*Conform EN 14511
** Moisture removal at 32°C, 80% RH
Defective electrical devices and batteries must be kept separate from household
waste. Ensure that there is effective recycling where possible. Ask you local
council or dealer for expert advice on recycling.
4
4
BPARTS
INDOOR UNIT
Air inlet
Front panel
Emergency button
Display
Air outlet
Vertically
adjustable vane
Horizontally
adjustable vane
OUTDOOR UNIT
Active carbon
filter (optional)
Healthy air filter
(optional)
Air filter
Remote control
Air inlet
Drainage hose
Note: Condensation is drained
during COOLING or DR
Pipes and power
cable
Air outlet
YING
The diagrams in these instructions are based on a standard model.
The air conditioner you have pur
chased may be a different model.
4
5
CBEFORE USING
Check and adjust the following before using the air conditioner.
Adjusting the remote control
T
he manufacturer has NOT preset the remote control heating or cooling options.
The arrow for ‘Heat’ or ‘Cool’ on the remote control display will flash after the batteries in the remote
control have been replaced.
Depending on the type of air conditioner that you have purchased, the remote control can be adjusted as
follows:
Press any button while the ‘Heat’ arrow is flashing. This sets the heat pump.
Press any button while the ‘Cool’ arrow is flashing. The setting has been entered for cooling only.
If you do not press any button within 10 seconds, the remote control is automatically preset to the heat
pump. Type S95, S125, S185 and S245 are fitted with a heat pump.
The Heat function can NOT be adjusted with the remote control when the remote control has been preset
to Cool Only.
Safety regulations
•Use the correct power supply (see type plate) in order to prevent serious faults, hazards or fire.
•Ensure that the circuit breaker or plug does not become dirty. Connect the plug/circuit breaker to the
power cable correctly. Insufficient contact may cause an electric shock or fire.
•Do not switch the unit off with the circuit breaker or by pulling the plug out of the socket. This may
produce sparks that could start a fire.
•Do not tie any knots in the power cable or pull the power cable. This may damage or break the cable,
causing an electric shock or fire.
•Never insert sticks or any similar object into the unit. The ventilator rotates at high speed and may
cause injury.
•It is detrimental to your health to remain in the cold airstream for an extended period of time. We
recommend that you allow the airstream to flow freely into the room, without obstruction.
•If a fault occurs, switch the machine off with the remote control before pulling the plug out of the
socket.
•Do not carry out any repairs. Incorrect repairs may cause electric shocks, etc.
•Do not place gas burners or ovens in the airstream.
•Do not operate the buttons with wet hands.
•Do not place any objects on the outdoor unit.
•The user is responsible for the earth connection. This must be fitted by a recognised installer in
accordance with local regulations and ordinances.
4
6
DINSTALLATION INSTRUCTIONS
Installation diagram
Distance to the wall
must be a minimum
of 50 mm.
Distance to the ceiling must be
a minimum of 50 mm.
istance to the wall must be
D
a minimum of 50 mm.
Distance between
the air inlet and the
wall must be a minimum of 250 mm.
Distance between the air
outlet and the wall must be
a minimum of 500 mm.
-The diagram above is a simplified illustration of the unit and may differ from the unit that
you have purchased.
G
-The installation must be carried out by a recognised installer and connected in accordance
with national regulations.
Distance between the air
inlet and the wall must be
a minimum of 250 mm.
min. 250 mm.
4
7
Connecting the power cable
Wiring between the indoor and outdoor unit:
1.Remove the plastic cover from the indoor unit.
2.Use the circuit diagram (attached to the indoor unit) as
a reference for the connections.
3
.Replace the cover, “B” on the outside.
Select the correct location
No obstacles in the vicinity of the air outlet. The air stream
must be allowed to reach the entire room unhindered.
It must be possible to install the pipes and drill the hole in
the wall at an accessible location.
Ensure that there is sufficient distance between the unit,
ceiling and wall (refer to Chapter D).
It must be possible to remove the air filter easily.
The unit and remote control must be placed at least 1 metre
from televisions, radios, etc.
Strip lights may cause faults. Ensure that there is sufficient
distance.
Do not place any object in the vicinity of the air inlet. The
air intake may not be blocked.
The wall must be strong enough to bear the weight of the
unit. The wall construction may not cause any increase in
noise and vibrations.
Front panel
Connecting
clamp (inside)
Housing
Installation diagram
Indoor unit
Not higher
than 5 m
Outdoor unit
Location for the installation of the outdoor unit
In an accessible, well ventilated location. Do not mount at
potentially hazardous locations, e.g. where there is a danger of a gas leak.
