Digital Indicator. In normal operation, all actions
taken by the user are to be in front of the panel.
Volume II:This supports the installation, commissioning and
configuring of the
1
-DIN Digital Indicator. It is
8
intended for use only by personnel who are trained,
equipped and authorised to carry out these functions.
1
-DIN
8
CAUTION: REFER TO MANUAL
THE INTERNATIONAL HAZARD SYMBOL IS INSCRIBED ADJACENT TO
THE REAR CONNECTION TERMINALS. IT IS IMPORTANT TO READ THE
MANUAL BEFORE INSTALLING OR COMMISSIONING THE UNIT.
59039
1
-DIN Digi tal In di ca tor
8
Prod uct Man ual - Vol ume I
1
-DIN DIGITAL INDICATOR
8
PRODUCT MANUAL
VOLUME I
OPERATING INSTRUCTIONS
In normal operation, the operator must not remove the
Indicator from its housing or have unrestricted access to the
rear terminals, as this would provide potential contact with
hazardous live parts.
Installation and configuration must be undertaken bytechnically competent servicing personnel. This is covered in
Volume II of this manual.
SM067- V1November, 2000(i)
1
-DIN Digi tal In di ca tor59039
8
Prod uct Man ual - Vol ume I
Con tents
1IN TRO DUC TION1-1
2OP ERA TOR MODE2-1
3SET UP MODE3-1
4RS485 SE RIAL COM MU NI CA TIONS4-1
Ap pen di ces
AAl pha beti cal In dexA-1
(ii)November, 2000SM067- V1
59039
1
-DIN Digi tal In di ca torSec tion 1
8
Prod uct Man ual - Vol ume IIn tro duc tion
SEC TION 1
INTRODUCTION
1
The
-DIN Digital Indicator is an easy-to-operate microprocessor-based instrument,
8
incorporating the latest in surface-mount and CMOS technology. The standard features
include:
Large four- digit LED dis play (or der able as red or green).
*
Dis play for units in di ca tion
*
Uni ver sal sen sor in put - ther mo cou ple, three- wire RTD or DC lin ear
*
(mA, mV or V)
In put range se lected from the front panel.
*
Alarm 1 latch ing or non- latching (user- selectable) re lay out put
*
Alarm hys tere sis
*
Maxi mum Hold, Mini mum Hold and Time Elapsed fea tures.
*
OM067-1November, 20001-1
Sec tion 1
In tro duc tionProd uct Man ual - Vol ume I
90 - 264V AC power sup ply.
*
De signed to com ply with EN50081 Part 2 (Emis sion) and EN50082
*
(Im mu nity) EMC speci fi ca tions.
Front panel seal ing to IP65 (NEMA 4) stan dard.
*
Pro gram ma ble digi tal fil ter.
*
Proc ess Vari able off set fa cil ity
*
Alarm type se lected from front panel.
*
Sen sor Break in di ca tion.
*
and the many optional features include:
1
-DIN Digi tal In di ca tor59039
8
Alarm 2 and Alarm 3 re lay out puts
*
Re mote re set of latched alarm
*
Re- transmitted Proc ess Vari able out put
*
Trans mit ter power sup ply
*
ASCII and MOD BUS com mu ni ca tions pro to cols
*
RS485 se rial com mu ni ca tions.
*
1-2November, 2000OM067-1
59039
1
-DIN Digi tal In di ca torSec tion 2
8
Prod uct Man ual - Vol ume IOp era tor Mode
SEC TION 2
OPERATOR MODE
2.1INTRODUCTION
The Operator Mode is the normal mode of the Indicator, once it has been set up and
configured as required. The front panel displays, indicators and keys are shown in
Figure 2-1.
