ABB C1900R Programming Guide

Programming Guide
Circular Chart Recorder
IM/C1900–PGR_10
C1900
ABB
The Company
EN ISO 9001:2000
We are an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liquid analysis and environmental applications.
Cert. No. Q 05907
application expertise, service and support worldwide.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivalled
EN 29001 (ISO 9001)
service and support.
The quality, accuracy and performance of the Company’s products result from over 100 years experience, combined with a continuous program of innovative design and development to
Lenno, Italy – Cert. No. 9/90A
incorporate the latest technology.
The UKAS Calibration Laboratory No. 0255 is just one of the ten flow calibration plants operated
Stonehouse, U.K.
by the Company and is indicative of our dedication to quality and accuracy.
0255
Electrical Safety
This equipment complies with the requirements of CEI/IEC 61010-1:2001-2 'Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use'. If the equipment is used in a manner NOT specified by the Company, the protection provided by the equipment may be impaired.
Symbols
One or more of the following symbols may appear on the equipment labelling:
Warning – Refer to the manual for instructions
Caution – Risk of electric shock
Protective earth (ground) terminal
Earth (ground) terminal
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of the Technical Publications Department.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the information given.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressure and/ or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets (where applicable) may be obtained from the Company address on the back cover, together with servicing and spares information.
Direct current supply only
Alternating current supply only
Both direct and alternating current supply
The equipment is protected through double insulation
Part No.
IM/C1900–INS
INSTALLATION
Product Identification Siting Mounting Electrical Connections Installation Record
OPERATION
Setting Up
Operating Level Simple Fault Finding
PROGRAMMING
General Programming Basic Config. Level Advanced Config. Level Connections and Links
DATA SHEET
Full Specification
Part No.
IM/C1900–OGR
Displays & Controls
Part No.
IM/C1900–PGR
Part No.
SS/C1900
Flow Totalization Ramp/Soak Profile Math Functions Timer Functions
MODBUS (RTU)
Serial Adaptors Serial Connections Programming Pages ASCII Tables
Part No.
IM/C1900–ADV
Part No.
IM/C1900–MOD
ADVANCED SOFTWARE
OPTIONS
A – Standard Manuals
B – Supplementary Manuals

CONTENTS 1 INTRODUCTION

Section Page
1 INTRODUCTION ........................................................... 1
2 GENERAL PROGRAMMING ........................................ 2
2.1 Preparation for Changes to the Parameters ........ 2
2.2 Security System.................................................. 2
3 BASIC CONFIGURATION LEVEL ................................. 3
3.1 Set Up Input (Process Variable) ........................... 4
3.2 Set Up Pen Range/Event Source ........................ 8
3.3 Set Up Chart ......................................................9
3.4 Set Up Alarms .................................................. 10
3.5 Set Up Relay Output .........................................15
3.6 Set Up Digital Output ........................................ 17
3.7 Set Up Analog Output.......................................19
3.8 Digital Inputs ..................................................... 21
3.9 Access Page .................................................... 22
3.10 Scale Adjust .....................................................23
4 ADVANCED CONFIGURATION LEVEL ...................... 26
4.1 Set Up Function Keys .......................................27
4.2 Set Up Logic.....................................................28
4.3 Set Up Pen Functions ....................................... 31
5 CONNECTIONS & LINKS ...........................................32
The documentation for the C1900 series of circular chart recorders is shown in Fig. 1.1. The
Standard Manuals, including
the data sheet, are supplied with all instruments. The
Supplementary Manuals supplied depend on the specification of
the instrument.
Fig. 1.1 C1900 Documentation
1

2 GENERAL PROGRAMMING

The programming procedures are used to make changes to the operating parameter values and for scale adjustment.
The programming of all channels is performed using faceplate 1 – see Fig. 2.1.
When changing the input type it may be necessary to reposition the input selector links accordingly – see Section 5,
CONNECTIONS & LINKS.

2.1 Preparation for Changes to the Parameters

Isolate all external alarm/control circuits to prevent inadvertent operation during programming.
Changes to the operating parameters are implemented using
or keys – see Section 3 of the Operating Guide.
the
Note. The recorder responds instantly to parameter changes which are saved automatically when leaving the current frame.

2.2 Security System

A security system is used to prevent tampering with the programmed parameters by restricting access to programming levels, other than the this level.
A security password is used to give access to the programming pages. The password can be set to any value from 0 to 9999. The recorder is despatched with the password set to '0' – see Section 4.5 of
OPERATOR LEVEL; all users have access to
Operating Guide.
Faceplate 1
Fig. 2.1 Location of Faceplate 1
2
SEtUP
INPUt
Set Up Input (PV)
Input Type (PV)
Temperature Units
ENG–LO
____
dEC–Pt
____
rNG–HI
_.__
Input Range High
IntYP
____
SEtUP
ALArMS
Set Up Alarms
Acknowledge Type
SELECt
__
CHArt
____
Chart Time
Stop Chart Signal
Select PV/Pen/Filter
Scale Reset
Offset Adjustment
Cal. Pen At 100%
Cal. Pen At 0%
Select Alarm
trIP
____
Trip Level
Span Adjust
Set Up Inputs
Section 3.1 Page 4
Set Up Pen Range
Section 3.2 Page 8
Set Up Alarms
Section 3.4 Page 10
Setup Chart
Section 3.3 Page 9
Scale Adjust
Section 3.10 Page 23
UNItS
____
ENG–HI
____
Input Range Low
FdLP-I
_.__
Fault Detection Level
Programmable Filter
PrGFLt
_.__
bSPd
____
Broken Sensor Drive
rNG–LO
_.__
HYSt
____
Hysteresis
Select Pen
Pen Range High
Pen Range Low
In Source
SEtUP
PENrNG
Set Up Pen Range
tYPE
____
Alarm Type
ACKtYP
____
t–HYSt
____
Time Hysteresis
Select Channel
SELECt
____
SELECt
____
rESEt
__
OFFSEt
____
SPAN
____
SEtPEN
At100
Scale Adjust
SCALE
AdJUSt
Set Up Chart
SELECt
____
PEN–HI
____
PEN–LO
____
Out Source
IN SrC
______
OUt.SrC
______
SEtUP
CHArt
CH–StP
______
Engineering High
Decimal Point
Engineering Low
Linearizer Type
LNtYP
____
ACKSrC
______
Alarm Ack Source
Select Output
Output Range High
Output Range Low
Output Source
Set Up Analog Output
*
Section 3.7 Page 19
SELECt
____
Set Up Relay Output*
Section 3.5 Page15
Select Relay
SELECt
____
Relay Source
Set Up Output
SEt UP
ANALOG
Set Up Relay
SEt UP
rELAYS
Retrans. Range Hi
Retrans. Range Low
SOUrCE
____
HI–OP
____
LO–OP
____
OP–SrC
____
rNG–HI
____
rNG–LO
____
Polarity
POLrtY
____
ACCESS
PAGE
Access Page
Access Page
Section 3.9 Page 22
Configure Password
C– PASS
__
dIGtAL
INPUtS
Digital Inputs
Digital Inputs
*
Section 3.8 Page 21
Polarity
POLrtY
___
Select Digital I/P
SELECt
____
SEtPEN
At 0
Check Pen Cal.
CHECK
__._
Auto Pen Drop
AUtdrP
___
Pen Lift Enable
LIFt.EN
___
Pen Lift/Pen Status
PENLFt
____
OPrtOr
LEVEL
bASIC
CONFIG
AdVNCd
CONFIG
Basic Config
Advanced Config
Operator Level
Set Up Digital Output
Section 3.6 Page 17
Select Output
SELECt
____
Output Source
Digital Outputs
dIGtAL
OUtPtS
SOUrCE
____
Polarity
POLrtY
____
Mains Filter
FILtEr
__ Hrt
PEN-AJ
____
Pen Adjust Enable
PA-PAS
____
Pen Adj. Password
dELAY
____
Alarm Delay
EN-Sr-C
____
Enable Source