Maintain the required distance from the wall.
Do not expose the outdoor unit to greasy dirt or salty sea
air. Do not mount in the vicinity of gas pipes.
Do not mount on the street side due to the risk of water
splashing onto the unit.
Mount on a fixed foundation in order to prevent excessive
noise.
The air outlet must not be obstructed.
10 m (S95) or a
max. of 15 m
Max. length of
Outdoor unit
Not higher than
5 m
Indoor unit
(S125, S185, S245).
Max. length of 10 m
(S95) or a max. of
15 m (S125, S185,
S245).
4
8
INSTALLATION OF THE INDOOR UNIT
1.Installing the mounting plate
-Fit the mounting plate at the location
where the indoor unit will be hung. Take
a
ccount of the direction of the pipes.
-Place the mounting plate horizontally with
the aid of a level indicator or plumb line.
-Drill holes with a depth of 32 mm in order
to mount the plate.
-Insert the plastic plugs into the holes and
screw the plate into position with selftapping screws.
-Check that the mounting plate is firmly in
position and drill the hole for the pipes.
Note: the shape of the mounting plate may differ per model. However, the installation method is the same.
2.Drilling a hole for wires/pipes
-Determine the position of the lead-through hole for the wires/pipes on the basis of the drilling hole in
the mounting plate.
-Drill the hole in the wall. The hole must slope a little to the outside.
-Place a pipe sleeve in the hole in order to protect the wall.
3.Indoor unit wire/pipe installation
-Insert he wires/pipes (gas and liquid
pipes) through the hole from the
outside, or from the inside if you
have installed the indoor unit first.
-Create a recess that corresponds with
the direction of the pipes.
Note: create recess 1, 2 or 4, depending on the position you have chosen for the hole in the indoor unit.
-Fit the drainage hose after connecting the wires/pipes. Now connect the power cables. Finish by
insulating the pipes, cables and drainage hose.
Insulation of the pipe connections:
them in vinyl tape.
Insulate the connection pieces with insulating material and then wrap
4
9
P
ipe insulation:
a.Place the drainage hose under the pipe.
b.Use insulating material exceeding 6 mm in
Power cable
Large pipe
Insulating pipe
thickness.
mall
-The drainage hose must slope downwards
s
lightly in order to allow moisture to drain
Power cable 1
heat pump)
(
S
pipe
away easily.
Ensure that the drainage hose is not
twisted and does not protrude. The end
iring of defrosting
W
regulator (heat pump)
Tape
rainage hose
D
may not hang in the water.
If the drainage hose is extended with a hose, the section running alongside the indoor unit must be
insulated.
-If the wire/pipes are on the right hand side, the wires/pipes, power cable and drainage hose must be
insulated and fastened to the back of the indoor unit with a pipe clamp.
A.Fasten the pipe clamp to the groove.
Mounting plate
Pipe clamp
Mounting plate
Pipe clamp
B.Press the clamp to attach it to the mounting plate.
Connecting the pipes
a.Connect the indoor unit pipes with two nut spanners. Select the
correct tightening moment in order to prevent the pipes, connecting pieces and nuts from being deformed or damaged.
b.First tighten by hand, and then with nut spanners.
ightening
Model
S95/S125/S185
S245
S95
S125/S185
S245
Pipe dimensions
T
moment
Push through
here
Mounting plate
Nut
size
Hook here
4
10
4
.Connecting the cable
-Indoor unit
Connect the power cable to the indoor unit by connecting
the cables to the units to the clamps on the terminal board
in the correct sequence. The colours of the wires and the
r
eference on the clamps must correspond.
Note: In some models, the cover must be removed in order
to connect the wiring.
-Outdoor unit
1.Remove the access cover of the unit by loosening the
screw. Connect the wires to the clamps on the terminal
board in the following manner:
2.Connect the power cable to the terminal board.
3.Replace the cover and tighten the screw.
4.Place an approved circuit breaker between the power
source and the unit for model S245. Install a suitable
main switch.
Front panel
Indoor unit
Outdoor unit
Terminal board
(inside)
Base plate
Housing
Access cover for
terminal board
(inside)
The illustrations are based on standard models.
The air conditioner you have purchased may be a different model.
Warning:
1.Always connect the air conditioner to a separate power circuit. Refer to the diagram on the inside of
the access cover for the connection of the wires.
2.Check that the cable thickness conforms to regulations (see table below).
3.Check that all wiring is securely connected.
4.Install an earth leak switch.