Fig ure 2-1Front Panel Con trols, Dis plays and In di ca tors
2.2FOUR-DIGIT DISPLAY
In Operator Mode, this normally displays the process variable value. Using the Scroll
key, the operator may view, in a sequence according to the Operator Mode Display
Strategy parameter in Set Up Mode (see NOTES ON TABLE 3-1):
(i) Cur rent maxi mum value at tained by pro cess vari able (since the maxi mum
value was last re set) - MAX in di ca tor ON when this is dis played. Also saves
the Sen sor Break (see Sub sec tion 2.6) and Over- Range (see Sub sec tion
2.5) con di tions.
(ii) Cur rent mini mum value at tained by pro cess vari able (since the mini mum
value was last re set) - MIN in di ca tor ON when this is dis played. Also saves
the Sen sor Break (see Sub sec tion 2.6) and Under- Range (see Sub sec tion
2.5) con di tions.
OM067-2November, 20002-1
Sec tion 2
Op era tor ModeProd uct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
(iii) Time elapsed in the Alarm 1 ac tive con di tion (units dis play shows ).
The dis play is in the for mat mm.ss [mm = min utes, ss = sec onds] or mmm.s
[mmm = min utes, s = sec onds (tens)]. If elapsed time is greater than 999 min utes 59 sec onds, dis play will show:
NOTE: This does not in clude time when Alarm 1 is latched but alarm con di tion is cleared
(iv) Alarm 1 value (units dis play shows or, if only Alarm 1 pres ent, ).
(v) Alarm 2 value, if fit ted and con fig ured (units dis play shows ).
(vi) Alarm 3 value, if fit ted and con fig ured (units dis play shows ).
(iv) Proc ess vari able value.
Further depressions of the Scroll key will repeat this display sequence.
2.3ALARM STATUS INDICATORS
The Alarm Status indicators show the current state of the alarm(s):
AL1 -Flashes when Alarm 1 is ac tive (with latch ing alarm, ON whenAlarm 1 is latched but alarm con di tion has cleared)
AL2 -Flashes when Alarm 2 is ac tive
AL3 -Flashes when Alarm 3 is ac tive
For descriptions of the operation of the various types of alarm available, see Section 3.
2.4RESETTING THE MAXIMUM VALUE/MINIMUM VALUE OR TIME ELAPSED
VALUE
To reset the maximum value, minimum value (to the process variable value at the
instant of resetting) or time elapsed value (to zero):
1. Se lect the dis play of the maxi mum value, mini mum value or time
elapsed value (as ap pro pri ate - see above).
2. De press the Raise key or Lower key for three sec onds.
The resetting of the value is indicated by the four-digit display showing:
for two sec onds be fore re vert ing to the maxi mum value or mini mum value dis play.
2 -2November, 2000OM067-2
59039
1
-DIN Digi tal In di ca torSec tion 2
8
Prod uct Man ual - Vol ume IOp era tor Mode
2.5OVER-RANGE/UNDER-RANGE DISPLAYS
If the process variable attains a value higher than the input scale maximum limit
(over-range) or lower than the input scale minimum limit (under-range), the upper
display will show:
for the over-range condition and:
for the under-range condition.
2.6SENSOR BREAK INDICATION
If a break is detected in the sensor circuit, the four-digit display will show:
The reaction of the alarms to a detected sensor break is dependent upon the input type.
2.7COLD JUNCTION COMPENSATION DISABLED
If a thermocouple input is fitted, the Cold Junction Compensation should
be enabled. If it is disabled, whenever the process variable is displayed,
the unit display will be as shown on the right.
2.8RESETTING THE LATCHED ALARM
If Output 1 is configured to be a latched alarm output, once it becomes active it will
remain active (even if the alarm condition itself is cleared) until reset either from the
front panel or via the Remote Reset hardware option. To reset the latched alarm from
the front panel:
1. En sure that the nor mal Op er at ing Mode dis play (i.e. pro cess vari able)
is shown.