3 BASIC CONFIGURATION LEVEL

These pages do not appear on the
*
non-upgradeable version (1901J)
Fig. 3.1 Basic Configuration Level Overview
3
…3 BASIC CONFIGURATION LEVEL

3.1 Set Up Input (Process Variable)

Information.
• Universal inputs – mV, mA, V, THC, RTD and resistance.
•Internal cold junction compensation.
•Linearization – of temperature sensors to allow use of non-linearizing transmitters or any electrical input.
•Programmable fault levels and actions.
Digital filter – to reduce the effect of noise on inputs.
Example A – setting up:
•a current input of 4 to 20mA
•displaying a range of 0 to 200psi
•a fault detection level 10% above 200psi (engineering/display range) and 10% below 0psi (engineering/display range)
•in the event of a fault being detected and/or the fault detection level being exceeded the process variable is driven downscale.
Input
Type
RTD THC
Current
Voltage Millivolts Low resistance High resistance
Linearizer
Type
5/2 3/2
RTD THC B THC N THC E THC J THC T THC S THC R THC K
None
Temp. Units
FC
None
Electrical
Range
20.0
(Input Range High)
4.0
(Input Range Low)
Engineering Range
(Display Range)
220
0
–20
Fault Detection
Level
10%
200
Fault Detection
Level
10%
Broken Sensor
Protection Drive
Downscale
Upscale
Programme
Value set to 0
Value set low
Value set high
Example B – setting up:
•a Type K thermocouple
•displaying temperature in F
•displaying a range of 0 to 2000F
•a fault detection level 10% above 2000F (engineering/display range) and 10% below 0F (engineering/display range)
•in the event of a fault being detected and/or the fault detection level being exceeded the process variable is driven upscale.
Input
Type
RTD
THC
Current Voltage Millivolts Low resistance High resistance
Linearizer
Type
5/2 3/2
RTD THC B THC N THC E THC J THC T THC S THC R
THC K
None
Temp. Units
F
C
None
Engineering Range
(Display Range)
2200
–200
Fault Detection
Level
10%
2000
0
Fault Detection
Level
10%
Broken Sensor
Protection Drive
Downscale
Upscale
Programme
Filter
Value set to 0
Value set low
Value set high
Filter
4
…3.1 Set Up Input (Process Variable)
SEt UP INPUt
Page Header – Set Up Input (Process Variable)
To advance to
3 BASIC CONFIGURATION LEVEL…
Set Up Pen Range Page press the key.
SELECt PV–4 PV–3 PV–2 PV–1
INtYP rtd tCPL VOLt LO OHM HI OHM MAMP MVLt NONE
NONE
LNtYP 5/2 3/2 SQrt rtd tC–b tC–N tC–E tC–J tC–t tC–S tC–r tC–K NONE
Select Channel
Select the channel to be programmed:
PV– 1 Channel 1 PV– 2 Channel 2 PV– 3 Channel 3 PV– 4 Channel 4
Note. In the remaining frames press the
Input Type (Process Variable)
Caution. Ensure the correct input link positions are selected and the input is wired correctly – see
Section 5,
Select the input type required:
Linearizer Type
Select the linearizer type required:
Continued on next page.
CONNECTIONS & LINKS.
rtd – Resistance thermometer tCPL – Thermocouple VOLt –Voltage LO OHM – Low resistance (750) HI OHM –High resistance (>750) MAMP – Current MU.Lt –Millivolt (150mV) NONE – None
5/2 –x 3/2 –x SQrt – Square Root rtd – Resistance thermometer tC–b –Type B thermocouple tC–N –Type N thermocouple tC–E –Type E thermocouple tC–J –Type J thermocouple tC–t –Type T thermocouple tC–S –Type S thermocouple tC–r –Type R thermocouple tC–K –Type K thermocouple NONE – No linearizer
5/2
Open channel flow applications
3/2
key to view the channel selected.
5
…3 BASIC CONFIGURATION LEVEL
…3.1 Set Up Input (Process Variable)
rNG–HI
20.0
Input Range High
Set the maximum electrical input value required (in electrical units).
Note. The value set must be within the limits detailed in the table below.
Input Type
rtd
or
tCPL
rNG–LO
4.0
UNItS dEG–F dEG–C NONE
ENG–HI 1000
epyTtupnI.niMwoLegnaR.xaMhgiHegnaR)hgiHotwoL(egnaR.niM
stlovilliM00510.5
stloV051.0
spmailliM0050.1
woLecnatsiseR005702
hgiHecnatsiseR09999004
Input Range Low
Set the minimum electrical input value required (in electrical units).
Note. The value set must be within the limits detailed in the above table.
Temperature Units
Select units required.
Engineering Range High
Set the maximum engineering (display) value required.
Note. The value set must be within the limits detailed in the tables below.
epyTreziraeniL
BepyT 02723872181–0081017 EepyT 841–256118001–00954 JepyT 841–256109001–00905 KepyT 841–2732711001–003156 NepyT 823–2732261002–003109
S&RepyT 0290367581–0071023
TepyT 814–275801052–00306
.niM.xaMnapS.niM.niM.xaMnapS.niM
tiehnerhaFseergeDsuisleCseergeD
DTR 823–211154002–00652
Performance accuracy is not guaranteed below 725F/400C for types B, R and S thermocouples. Minimum span below zero Type T 126F/70C Minimum span below zero Type N 189F/105C THC standard DIN 4730 IEC 584 RTD standard DIN 43760 IEC 751
epyTreziraeniL
2/5 2/3
tooRerauqS
enoN
Continued on next page.
6
.niM.xaM
9999–9999+
woLdnahgiHegnaRgnireenignE
…3.1 Set Up Input (Process Variable)
3 BASIC CONFIGURATION LEVEL…
dECPt 1000
ENG–LO 0
bSPd UP NONE dN
FdLP ––––––
Decimal Point
Set the decimal point position required for low values.
Engineering Range Low
Set the minimum engineering (display) value required,
Note. The value set must be within the limits detailed in
Broken Sensor Protection Drive
In the event of a fault being detected on the input and/or if the Fault Detection Level Percentage is exceeded (see next frame), the process variable is driven in the direction of the drive selected.
Select the broken sensor drive required:
both the engineering range high and engineering range
Engineering Range High tables opposite.
NONE – No drive UP – Upscale drive dN – Downscale drive.
Fault Detection Level Percentage
A fault level percentage can be set to detect a deviation above or below the display limits.
For example, if FdLP is set at 10.0%, a fault is detected if an input goes more than 10% above
Engineering Range High or more than 10% below Engineering Range Low.
On some ranges the input circuitry may saturate before the fault level set is reached. In this case an error is detected below the level set.
SELECt
PrGFLt ––
Set the level required, between 0.0 and 100.0% of engineering span (range low to high) in 0.1% increments.
Note. If an input exceeds the minimum or maximum value for the linearizer selected an error is detected regardless of any fault level.
Programmable Filter
Filters the process variable input, i.e. if the input is stepped it smooths the transition between steps and may also be used for some degree of cleaning of noisy inputs. The filter time represents the time a step in the input takes to change the displayed process variable from 10 to 90% of the step.
Set the value required, between 0 and 60 in 1 second increments.
Return to Select Channel frame.
7
…3 BASIC CONFIGURATION LEVEL

