Belshaw Adamatic Bakery Group.
814 44
Auburn, WA 98001 USA
Phone: 206-322-5474
Fax: 206-322-5425
http://www.belshaw.com
102907
th
Street NW, Suite 103
THE INFORMATION IN THIS MANUAL IS CRUCIAL AND MUST BE RETAINED FOR FUTURE REFERENCE.
READ, UNDERSTAND, AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL.
DANGER
WARNING
CAUTION
NOTICE
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN DEATH.
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.
Helpful operation and installation instructions and tips are
present.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY
OR DEATH. READ THE INSTALLATION, OPERATING AND MAINTENANCE
INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS
EQUIPMENT.
Model #: Purchased From:
Serial #:
Location:
Date Purchased:
Purchase Order #:
Date Installed:
For Service, Call:
TABLE OF CONTENTS
CHAPTER PAGE
TABLE OF CONTENTS ..........................................................................................3
READ FIRST ............................................................................................................4
MOVING PARTS HAZARD. FOLLOW LOCKOUT PROCEDURES BEFORE
REMOVING AIR DUCT OR EVAPORATOR FAN GUARDS
ELECTRICAL HAZARD BEHIND UPPER FRONT TRIM. FOLLOW LOCKOUT
PROCEDURES BEFORE SERVICING.
THIS PROOFER PRODUCES HUMIDITY WHICH WILL NATURALLY
CONDENSE AND ACCUMULATE WATER ON THE INTERIOR F L OOR
CAUSING IT TO BECOME SLIPPERY. ADJACENT EXTERIOR FLOOR MAY
ALSO BECOME SLIPPERY. USE EXTREME CAUTION WHEN WALKING IN
OR AROUND THIS APPLIANCE.
NOTICE
DANGER
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
CAUTION
This picture shows an BAP1, BAP2, and BAP3. The BAP1 and some BAP2
models have only one climitizer. Larger models have two climitizers.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
For best results, always allow your proofer to reach set temperature and
humidity before putting product in.
For best results, proof at lower temperatures rather than higher.
To dry proof: Set humidity to the lowest setting (either 45% or less). At
this setting the humidity generator is turned off and will not produce
humidity.
When the actual humidity is less than 46% display will show 45. When the
actual humidity is higher than 45%, display will show the actual humidity.
Service on this or any other equipment must be performed by qualified
personnel only. Consult your authorized service agency directory or call
the factory.
The BAP1 has hinges mounted on the right jamb only.
THIS APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE
ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE,
ANSI/NFPA 70-1996.
ETL File E8138
4
IMPORTANT READ FIRST IMPORTANT
CAUTION
WARNING
FOR INSTALLATION IN CANADA THE INSTALLATION MUST BE IN
ACCORDANCE WITH CAN/CGA-B149.1&2 OF THE INSTALLATION CODE,
AND LOCAL CODES WHERE APPLICABLE. ALL ELECTRIC WIRING MUST
BE IN ACCORDANCE WITH THE CURRENT CANADIAN ELECTRICAL
CODE, C22.1 PART 1. GROUNDING THIS APPLIANCE MUST CONFORM
TO CANADIAN ELECTRICAL CODE, CSA C22.2.
INSTALLATION OF THE UNIT MUST BE DONE BY PERSONNEL QUALIFIED
TO WORK WITH ELECTRICITY AND PLUMBING. IMPROPER
INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND /OR DAMAGE
TO EQUIMENT. UNIT MUST BE INSTALLED IN ACCORDANCE WITH ALL
APPLICAL CODES
ETL File E8138
5
SAFETY PROCEDURES
WARNING
WARNING
WARNING
MOVING PARTS HAZARD. FOLLOW LOCKOUT PROCEDURES BEFORE
REMOVING AIR DUCT OR EVAPORATOR FAN GUARDS
ELECTRICAL HAZARD BEHIND UPPER FRONT TRIM. FOLLOW LOCKOUT
PROCEDURES BEFORE SERVICING.
THIS PROOFER PRODUCES HUMIDITY WHICH WILL NATURALLY
CONDENSE AND ACCUMULATE WATER ON THE INTERIOR F L OOR
CAUSING IT TO BECOME SLIPPERY. ADJACENT EXTERIOR FLOOR MAY
ALSO BECOME SLIPPERY. USE EXTREME CAUTION WHEN WALKING IN
OR AROUND THIS APPLIANCE.
Lockout Procedure
1. Announce lockout to other personnel.
2. Turn both heat and control power off at main panel.
3. Clear unit of all personnel.
4. Test lockout by turning power switch on and observing if control panel displays or fan(s) come on.
Check heater circuit with voltmeter.
5. Perform necessary repairs or tests.
6. Clear unit of personnel before restarting.
7. Turn power on at main panel.
8. Announce unit is “on” to other personnel.
Safety Precautions
The Factory hereby disclaims any and all responsibility for injury, damage, loss or other claim that may
occur to person or property from improper alteration, modification, addition, operation, maintenance or
service, whether it be mechanical, electrical, fuel, operator, motor or otherwise, which may occur from
such improper alteration, modification, addition, operation, maintenance or service to this piece of
equipment.
Safety Considerations
Your proofer is manufactured to rigid standards. This equipment is E.T.L. listed and meets safety and
sanitation standards.
The presence of safety equipment control and interlocks on an appliance and attendant components of
installation cannot, in and of themselves, assure absolute safety of operation. Diligent, capable, well
trained operators and maintenance personnel, as well as proper programs of operation and maintenance,
are essential to the safe and reliable operation of this appliance.
A. The responsibility of the manufacturer
recommendations for the operation and maintenance of the appliance.
B. Trained, qualified and factory-authorized personnel must perform all operation, maintenance and
repair of these appliances. It is the responsibility of the owner / operator
happens.
C. A regular periodic program of cleaning, inspection and maintenance must be established and
comprehensive maintenance records maintained. It is the sole responsibility of the user
schedule and enforce the frequency and scope of these programs in keeping with recommended
practice and with due consideration given to actual operating conditions.