Note: All cables used must be approved in accordance with local regulations.
1.Fit the drainage outlet and drainage hose (only for models with a
heat pump).
Condensation will drip off the outdoor unit when the indoor unit
i
s operating in Heating mode. Fit a drainage outlet and a drainage
hose in order to drain the water effectively. Fit the drainage outlet
and rubber washer to the base plate of the outdoor unit (see fig.).
2.Installing and fitting the outdoor unit
Bolt the unit to a level and solid base.
Ensure that the unit is mounted securely in order to prevent problems caused by strong wind and
vibrations.
3.Connecting the outdoor unit pipes
Remove the covers of the two-way and three-way valve.
Close the pipes separately with the appropriate tightening moment.
4.Outdoor unit cable connection (see previous page)
Purging the pipe system
Air and moisture that remain in the pipe system after installation can damage the compressor. After the
indoor and outdoor units have been connected, air and moisture must be removed with the aid of a vacuum
pump (see below).
Vacuum pump
Three-way valve diagram
4
12
1
.Unscrew the two-way and three-way valve and remove the covers.
2.Unscrew the supply pipe and remove the cover.
3.Connect the flexible hose of the vacuum pump to the supply pipe.
4.Allow the vacuum pump to operate for 10-15 minutes until a pressure of 10 mmHg absolute is
achieved.
5
.Close the low-pressure button on the vacuum pump while the pump is still operating. Now switch the
pump off.
6.Open the two-way valve (1/4 turn), and close it again after 10 seconds. Check all connections with
liquid soap or an electronic leak detector.
7.Turn the two-way and three-way valves to their operating positions. Disconnect the hose from the
vacuum pump.
8.Replace and tighten all covers.
Note
-Read these instructions for use before commencing installation.
-Make sure that no air remains in the cooling system and that no refrigerant is leaking.
-Testing: switch the air conditioner on after installation and take notes on the operation.
-Fuse of the indoor unit controller for types S95 and S125: 50T, permitted value 3.15 A,T, 250V. For
types S185 and S245: 3.15A, T, 250V.
-The fuse for the unit as a whole must be suitable for maximum power.
-The plug must be easily accessible in order to be able to switch the unit off in case of emergency.
If there is no easy access, a bipolar main switch must be installed at an easily accessible location.
4
13
EINSTRUCTIONS FOR USE
Operation and display
POWER INDICATOR
Lights up when power supply is
connected.
SLEEP MODE INDICATOR
Lights up when this function is
ctivated.
a
RECEIVER
Receives the signal from the remote control.
TIME INDICATOR
Lights up during preset time.
OPERATING INDICATOR
Lit when the unit is in operation.
EMERGENCY BUTTON
To operate the
unit if the remote
control is not operational.
EMERGENCY BUTTON
To operate the unit if
the remote control is
not operational.
Adjustment of automatic restart
The machine has been programmed by the manufacturer to restart
automatically.
Following a power cut, the machine will resume operation in the last
selected function.
The shapes and positions of the switches and indicators may differ for
each model. However
, the functions are identical.
4
14
Remote control
The remote control transmits signals to the system.
To activate or deactivate the sleep mode.
To select the TIMER function.
To select the operating mode: Feel, Cooling,
Dry, Fan and Heating.
DOWN button (TOO W
To lower the preset room temperature and
SLEEP button
TIMER button
MODE button
ARM button)
reduce time periods.
UP button (TOO COLD button)
To raise your preset room temperature and extend time periods.
FAN SPEED operation button
or the selection of the ventilator speed in the
F
indoor unit: automatic, high, medium and low.
orizontal plate button
H
To adjust the direction of the airstream.
ON/OFF button
For activation and deactivation.
Note: Each mode and the relevant functions will be specified hereafter.
Placing the batteries
Remove the battery cover in the direction of the arrow.
Place the new batteries as indicated (ensure that the positive (+) and negative poles (-) are in the correct
positions. Slide the battery cover back into place.
Note: Use 2 LR03 AAA (1.5 Volt) batteries. Do not use rechargeable batteries. Replace the batteries with new
batteries of the same type (see above) when the display starts to fade.
Storage of the remote control and tips for use
The remote control can be placed in a
wall-mounted holder.
Note: The remote control holder is
optional.
Using the remote control
Point the r
emote control at the receiver on the indoor unit of the
Receiver
air conditioner. The air conditioner can be operated in this manner up to a distance of 7 metres.