3.2 Set Up Pen Range/Event Source

Information.
•Trend pens – have an independent chart range allowing a selected part of the engineering (display) range to be used for
extra resolution on the chart.
Three position event pen function – can be driven by digital inputs, alarms, logic equation results and real time events (when timer option is fitted).
Select Pen Range (in engineering units)
1000
(Eng. Range High)
700
(Pen Range High)
400
(Pen Range low)
0
(Eng. Range Low)
Record Function Event Function
SEt UP PENrNG
SELECt PEN 4 PEN 3 PEN 2 PEN 1 NONE
NONE
TREND
Page Header – Set Up Pen Range
To advance to
Select Pen
Select the pen to be programmed
Note.
•In the remaining frames press the key to view the pen selected.
Record (trend) or event pen function is set in the Time Event Pen option is selected, the fourth pen is fitted with a special pen arm and is set automatically for event
Select 'In' Source Select 'Out' Source
*Source on
Source off
*In source takes priority if both sources enabled
Set Up Chart Page press the key.
pen function) – see Section 4.3, Set Up Pen Functions.
Event Pen Chart Position
*Pen 4 at 80%
Pen 3 at 60%
Pen 2 at 40%
Pen 1
at 20%
Source on
Source off
*With Real Time Event Pen option fitted, Pen 4 is above 100%
ADVANCED CONFIGURATION LEVEL (if True
EVENT
SELECt
8
PEN HI ––––––
PEN LO ––––––
IN SrC EQN–4
NONE
OUt.SrC EQN–4
NONE
SELECt
Pen Range High
Set the maximum value required on the chart, in engineering units (the value must be within the engineering range set in
Set Up Input Page – see Section 3.1).
Pen Range Low
Set the minimum value required on the chart, in engineering units (the value must be within the engineering range set in
Set Up Input Page).
In Source
Select a source to move the pen inwards on the chart.
For a description of sources – see Table 3.1 on page 16.
Out Source
Select a source to move the pen outwards on the chart.
For a description of sources – see Table 3.1 on page 16.
Return to Select Pen frame.
3 BASIC CONFIGURATION LEVEL…

3.3 Set Up Chart

Information.
Programmable chart duration – between 1 and 167 hours or 7 and 32 days.
Chart stop function – the chart can be stopped by an alarm, digital input, logic equation result or a real time event (if timer option is fitted).
Auto pen drop – automatically drops the pen(s) onto the chart after a 5 minute delay to ensure recording is not left disabled inadvertently.
SEt UP CHArt
SEt UP CHArt
CHArt 32dY
1Hr
CH–StP EQN–4
NONE
AUtdrP –––
LFt EN –––
Page Header – Set Up Chart
To advance to
Chart Duration
Select the chart duration required per revolution of the chart; between 1 and 167 hours or 7 and 32 days.
Stop Chart Source
Select the source required for stopping the chart.
For a description of sources – see Table 3.1 on page 16.
Auto Pen Drop
Select '
YES' selected, pen(s) drop automatically onto the chart 5 minutes after they are lifted.
If '
If '
NO' selected, the pen(s) remain lifted until they are manually dropped by the operator.
Pen Lift Enable/Disable
The
Set Up Alarms Page press the key.
YES' to enable or 'NO' to disable.
key can be disabled if required. Select 'YES' to enable or 'NO' to disable.
PENLFt rECOrd
LIFt
PArK
At rEF
drOP
rEtUrN
Pen Lift/Pen Status
To raise pen(s) press
key. The following status displays are shown:
rECOrd – pen records on chart LIFt – pen lifts off chart PArK – pen moves to park position At rEF – pen at reference position
To lower pen(s) press
key. The following status displays are shown:
rEtUrN – pen returns to record position drOP –drops (lowers) onto chart rECOrd – pen records on chart
Return to top of Set Up Chart Page.
9
…3 BASIC CONFIGURATION LEVEL

