ZyXEL SHD1115 User Manual

1
SHD1115
The photoelectric Smoke Detector is a Z-WaveTM enabled device which is fully compatible with any Z-WaveTM enabled network. Z-WaveTM enabled devices displaying the Z-WaveTM logo can also be used with it regardless of the manufacturer, and ours can also be used in other manufacturers Z-WaveTM enabled networks. Inclusion of this detector on other manufacturers Wireless Controller menu allows remote operation of connected modules when the detector is triggered. Z-Wave node in the system also acts as a repeater, so as to re-transmit the RF signal to ensure that the signal is received by its intended destination by routing the signal around obstacles and radio dead spots.
The detector is designed to sense smoke that comes into the detector chamber. It does not sense gas, heat, or flame. The working principle is when the smoke detector detects a certain density of smoke, the horn of smoke detector will sound and in the meantime, the detector will emit the signals to the associated devices for further execution. It can provide precious time for you and your family to escape before a fire spreads.
Product Overview
Horn
Link Key
Test Button
Connector
LED
Tamper Switch
Connectors Hole
Link LED
Cover Latch
Mounting Bracket
Battery Cover
Include to or Exclude from a Z-WaveTM Network
Inside the detector, there is a link key which is used to carry out the function of inclusion, exclusion, association and reset. When first power is applied, its LED flashes on and off alternately and repeatedly for 4 minutes, which implies that it has not been assigned a node ID and cannot work with Z-Wave enabled devices. Please get familiar with the terms below before starting the operations.
Function
Description
Inclusion
Add a Z-Wave enabled device (e.g. Smoke Detector) to Z-Wave network.
Exclusion
Delete a Z-Wave enabled device (e.g. Smoke Detector) from the network.
Association
After inclusion, you have to define the relationship between devices. Trough association, device can be assigned as master/slave, and specify which slave is going to be controlled by which master.
Reset
Restore Smoke Detector to factory default.
The table below lists an operation summary of basic Z-Wave functions. Please refer to the instructions for your Z-WaveTM Certificated Primary Controller to access the setup function, and to include/exclude/associate devices.
Action/Status
Description
Link LED Indication
No node ID
The Z-Wave Controller does not allocate a node ID to the detector.
2-second on, 2-second off
Inclusion
1. Have Z-Wave Controller entered inclusion mode.
Flashes when link key is pressed
2. Pressing link key three times within 1.5
second will enter inclusion mode. The Detector will stay awake for 10 minutes to allow time for setting and device status enquiring.
Exclusion
1. Have Z-Wave Controller entered
exclusion mode.
Flashes when link key is pressed
4
5
6
2
2. Pressing link key three times within 1.5
second will enter exclusion mode. The Detector will stay awake for 10 minutes to allow time for setting and device status enquiring.
Node ID has been excluded.
2-second on, 2-second off
Action/Status
Description
Link LED Indication
Reset
1. Pressing link key three times within 1.5
second will enter exclusion mode
Flashes when link key is pressed
2. Within 1 second, press link key again
and hold it until LED is off
LED is on for 5 seconds
3. Node ID is excluded, and it sets the
device back to factory default state.
2-second on, 2-second off
Association
1. Have Z-Wave Controller entered
association mode.
Flashes when link key is pressed
2. Pressing link key 3 times within 1.5
second will enter association mode
3. Refer to group support as described
on page 5
Failed or success in including/excluding the node ID can be viewed from the Z-Wave Controller.
Choosing a Mounting Location
The detector is designed for use in a single residential unit only, such as a single family home or apartment. It is not meant to be used in lobbies, hallways, basements, or another apartment in multi-family buildings, unless there are already working detectors in each family unit. Smoke detectors, placed in common areas outside of the individual living unit, such as on porches or in hallways, may not provide early warning to residents. In multi-family buildings, each family living unit should set up its own detectors.