4
15
OPERATING INSTRUCTIONS
Less than 20 °C
23 °C
FEEL mode operating procedure
The operating mode is selected automatically (HEATING, DRY,
FAN, COOLING), depending on the room temperature at the
t
ime the selection takes place.
With the remote control pointed at the air conditioner.
1.Activation
Press the ON/OFF/RUN button. The RUN indicator on the
indoor unit will light up when the machine receives a signal.
When the unit is not in the FEEL mode.
2.Selecting the FEEL mode
Press the MODE selector button.
Adjust the MODE to the FEEL setting.
The operating mode and temperature are determined by the
indoor temperature.
Indoor temperatureOperating modeDesired temperature
Heating for ‘heat pump’ type
Ventilator for ‘cooling only’ type
20 – 26 °CDRY18 °C
More than 26 °CCOOLING23 °C
3.Temperature adjustment
Press the
When the
g button or the h button.
g button is pressed, the value of the preset temperature increases by 1°C.
The indicator will not change after the temperature has been increased by 2°C.
When the
h button is pressed, the value of the preset temperature is lowered by 1°C.
The indicator will not change after the temperature has been lowered by 2°C.
Note:
It may occur that no air is expelled from the unit while it is in operation.
The unit will not always start operating immediately after the mode has been changed.
TIMER mode
If you program the timer with the TIMER button upon leaving, it will be pleasantly warm when you return
home. Y
ou can deactivate the timer at night if you wish.
4
16
ADJUSTING THE TIMER
To activate the air conditioner at the desired time, follow the procedure specified below (the remote
control and air conditioner are switched off):
1.Press the Timer button.
2
.Select the desired mode by pressing the Mode button.
3.Select the desired temperature by pressing the
possible when the ‘cool’ or ‘heat’ mode is selected).
4.Select the ventilator speed (low, medium or high) or automatic mode
(only possible when the Feel, Cool or Heat mode is selected) by pressing
the Fan button.
The ventilator always operates in the Auto mode when the Dry mode is
selected.
5.Select Swing or no Swing by pressing the Swing button.
6.Press the Timer button (‘h’ flashes).
7.Use the
activate (between 0 and 10 hours can be set at every half hour –
between 10 and 24 hours can be set at every hour).
8.Press the Timer button (‘h’ stops flashing) and the preset time appears
in the display.
9.Press the Timer button again to delete the selected data from the memory.
gh button to select the time at which the air conditioner must
gh button (only
Note: If no buttons are pressed during the programming of the timer function, the remote control will
switch off automatically after 10 seconds.
To switch the air conditioner off at the desired time, follow the procedure specified below (the remote
control and air conditioner are switched off):
1.Press the Timer button.
2.Use the
hours can be set at every half hour – between 10 and 24 hours can be set at every hour).
3.Press the Timer button (‘h’ stops flashing), and the preset time will appear in the display.
4.Press the Timer button again to delete the selected data from the memory.
Note: If no buttons are pressed during the programming of the timer function, the remote control will
switch off automatically after 10 seconds.
Note: if ‘h’ is flashing and you press the ON/OFF/RUN button once, the preset temperature will appear in
the display. You can now adjust the temperature with the
display the time, which can now also be adjusted*. If the Timer button is pressed again, the data is stored
and the remaining time (that the air conditioner will be in operation) will appear in the display.
*
Pressing the ON/OFF/RUN button instead of the Timer button deactivates the remote control.
gh button to select the time at which the air conditioner must deactivate (between 0 and 10
gh button. Press the Timer button again to
Note
G
Press the Timer function to check the settings in the display
Check that the TIMER INDICA
TOR on the indoor unit lights up after the timer has been set.
.
4
17
FMAINTENANCE
Cleaning the front panel
1Switch the machine off and remove the plug from the socket.
2Hold the front panel at position “a” and pull it towards you.
3
Clean with a soft dry cloth.
Use lukewarm water (max. 30˚ C) to remove stubborn dirt.
4Never use volatile substances, such as benzene, or abrasives to
remove dirt.
5Never spray water on the indoor unit.
Dangerous! Electric shock!
6Replace the front panel and close it by pushing position “b” down.
Cleaning the air filter
The air filter must be cleaned regularly.
Follow this procedure:
1.Switch the machine off completely.
-Open the front panel.
-Carefully pull the filter handle towards you.
-Grip the handle and slide the filter out.
2.Clean and replace the air filter.
To remove stubborn dirt, clean the filter in lukewarm water with detergent. After cleaning, allow the
filter to dry completely out of direct sunlight.
3.Close the front panel.
