ABB AF40N2R & AF80N3R Catalog Page

AF40N2R & AF80N3R 3-pole NEMA rated reversing contactors
100 3.94"
110 4.33"
M6 ¼-20 UNC
130 5.12"
110 4.33"
M6 ¼-20 UNC
Sizes 2 & 3 AC / DC operated
Description
Note: for mechanically and electrically interlocked devices without power bus, replace the R in the catalog number with an M (ie. AF40N2R-30-22-13 becomes AF40N2M-30-22-13).
– control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range
(e.g. 100...250 V AC and DC), only 4 control voltage ranges covering 24...500V 50/60 Hz and 20...500 V DC
- can manage large control voltage variations
- reduced panel energy consumption
- very distinct closing and opening
AF40N2M-3022
A1
315 315
42 6 426
A2
Power bus diagram
A1
A2
– built-in surge suppression – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories
Ordering details
NEMA Rated control circuit Size Continuous
current
3-phase motor rating
voltage Uc min. … Uc max.
230V 460/575
A hp hp V 50/60Hz V DC kg
2
45
15
25
24…60 - 2 2 AF40N2R-3022-41 2.283 24…60 20…60 (1) 2 2 AF40N2R-3022-11 2.283 48…130 48…130 2 2 AF40N2R-3022-12 2.283 100…250 100…250 2 2 AF40N2R-3022-13 2.263 250…500 250…500 2 2 AF40N2R-3022-14 2.263
3
90
30
50
24…60 - 2 2 AF80N3R-3022-41 2.858 24…60 20…60 (1) 2 2 AF80N3R-3022-11 2.858 48…130 48…130 2 2 AF80N3R-3022-12 2.858 100…250 100…250 2 2 AF80N3R-3022-13 2.758
250…500 250…500 2 2 AF80N3R-3022-14 2.758 (1) AF..-30-..-11 not suitable for direct control by PLC-output. (2) Normally closed contacts included as part of the electrical interlock. Normally open auxiliaries are either integral or front-mount. (3) Available in the US and Canada only.
Auxiliary contacts fitted (2)
Catalog number
Global reference code (3)
Weight
Pkg (1 pce)
1
2
Mounting dimensions mm, inches
M4 8-32 UNC
100 3.94"
ø 4.2 0.17"
ø 6.4 0.25"
AF40N2R AF80N3R
4.6 0.18"
5 0.20"
100 3.94"
ø 6.4 0.25"
4.6 0.18"
5 0.20"
Loading...