The detector is not meant to be used in non-residential buildings. Warehouses, industrial or commercial buildings, and special purpose non-residential buildings require special fire detection and alarm systems. This detector is not a suitable substitute for complete fire detection systems for places where many people live or work, such as hotels or motels. The same is true of dormitories, hospitals, nursing homes or group homes of any kind, even if they were once single family homes.
For complete coverage in residential units, it should be installed in all rooms,
halls, storage areas, basements and attics in each family living unit. Minimum coverage is one detector on each floor and one in each sleeping area. Useful tips are listed hereunder:
1. Install a detector in the hallway outside every separate bedroom area as shown in FIGURE 1. Two detectors are required in homes with two bedroom areas as shown in FIGURE 2.
2. Install a detector on every floor of a multi-floor home or apartment as shown in FIGURE 3.
3. Install a minimum of two detectors in any household.
4. Install a detector inside every bedroom.
5. Install smoke detectors at both ends of a bedroom hallway if the hallway is
FIGURE 1
Locations for placing smoke detectors for single residence with only one sleeping area.
FIGURE 2
Locations for placing smoke detectors for single-floor residence with more than one sleeping area.
FIGURE 3
Locations for placing smoke detectors for a multi-floor residence.
3
more than 40 feet (12 meters) long.
6. Install a detector inside every room where one sleeps with the door partly or completely closed, since smoke could be blocked by the closed door and a hallway alarm may not wake up the sleeper if the door is closed.
7. Install detectors as close to the center of the ceiling as possible. If this is not practical, put the detector on the ceiling, no closer than 4 inches (10 cm) from any wall or corner as shown in FIGURE 4.
8. If ceiling mounting is not possible, put wall-mounted detectors between 4 and 6 inches (10~15 cm) from the ceiling (FIGURE 4).
9. If some of your rooms have sloped, peaked, or gabled ceilings, try to mount detectors 3 feet (0.9 meter) measured horizontally from the highest point of the ceiling as shown in FIGURE 5.
Locations Not To Install the Detector
Nuisance alarms take place when smoke detectors are installed where they will not work properly. To avoid nuisance alarms, do not install smoke detectors in the following situations:
1. Combustion particles are the by-products of something that is burning. Thus, in or near areas where combustion particles are present you do not install the smoke detectors to avoid nuisance alarms, such as kitchens with few windows or poor ventilation, garages where there may be vehicle exhaust, near furnaces, hot water heaters, and space heaters.
2. Do not install smoke detectors less than 20 feet (6 meters) away from places where combustion particles are normally present, like kitchens. If a 20-foot distance is not possible, e.g. in a mobile home, try to install the detector as far away from the combustion particles as possible, preferably on the wall. To prevent nuisance alarms, provide good ventilation in such places.
IMPORTANT: For any reason, do not disable the detector to avoid nuisance alarms.
3. When air streams passing by kitchens, the way how a detector can sense combustion particles in normal air-flow paths is graphically shown in FIGURE 6, which indicates the correct and incorrect smoke detector locations concerning this problem.
4. In damp or very humid areas, or near bathrooms with showers. Moisture in humid air can enter the sensing chamber, then turns into droplets upon cooling, which can cause nuisance alarms. Install detectors at least 10 feet (3 meters) away from bathrooms.
5. In very cold or very hot areas, including unheated buildings or outdoor rooms. If the temperature goes above or below the operating range of smoke detector, it will not work properly. The temperature range for your smoke detector is 4°C to 38°C (40°F to 100°F).
6. In very dusty or dirty areas, dirt and dust can build up on the detectors sensing chamber, to make it overly sensitive. Additionally, dust or dirt can
FIGURE 4
Recommended best and acceptable locations to mount smoke detectors.
FIGURE 5
Recommended location to mount smoke detectors in rooms with sloped, gabled or peaked ceiling.
FIGURE 6
Recommended smoke detector locations to avoid air streams with combustion particles.
Loading...
+ 4 hidden pages