D. The appliance must be operated within limits which will not exceed the working limits of any
component within the appliance as a whole.
is to supply suitable, comprehensive instructions and
to ensure that this
to establish,
ETL File E8138
6
EQUIPMENT DESCRIPTION
Exterior
BAP1
•The Proofer exterior dimensions are 38.4” (97.5 cm) wide x 91.5” (232.5 cm) high x a depth dependent
upon model number [39.3”(100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
BAP2
•The Proofer exterior dimensions are 78.8” (200 cm) wide x 91.5” (232.5 cm) high x a depth dependent
upon model number [39.3”(100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
BAP3
•The Proofer exterior dimensions are 102.5” (260 cm) wide x 91.5” (232.5 cm) high x a depth dependent
upon model number [39.3”(100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
All Units
• Modular design allows for a wide variety of sizes.
• The proofer door is constructed of stainless steel and comes with both single and double doors.
Interior
BAP1
•The Proofer interior dimensions are 33.1” (84 cm) wide x 74.1” (188.1 cm) high x a depth dependent upon
model number [22.1”(56 cm) to 112.1” (284.7 cm)]. The Top, Front, Back, and Sides are constructed of
stainless steel.
BAP2
•The Proofer interior dimensions are 68.1” (173 cm) wide x 74.1” (188.25 cm) high x a depth dependent
upon model number [27.1”(68.8 cm) to 117.1” (297.4 cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
BAP3
•The Proofer interior dimensions are 91.8” (233cm) wide x 74.1” (188.25 cm) high x a depth dependent
upon model number [27.1”(68.8 cm) to 117.1” (297.4 cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
All Units
• Floor level loading.
Cabinet
Rigid, formed stainless steel panels filled with polyurethane foam insulation re-joined with cam-locks and
sealed with gaskets to form a strong, energy-efficient, tight and sanitary enclosure.
Doors
The welded stainless steel door is polyurethane foam-filled. Door bumpers on the inside protect the finish.
Controls
•The microprocessor-based digital controls are mounted for ease in the door. In some models power and
light switches are located above the door.
•Digital read-out with solid-state temperature sensing and controls.
Air-Duct(s)
Each proofer comes with one or two air ducts. These air ducts perform the tasks of heating, humidifying,
and circulating the air within the unit. Each duct contains a heater plate, spray nozzle, drain pan, and fan.
ETL File E8138
7
GENERAL DESCRIPTION
Theory of Operation
The BAP Proofer is a controlled atmosphere chamber. Temperature and humidity can be set
independently to meet your particular proofing needs. In Proof mode air temperature is increased as the air
duct heater is energized. Humidity is increased as water is sprayed in the air duct. Air is circulated
continuously to provide positive movement from bottom to top, creating a uniform distribution of warm,
humid air.
Proofer Theory
NOTICE
ETL File E8138
This picture shows an BAP2. The BAP1 has only one door and the air duct
heater is mounted on the back wall.
8
GENERAL OPERATION
DANGER
NOTICE
NOTICE
NOTICE
NOTICE
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
For best results, always allow your proofer to reach set temperature and
humidity before putting product in.
For best results, proof at lower temperatures rather than higher.
To dry proof: Set humidity to the lowest setting (either 45% or less). At this
setting the humidity generator is turned off and will not produce humidity.
When the actual humidity is less than 46% display will show 45. When the
actual humidity is higher than 45%, display will show the actual humidity.
See Programming Manual for Operation Instructions!
ETL File E8138
9
GENERAL MAINTENANCE
WARNING
NOTICE
Every Day
Clean interior and exterior of proofer. See Equipment
Every Six Months
Have factory authorized service personnel check proofer for proper temperature readings. Also inspect air duct drain,
heater plate, spray nozzle for proper operation and mineral deposits; de-scale as needed.
As Needed
Clean interior and exterior walls and replace light bulb or any other components as needed.
Specifications
THIS PROOFER PRODUCES HUMIDITY WHICH WILL NATURALLY
CONDENSE AND ACCUMULATE WATER ON THE INTERIOR F L OOR
CAUSING IT TO BECOME SLIPPERY. ADJACENT EXTERIOR FLOOR MAY
ALSO BECOME SLIPPERY. USE EXTREME CAUTION WHEN WALKING IN
OR AROUND THIS APPLIANCE.
Service on this or any other equipment must be performed by qualified
personnel only. Consult your authorized service agency directory or call
the factory
Temperature, humidity, and timer setting ranges:
Thaw:
Proof:
Timers:
Power:
Water
Consumption:
70-120°F (18-66°C)
50-95% Relative Humidity
70-120°F (18-46°C)
50-95% Relative Humidity
0-99 Hours and 0-99 Minutes
Varies depending on model and size (See data plate located on the underside of the valence
for the specific ratings or contact the factory for the information needed if the data plate is
not legible).
.73 gallons per hour average per air duct (2 ducts maximum) @ 30 PSI.
1.70 gallons per hour average per air duct (2 ducts maximum) @ 80 PSI.
Unit will use about 4 gallons per hour when powered on until humidity levels reach set point.
Blue to Black Red to Black Yellow to Yellow (no red stripe)
ETL File E8138
10
NOTE: ON UNITS WITH FLOOR ONLY!
Countersunk sides of
holes go up.
ASSEMBLY
Place floor onto prepared surface and mark
position. Take into consideration drain location.
Note: Tile that may come loose
over time should be removed.
Place floor adhesive onto floor and spread with provided
trowel. Seal bottom with a good continuous bead along
edge before setting into final resting position. Apply
weight to floor while adhesive sets.
Note: Row of 3/8” holes is front of
floor. Countersunk sides of holes go up.
Drill holes with rotary drill and install anchors in front row
(and middle row if applicable). Drill 10MM diameter hole
1 ½” deep and remove all dust from hole. Do not drill too
deep. Install anchor with provided insert tool.
Note: If concrete subfloor has additional
layer of softer leveling slag and anchors
do not hold, a longer anchor bolt may be
necessary.
Do not install anchors at edges or corners at this time.
One good blow is better then many small taps when installing anchors.
ETL File E8138
11
Note: Units without Stainless Floor start here
Side Chanel
Rear Base
Channel
Place wall base channels as pictured. Outside
dimensions should match Specification
Sheet. Mark outside edge with non
permanent marker.
ASSEMBLY CONT’D
.
Each proofer is supplied with enough track to install a
120” deep proofer.
Holes in side channel indicate cutting points for base
channels. Cut side channels short enough to leave front
corners exposed.
You may need both channel pieces depending on the
size of the proofer.
Side Chanel
No base channel on door side of proofer.
Optional: Seal base channels with small amount of
silicone to stop leaks from developing at bottom of unit.
Press base channel to floor.
Note: Recheck dimensions to insure
wall panels fit into track. Once
silicone dries, base channels are hard
to move. See Spec. Sheet.