2. Press ei ther the Raise key or the Lower key for at least three sec onds.
The four-digit display will then show:
OM067-2November, 20002-3
Sec tion 2
Op era tor ModeProd uct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
for two seconds, indicating that the latched alarm has been reset. The latched Alarm 1
can be reset only if the original alarm condition has been cleared; this reset has no
effect whilst the alarm condition prevails.
2.9VIEWING THE HARDWARE DEFINITION CODE
The operator may view the current Hardware Definition Code setting in the four-digit
display by simultaneously depressing the Lower and Scroll keys. A return may be made
to the normal Operator Mode display by simultaneously depressing the Lower and
Scroll keys.
NOTE: An automatic return is made to the normal Operator Mode
display after 30 seconds.
To view the Hardware Option setting, press the Scroll key whilst the Hardware
Definition Code is displayed. To return to the Hardware Definition Code display,
depress the Lower and Scroll keys simultaneously.
2-4November, 2000OM067-2
59039
1
-DIN Digi tal In di ca torSec tion 3
8
Prod uct Man ual - Vol ume ISet Up Mode
SEC TION 3
SET UP MODE
3.1ENTRY INTO SET UP MODE
To enter Set Up Mode, with the instrument initially in Operator Mode displaying the
process variable value, depress the Raise and Scroll keys simultaneously for three
seconds. The instrument will then enter Set Up Mode and the SET indicator will come
ON, the instrument still displaying the process variable value.
NOTE: If the four-digit display shows:
(i.e. all decimal point positions illuminated), this indicates that one or
more of the critical Configuration Mode parameters - typically input
range - have been altered in value/setting and, as a consequence, all
Set Up Mode parameters have been automatically set to their default
values/settings. To clear this display, simply alter the value/setting of
any Set Up Mode parameter (see below).
The pa rame ters avail able for view/ad just ment in Set Up Mode are sum ma rised in Ta ble
3-1. When Set Up Mode is ac tive, the units dis play (nor mally oF, oC or blank) will show
the single- character leg end for the se lected pa rame ter and the value for that pa rame ter
will be shown in the four- digit dis play. The user may step through the Set Up Mode
pa rame ters by de press ing the Scroll key. The value/set ting may be al tered us ing the
Raise/Lower keys.
OM067-3November, 20003-1
Sec tion 3
1
-DIN Digi tal In di ca tor59039
8
Set Up ModeProd uct Man ual - Vol ume I
Table 3-1Set Up Pa rame ters
Parameter
Alarm 1 Value
1
Alarm 1 Hysteresis
Alarm 2 Value
Alarm 2 Hysteresis
Alarm 3 Value
Alarm 3 Hysteresis
2
2
3
3
Process Variable Offset
Digital Filter Time Const.
Legend
or
Adjustment Range
Range Min. to Range Max.
1 LSD to 10% of span expressed
as display units
Range Min. to Range Max.
1 LSD to 10% of span expressed
as display units
Range Min. to Range Max.
1 LSD to 10% of span expressed
as display units
input span of instrument
0.0 secs. (OFF) to 100.0 secs. in
0.5 sec. increments.
Default
Range Max. (Proc. High)
Range Min. (Proc. Low)
1 LSD
Range Max. (Proc. High)
Range Min. (Proc. Low)
1 LSD
Range Max. (Proc. High)
Range Min. (Proc. Low)
1 LSD
0
2.0 secs.
Linear Input Decimal
Point Position
Linear Input Scale
Range Minimum
Linear Input Scale
Range Maximum
4
4
4
Recorder Output Scale
Minimum
Recorder Output Scale
Maximum
Operator Mode Display
Strategy
5
0 (XXXX), 1 (XXX.X), 2 (XX.XX)
or 3 (X.XXX)
–1999 to 9999
–1999 to 9999
–1999 to 9999
–1999 to 9999
0, 1, 2, 3 or 4
1
0000
1000
Range Min.
Range Max.
0
3-2November, 2000OM067-3
59039
1. The legend for this parameter will be if only Alarm 1 is fitted/configured or if o ther
alarms are fitted/configured.