3.4 Set Up Alarms

Information.
Four alarms per channel – identified A1 to D1 (for channel 1) up to A4 to D4 (for channel 4).
Three operator acknowledge options.
Global alarm acknowledgment – by digital input, alarm, logic equation result or real time event (if option fitted).
High/low process alarms.
Delayed high/low process alarms.
Fast/slow rate of change – of process variable alarms.
Adjustable hysteresis value – to prevent oscillation of alarm state.
Time hysteresis – to allow delayed triggering of alarms.
Process Variable
Hysteresis
Trip Point
Hysteresis
High
Process
Low
Process
Output
Time in seconds
Counter
Started
Fig. 3.2 High and Low Process Alarm with Hysteresis
70 130
40 00
Counter
Reset
Counter
Started
Hysteresis Time
Elapsed
Alarm On
Alarm Off
Alarm On
Alarm Off
Alarm Trip Point
Alarm On
Alarm Off
Counter
Reset
10
Time Hysteresis Status
Example shows time hysteresis set to 70 seconds used with a high process alarm
Fig. 3.3 Time Hysteresis Alarm
…3.4 Set Up Alarms
Process
Variable
3 BASIC CONFIGURATION LEVEL…
Trip Point
Hysteresis
Alarm Enabled
Delay Time
Alarm Disabled
Alarm On
Alarm Off
1 2 3 4 5 6 7
The operation of a delayed high/low process alarm is identical to that of the standard high/low process alarm but the alarm can be enabled/disabled by use of a digital signal.
The alarm state is held off whilst the enable signal is off and continues to be held off for a pre-configured period of time after the enable signal is switched ON (irrespective of the process variable value). Once the pre-configured alarm delay time has expired then the alarm operates in the same manner as a standard high/low process alarm.
Process variable goes above trip point but alarm is not activated because enable signal is low (Alarm Disable).
1
Alarm Enable signal is switched On. Alarm delay timer started.
2
Process variable goes above trip point but alarm is not activated because alarm delay time has not expired.
3
Alarm delay timer expires, alarm is now enabled. Alarm is activated because process variable is above trip point.
4
Process variable goes below trip (hysteresis) point therefore alarm is de-activated.
5
Process variable goes above trip point, alarm is activated (alarm is enabled and delay time has expired).
6
Alarm Enable signal is switched Off. Alarm is disabled immediately. Alarm de-activates.
7
Fig. 3.4 Delayed High Process Alarm
11
…3 BASIC CONFIGURATION LEVEL
…3.4 Set Up Alarms
9.5 1 hour
The maximum time it takes to detect an alarm condition is present (T), in seconds, is calculated as follows:
T = 10.81 + x 2
The time it takes for the alarm state to be cleared once the alarm condition has been removed is also equal to T.
1800
Trip Value
10.1
10.1
10.1
1 hour
T T
Alarm On
Alarm Off
Falling Fast Rate
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
T = 10.81 + x 2
1800
10
T=382 seconds
1 hour
Alarm On
Alarm Off
Fig. 3.5 Slow Rate Alarms with Hysteresis
The maximum time it takes to detect an alarm condition is present (T), in seconds, is calculated as follows:
1800
Trip Value
1 hour
T = 10.81 + x 2
The time it takes for the alarm state to be cleared once the alarm condition has been removed is also equal to T.
1 hour
9.5
T T
Rising Fast Rate
10.1
1 hour
12
9.5 1 hour
Alarm On
Alarm Off
Falling Slow Rate Rising Slow Rate
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
T = 10.81 + x 2
1800
10
Alarm On
Alarm Off
T=382 seconds
Fig. 3.6 Fast Rate Alarms with Hysteresis
1 hour
T T T
9.5
T
…3.4 Set Up Alarms
3 BASIC CONFIGURATION LEVEL…
SEt UP ALArMS
ACKtYP LAtCH NOrMAL NONE
Page Header – Set Up Alarms
To advance to
Alarm Acknowledge Type
Alarms may be acknowledged while they are displayed. Select the alarm acknowledge type:
Set Up Relay Output page press the key.
NONE – no acknowledge facility. If the cause of the alarm no longer exists, the alarm state and
display are cleared automatically.
esuacmralADELetatSmralA
tneserPgnihsalFevitcA
tneserPtoNffOevitcanI
NOrMAL and LAtCH – if the cause of the alarm no longer exists, the alarm display remains
until it has been acknowledged.
esuacmralAegdelwonkcADELetatSmralA
tneserPoNgnihsalFevitcA tneserPseYydaetSevitcA
tneserPtoNdegdelwonkcaylsuoiverPffOevitcanI
tneserPoNgnihsalFevitcA
tneserPtoNoNgnihsalF*evitcanI/evitcA tneserPtoNseYffOevitcanI
*Alarm state is active if
LAtCH is selected or inactive if NOrMAL is selected.
Ch. 4
Ch. 3
Ch. 2
Ch. 1
ACKSrC ALM d4
NONE
SELECt ALM d4
ALM A4 ALM d3
ALM A3 ALM d2
ALM A2 ALM d1
ALM A1 NONE
NONE
Global Alarm Acknowledge Source
Select the alarm acknowledgment source required.
For a description of sources – see Table 3.1 on page 16.
Select Alarm
Select the alarm to be programmed.
Note. In the remaining frames press the
key to view the alarm selected.
Continued on next page.
13
…3 BASIC CONFIGURATION LEVEL
…3.4 Set Up Alarms
SELECt
tYPE dLY-LO dLY-HI S–rAtE F–rAtE LO–PrC HI–PrC OFF
OFF
trIP ––––––
HYSt ––––––
Alarm Type
Select the alarm type required for the alarm selected.
dLY-LO – delayed low process dLY-HI – delayed high process HI–PrC –high process LO–PrC –low process F–rtE –fast rate (rate of change of process variable) S–rtE –slow rate (rate of change of process variable) OFF –alarm off
Trip Level
Set the trip value required for the alarm selected.
The following are displayed in engineering units:
HPrC, LPrC.
The following are displayed as a percentage of the engineering span (engineering range high – engineering range low) per hour between 0.5 and 500%:
FrtE and SrtE.
Hysteresis
Hysteresis is operational when the alarm is active.
SELECt
All Others
SELECt
t–HYSt ––––––
dLY-HI
or
dLY-LO
dELAY
EN-SrC
NONE
Set the hysteresis value required for high/low process, in engineering units (within the engineering range) or in 0.1% increments for rate alarms. The alarm is activated at the trip level but is only turned off after the alarm variable has moved into the safe region by an amount equal to the hysteresis value. For rate alarms this setting is a percentage of the trip rate – see ' previous frame.
Time Hysteresis
Set the time hysteresis value required between 0 and 9999 seconds.
Note. The alarm condition must be present continually for the time set, before the alarm becomes active. If a hysteresis level is also set, the alarm condition remains active until the process variable moves outside the hysteresis band. When the alarm condition no longer exists the alarm becomes inactive, i.e. time hysteresis does not affect turning off of alarm states.
Alarm Delay
0
After a transition of the enable signal from disabled to enabled, the alarm remains disabled for this period of time. Set 0 to 250 minutes.
Enable Source
Any digital signal can be assigned as the signal to enable/disable the alarm.
FrtE' and 'SrtE' in
14
Return to Select Alarm frame.
3 BASIC CONFIGURATION LEVEL…