If the air conditioner is operating in an extremely dusty environment, it must be cleaned every two
weeks.
GSAFETY
Operating status
The safety components can detect faults and deactivate the unit in the following cases:
HEATING
The outside temperature is above 24°C
The outside temperature is under -7°C
The room temperature is above 27°C
COOLING
The outside temperature is above 43°C
The r
oom temperature is under 21°C
DRY
The r
oom temperature is under 18°C
4
18
Warning
If the air conditioner is operating in the COOLING or DRY mode while relative humidity is over
G
Noise
-Install the air conditioner on a solid base in order to prevent excessive noise.
-Install the outdoor unit in such a way that the expelled air does not cause a nuisance for neighbours.
-Do not place obstacles in the path of the air expelled from the outdoor unit, this increases noise.
Safety features
1The safety feature deactivates the unit in the following cases:
2.Press the ON/OFF button to restart after the unit has deactivated due to the operation of the safety
80%, moisture may drip out of the air outlet of the indoor unit (due to a window or door being
open, for instance).
- When the function is stopped or changed while the unit is operating. Wait 3 minutes before
switching the air conditioner on again.
- After the plug has been inserted in the socket and the unit has been immediately switched on. The
unit will activate after approximately 20 seconds.
feature. The Timer must then be reset.
Checks
The following must be checked after the air conditioner has been in use for an extended period of time:
-Overheating of the power cable and the plug. Can you smell burning?
-Is there more noise or vibration than normal?
-Does the indoor unit leak water?
-Is the metal housing live?
Switch the air conditioner off in all the above cases! We recommend periodic inspection by a registered
installer (at least once every five years).
Feature of the HEATING mode
For heating
When the HEATING function is activated, the airstream will only start to flow from the indoor unit after
2 – 5 minutes.
After Heating
When the Heating function is deactivated, the ventilator of the indoor unit will continue operating for
another 2 – 5 minutes.
Defr
osting
During HEATING, the machine will defrost automatically in order to ensure optimum operating efficiency.
This procedure usually takes 2-10 minutes. The ventilator function stops during defrosting. The HEATING
function r
estarts automatically after defrosting.
4
19
HPROBLEM SOLVING
ProblemCause / Solution
The plug is not inserted firmly in the socket.
The batteries in the remote control are empty.
The safety feature has been activated or the fuse has burnt out.
A
re the air inlets or outlets blocked?
Is the temperature set correctly?
Is the air filter dirty?
No effective operation.
Faults (due to static electricity discharges or disruptions in the
power supply) will prevent the machine from operating correctly.
If this is the case, pull the plug out of the socket, and then reinsert it after 2-3 seconds.
Does not start immediately.Changing the mode during operation: 3 minute delay.
Unusual odour.
Odour may be caused by another source – furniture, cigarettes,
etc. The unit expels air that it has sucked in.
Caused by the refrigerant in the air conditioner: this does not
indicate a fault.
The sound of defrosting in the heating mode.
A creaking sound.
The sound may be caused by the expansion/shrinkage of the front
panel as a consequence of temperature fluctuations.
Mist/moisture is expelled from the air outlet.
Condensation/mist is created when the air temperature in the
room drops significantly due to the fact that cold air is expelled in
the COOLING or DRY mode.
The red compressor indicator flashes
constantly and the ventilator in the indoor
unit ceases to operate.
The unit will switch from the heating mode to the defrosting
mode. The indicator light will go out within 10 minutes and the
unit will return to the heating mode.
No cooled or heated air.
The sound of running water.
The unit does not operate.
The following problems do not always indicate a fault. Please check them before contacting the service
department:
4
20
IGUARANTEE CONDITIONS
There is a 24-month guarantee on the air conditioner from the purchase date. Within this period, all
material and manufacturing defects will be repaired free of charge. The following rules will apply:
•
We expressly reject all further claims to damage compensation, including claims relating to secondary
damage.
•Repairing or replacing components within the guarantee period will not extend the guarantee.
•The guarantee is invalidated if any modifications have been made to the machine, non original parts
have been fitted or repairs have been carried out by third parties.
•Components subject to normal wear, such as the filter, are not covered by the guarantee.
•The guarantee is valid exclusively when you present the original, dated and unaltered purchase
invoice.
•The guarantee does not cover damage caused by actions that deviate from the instructions for use or
neglect.
•Shipment costs and the risks associated with shipping the air conditioner or parts thereof will always
be borne by the buyer.
To prevent unnecessary expense, we recommend that you first always consult the instructions for use
carefully. If this does not provide a solution, ask your dealer to repair the air conditioner.