2. These parameters appear in the display sequence only if Alarm 2 is fitted/configured.
3. These parameters appear in the display sequence only if Alarm 3 is fitted/configured.
4. Only applicable if a DC Linear input is fitted.
5. Defines the parameters displayed in sequence in Operator Mode:
1
-DIN Digi tal In di ca torSec tion 3
8
Prod uct Man ual - Vol ume ISet Up Mode
NOTES ON TABLE 3-1
Parameter Setting
0
PV value
Max. PV value
Min. PV value
Elapsed Time
1
PV value
Max. PV value
Min. PV value
2
PV value
Alarm 1 value
Alarm 2 value *
Alarm 3 value *
* If configured/fitted
3
PV value
Max. PV value
Min. PV value
Alarm 1 value
Alarm 2 value *
Alarm 3 value *
4
PV value
Max. PV value
Min. PV value
Elapsed Time
Alarm 1 value
Alarm 2 value *
Alarm 3 value
3.2ALAR M 1 VALUEor
If Alarm 1 is selected to be a Process High alarm, this defines the process variable
value at or above which Alarm 1 will be active; the default value will be Input Range
Maximum. If Alarm 1 is selected to be a Process Low alarm, this defines the process
variable value at or below which Alarm 1 will be active; the default value will be Input
Range Minimum. Its value may be adjusted between Input Range Maximum and Input
Range Minimum. Alarm operation is illustrated in Figure 3-1.
3.3ALARM 1 HYSTERESIS
This parameter applies a hysteresis band on the “safe” side of the Alarm 1 value. The
effect of the hysteresis value on alarm operation is shown in Figure 3-2.
3.4ALARM 2 VALUE
If Alarm 2 is selected to be a Process High alarm, this defines the process variable
value at or above which Alarm 2 will be active; the default value will be Input Range
Maximum. If Alarm 2 is selected to be a Process Low alarm, this defines the process
variable value at or below which Alarm 2 will be active; the default value will be Input
Range Minimum. Its value may be adjusted between Input Range Maximum and Input
Range Minimum. Alarm operation is illustrated in Figure 3-1.
3.5ALARM 2 HYSTERESIS
This parameter applies a hysteresis band on the “safe” side of the Alarm 2 value. The
effect of the hysteresis value on alarm operation is shown in Figure 3-2.
OM067-3November, 20003-3
Sec tion 3
Set Up ModeProd uct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
3.6ALARM 3 VALUE
If Alarm 3 is selected to be a Process High alarm, this defines the process variable
value at or above which Alarm 3 will be active; the default value will be Input Range
Maximum. If Alarm 3 is selected to be a Process Low alarm, this defines the process
variable value at or below which Alarm 3 will be active; the default value will be Input
Range Minimum. Its value may be adjusted between Input Range Maximum and Input
Range Minimum. Alarm operation is illustrated in Figure 3-1.
3.7ALARM 3 HYSTERESIS
This parameter applies a hysteresis band on the “safe” side of the Alarm 3 value. The
effect of the hysteresis value on alarm operation is shown in Figure 3-2.
3.8PROCESS VARIABLE OFFSET
This parameter is used to modify the actual process variable value (measured at the
input terminals) in the following manner:
Offset PV value = Actual PV value + Process Variable Offset value.
The offset process variable value is used for all PV-dependent functions (display,
alarm, recorder output).
CAU TION: This is, in ef fect, a cali bra tion ad just ment. In ju di cious ap pli ca tion
of val ues to this pa rame ter could lead to the dis played pro cess vari able value
bear ing no mean ing ful re la tion ship to the ac tual pro cess vari able value.
There is no front panel in di ca tion when this pa rame ter is in ef fect (i.e.
has been set to a non- zero value).
The default value is 0.