3.5 Set Up Relay Output

Information.
Relay Output – not applicable to 1901J (non-upgradeable version).
Relays – can be energized by alarms, logic equation results, digital inputs, real time events (timer option) and totalizer wrap signal (totalizer option).
External Totalizer count function – external counter can only be driven by module type 3 (4 relays module) fitted in module positions 4, 5 and 6.
Polarity – to allow failsafe settings.
Select Relay Output
Relay 5.1
Relay 5.2 Relay 5.3 Relay 5.4
Module Position Relay No.
SEt UP rELAYS
SELECt rLY 1.1
Module Position Relay No.
NONE
NONE
Relay Source
Alarm Acknowledge
Logic Equation 1
Logic Equation 8
Digital Input 1 Digital Input 2
Alarm A1
Alarm D4
None
Source State Polarity Relay State
Alarm A1
Active
Alarm A1
Active
Alarm A1
Inactive
Alarm A1
Inactive
Polarity Selection
Positive
Negative
Positive
Negative
Energized
De-energized
De-energized
Energized
Relay Contacts
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
Page Header – Set Up Relays
To advance to
Set Up Digital Output Page press the key.
Select Relay Output
Select the output to be programmed. The selections in this frame relate to the number of fitted modules with relays and their relative module positions.
Example – for a type 3 (four relays) module fitted in position five the following selections are also
programmable:
rELAY 5.1 (position 5, relay 1) rELAY 5.2 (position 5, relay 2) rELAY 5.3 (position 5, relay 3) rELAY 5.4 (position 5, relay 4)
NONE
SOUrCE
EQN–4
NONE
Note. In the remaining frames press the
key to view the relay selected.
Relay Source
Select the source required to activate the selected relay.
For a description of sources – see Table 3.1 on page 16.
Note. To drive an external counter
COUNt.x must be selected.
Continued on next page
15
…3 BASIC CONFIGURATION LEVEL
…3.5 Set Up Relay Output
POLrtY POStVE NEGtVE
SELECt
Polarity
The polarity selection is used to invert the effect of the digital source state on the relay state as shown in the following table:
etatSecruoSytiraloPetatSyaleR
evitcA
evitca-noN
Select the polarity required
Caution. Check connections before operating – see Section 5,
Return to Select Relay Output frame.
Source Description
AL_ACK
tIMEr..2 tIMEr.1
EQN–4 EQN–3 EQN–2 EQN–1
Alarm Acknowledge – Unacknowledged process alarm anywhere in the unit
Real time event 2 Real time event 1
Programmable logic equation 4 Programmable logic equation 3 Programmable logic equation 2 Programmable logic equation 1
Real time events (available only if timer option fitted – see
Programmable logic equations – see Section 4.2,
evitisoP
evitageN
evitisoP
evitageN
CONNECTIONS & LINKS.
Advanced Software Options Manual
Set Up Logic
dezigrenE
dezigrene-eD dezigrene-eD
dezigrenE
).
rAP–4 COUNt. 4
*
rAP–1 COUNt.1
*
dIG–6.8
dIG–1..1
AL–d4 AL–C4 AL–b4 AL–A4
AL–d3 AL–C3 AL–b3 AL–A3
AL–d2 AL–C2 AL–b2 AL–A2
AL–d1 AL–C1 AL–b1 AL–A1
Wrap around on total 4 Total 4 external counter drive
Wrap around on total 1 Total 1 external counter drive
Digital Input 6.8
Digital input 1.1
Digital Input number Module number
Alarm D Alarm C Alarm B Alarm A
Alarm D Alarm C Alarm B Alarm A
Alarm D Alarm C Alarm B Alarm A
Alarm D Alarm C Alarm B Alarm A
Channel 4 Alarms (if applicable)
Channel 3 Alarms (if applicable)
Channel 2 Alarms (if applicable)
Channel 1 Alarms
Wrap around and count (available only if totalizer option fitted)
NONE
* Available only on 4-relay and 8-digital output modules (types 3 and 5), fitted in module positions 4,5 and 6.
No source required
Table 3.1 Description of Sources
16
3 BASIC CONFIGURATION LEVEL…

3.6 Set Up Digital Output

Information.
This page is displayed only if digital outputs are fitted.
Up to 24 digital outputs are available – depending on the module types fitted.
Digital outputs – can be energized by alarms, logic equations results, digital inputs, real time events (timer option) and totalizer wrap signal (totalizer option).
External Totalizer count function – external counter can only be driven by module type 5 (8 digital outputs module) fitted in module positions 4, 5 and 6.
Polarity – inverts the effect of the selected source on the output state.
Select Digital Output
Module Position Output No.
Output 5.1
Output 5.2 Output 5.3 Output 5.4 Output 5.5 Output 5.6 Output 5.7 Output 5.8
Digital Source
Alarm Acknowledge
Logic Equation 1
Logic Equation 4
Digital input 1
Digital input 2
Alarm A1
Alarm D4
None
Polarity Selection
Source State Polarity Output State
Digital Input 1
Active
Digital Input 1
Active
Digital Input 1
Inactive
Digital Input 1
Inactive
Positive
Negative
Positive
Negative
Energized
De-energized
De-energized
Energized
17
…3 BASIC CONFIGURATION LEVEL
…3.6 Set Up Digital Output
dIGtAL OUtPtS
SELECt OUt 1.1
Module Position Output No.
NONE
SOUrCE EQN–4
NONE
NONE
NONE
Page Header – Set Up Digital Outputs
to advance to
Select Digital Output
Select the output to be programmed – the selections in this frame relate to the number of fitted digital output modules and their relative module positions.
Example – for a type 5 (eight digital outputs) module fitted in position five the following selections are
also programmable:
Set Up Analog Output page press the key.
OUt 5.1 (position 5, output 1) OUt 5.2 (position 5, output 2) OUt 5.3 (position 5, output 3) OUt 5.4 (position 5, output 4) OUt 5.5 (position 5, output 5) OUt 5.6 (position 5, output 6) OUt 5.7 (position 5, output 7) OUt 5.8 (position 5, output 8)
Note. In the remaining frames press the
Output Source
Select the source required to activate the selected digital output.
For a description of sources – see
Note. To drive an external counter
Table 3.1 on page 16.
COUNt.x must be selected.
key to view the output selected.
SELECt
POLrtY
POStVE NEGtVE
Polarity
The polarity selection is used to invert the effect of the source state on the output as shown in the following table:
etatSecruoSytiraloPetatStuptuO
evitcA
evitca-noN
Select the polarity required.
Caution. Check connections before operating – see Section 5,
Return to Select Digital Output frame.
evitisoP
evitageN
evitisoP
evitageN
CONNECTIONS & LINKS.
dezigrenE
dezigrene-eD dezigrene-eD
dezigrenE
18
3 BASIC CONFIGURATION LEVEL…

