u161...65535
3W3_TYPType value transformer 3u161...65535
4W_CTRLTransformer settingu160...65535bit coded
5U_TYPType value U networku161…260
7T0Measuring and cycle timeu161…15000
39 DAC1_OFOffset 1u160…4095
40 DAC1_FAScale end value 1u160…4096
41 DAC1_CTRLOutput value 1u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
42 DAC2_OFOffset 2u160…4095
43 DAC2_FAScale end value 2u160…4096
44 DAC2_CTRLOutput value 2u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
45 DAC3_OFOffset 3u160…4095
46 DAC3_FAScale end value 3u160…4096
47 DAC3_CTRLOutput value 3u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
48 DAC4_OFOffset 4u160…4095
49 DAC4_FAScale end value 4u160…4096
50 DAC4_CTRLOutput value 4u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
51 DAC5_OFOffset 5u160…4095
52 DAC5_FAScale end value 5u160…4096
53 DAC5_CTRLOutput value 5u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
54 DAC6_OFOffset 6u160…4095
55 DAC6_FAScale end value 6u160…4096
56 DAC6_CTRLOutput value 6u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
6. Acyclic parameter table Thyro Input-Output Unit
Table F: TIO parameters slot 1-8
Controller parameter
SymbolNameData
Index
1W1_TYPType value transformer 1u161...65535
2W2_TYPType value transformer 2u161...65535
3W3_TYPType value transformer 3u161...65535
4W_CTRLTransformer settingu160...65535bit coded
5U_TYPType value U mainsu161…260
7T0Measuring and cycle timeu161…1500
39 DAC1_OFOffset 1u160…4095
40 DAC1_FAScale end value 1u160…4096
41 DAC1_CTRLOutput value 1u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
42 DAC2_OFOffset 2u160…4095
43 DAC2_FAScale end value 2u160…4096
44 DAC2_CTRLOutput value 2u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
45 DAC3_OFOffset 3u160…4095
46 DAC3_FAScale end value 3u160…4096
47 DAC3_CTRLOutput value 3u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
48 DAC4_OFOffset 4u160…4095
49 DAC4_FAScale end value 4u160…4096
50 DAC4_CTRLOutput value 4u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
51 DAC5_OFOffset 5u160…4095
52 DAC5_FAScale end value 5u160…4096
53 DAC5_CTRLOutput value 5u161…16transformer1, transformer2, transformer3, U mains, setpoint1,
54 DAC6_OFOffset 6u160…4095
55 DAC6_FAScale end value 6u160…4096
56 DAC6_CTRLOutput value 6u161…16transformer1, transformer2, transformer3, U mains, setpoint1,