3.9INPUT FILTER TIME CONSTANT
The input is equipped with a digital filter which is used to filter out any extraneous
impulses on the process variable. This filtered PV is used for all PV-dependent
functions (alarms etc.). The time constant for this filter may be adjusted in the range 0.0
seconds (filter OFF) to 100.0 seconds in 0.5 second increments. The default setting is
2.0 seconds.
CAUTION: If this parameter is set excessively high, the indication
quality may be significantly impaired. The value chosen should be
sufficiently large to attenuate stray noise but no larger.
3.10LINEAR INPUT SCALE RANGE MINIMUM
This parameter, applicable only if a linear input is fitted, defines the scaled input value
when the process variable input is at its minimum value. It is adjustable between –1999
and 9999 (with decimal point as defined by Linear Input Decimal Point Position). The
default value is 0. This parameter can be set to a value greater than (but not equal to)
Linear Input Scale Range Maximum, in which case the sense of the input is reversed.
3-4November, 2000OM067-3
59039
1
-DIN Digi tal In di ca torSec tion 3
8
Prod uct Man ual - Vol ume ISet Up Mode
3.11LINEAR INPUT SCALE RANGE MAXIMUM
This parameter, applicable only if a linear input is fitted, defines the scaled input value
when the process variable input is at its maximum value. It is adjustable between –1999
and 9999 (with decimal point as defined by Linear Input Decimal Point Position). The
default value is 1000. This parameter can be set to a value less than (but not equal to)
Linear Input Scale Range Minimum, in which case the sense of the input is reversed.
3.12RECORDER OUTPUT SCALE MINIMUM
This parameter defines the value of the process variable at which the Recorder Output
reaches its minimum value; for example, for a 0 - 5V Recorder Output, this value
corresponds to 0V. It may be adjusted within the range –1999 to 9999. The decimal
point position for the Recorder Output is always the same as that for the process
variable input range. The default value is Input Range Minimum. This parameter is not
applicable if the Recorder Output option is not fitted.
NOTE: If this parameter is set to a value greater than that for the
Recorder Output Scale Maximum (see Subsection 3.13), the
relationship between the process variable value and the Recorder
Output is reversed.
3.13RECORDER OUTPUT SCALE MAXIMUM
This parameter defines the value of process variable at which the Recorder Output
reaches its maximum value; for example, for a 0 - 5V Recorder Output, this value
corresponds to 5V. It may be adjusted within the range –1999 to 9999. The decimal
point position for the Recorder Output is always the same as that for the process
variable input range. The default value is Input Range Maximum. This parameter is not
applicable if the Recorder Output option is not fitted.
NOTE: If this parameter is set to a value less than that for the RecorderOutput Scale Minimum (see Subsection 3.12), the relationship
between the process variable/setpoint value and the Recorder Output
is reversed.
3.14OPERATOR MODE DISPLAY STRATEGY
This defines the sequence of parameter displays available in Operator Mode (see
NOTES ON TABLE 3-1).
3.15EXIT FROM SET UP MODE
To leave Set Up Mode, select the initial Operator Mode display (process variable value)
then depress the Raise and Scroll keys simultaneously, whereupon the SET indicator
will go OFF and the instrument will return to Operator Mode.
NOTE: An automatic return to Operator mode will be executed if there
is no key activity in Set Up Mode for one minute.
OM067-3November, 20003-5
Sec tion 3
Set Up ModeProd uct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
Process High Alarm
direct-acting
Process High Alarm
reverse-acting
Process Low Alarm
direct-acting
Process Low Alarm
reverse-acting
PROCESS
HIGH
ALARM
PROCESS
LOW
ALARM
Figure 3-1Alarm Op era tion
Alarm Hysteresis
Alarm Inactive
Process Variable
Alarm Hysteresis
Alarm Inactive
Alarm Active
Figure 3-2Alarm Hys tere sis Op era tion
Alarm Value
Process Variable
Alarm Inactive
Alarm Value
Alarm InactiveAlarm Active
3-6November, 2000OM067-3
59039
1
-DIN Digi tal In di ca torSec tion 4
8
Product Man ual - Vol ume IRS485 Se rial Com mu ni ca tions
SEC TION 4
RS485 SERIAL COMMUNICATIONS
This three-wire RS485-compatible serial communications option is the means by which
communication may occur between the instrument and a master device (e.g. a
computer or terminal).