3.7 Set Up Analog Output

Information.
Analog Output – not applicable to 1901J (non-upgradeable version).
Fitted analog outputs – assignable to retransmit any process variable.
Selectable retransmission range – allows maximum resolution on range of interest.
Adjustable output range – for non-standard and reversed outputs.
Note. The example below shows analog output 1 set to retransmit part of process variable 1's engineering range (250 to 750C) as a 4.0 to 20.0mA current output.
Select Analog
Output
Position 1
Position 6
Select Output
Source
PV1
PV2 PV3 PV4
Setting Output Ranges
1000C (Engineering Range High)
750C (Retransmission Range High)
Range to be
transmitted
250C (Retransmission Range Low)
0C (Engineering Range Low)
20.0mA (Output Range High)
4.0mA (Output Range Low)
19
…3 BASIC CONFIGURATION LEVEL
…3.7 Set Up Analog Output
SEt UP ANALOG
SELECt POSN–1
OP–x NONE
NONE
OP–SrC
PV–4
PV–1 NONE
rNG–HI
––––
rNG–LO
––––
NONE
Page Header – Set Up Analog Output
To advance to
Select Analog Output
Select the analog output position to be programmed. The selections in this frame relate to the number of fitted modules with analog output.
Example – Output 1 is the analog output in position 1 (fitted on the main board), output 3 is the analog output fitted in module position 3.
Note. In the remaining frames press the
Output Source
Select output source required. The selections in this frame correspond to the channels on the recorder (as available) – PV1 (channel 1), PV2 (channel 2) etc.
Retransmission Range High
Set the engineering range value (in engineering units) at which maximum output is required.
Retransmission Range Low
Set the engineering range value (in engineering units) at which minimum output is required.
Digital Inputs Page press the key.
key to view the analog output selected.
SELECt
HI–OP
––.––
LO–OP
–.–
Output Range High
Set the maximum current output required for the and 20.0mA.
Output Range Low
Set the minimum current output required for the and 20.0mA.
Return to Select Analog Output frame.
Retransmission Range programmed between 2.0
Retransmission Range programmed between 2.0
20

3.8 Digital Inputs

Information.
Digital Input – not applicable to 1901J (non-upgradeable version).
Up to 30 digital inputs are available – depending on the module types fitted.
Volt-free contacts or TTL levels.
Polarity – sets the logic state (unchanged or inverted) for the module position(s).
3 BASIC CONFIGURATION LEVEL…
Select Digital Input
Position 1 Position 2 Position 3 Position 4 Position 5 Position 6
dIGtAL INPUtS
SELECt
POSN 1
POSN x NONE
SELECt
NONE
Input State
Switch Input
(volt-free)
or
or
Logic Input
(TTL)
5V
0V
5V
0V
Page Header – Digital Inputs
To advance to
Access Page press the key.
Select Digital Input
Select digital module position to be programmed.
Note. In the remaining frames press the
key to view the module selected.
Polarity
Selected
Negative
Positive
Negative
Positive
Logic State
Input Active
Input non-active
Input non-active
Input Active
POLrtY POStVE NEGtVE
Polarity
Select the polarity required for the module position selected above:
POStVE –logic input state unchanged NEGtVE –logic input state inverted
Return to Select Digital Input frame.
21
…3 BASIC CONFIGURATION LEVEL

3.9 Access Page

Information.
Configurable password protection – of
Internal security link – enable/disable password protection.
PROGRAMMING LEVELS.
ACCESS PAGE
C-PASS
0
PEN-AJ ENbL-Y
PA-PAS
Page Header – Access Page.
To advance to
Scale Adjust Page press the key.
Configuration Password
Prevents access to the
Programming Pages.
Pen Adjust Enable
Enables / Disables the pen adjustment feature. This allows the position of any trend to be adjusted for checking against a reference standard. The displayed value is not changed.
Pen Adjust Password
0
Prevents access to the pen adjustment.
Set the required password, between 0 and 9999.
Return to top of Access Page.
Operating
Pages
Without Correct
Security Code
Security Code
SECODE ____
Enter Security Code
(programmed in Access Page)
With Correct
OPrtOr
LEVEL
bASIC LEVEL
AdVNCd
LEVEL
Fig. 3.8 Location of Security LinkFig. 3.7 Use of Security Code in Operator Level
2 3 4 5 6
4
LK3
1
Enable Security position, allows access to configuration levels with correct security code.
4
LK3
1
Disable Security position,
allows unprotected access to configuration level.
3
ON
2
OFF
3
ON
2
OFF
22
3 BASIC CONFIGURATION LEVEL…