See wall panel location Chart 1 for panel placement.
ETL File E8138
12
ASSEMBLY CONT’D
Chart 1,
Panel locations
155-707 155-709 155-706 155-707
155-706-4 155-710
155-709155-705-10 155-710 155-705
Ceiling Panels should match side wall panels.
Example: On a BAP2-30 you should have 1 20” ceiling and 2 20” wall panels.
ETL File E8138
13
ASSEMBLY CONT’D
Place header assembly on floor upside down.
Note: When installing Panel
Assemblies inspect to insure gasket
material is installed along all edges.
Gasket
on all
three
sides
Header panel requires gasket material as shown. If gasket
is missing moisture will migrate into panel sections.
All three sides pictured have grey gasket material
installed.
Note: When locking a cam it may be necessary
to first rotate cam all the way back until a
positive click is heard. This will ready the cam
for locking. DO NOT OVER TIGHTEN! Over
tightening will damage the cam.
Once the cam is reset it will not click again until you attempt
to lock the cam into its receiver, or onto a screwdriver shaft.
If cam will not reset or lock, lubricate cam with WD-40® or
equivalent and work cam open and closed until it resets and
locks.
If front corners have two screws installed,
remove two screws from each front corner
panel top. These screws will later be reused
to secure the valance.
Screw
in top of
front
ETL File E8138
14
Install Front Corner panel and tighten cams.
Note: Do not over tighten.
A positive click should be felt when cam is locked. If
cam will not click into locked position do not over
tighten. Lube cam and work until cam locks. See note
on previous page.
Flip front assembly over.
ASSEMBLY CONT’D
Reinstall screw in top of each front corner panel
securing valance.
Shim Part # 155-249
Note: Check sides for gasket material on all sides!
Install one left and one right side to front. Place front with side panels into base track, then plumb front corners. To plumb place
level on front as pictured in center photo. Cams may need to be repositioned to achieve plumb. Shim (Part #155-249) front to achieve level, left to right only. Shims, pictured below level, are provided with unit.
See Chart 1 on page 13 for correct panel placements. Continue to add side panels 90º in relation to ground. Keep the front plumb and level. Shim sides as needed. Allow top of panels to be uneven if necessary to maintain to maintain 90 º angles from
ground. Drain holes on back corners go to bottom back of unit.
ETL File E8138
15
b
Align front as necessary, then mark rear base channel
position.
Remove rear corners.
ASSEMBLY CONT’D
Note: Drain holes on back corners go to
bottom back as pictured.
Drain hole
always goes to
ottom, back
Drill holes with rotary drill and install anchors in rear base
channel. Drill 10MM diameter hole 1 ½” deep and remove
all dust from hole. Do not drill too deep. Install anchor with
provided insert tool.
Note: If concrete subfloor has additional
layer of softer leveling slag and anchors
do not hold, a longer anchor bolts may
be necessary.
Note: Make sure all hinge mounting
screws are tight.
Hang door(s). Use a 30”x 1”x 4” board (as shown) or a
Hinge
Washe
dolly to lift door and move into position.
Make sure both hinges seat and hinge washers are
present.
Remove two screws from conduit mounting hole.
Insert wire harness and short end of conduit into door.
Reinstall two screws through bracket and gasket.
Plug temperature / humidity sensor into board with
flat side of connector up as pictured.
Plug connector from control panel into connector
from door. Align D shaped male pin with D shaped
receptacle. Verify wire #’s on both sides of
connector correspond.
Check to assure all wires in connecter seat
Temp/Humidity
Sensor flat side up
tightly together.
ETL File E8138
17
Screw control panel into door using supplied screws.
Bend tabs as necessary to align with center set of
holes.
Bezel may need to be bent slightly to create tight fit to
panel.
Install bezel as shown using supplied screws.
Optional: A small bead of silicone around bezel will
seal bezel.
ASSEMBLY CONT’D
Install door handles and bumpers onto
door(s).
Install conduit bracket and gasket in valance.
Note: Inspect ceiling panels for
gasket material on bottom.
Install ceiling panels flush with sides.
ETL File E8138
18
ASSEMBLY CONT’D
Align back corners and install one screw. Recheck door alignment and plumb of front. Shim front with part #
155-249 as needed to obtain plum.
Align ceiling panels flush with side and install
remaining 3” hex head ceiling screws.
Peel all vinyl from inside unit.
Fill cam holes with caulk and install plugs.
Check for gaps and caulk header to top seam
openings.
and all other
Note: If unit is a pass through leave out 2 upper
corner plugs in corner without climatizer;
instead, install stiffener plate Part #155-323 in
corners without climatizer installed. Stiffener
plate should join corner and header and be
secured with supplied stainless steel hardware.
ETL File E8138
19
t
m
Install left and right jam trim, and anchor bracket
Jam Tri
155-377 anchor bracke
to unit. Drill and tap bracket mounting holes.
Shim if needed with 155-377-1.
Secure only with Stainless Steel
provided.
Anchor brackets to floor; see page 16 for anchor
instructions.
Caulk base channels to floor inside and out.
Install rear corners behind base molding.
Cut to fit and install base trim over corners.
Drill trim mounting holes with provided drill bit. Lube
holes and tap with provided tap. Secure with provided
Stainless Steel
ASSEMBLY CONT’D
screws
machinescrews.
Install top trim part #155-745 using provided
screws.
Do not over tighten.
ETL File E8138
20
ASSEMBLY CONT’D
Apply caulk to backside of high limit mounting
bracket and install high limit and bracket.
Gasket
must be
installed
On BAP1 and BAP2 models Install 250V light
bulb, gasket, and globe.
New BAP3 models will have Florescent Lamps
pre-installed.
Note: If 120V bulbs are
installed fuses will blow.
Remove fan guard, cover, and water line from air duct
assembly.
Determine duct location.
Single Door Proofers - Back wall tight to left side.
Double Door Proofers - Left side wall tight to front.
Double Duct Proofers - Mount first duct on left side wall tight
to front. Mount second duct on same side tight to back.
BAP3 Models – Ducts can be mounted on left or right side
determine by drain location.
Remove climatizer mounting screws from applicable corner.
ETL File E8138
21
m
g
g
NOTE: Hold Climatizer as tight to top as possible when
drillin
holes to prevent gap at top causing uneven proofin
ASSEMBLY CONT’D
!