4
21
Egregio Signore, Gentile Signora,
Ci congratuliamo con per l’acquisto del condizionatore d’aria. Lei ha acquistato un
prodotto di qualità, che Le offrirà molti anni di comfort, a condizione che venga usato in
modo responsabile. Per una durata ottimale del condizionatore d’aria La invitiamo a
leggere le istruzioni d’uso. A nome del fabbricante Le offriamo 24 mesi di garanzia per
tutti i danni imputabili alla produzione o al materiale.
Le auguriamo molta freschezza e comfort.
Cordiali saluti,
PVG International b.v.
Reparto Assistenza Clienti
1. LEGGERE DAPPRIMA LE ISTRUZIONI D’USO
2. IN CASO DI DUBBIO, RIVOLGERSI AL RIVENDITORE
>
22
CONTENUTO
ASpecifichepagina24
BComponentipagina25
COperazioni preliminaripagina26
DIstruzioni per l’installazionepagina27
EIstruzioni d’usopagina34
FManutenzione pagina38
GSicurezza pagina38
HRisoluzione dei problemi pagina40
ICondizioni della garanziapagina41
>
23
ASPECIFICHE
m3/
h
4805507301000
m
3
90110150200
C
OP *
Modello
E
E Class
E
ER *
COP Class
I valori riportati sono indicativi, dati soggetti a modifiche
S95S125S185S245
a. di raffreddamento*kW2,73,55,37,0
C
DDDD
2,82,82,82,9
apacità di riscaldamentokW2,83,85,77,6
C
D
,23,23,43,5
3
eumidificazione (max) **L/24 h19243648
D
Assorbimento energia in raffreddamentokW0,881,171,92,6
Assorbimento energia in riscaldamentokW0,881,171,92,6
Livello di rumore unità interna (max)dB(A)36384347
Livello di rumore unità esterna (max)dB(A)50506054
Temperatura di esercizioºC10-4010-4010-4010-40
Protezione unità internaIPIP X0IP X0IP X0IP X0
Protezione unità esternaIPIP X4IP X4IP X4IP X4
DDD
*Conforme a EN 14511
** Tasso di humidità relativa pari al 80% ad una temperatura di 32°C
Gli apparecchi elettrici difettosi e le batterie usate non devono essere smaltiti
come rifiuti domestici. Se possibile utilizzarli per il riciclaggio. Eventualmente
informarsi presso il proprio comune o il rivenditore locale sulle possibilità di
riciclaggio o di smaltimento ecologico.
>
24
BIDENTIFICAZIONE DEI COMPONENTI
UNITÀ INTERNA
Presa d’aria
Quadro frontale
Pulsante di
emergenza
Display
Uscita dell’aria
Regolazione ver-
ticale delle lame
Regolazione oriz-
zontale delle lame
Filtro anti-par-
ticelle di carbon
attivo (optional)
Filtro di sicurez-
za per la tutela della
salute (optional)
UNITÀ ESTERNA
Le figure riportate nel presente manuale si riferiscono a un modello standard.
Il vostr
o condizionatore può essere un modello diverso.
Filtro dell’aria
Telecomando
Presa d’aria
Tubo flessibile di
scarico*
Tubi e cavo di
alimentazione
Uscita dell’aria
* NB: la funzione di scarico dell’aria di condensa è attiva in modalità CONDIZIONAMENTO o DEUMIDIFICAZIONE
>
25
CPREPARATIVI PRIMA DELL’USO
Prima di utilizzare il condizionatore d’aria, verificare e impostare i seguenti parametri.
Impostazione del telecomando
I
l telecomando NON è impostato direttamente in fabbrica per utilizzare l’apparecchio come generatore di
aria fredda ad uso condizionamento (condizionatore) o di aria calda ad uso riscaldamento (pompa di
calore). Ad ogni sostituzione delle batterie del telecomando, sul display frontale lampeggerà l’apposita
freccia luminosa “Heat” (“caldo”) o “Cool” (“freddo”).
È possibile impostare il telecomando in funzione del tipo di apparecchio acquistato nel modo seguente:
premere un pulsante qualsiasi quando la freccia luminosa posta sul display frontale lampeggia in
corrispondenza della dicitura “Heat” (“caldo”), viene selezionata la funzione “pompa di calore”.
premere un pulsante qualsiasi quando la freccia luminosa posta sul display frontale lampeggia in
corrispondenza della dicitura“Cool” (“freddo”), viene selezionata la funzione “condizionamento”.
