Slant-Fin Monitron EH Boilers User Manual

5 (1)

A major answer to the changing heating-fuel situation

HOT WATER MODELS IN 9 SIZES

8 kw (27,301 Btuh) to 40 kw (136,506 Btuh)

Before purchasing this appliance, read important energy cost and efficiency information available from your contractor.

Slant-Fin Monitron EH Boilers User Manual
TYPICAL WIRING DIAGRAM

TM

Monitron Compact, easy to install for new or “standby” installations

Monitron combines the availability and dependability of electricity with the comfort and performance of conventional hydronic heating using baseboard, radiant or cast-iron radiators.

Monitron as a replacement unit: Works with virtually any existing hot water hydronic radiation system. Although rated in kilowatts, it is also clearly identified by BTU output.

Monitron as a standby unit: Particularly suitable for commercial and industrial facilities, or office buildings which can’t risk down-time with their existing heating equipment. If oil or gas is temporarily unavailable, the owner easily switches the heating system to the electric boiler.

Monitron as a primary heating unit offers:

The convenience of electricity and the comfort of hydronics.

The elimination of a chimney.

Competitive pricing with electric baseboard systems.

Simple zoning by zone valves.

Monitron by Slant/Fin is the electronic-age boiler designed to save energy for new or existing heating systems.

TO ZONE VALVE TRANSFORMER WHEN USED

Monitron installed as primary boiler.

America’s Best - Built Electric Boiler

One piece cast-iron heat exchanger.

Built in air eliminator.

Internal baffles improve heat transfer.

Energy-saver

electric sequential control package *

With manual mild-weather energy-saver switches *

NORMAL OPERATIONS

When the thermostat calls for heat, the circulator turns on and the first electric heater bank is energized. At preset 30-second intervals, the other heater banks automatically energize. The circulator continues operating until the room thermostat is satisfied. A flow switch supplied by Slant/Fin or others is required. It prevents the elements from being energized unless the circulator is operating. This avoids element burnout.

* All models except EH-8 and EH-10

OPTIONAL MILD-WEATHER OPERATION

Mild-weather energy savings are made possible through the use of circuit breakers on the breaker panel. This permits the owner to manually switch off one or more of the elements. Then, when just a moderate amount of heat is needed, all the elements are not energized, cycling is reduced, and overheating is diminished. This ener- gy-saving feature is standard on Monitron models EH-12-S through EH-40-S.

Standard equipment

Dual limit aquastat

Altitude pressure and temperature gauge

Safety relief valve (unmounted)

Circulator relay and heater contactors

Circuit breaker (one or two heaters per breaker)

Low voltage thermostat with adjustable heat anticipator (packed separately)

Drain cock, 34 " (packed separately)

Built-in air separator

Cast-iron ASME approved heat exchanger

Terminal blocks for circulator, thermostat, flow switch and for zone valve transformer

Sequencer

Complete jacketing

U.L. listed, ASME authorized

Flow switch. Not included with, but necessary on all models

Circuit breaker for circulator and control circuit.