Hold duct in position using 17 ½” chalk block to support weight while holding tight to side and top. Shim chalk
block as necessary to align left side mounting holes.
CAUTION! Hold duct in place tight to top until all mounting screws are inserted.
Right side holes are pre-threaded; insert top two screws. Bottom left screw may need to be remarked, drilled, and
tapped as pictured on right
Drill and tap duct right hand mounting holes with drill bit and tap provided. Secure with provided Stainless Steel
achine screws in 6 places.
Route wires through black bushing in ceiling.
Note: Protect your wires. Make sure wires are
away from moving parts and plastic bushings are
installed into header.
Insert water supply line, ferrule, and nut through ceiling.
BAP1 Models Only
Install water line pointing towards rear of proofer.
Make sure water line is long enough to reach back of unit.
ETL File E8138
22
y
ASSEMBLY CONT’D
Install 90º fitting to water line pointing down into unit.
Install climatizer water line into 90º fitting; this water line
ships with climatizer and has a 90º bend that points into
nozzle assembly.
Install water line into nozzle assembly.
Reinstall covers onto climitizer.
Note: Silicone all water line and
electrical holes leading into
proofer.
BAP2 Models Only
Install climatizer water line into 90º fitting; this water
line ships with climatizer and has a 90º bend that
points into nozzle assembly.
See above step; install water line into nozzle
assembl
.
ETL File E8138
23
ASSEMBLY CONT’D
BAP2 with 2 Climatizers Only
Cut climatizer water line below ferrule and nut,
leaving room on short piece to add T fitting as
pictured below.
This may be necessary on some BAP3 models also.
Install T fitting as pictured with 90º facing rear
climatizer assembly.
Install water line pointing towards rear of
proofer.
Make sure water line is long enough to reach
back of unit.
Go to top of page 22. Install line to
climatizer.
ETL File E8138
24
BAP with 2 Climatizers Only
If climatizers are to be mounted on right hand side remove
pictured fan jumper wires and relocate jumper to right hand
side of additional harness mounted inside header. This harness
is only used when climatizers are mounted on the right. It
brings power from the left side of the header to the right side
of the header. Connect wires 10 and 16 disconected from fan
jumper wires to left side of this additional harness.
Wires 10 and 16
ASSEMBLY CONT’D
Pass Through Models Only.
Install rear light jumper harness to
front header as pictured.
Pass Through Models Only.
Use self drilling screws to attach harness to rear header as pictured.
Pass Through Models Only.
Connect light jumper wires at front
header to wires 10 and 16 and to rear
header ballast.
Pass Through Models Only.
Install Angle Bumper to protect Climatizer assembly
from racks using supplied stainless sheet metal screws.
ETL File E8138
25
ASSEMBLY CONT’D
BAP3 Models
Install 2 water lines as pictured. Shape one
water line to rear climatizer and one water
line to front climatizer.
Install 90º fitting to water line pointing down into unit.
Install climatizer water line into 90º fitting; this water
line ships with climatizer and has a 90º bend that points
into nozzle assembly.
Note: After wiring elements and plumbing,
silicone all wire and plumbing access holes
to top of proofer.
Install water line into nozzle assembly.
Reinstall covers onto climitizer.
Note: After wiring elements and
plumbing, silicone all water line and
electrical holes leading into proofer.
ETL File E8138
26
Silicone
openings after
wiring and
plumbing are
complete.
ASSEMBLY CONT’D
Silicone
openings
For Model BAP3 With right hand climatizers only. Additional harness is mounted inside header
to bring power from contactors and wires 10 and 16 (fan power wires) to right si de of header.. All connections
at rear are made at terminal block as drawn in above Detail B. Push all wires through Front Electrical Cover
into header.
ETL File E8138
All front conections made at terminal block inside header as drawn above in Detail A.
27
ASSEMBLY CONT’D
Step 11
Wire Cover channel installation for heat boxes
• Caulk wires into the hole in the ceiling panel to form a vapor barrier.
• If only one heat box is present, no conduit or relay connection box is necessary
Illustration 11
On BAP1 cover will go tight to
front over element wires.
ETL File E8138
28
ASSEMBLY CONT’D
CAUTION
CAUTION
WARNING
THIS APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE ABSENCE
OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA
70-1996.
FOR INSTALLATION IN CANADA THE INSTALLATION MUST BE IN
ACCORDANCE WITH CAN/CGA-B149.1&2 OF THE INSTALLATION CODE,
AND LOCAL CODES WHERE APPLICABLE. ALL ELECTRIC WIRING MUST
BE IN ACCORDANCE WITH THE CURRENT CANADIAN ELECTRICAL CODE,
C22.1 PART 1. GROUNDING THIS APPLIANCE MUST CONFORM TO
CANADIAN ELECTRICAL CODE, CSA C22.2.
INSTALLATION OF THE UNIT MUST BE DONE BY PERSONNEL QUALIFIED
TO WORK WITH ELECTRICITY AND PLUMBIN IMPROPER INSTALLATION
CAN CAUSE INJURY TO PERSONNEL AND /OR DAMAGE TO EQUIMENT.
UNIT MUST BE INSTALLED N ACCORDANCE WITH ALL APPLICAL CODES
Electrical Connection
Electrical connection can be made through a 3/4” knockout in the back of the valence. A three pole
terminal block has been provided on the component assembly for power connection. Please refer to wiring
diagram for phasing.
½” NPT Fitting provided at the top of the
unit behind the valance.
Drain Connection
Water drain connection can be made at a ½” NPT nipple provided at the bottom left hand corner of the proofer. Drain
must be vented for proper drainage.
Drain Bumper
Bumpers
Drain Bumper
Temporarily install drain bumpers, mark mounting holes.
Remove drain bumper, drill mounting holes with provided
drill bit. Lube holes and tap with provided tap. Secure with
provided Stainless Steel
machinescrews.
Note: White Nylon Bumper Guard not needed on
wall above drain bumper.
Install White Bumpers on climatizer(s) and remaining
sides of proofer with provided Stainless Steel
Do not install above Drain Bumper.
screws.
White Nylon Bumper (not installed
above Drain Bumper)
ETL File E8138
30
Single Phasing BAP1 Models Only
See wiring diagram for models BAP2 and BAP3
ASSEMBLY CONT’D
208/240V single phase
Ground
Renumber to 4, 5, and
6, if needed
ETL File E8138
31
Single Phasing BAP1 Models Only
See wiring diagram for models BAP2 and BAP3
ASSEMBLY CONT’D
Reposition wires as
pictured.