Se non viene premuto alcun pulsante entro 10 secondi, il telecomando viene impostato automaticamente
per la funzione “pompa di calore”. Gli apparecchi S95, S125, S185 e S245 sono dotati di una pompa di
calore.
Impostando il telecomando per utilizzare l’apparecchio solo a fini di condizionamento, NON è possibile
impostare la funzione di riscaldamento con il telecomando.
Precauzioni di sicurezza
•Utilizzare il corretto valore di tensione in funzione di quanto indicato sull’apposita targhetta per
evitare gravi danni all’apparecchio o rischi di incendio.
•Tenere costantemente pulito l’interruttore o la spina di alimentazione. Collegare l’interruttore/spina in
modo saldo e preciso al cavo di alimentazione. Un contatto insufficiente potrebbe essere causa di
elettroshock o incendio.
•Non utilizzare l’interruttore o togliere la spina per spegnere l’apparecchio quando è in funzione. Esiste
il rischio di propagazione di scintille che potrebbero causare un incendio.
•Non torcere, tirare o schiacciare il cavo di alimentazione per evitare rischi di elettroshock o incendio.
•Non inserire oggetti estranei quali bastoni o simili nell’apparecchio. A causa dell’elevata velocità di
rotazione della ventola possono verificarsi incidenti.
•Evitare un’esposizione diretta prolungata al flusso di aria fredda in provenienza dall’apparecchio. Si
consiglia di optare per un flusso diffuso.
•In caso di malfunzionamento, spegnere l’apparecchio con il telecomando prima di togliere la spina
dalla presa di alimentazione
•Non procedere direttamente alla riparazione dell’apparecchio. Riparazioni non eseguite da personale
specializzato possono provocare elettroshock ecc….
•Evitare di dirigere il flusso d’aria verso cucine a gas e stufe.
•Non toccare i pulsanti con le mani bagnate.
•
Non inserire alcun oggetto nell’unità esterna.
•La messa a terra conforme alle leggi o norme locali da parte di un tecnico autorizzato rientra nelle
responsabilità dell’utente.
>
26
DISTRUZIONI PER L’INSTALLAZIONE
Schema di installazione
La distanza dal muro
deve essere superiore
a 50 mm.
La distanza dal soffitto deve
essere superiore a 50 mm.
a distanza dal muro deve
L
essere superiore a 50 mm.
La distanza tra il
bocchettone di
uscita dell’aria e
il muro deve
essere superiore
a 250 mm.
La distanza tra il bocchettone
di uscita dell’aria e il muro deve
essere superiore a 500 mm.
-La figura sovrastante è una presentazione semplificata dell’apparecchio, che potrebbe
differire rispetto al prodotto da voi acquistato.
G
-L’installazione deve essere eseguita esclusivamente da personale autorizzato nel rispetto
delle normative nazionali.
La distanza tra il bocchettone di
uscita dell’aria e il muro deve
e superior
esser
minimo 250 mm.
e a 250 mm.
>
27
Collegamento del cavo di alimentazione
Connessione tra l’unità interna e l’unità esterna
1.Rimuovere il rivestimento in plastica dell’unità interna.
2.Per il collegamento far riferimento al diagramma dei
cablaggi (allegato all’unità interna).
3
.Ricollocare il rivestimento in plastica. Verificare che il
lato “B” sia all’esterno.
Scegliere la migliore collocazione per l’apparecchio.
Non collocare alcun ostacolo nei pressi del bocchettone di
uscita dell’aria in modo tale che l’aria sia libera di circolare
in ogni punto della stanza.
I tubi e il foro da praticare nel muro devono essere in
posizioni accessibili.
Predisporre uno spazio adeguato dall’apparecchio al
soffitto e al muro (cfr. capitolo D).
I filtri dell’aria devono essere facilmente estraibili.
Tenere l’apparecchio e il telecomando a una distanza
minima di 1 m da televisore, radio, ecc.
Le lampade fluorescenti possono causare interferenze.
Tenerle ad adeguata distanza.
Non mettere nulla vicino al bocchettone di uscita dell’aria,
in modo tale da garantire la massima circolazione dell’aria.
Il muro deve essere sufficientemente solido per sostenere il
peso del condizionatore e non contribuire ad aumentare il
rumore e le vibrazioni prodotti durante il funzionamento.
Quadro frontale
Morsetto di collegamento (interno)
Cassa
Schema di installazione
Unità interna
Altezza max.
pari a 5 m.
Unità esterna
Collocazione dell’unità esterna
Collocare l’unità esterna in un punto accessibile e ben
ventilato; non collocarla, per esempio, in un punto che
presenti pericolo di perdite di gas.