3.10 Scale Adjust

Information.
Analog Inputs – do not require re-calibrating when the input type or range is changed.
Process variable adjust reset – removes any previously programmed offset or scale adjustment settings.
System offsets errors – can be removed using process variable scale offset adjustment.
System scale errors – can be removed using process variable span adjustment.
Process variable offset/span adjustment – can be used to perform spot calibration
Pen(s) – can be independently calibrated and checked across the full range of the chart.
Mains filter – selectable for maximum noise rejection.
Pen Linearity Check – automatically draws a pen linearity test pattern.
Scale Adjustment
PV1
100C
(x) Span Adjust
(+) Offset
Engineering Range
250.0C
50.0C
Engineering Range
PV1
Offset Adjustment
Display
OFFSEt
99.8
CH2
CH3
CH4
Span Adjustment
Display
Chart
AL4AL3AL2AL1CH1
Display
200.3
AND
CH2
CH3
CH4
AL4AL3AL2AL1CH1
Offset Adjustment Display
OFFSEt
100.0
CH2
CH3
CH4
Span Adjustment Display
AL4AL3AL2AL1CH1
250.0C
SPAN
225.5
CH2
CH2
CH3
CH3
CH4
CH4
225C
Note. As a general rule:
use Offset adjustment for spot calibration at <50% of engineering range span. use Span adjustment for spot calibration at >50% of engineering range span.
50.0C
AL4AL3AL2AL1CH1
AL4AL3AL2AL1CH1
SPAN
225.0
CH2
CH2
CH3
CH3
CH4
CH4
AL4AL3AL2AL1CH1
AL4AL3AL2AL1CH1
23
…3 BASIC CONFIGURATION LEVEL
…3.10 Scale Adjust
SCALE AdJUSt
SELECt LINCHK FILtEr PEN–4
PEN–1
PV–4
PV–1 NONE
rESEt YES NO
OFFSEt
––––––
NONE
Page Header – Scale Adjust
To advance to
Select Process Variable/Pen
Select linearity check, process variable or pen required:
BASIC CONFIGURATION LEVEL frame use the key.
LINCHK –the pens automatically draw a test pattern to check pen linearity. dONE is
displayed on completion
FILtEr – mains frequency filter PEN x – pens 1 to 4 PV–4 –process variable on channel 4 PV–3 –process variable on channel 3 PV–2 –process variable on channel 2 PV–1 –process variable on channel 1 NONE – None
Note. In the remaining frames press the
Process Variable Scale Adjustment Reset
YES to reset the process variable offset and span values to their nominal values (values are reset
Set when frame is exited).
Process Variable Offset Adjustment
Electrical and resistance thermometer inputs: apply the correct input for the spot calibration required.
RTD inputs: use resistance values obtained from standard tables.
key to view the process variable or pen selected.
SPAN ––––––
SELECt
Thermocouple Inputs: measure the ambient temperature at the output terminals of the signal source
(calibrator). From thermocouple tables obtain the millivolt equivalent of this temperature (a) and that for the spot calibration temperature (b). Subtract (a) from (b) and set the signal source to the resultant value. (The voltage is negative if the spot calibration temperature is below the measured ambient temperature).
Note. The displayed units are engineering units.
Set the value required. The decimal point position is set automatically.
Example – If the display range is 50.0 to 250.0 and a spot calibration is required at 100 and 225,
inject a signal equivalent to 100 and set the display to 100.0 using the
Span Adjust
Proceed as for The displayed units are engineering units. Set the value required. The decimal point is set automatically.
For the example above, inject a signal equivalent to 225 and set the display to 225.0.
Continued on next page.
Offset Adjustment above and apply the correct input for the spot calibration required.
and keys.
24
…3.10 Scale Adjust
SELECt
PEN
SEtPEN At 100
3 BASIC CONFIGURATION LEVEL
Calibrate Pen At 100%
Drives the pen automatically to the full scale position on the chart.
Use the
and keys to set pen to 100% on the chart.
SELECt
PEN
SELECt
FILtEr
SELECt FILtEr
SEtPEN At 0
CHECK
__
FILtEr 60 Hrt 50 Hrt
Calibrate Pen At 0%
Drives the pen automatically to the zero position on the chart.
Use the
Check Pen Calibration
The pen calibration can be checked at any point on the chart.
Use the the chart.
Note. If the true time event option is fitted the red pen does not move beyond the 94% position on the chart.
Select Filter
Select the mains frequency of the supply used to ensure maximum noise rejection on analog inputs.
Return to Select Process Variable/Pen frame.
and keys to set pen to 0% on the chart.
and keys to move the selected pen from the zero point up to the 100% position on
25

4 ADVANCED CONFIGURATION LEVEL

OPrtOr
LEVEL
Operator Level
bASIC
CONFIG
Basic Config
AdVNCd CONFIG
Advanced Config
Set Up Functions Keys
Section 4.1 Page 27
SEt UP F – KEYS
Set up Function Keys
F–KEY1 ______
Function Key 1
F–KEY 2 ______
Function Key 2
Set Up Logic
Section 4.2 Page 28
SEtUP LOGIC
Set Up Logic
SELECt ECN. _ _
Select Equation
EQN. _.1 ______
Configure Logic
EQN. _.7 ______
Configure Logic
Set Up Pen Functions
Section 4.3 Page 31
PEN FUNCtN
Pen Functions
PEN– 1 _____
Pen 1 Function
PEN– 4 _____
Pen 4 Function
Fig. 4.1 Advanced Configuration Level Overview
26
4 ADVANCED CONFIGURATION LEVEL...

4.1 Set Up Function Keys

Information.
Programmable function key – on each faceplate
Home function – returns the instrument display to the start of the operating page when at the top of any page.
Global alarm acknowledge function – acknowledges any unacknowledged alarms on all channels.
SEt UP F–KEYS
F–KEY1
HOME ALMACK
F–KEY2 ALMACK
Page Header – Set Up Function Keys
To advance to the
Function Key 1
Select function required.
HOME – Home (return to Operating Page in OPERATING LEVEL) ALMACK – Acknowledge alarm
Function Key 2
Select function required (if applicable).
Return to Set Up Function Keys frame.
Set Up Logic press the key.
27
…4 ADVANCED CONFIGURATION LEVEL

4.2 Set Up Logic

Information.
4 logic equations
7 elements per equation
OR/AND operators
Can combine internal and external digital signals – i.e. alarms, digital inputs, other logic equation results and real time events (timer option).
For each equation, the logic elements 1 to 7 are arranged sequentially, as shown below. Odd numbered elements are used for logic inputs and even numbered elements for logic gates.
Logic inputs must be set to one of the digital sources listed in Table 3.1 on page 16. Logic gates must be set to ANd, Oror End. Setting an element to End terminates the equation.
EQN1.1
EQN1.3
Logic Inputs
EQN1.5
EQN1.7
EQN1.2
ANd/Or
EQN1.4
ANd/Or
EQN1.6
ANd/Or
Result
Note. Elements on each equation are calculated sequentially, i.e. elements 1, 2 and 3 are evaluated first and this result is then combined with elements 4 and 5. Similarly, this resultant is then combined with elements 6 and 7 to give the logic equation result.
28
4 ADVANCED CONFIGURATION LEVEL...
...4.2 Set Up Logic
Example – Reservoir level monitoring using:
•process variable 1 with an engineering range 0 to 100 feet
•logic equation 1 result assigned to relay 1.1 which is used to operate the control valve.
Manual Overide
Control
Valve
Alarm B1
Alarm A1
80
feet
Close reservoir control valve if:
• Reservoir level >50 feet AND rate of change >10 ft/hr
OR
• Reservoir level >80 ft OR
• Manual override switch operated
50
feet
Flow Conditions
Relay Output
Level Sensor
Input Elements
Alarm A1 – set to high process trip at 50 ft
Alarm B1 – set to high process trip at 80 ft
Alarm C1 – set to fast rate trip at 10% of range per hour (10 ft/hr)
Manual override switch: Connected to digital input 1.1
Digital input number
Module number Negative polarity Volt-free switching
Level
Alarm C1
Entering the
Logic Equation
EQN1.1 EQN1.2 EQN1.3 EQN1.4 EQN1.5 EQN1.6 EQN1.7
Rate of change > 10ft/hr
Time
AL–A1 ANd AL–C1 Or AL–B1 Or dIG–1.1
29
...4 ADVANCED CONFIGURATION LEVEL
…4.2 Set Up Logic
SEt UP
LOGIC
SELECt EQN1
EQN2 EQN3 EQN4
NONE
EQN 1-1
EQN4
NONE
NONE
EQN1-2 Or
ANd ENd
END
NONE
Equation No.
Element No.
Page Header – Set Up Logic
To advance to
Select Equation
Select equation to be constructed.
In the remaining frames press the
Equation n/Element 1
Select the source required for element 1.
For a description of sources – see
Equation n/Element 2
Select the operator required to combine elements 1 and 3:
Or –Or ANd – And ENd – Ends equation
Set Up Pen Functions Page press the key.
key to view the equation selected.
Table 3.1 on page 16.
EQN 1-3
EQN4
NONE
Equation n/Element 3
Repeat previous two steps for elements 3 to 7.
Odd numbered elements = sources Even numbered elements = operators
Return to Select Equation frame.
30