Elements should be numbered
1,2,3,4,5 and 6 (See wire
diagram) and hooked up to
match wire numbers on
terminal block.
Terminal Block should be
numbered 1,2,3,4,5 and 6.
ETL File E8138
32
WIRING DIAGRAM
On BAP2 and BAP3 models connect as shown here.
BAP1 Models see connection instructions at bottom of page.
Single phase BAP2, BAP3
connect odd # wires to L1
and even # wires to L2 on
load side of terminal block
On single phase
BAP1 models only;
BAP1
Models
ETL File E8138
Connect power
supply to L1 and L3
of terminal block
and all element
leads odd # wires to
L1 and element lead
even # wires L2 of
contactor as
pictured below.
33
PARTS LIST
Item No. Qty. Part No. Description
Pictured
Below
Not Shown 1 40102-21
Not Shown 1 40102-65
Not Shown 1 40102-65-1
Pictured
Below
1 40102-62 Control Board
4 Channel Timer Board (LRP3 Models
only)
Control Board with 4 channel timer
mount without 40102-21 Timer Board
Control Board LRP3 complete with 4
channel timer
1 40106-05 Temp/Humidity Sensor
40102-62 Pictured.
Comes with Temp/Humidity Combination
THE INFORMATION IN THIS MANUAL IS CRUCIAL AND MUST BE
RETAINED FOR FUTURE REFERENCE. READ, UNDERSTAND AND
FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS
MANUAL.
DANGER
WARNING
CAUTION
NOTICE
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN DEATH.
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.
POTENTIALLY HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, MAY RESULT IN MINOR OR MODERATE INJURY.
Helpful operation and installation instructions and tips are
present.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY
OR DEATH. READ THE INSTALLATION, OPERATING AND MAINTENANCE
INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS
EQUIPMENT.
MOVING PARTS HAZARD. FOLLOW LOCKOUT PROCEDURES BEFORE
REMOVING AIR DUCT OR EVAPORATOR FAN GUARDS
ELECTRICAL HAZARD BEHIND UPPER FRONT TRIM. FOLLOW LOCKOUT
PROCEDURES BEFORE SERVICING.
THE BARP SERIES PROOFER / RETARDER PRODUCES HUMIDITY WHICH
WILL NATURALLY CONDENSE AND ACCUMULATE WATER ON THE
INTERIOR FLOOR CAUSING IT TO BECOME SLIPPERY. ADJACENT
EXTERIOR FLOOR MAY ALSO BECOME SLIPPERY. USE EXTREME
CAUTION WHEN WALKING IN OR AROUND THIS APPLIANCE.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
For best results, always allow your proofer to reach set temperature and
humidity before putting product in.
For best results, proof at lower temperatures rather than higher.
To dry proof: Set humidity to the lowest setting (either 45% or less). At
this setting the humidity generator is turned off and will not produce
humidity.
When the actual humidity is less than 46% display will show 45. When the
actual humidity is higher than 45%, display will show the actual humidity.
The Retard mode will operate without using the timer if continuous
retarding is desired.
The Proof mode will operate without using the timer if continuous proofing
is desired.
Service on this or any other equipment must be performed by qualified
personnel only. Consult your authorized service agency directory or call
the factory for the service agent nearest you.
NOTICE
The BARP1 has hinges mounted on the right jamb only.
NOTICE
NOTICE
WARNING
ETL File E8138 Rev. A 2001
A qualified & licensed refrigeration mechanic must perform connection,
evaluation & charging of refrigeration lines. The condenser unit, if
supplied, is recharged, but additional refrigerant may be required.
For units needing more than one piece of trim to span one side, join the
two pieces by overlapping with the ceiling trim cap.
TO REDUCE THE RISK OF FIRE, THE APPLIANCE IS TO BE MOUNTED ON
FLOORS OF NON-COMBUSTIBLE CONSTRUCTION WITH NONCOMBUSTIBLE FLOORING AND SURFACE FINISH AND WITH NO
COMBUSTIBLE MATERIAL AGAINST THE UNDERSIDE THEREOF, OR ON
NON-COMBUSTIBLE SLABS OR ARCHES HAVING NO COMBUSTIBLE
MATERIAL AGAINST THE UNDERSIDE THEREOF. SUCH CONSTRUCTION
SHALL IN ALL CASES EXTEND NOT LESS THAN 12 INCHES BEYOND THE
EQUIPMENT ON ALL SIDES.
42
IMPORTANT READ FIRST IMPORTANT
CAUTION
CAUTION
WARNING
WARNING
WARNING
WARNING
THIS APPLIANCE, WHEN INSTALLED, MUST BE ELECTRICALLY
GROUNDED IN ACCORDANCE WITH LOCAL CODES, OR IN THE
ABSENCE OF LOCAL CODES, WITH THE NATIONAL ELECTRICAL CODE,
ANSI/NFPA 70-1996.
FOR INSTALLATION IN CANADA THE INSTALLATION MUST BE IN
ACCORDANCE WITH CAN/CGA-B149.1&2 OF THE INSTALLATION CODE,
AND LOCAL CODES WHERE APPLICABLE. ALL ELECTRIC WIRING MUST
BE IN ACCORDANCE WITH THE CURRENT CANADIAN ELECTRICAL
CODE, C22.1 PART 1. GROUNDING THIS APPLIANCE MUST CONFORM
TO CANADIAN ELECTRICAL CODE, CSA C22.2.
INSTALLATION OF THE UNIT MUST BE DONE BY PERSONNEL QUALIFIED
TO WORK WITH ELECTRICITY AND PLUMBING IMPROPER
INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND /OR DAMAGE
TO EQUIMENT. UNIT MUST BE INSTALLED IN ACCORDANCE WITH ALL
APPLICAL CODES
MOVING PARTS HAZARD. FOLLOW LOCKOUT PROCEDURES BEFORE
REMOVING AIR DUCT OR EVAPORATOR FAN GUARDS
ELECTRICAL HAZARD BEHIND UPPER FRONT TRIM. FOLLOW LOCKOUT
PROCEDURES BEFORE SERVICING.
THE BARP SERIES PROOFER / RETARDER PRODUCES HUMIDITY WHICH
WILL NATURALLY CONDENSE AND ACCUMULATE WATER ON THE
INTERIOR FLOOR CAUSING IT TO BECOME SLIPPERY. ADJACENT
EXTERIOR FLOOR MAY ALSO BECOME SLIPPERY. USE EXTREME
CAUTION WHEN WALKING IN OR AROUND THIS APPLIANCE.