4.1PHYSICAL REQUIREMENTS
There are two communications protocols available with this option:
(a) AS CII
(b) MOD BUS
4.1.1Char ac ter Trans mis sion
Data format is fixed to be seven data bits and one stop bit. The Baud rate may be
selected to be 1200, 2400, 4800 (default) or 9600 Baud. For ASCII protocol, the parity
is even. For MODBUS protocol, the parity is selectable to be even, odd or none.
4.1.2Line Turn- Round
AS CII Pro to col: The com mu ni ca tions link is op er ated as a multi- drop half
du plex sys tem. When a de vice is trans mit ting, it drives the trans mis sion lines
to the ap pro pri ate lev els; when it is not trans mit ting, its out puts are set to a
high im ped ance in or der that an other de vice can trans mit. It is im por tant that
a trans mit ter re leases the trans mis sion lines be fore an other de vice starts
trans mis sion. This im poses the fol low ing re straints on the mas ter de vice:
(a) The transmitter must release the transmission lines within 6ms of
the end of the last character of a message being transmitted. Note that
delays due to buffers such as those used in universal asynchronous
receivers/transmitters (UARTs) within the master device must be taken
into account.
(b) The transmitter must not start transmission until 6ms has elapsed
since the reception of the last character of a message.
All in stru ments in this range hav ing an RS485 com mu ni ca tions fa cil ity ad here to this stan dard; thus, pro vided that the mas ter de vice con forms simi larly to the stan dard, there should be no line con ten tion prob lems.
MOD BUS Pro to col: The line turn- round tim ings ad here to the in dus try stan dard.
4.2ASCII PROTOCOL
This protocol assumes half duplex communications. All communication is initiated by
the master device. The master sends a command or query to the addressed slave and
the slave replies with an acknowledgement of the command or the reply to the query.
All messages, in either direction, comprise:
OM067-4November, 20004-1
Sec tion 4
RS485 Se rial Com mu ni ca tionsProduct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
(a) A Start of Message character
(b) One or two address characters (uniquely defining the slave)
(c) A parameter/data character string
(d) An End of Message character
Messages from the master device may be one of four types:
Type 1:L {N} ? ? *
Type 2:L {N} {P} {C} *
Type 3:L {N} {P} # {DATA} *
Type 4:L {N} {P} I *
where all characters are in ASCII code and:
Lis the Start of Mes sage char ac ter (Hex 4C)
{N}is the slave ad dress (in the range 1 - 32); ad dresses 1 - 9
may be rep re sented by a sin gle digit (e.g. 7) or in two- digit
form, the first digit be ing zero (e.g. 07).
{P}is a char ac ter which iden ti fies the pa rame ter to be in ter ro -
gated/modi fied - see Ta ble 4-2.
{C}is the com mand (see be low)
#in di cates that {DATA} is to fol low (Hex 23)
{DATA}is a string of nu meri cal data in AS CII code (see Ta ble 4-1)
*is the End of Mes sage char ac ter (Hex 2A)
No space char ac ters are per mit ted in mes sages. Any syn tax er rors in a re ceived
mes sage will cause the slave to is sue no re ply and await the Start of Mes sage
char ac ter.