4.3 Set Up Pen Functions

Information. Any fitted pen can be assigned to a trend or an event function.
4 ADVANCED CONFIGURATION LEVEL
PEN FUNCtN
PEN FUNCtN
PEN–1
trENd
EVENt
PEN–2
PEN–4
Page Header – Pen Functions
To advance to
Pen 1
Select pen function required:
Advanced Configuration frame press the key.
trENd –Trend pen EVENt – Event pen
Note. The event pen and true time line event pen are separate functions and only the event pen can be selected in this page. The true time line event pen option allows event marking on the same time line as the red pen and requires a special pen arm and motor assembly. Refer to the order code in
Specification Sheet.
the
Pen 2 to 4
Repeat as for
Return to top of Set Up Pen Functions Page.
Pen 1 (if applicable).
31
1
2
7
8
9
10
1
12
3
4
5
6
Common
Input 1
Common
Input 7
Input 8
Input 5
Input 6
Input 3
Input 4
Input 2
Common
Output 1
Common
Output 7
Output 8
Output 5
Output 6
Output 3
Output 4
Output 2
8 Digital Inputs/Outputs Module
Digital O/Ps
2
1
3
4
2
1
3
4
Digital I/Ps
Digital I/O Module
PL2
1
2
7
8
9
10
1
12
3
4
5
6
NC
NO
Relay 1
C
Relay 2
Relay 3
Relay 4
NC
NO
C
NC
NO
C
NC
NO
C
4 Relays Module
+
Voltage
3
6
RTD (2-lead) &
Resistance
White
Red
Link
4
6
5
+
3
4
Current
Red
White
Red
4
6
5
RTD (3-lead)
2
1
3
4
PL8
1
4
8
5
PL1
58
41
PL1
PL3
23
14
+
Tx
2-wire Transmitter
4
6
*
2
1
3
4
PL8
1
4
8
5
PL1
58
41
PL1
PL3
23
14
1
2
7
8
9
10
1
12
Analog Output
+
Relay Output
Normally Open
Common
Normally Closed
Logic Inputs
Common
Logic 1
Logic 2
Analog Input
3
4
5
6
*
*
Not fitted on Analog + Relay Module
*
Main Input, Standard Input & Analog + Relay
+
THC & mV
3
6
58
41
1
4
8
5
2
1
3
4
PL1
PL8
PL1
PL3
2
1
3
4
2
3 4
5
6
INPUT/OUTPUT MODULE
3
4
5
6
Main
Board
I/O
Module
*
*
Recommended diode:
Diode forward voltage > 0.8 V @ 20 mA or use 2 x 1N4001 general purpose diodes in series.

5 CONNECTIONS & LINKS

32
PRODUCTS & CUSTOMER SUPPORT
Products
Automation Systems
• for the following industries:
– Chemical & Pharmaceutical – Food & Beverage –Manufacturing – Metals and Minerals –Oil, Gas & Petrochemical – Pulp and Paper
Drives and Motors
• AC and DC Drives, AC and DC Machines, AC Motors to 1kV
• Drive Systems
• Force Measurement
• Servo Drives
Controllers & Recorders
•Single and Multi-loop Controllers
•Circular Chart and Strip Chart Recorders
• Paperless Recorders
• Process Indicators
Flexible Automation
• Industrial Robots and Robot Systems
Customer Support
We provide a comprehensive after sales service via a Worldwide Service Organization. Contact one of the following offices for details on your nearest Service and Repair Centre.
United Kingdom
ABB Limited Te l: +44 (0)1480 475321 Fax: +44 (0)1480 217948
United States of America
ABB Inc. Te l: +1 215 674 6000 Fax: +1 215 674 7183
Flow Measurement
•Electromagnetic Flowmeters
•Mass Flow Meters
• Turbine Flowmeters
•Flow Elements
Marine Systems & Turbochargers
•Electrical Systems
•Marine Equipment
•Offshore Retrofit and Refurbishment
Process Analytics
• Process Gas Analysis
• Systems Integration
Transmitters
• Pressure
• Temperature
• Level
• Interface Modules
Valves, Actuators and Positioners
• Control Valves
•Actuators
• Positioners
Water, Gas & Industrial Analytics Instrumentation
• pH, Conductivity, and Dissolved Oxygen Transmitters and Sensors
•Ammonia, Nitrate, Phosphate, Silica, Sodium, Chloride, Fluoride, Dissolved Oxygen and Hydrazine Analyzers.
•Zirconia Oxygen Analyzers, Katharometers, Hydrogen Purity and Purge-gas Monitors, Thermal Conductivity.
Client Warranty
Prior to installation, the equipment referred to in this manual must be stored in a clean, dry environment, in accordance with the Company's published specification.
Periodic checks must be made on the equipment's condition. In the event of a failure under warranty, the following documentation must be provided as substantiation:
1. A listing evidencing process operation and alarm logs at time of failure.
2. Copies of all storage, installation, operating and maintenance records relating to the alleged faulty unit.
ABB has Sales & Customer Support expertise in over 100 countries worldwide
www.abb.com
The Company’s policy is one of continuous product improvement and the right is reserved to modify the
information contained herein without notice.
Printed in UK 10.08)
© ABB 2008
IM/C1900–PGR Issue 10
ABB Limited
Howard Road, St Neots Cambridgeshire PE19 8EU UK Tel: +44 (0)1480 475321 Fax: +44 (0)1480 217948
ABB Inc.
125 E. County Line Road Warminster PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183
Loading...