ETL File E8138 Rev. A 2001
43
LOCKOUT PROCEDURE
Lockout Procedure
9. Announce lockout to other personnel.
10. Turn both heat and control power off at main panel.
11. Clear unit of all personnel.
12. Test lockout by turning power switch on and observing if control panel displays or fan(s) come on.
Check heater circuit with voltmeter.
13. Perform necessary repairs or tests.
14. Clear unit of personnel before restarting.
15. Turn power on at main panel.
16. Announce unit is “on” to other personnel.
Safety Precautions
The Factory hereby disclaims any and all responsibility for injury, damage, loss or other claim that may
occur to person or property from improper alteration, modification, addition, operation, maintenance or
service, whether it be mechanical, electrical, fuel, operator, motor or otherwise, which may occur from
such improper alteration, modification, addition, operation, maintenance or service to this piece of
equipment.
Safety Considerations
Your Proofer / Retarder is manufactured to rigid standards. This equipment is E.T.L. listed and meets
safety and sanitation standards.
The presence of safety equipment control and interlocks on an appliance and attendant components of
installation cannot in and of themselves, assure absolute safety of operation. Diligent, capable, well
trained operators and maintenance personnel, as well as proper programs of operation and maintenance,
are essential to the safe and reliable operation of this appliance.
E. The responsibility of the manufacturer
recommendations for the operation and maintenance of the appliance.
F. Trained qualified and factory-authorized personnel must perform all operation, maintenance and
repair of these appliances. It is the responsibility of the owner / operator
happens.
G. A regular periodic program of cleaning, inspection and maintenance must be established and
comprehensive maintenance records maintained. It is the sole responsibility of the user
schedule and enforce the frequency and scope of these programs in keeping with recommended
practice and with due consideration given to actual operating conditions.
H. The appliance must be operated within the limits, which will not exceed the working limits of
any component within the appliance as a whole.
is to supply suitable, comprehensive instructions and
to ensure that this
to establish,
ETL File E8138 Rev. A 2001
44
EQUIPMENT DESCRIPTION
Exterior
BARP1
•The Proofer / Retarder exterior dimensions are 38.4” (97.5 cm) wide x 91.5” (232.5 cm) high x a depth
dependent upon model number [39.3” (100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides
are constructed of stainless steel.
BARP2
•The Proofer / Retarder exterior dimensions are 78.8” (200 cm) wide x 91.5” (232.5 cm) high x a depth
dependent upon model number [39.3” (100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides
are constructed of stainless steel.
BARP3
•The Proofer / Retarder exterior dimensions are 102.5” (260 cm) wide x 91.5” (232.5 cm) high x a depth
dependent upon model number [39.3” (100 cm) to 129.3” (328.5cm)]. The Top, Front, Back, and Sides
are constructed of stainless steel.
All Units
• Modular design allows for a wide variety of sizes.
• The Proofer / Retarder door is constructed of stainless steel and comes with both single and double doors.
Interior
BARP1
•The Proofer / Retarder interior dimensions are 33.1” (84 cm) wide x 74.1” (188.25 cm) high x a depth
dependent upon model number [22.1” (56 cm) to 112.1” (284.7 cm)]. The Top, Front, Back, and Sides are
constructed of stainless steel.
BARP2
•The Proofer / Retarder interior dimensions are 68.1” (173 cm) wide x 74.1” (188.25 cm) high x a depth
dependent upon model number [27.1” (68.8 cm) to 117.1” (297.4 cm)]. The Top, Front, Back, and Sides
are constructed of stainless steel.
BARP3
•The Proofer / Retarder interior dimensions are 91.8” (173 cm) wide x 74.1” (188.25 cm) high x a depth
dependent upon model number [27.1” (68.8 cm) to 117.1” (297.4 cm)]. The Top, Front, Back, and Sides
are constructed of stainless steel.
All Units
•Floor level loading.
ETL File E8138 Rev. A 2001
45
EQUIPMENT DESCRIPTION CONT’D
Air-Duct(s)
Each Proofer / Retarder comes with one or two air ducts. These air ducts perform the tasks of heating,
humidifying and circulating the air within the unit. Each duct contains a heater plate, spray nozzle, drain
pan and fan.
Evaporator(s)
Each Proofer / Retarder comes with one or two evaporators. These evaporators perform the task of
cooling the interior of the unit, while maintaining a relatively high level of humidity. The evaporators,
manufactured by Russell, consist of refrigeration coils, a thermal expansion valve, and a fan.
Condensing Unit
The condensing unit may or may not be provided with the system. Customers may choose to run off of a
remote refrigeration system. If used, the condensing unit consists of a compressor, a fan, a receiver, a line
drier and a solenoid valve. If the condensing unit is not used, the solenoid valve will still be provided to
control unit cooling.
ETL File E8138 Rev. A 2001
46
CLEANING & SPECIFICATIONS
WARNING
NOTICE
THE BARP SERIES PROOFER / RETARDER PRODUCES HUMIDITY WHICH
WILL NATURALLY CONDENSE AND ACCUMULATE WATER ON THE
INTERIOR FLOOR CAUSING IT TO BECOME SLIPPERY. ADJACENT
EXTERIOR FLOOR MAY ALSO BECOME SLIPPERY. USE EXTREME
CAUTION WHEN WALKING IN OR AROUND THIS APPLIANCE.
Service on this or any other equipment must be performed by qualified
personnel only. Consult your authorized service agency directory or call
the factory for the service agent nearest you.
Every Day
Clean interior and exterior of Proofer / Retarder.
Every Six Months
Have factory authorized service personnel check Proofer / Retarder for proper temperature readings, air duct,
drain, heater plate, spray nozzle.
As Needed
Clean interior and exterior walls and replace light bulb or any other components as needed.
Water: .73 gallons per hour maximum per air duct, (2 ducts maximum) @ 30 PSI.
1 gallon per hour maximum per air duct, (2 ducts maximum) @ 60 PSI
1.70 gallons per hour maximum per air duct, (2 ducts maximum) @ 80 PSI.
Electrical: See Specification Sheet or BAP installation manual for electrical specifications. Control wires from
proofer are supplied for valve; however, compressor power feed is not included in specifications.
Drain: Tee into proofer drain. See installation instructions.