4-2November, 2000OM067-4
59039
1
-DIN Digi tal In di ca torSec tion 4
8
Product Man ual - Vol ume IRS485 Se rial Com mu ni ca tions
Table 4-1{DATA} Ele ment - Sign and Deci mal Point Po si tion
Identifier
Character
A
B
C
D
E
F
G
H
J
L
M
N
O
Q
T
Z
[
\
]
m
{DATA} Content
abcd0
abcd1
abcd2
abcd3
abcd5
abcd6
abcd7
abcd8
Sign/Decimal Point Position
+abcd
+abc.d
+ab.cd
+a.bcd
–abcd
–abc.d
–ab.cd
–a.bcd
Table 4-2Com mands/Pa rame ters and Iden ti fi ers
Parameter/Command
Maximum Process Variable value
Minimum Process Variable value
Alarm 1 value
Alarm 1 Hysteresis value
Alarm 2 value
Alarm 2 Hysteresis value
1
1
Scale Range Maximum
Read Only
Read Only
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write (linear inputs
only) - otherwise Read Only
Scale Range Minimum
Read/Write (linear inputs
only) - otherwise Read Only
Process Variable Offset value
Instrument Status
2
Process Variable value
Alarm 3 value
Alarm 3 Hysteresis
3
3
Scale Range Decimal Point Position
Read/Write
Read Only
Read Only
Read/Write
Read/Write
Read/Write (linear inputs
only) - otherwise Read Only
Time Elapsed
Instrument Commands
4
Recorder Output Scale Maximum
Recorder Output Scale Minimum
Scan Table
6
Input Filter Time Constant value
5
5
Read Only
Write Only
Read/Write
Read/Write
Read Only
Read/Write
Operation
NOTES
1. Applicable only if Alarm 2 is configured.
2. See Subsection 4.3.15.
3. Applicable only if Alarm 3 is configured.
4. See Subsection 4.3.16.
5. Applicable only if Output 2 is configured as a Recorder Output.
6. See Subsection 4.3.17.
OM067-4November, 20004-3
Sec tion 4
RS485 Se rial Com mu ni ca tionsProduct Man ual - Vol ume I
1
-DIN Digi tal In di ca tor59039
8
4.2.1Type 1 Mes sage
L {N} ? ? *
This message is used by the master device to determine whether the addressed slave
is active. The reply from the slave instrument, if it is active, is
L {N} ? A *
An inactive instrument will give no reply.
4.2.2Type 2 Mes sage
L {N} {P} {C} *
This type of message is used by the master device to interrogate or modify a parameter
in the addressed instrument. {P} identifies the parameter (as defined in Table 4-2) and
{C} represents the command to be executed, which may be one of the following:
+ (Hex 2B) - In cre ment the value of the pa rame ter de fined by {P}
– (Hex 2D) - Dec re ment the value of the pa rame ter de fined by {P}
? (Hex 3F) - De ter mine the cur rent value of the pa rame ter de fined by {P}
The reply from the addressed instrument is of the form:
L {N} {P} {DATA} A *
where {DATA} comprises five ASCII-coded digits whose format is shown in Table 4-1.
The data is the value requested in a query message or the new value of the parameter
after modification. If the action requested by the message from the master device would
result in an invalid value for that parameter (either because the requested new value
would be outside the permitted range for that parameter or because the parameter is
not modifiable), the instrument replies with a negative acknowledgement:
L {N} {P} {DATA} N *
The {DATA} string in the negative acknowledgement reply will be indeterminate.
Scan Tables
A parameter identifier character “]” in the message from the master device indicates
that a “Scan Table” operation is required. This provides a facility for interrogating the
values of a group of parameters and status in a single message from the master
device. The reply to such a command would be in the form:
L {N} ] 25 aaaaa bbbbb ccccc ddddd eeeee A *
The digits aaaaa, bbbbb etc. are expressed as shown in Table 4-1. For further
information, refer to Subsection 4.3.17.
4.2.3Type 3 Mes sage
L {N} {P} # {DATA} *
This message type is used by the master device to set a parameter to the value
specified in {DATA}. The command is not implemented immediately by the slave
instrument; the slave will receive this command and will then wait for a Type 4 message
(see below). Upon receipt of a Type 3 message, if the {DATA} content and the specified
parameter are valid, the slave reply is of the form:
4-4November, 2000OM067-4
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.