Mantenere la corretta distanza dal muro.
L’unità esterna non deve essere esposta ad aria di mare
sporca, grassa o salata o collocata nei pressi di tubi di
scarico.
Non installare lungo una strada per evitare spruzzi di
acqua.
Predisporre una base fissa per evitare l’aumento della
produzione di rumore.
Verificare che l’aria possa circolare liberamente.
dei tubi: 10 metri
Lunghezza max.
Unità esterna
Altezza max.
pari a 5 m.
Unità interna
(S95) o 15 metri
(S125, S185, S245)
tubi: 10 metri (S95)
o 15 metri (S125,
Lunghezza max. dei
S185, S245)
>
28
Installazione dell’unità interna
1.Installazione del piano di supporto
-scegliere il punto dove collocare il piano di
supporto dell’unità esterna tenendo conto
d
ella direzione dei tubi;
-disporre il piano di supporto orizzontalmente con l’ausilio di una riga orizzontale
o di una bolla;
-praticare fori di 32 mm di profondità nel
muro per fissare il piano di supporto;
-inserire i tasselli in plastica nei fori e fissare
il piano di supporto con viti a filetto
tagliente;
-verificare che il piano di supporto sia ben fissato. Praticare poi un foro per i tubi.
NB: la forma del piano di supporto varia da modello a modello, ma il metodo di installazione è identico.
2. Praticare un foro per i tubi
-Determinare la posizione del foro per i tubi nel muro in base al foro nel piano di supporto;
-praticare un foro nel muro. Il foro dovrebbe deviare leggermente verso l’esterno;
-inserire un manicotto nel foro per proteggere il muro.
3. Installazione tubi unità interna
-Inserire i tubi (del liquido e del gas) e
i cavi nel buco praticato nel muro
partendo dall’esterno verso l’interno
oppure dall’interno verso l’esterno
qualora sia già stata installata l’unità
interna;
-tagliare il segmento in plastica in funzione della direzione dei tubi.
NB: tagliare il segmento in plastica 1, 2 o 4, in funzione della posizione scelta per il foro nell’unità
interna.
-dopo aver installato i tubi, installare il tubo flessibile di scarico. Dopodiché collegare i cavi di alimentazione. Infine isolare i tubi, i cavi e il tubo flessibile di scarico.
Isolamento ter
applicar
mico giunti tubi. Avvolgere i giunti dei tubi con un materiale isolato termicamente e poi
e del nastro in vinile.
>
29
Isolamento termico tubi
a.collocare il tubo flessibile di scarico sotto i
tubi;
utilizzare materiale di isolamento con
b.
spessore maggiore di 6 mm;
-
il tubo flessibile di scarico deve puntare
verso il basso per agevolare lo scarico.
Verificare che il tubo flessibile di scarico
non sia piegato, avvolto su se stesso o
sporgente; non immergerne l’estremità in
Tubo di grandi dimensioni
Cavo di alimentazione
Cavo di alimen-
azione 1 (per
t
ompa di calore)
p
avo per regolazione dello
C
sbrinamento (per pompa
di calore)
Tubo di isolamento termico
ubo di piccole
T
dimensioni
Tubo flessibile
di scarico
astro
N
acqua.
Se il tubo flessibile di scarico è collegato a una prolunga, la parte che passa lungo l’unità interna deve
essere isolata.
-Quando i tubi sono diretti verso destra, i tubi, il cavo di alimentazione e il tubo flessibile di scarico
devono essere isolati e montati sul retro dell’unità interna con un apposito dispositivo di fissaggio.
Inserire
qui
Piano di
supporto
Dispositivo di fissaggio del tubo
Piano di
supporto
Dispositivo di fissaggio del tubo
Piano di
supporto
A. Inserire il dispositivo di fissaggio del tubo nell’alloggiamento
B. Premere per agganciare il dispositivo di fissaggio del tubo al piano di supporto
Vollegamento dei tubi
a.Collegare i tubi dell’unità interna con due chiavi. Prestare parti-
e attenzione alla coppia di ser
colar
tale da evitar
e che i tubi, i giunti e i dadi si defor
raggio consentita, in modo
mino o dan
-
neggino.
b.Stringergli prima con le dita, poi utilizzare le chiavi.
Modello
S95/S125/S185
S245
S95
S125/S185
S245
Dimensione del tubo
Serraggio
Ampiezza
dei dadi
Fissare qui
>
30
Loading...
+ 72 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.