ETL File E8138 Rev. A 2001
47
WORKING PRINCIPLE
NOTICE
ETL File E8138 Rev. A 2001
A qualified & licensed refrigeration mechanic must perform connection,
evaluation & charging of refrigeration lines. The condenser unit, if supplied,
is charged, but additional refrigerant may be required.
48
Instructions for Installer:
Note: Assemble the proofer per the BAP installation instructions provided.
Step 1:
Remove the evaporator(s) from the shipping container. Remove the cover with the fan installed and inspect the evaporator,
noting any dents or loose screws. Repair as needed. Inspect the evaporator tubing for holes leaks or unsoldered joints. (It is
easier to do this inspection before you mount the evaporators.)
Step 2:
Refer to the table page 49 for the correct location of the evaporator in the cabinet.
Note: A 12” minimum air gap to front
Evaporator Locations.
Hold the evaporator (less the cover) against the ceiling and mark the location of the 4 mounting holes. Drill these holes with
a ¼” drill through the ceiling. Mount the evaporator(s) with the ¼” x 3” stainless steel screws, washers, lock washers and
nuts provided. Locate the approximate location of the fan connection inside the evaporator(s). Drill a 3/8” hole through the
evaporator(s) and through the ceiling at this location. Install the 3/8” plastic busing in these holes to protect the electrical
wires.
10 Steps
wall is necessary for good circulation of air before temp probe. See Table:
INSTALLATION
Qualified Installer
ETL File E8138 Rev. A 2001
49
INSTALLATION
Qualified Installer
ETL File E8138 Rev. A 2001
50
Step 3:
Locate the flexible electrical conduit and connectors provided with the retarder kit. Install one connector in the available
conduit hole in the back of the header assembly.
Locate (do not attach at this time) the ventilated electrical connection box over the 3/8” diameter hole(s) in ceiling with the
bushing(s) installed. Install conduit connectors in these boxes.
Note: If there are two evaporators provided, a box will need to be installed over each electrical connection hole.
Stretch the electrical conduit from the header to the first box. Cut conduit to size and install between header and first box.
Repeat this procedure between the first and second box if applicable. Locate the liquid line solenoid valve provided with the
retarder kit and install a conduit connector. Stretch a reasonable length of conduit (approximately 48”) from the last
connection box to the liquid line solenoid valve. Connect conduit between the last box and the liquid line solenoid valve. See
“Fig: Wire covers and conduit installation for evaporator and condenser” on next page.
Step 4:
Feed the evaporator fan wires through the ceiling and onto the top of the retarder/proofer. Be sure that these wires are
secured in the evaporator so that normal servicing will not put tension on any wire going through the ceiling. Feed the 18
gauge wire provided through the conduit and connect to wires 16 and 18 in the header. Connect one wire from each
evaporator fan and one wire from the liquid line solenoid to wire 16 in each electrical box cover. Connect wire 18 to the other
evaporator fan wire in each connection box and at the liquid line solenoid. See drawing # 61124-08 on page 51.
Note: Evaporator fans and the liquid line solenoid will both function at the same time.
Step 5:
Screw both ends of the electrical connection boxes to the ceiling. Reinstall the cover on the liquid line solenoid connection
box. Reinstall the cover on the header. See “Fig: Wire covers and conduit installation for evaporator and condenser” on next
page.
INSTALLATION
Qualified Installer
ETL File E8138 Rev. A 2001
51
INSTALLATION
Qualified Installer
Fig: Wire covers and conduit installation for evaporator and condenser.
ETL File E8138 Rev. A 2001
52
INSTALLATION
ETL File E8138 Rev. A 2001
53
Step 6:
Units with local condensing unit only:
Place the condensing unit on top of the retarder proofer. Locate the condenser so that the refrigeration lines will easily
connect with the evaporator inside the retarder/proofer. Be sure that there is ample space around the condenser to allow
airflow at temperatures less than 90º F. Allow adequate space for air discharge to prevent air discharge from recycling
through the fan. Anchor the condenser to the top of the retarder/proofer through the mounting holes in the base.
INSTALLATION
Qualified Installer
ETL File E8138 Rev. A 2001
54
Step 7:
Collect the expansion valve(s), liquid line dryer, pressure switch (if provided; check parts list), and this manual. Please have
them available for the refrigeration technician.
Note: The refrigeration system must be assembled, tested, charged and certified by a certified refrigeration
technician.
Have electrician hook up power. Please partner with the electrician to make sure he has information in this manual necessary
to hook up power to proofer/retarder and compressor.
Note: The electrical connections must be made by a certified electrician.
Step 8:
Hook up drain. Note: Install union at evaporator to allow for servicing.
Install Union
INSTALLATION
Qualified Installer
Install Union
Install Union
ETL File E8138 Rev. A 2001
55
Step 9:
Before the refrigeration system is connected and charged, check electrical power, water and drain to the retarder/proofer.
Turn on the retarder proofer and operate in normal operation (see proofer installation instructions and installation start-up and
training check list).
Turn on the “Hold” or “Retard” functions and verify the following:
• Both evaporator fans operate while the retarder is cooling.
• The liquid line solenoid valve is activated when the retarder is cooling.
• Both the evaporator fans and the liquid line solenoid turn off when the retard temperature is set above the actual
temperature.
Turn on the “Proof” or “Rest” functions and verify the following:
• The climitizer fan turns on and stays on after the first call for heat.
• The evaporator fan turns off when the climitizer fan turns on.
Have refrigeration technician hook up refrigeration system.
Step 10:
Set the control clock to the correct day and time. Refer to the retarder control operating manual for set-up and operation
instructions. Be sure to arrange for training the operator on programming and use.
INSTALLATION
Qualified Installer
ETL File E8138 Rev. A 2001
56
Instructions for Electrician: 2 Steps
Step 1: Hook up power to BARP.
Electrical connection can be made through a 3/4” knockout in the back of the valence. A three pole
terminal block has been provided on the component assembly for power connection. Please refer to wiring
diagram for phasing.
Note: Condenser requires separate power connection.
BARP Electrical Specifications do not include condenser.
INSTALLATION
See “Table: Condensing Unit Electrical Specifications” on next page.
Instructions for assembling, inspecting, charging and testing the refrigeration
system:
Must be completed by certified refrigerationtechnician.
5 Steps:
Verify that the retarder proofer is assembled and that the evaporator is installed per the first half of these instructions.
Unless otherwise noted or requested, this retarder/proofer is designed for use with R404a refrigerant. Throughout assembly
and inspection, reasonably accepted practices should be used in conjunction with the refrigeration system. If you have any
questions or concerns please the Factory or the local supplier of the provided components.
Units with local condensing unit:
See “Table: Condensing Unit Electrical Specifications” on previous page for condensing unit specifications
Step 1:
Condensers rates at ½ hp and less need a pressure switch to control the condenser motors. If not previously installed, install
switch in the suction line Schrader valve and connect the wires to the condenser electrical box per the condenser
manufacturer’s schematic. Condensers equipped with adjustable pressure switches should be set at approximately 50 PSIG
cut-in and 30 PSIG cut-out for a low minimum system temperature of 20 degrees F.
See Drawing No: 61124-08 on page 51.
ETL File E8138 Rev. A 2001
59
Certified Refrigeration Technician
Note: The condenser is pre-charged with refrigerant ample for the condenser.
Additional refrigerant will need to be added once the refrigeration piping is installed, tested and evacuated.
Step 2:
Connect electrical power to the condenser per the condenser manufacturer’s instructions. Note: the condenser requires a
separate power supply from the retarder/proofer circuit.
INSTALLATION
Instructions for all retarder/proofers
Step 3:
Piping
: Refrigeration components are thoroughly cleaned and capped by the manufacturer of the component. Take care to
keep these sealed and as free as possible from moisture.
Step 4:
Install the expansion valve in the evaporator(s) in a position that will allow for adjustment of the evaporator superheat.
Verify that the expansion valve is the correct size for the evaporator load (see parts list). Install the sensing bulb in
accordance with the instructions provided with the expansion valve(s). Secure the capillary line so that it can not be damaged
while servicing the evaporator.
Notes to refrigeration technician
Connect liquid line using copper tubing sized to match the solenoid valve provided.
If two evaporators are provided reduce line size to ¼” at the tee connection on the top of the unit.
Insulate the return suction line to provide compressor cooling. Be sure that the resulting compressor superheat is
between 25º and 40º F.
Adjust expansion valve to obtain 8º to 10º F of evaporator superheat. Obtain the superheat by measuring the
discharge temps at the TXV and the evaporator.
ETL File E8138 Rev. A 2001
60
Certified Refrigeration Technician
Model # Kit # Part # Qty. Part Nomenclature Description / Kit Title
40102-63 1 Control, BARP "S" T ype All Retarder Proofers
All BARP
Models
BARP1-40
BARP1-50
BARP1-60
BARP1-70
BARP2-30
BARP1-40HO
BARP1-50HO
BARP1-80
BARP1-90
BARP1-100
BARP1-110
BARP2-40
BARP2-50
BARP1-120
BARP1-60HO
BARP1-70HO
BARP2-60
BARP1-80HO
BARP1-90CHO
BARP2-30HO
BARP2-40HO
BARP2-70
BARP2-80
BARP2-90
BARP3-60
BARP3-70
BARP3-80
155-673-1 1 Relay Harness, BARP All Retarder Proofers
30701-05 1 Relay 24VAC 2 pole All Retarder Proofers
155-749 1 Drain Kit, BARP All Retarder Proofers
72610-36 1 Kit includes parts below Kit Evaporator, A
91500-06 1 Evaporator Coil .21 Ton, 2,500 BTU
91500-23 1 Expansion Valve .25 Ton
91500-30 1 Switch, Pressure Suction Line Low Pressure Switch
91500-04 1 Solenoid Valve ¼” Dia.
91500-11 1 Dryer, Line ¼” Dia.
91500-26 1 Coil MCK1-240 208/240V Coil
72610-37 1 Kit includes parts below Kit Evaporator B
91500-07 1 Evaporator Coil .29 Ton 3,500 BTU
91500-10 1 Expansion Valve .50 Ton
91500-30 1 Switch, Pressure Suction Line Low Pressure Switch
91500-04 1 Solenoid Valve ¼” Dia.
91500-11 1 Dryer, Line ¼” Dia.
91500-26 1 Coil MCK1-240 208/240V Coil
72610-38 1 Kit includes parts below Kit Evaporator, C
91500-02 1 Evaporator Coil .38 Ton 4,500 BTU
91500-10 1 Expansion Valve .50 Ton
91500-30 1 Switch, Pressure Suction Line Low Pressure Switch
91500-04 1 Solenoid Valve ¼” Dia.
91500-11 1 Dryer, Line ¼” Dia.
91500-26 1 Coil MCK1-240 208/240V Coil
72610-39 1 Kit includes parts below Kit Evaporator, D
91500-08 1 Evaporator Coil .46 Ton, 5,500 BTU
91500-10 1 Expansion Valve .50 Ton
91500-30 1 Switch, Pressure Suction Line Low Pressure Switch
91500-04 1 Solenoid Valve ¼” Dia.
91500-11 1 Dryer, Line ¼” Dia.
91500-26 1 Coil MCK1-240 208/240V Coil
PARTS
ETL File E8138 Rev. A 2001
61
Model # Kit # Part # Qty Part Nomenclature Description / Kit Title
1
Kit includes parts below Kit Evaporator, E
2
2
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Evaporator Coil .29 Ton, 3,500 BTU
Expansion Valve .25 Ton
Switch, Pressure Suction Line Low Pressure Switch
Solenoid Valve 3/8” Dia.
Dryer, Line 3/8” Dia.
Coil MCK1-240 208/240V Coil
Kit includes parts below Kit Evaporator, F
Evaporator Coil .38 Ton, 4,500 BTU
Expansion Valve .50 Ton
Solenoid Valve 3/8” Dia.
Dryer, Line 3/8” Dia.
Coil MCK1-240 208/240V Coil
Kit includes parts below Kit Evaporator, .90 Ton
Evaporator Coil .46 Ton, 5,500 BTU
Expansion Valve .50 Ton
Solenoid Valve 3/8” Dia.
Dryer, Line 3/8” Dia.
Coil MCK1-240 208/240V Coil
Kit includes parts below Kit Evaporator, G
Evaporator Coil 1.6 Ton, 20,000 BTU
Expansion Valve 1.5 Ton
Solenoid Valve 3/8” Dia.
Dryer, Line 3/8” Dia.
Coil MCK1-240 208/240V Coil
Kit includes parts below Kit Evaporator, 1.25 Ton
Evaporator Coil 1.25 Ton, 15,000 BTU
Expansion Valve 1.5 Ton