Zephyr CTPE48BSX, CTPE60BSX User Manual

CTP-E48BSX CTP-E54BSX CTP-E60BSX
www.zephyronline.com
Model number: Serial Number: Date of Purchase: Sales Dealer:
Use, Care, and Installation Guide
JAN14.0101 © 2014 Zephyr Corporation
READ AND SAVE THESE INSTRUCTIONS
www.zephyronline.com
SAFETY NOTICE ................................................................. 2-3
LIST OF MATERIALS ....................................................... 4
INSTALLATION
Ducting Calculation Sheet Mounting Height & Clearance Ducting Options
........................................................... 7
Hood Specifi cations Blower Preparation Mounting the Range Hood
FEATURES & CONTROLS
Touch Controls Features
............................................................. 15
.......................................................................... 16
Optional Remote Control
MAINTENANCE
Cleaning and Installing Filters
TROUBLESHOOTING
WIRING DIAGRAMS
................................................................ 19
................................................................... 20-21
....................................... 5
................................ 6
................................................... 8
..................................................... 9-11
...................................... 12-14
Table of Contents
......................................... 17
............................... 18
LIST OF PARTS AND ACCESSORIES
.............................. 22
1
READ AND SAVE THESE INSTRUCTIONS
www.zephyronline.com
WARNING
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY SOLID-STATE CONTROL DEVICE.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: a. Use this unit only in the manner intended by the manufacturer, if you have questions, contact the manufacturer.
b. Before servicing or cleaning unit, switch power off at service panel and lock panel to prevent power from being switched on accidentally.
When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION
For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. Take care when using cleaning agents or detergents. Suitable for use in household cooking area.
WARNING
TO REDUCE THE RISK OF RANGE TOP GREASE FIRE: a. Never leave surface units unattended at high settings. Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly
on low or medium settings. b. Always turn hood ON when cooking at high heat or when fl aming food c. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or fi lter.
Important Safety Notice
d. Use proper pan size. Always use cookware appropriate for the size of the surface element. e. Keep fan, fi lters and grease laden surfaces clean. f. Use high setting on hood only when necessary. g. Don’t leave hood unattended when cooking. h. Always use cookware and utensils appropriate for the type of and amount of food being prepared.
WARNING
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE, OBSERVE THE FOLLOWING: a. SMOTHER FLAMES with a close-fi tting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS.
If the fl ames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT. b. NEVER PICK UP A FLAMING PAN – You may be burned. c. DO NOT USE WATER, including wet dishcloths or towels – a violent steam explosion will result. d. Use an extinguisher ONLY if:
1. You know you have a Class ABC extinguisher, and you already know how to operate it.
2. The fi re is small and contained in the area where it started.
3. The fi re department is being called.
4. You can fi ght the fi re with your back to an exit
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: a. Installation work and electrical wiring must be done by qualifi ed person(s) in accordance with all applicable codes and standards.
Including fi re-rated construction. b. Suffi cient air is needed for power combustion and exhausting of gases through the fl ue (chimney) of fuel burning equipment to prevent
back-drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National
Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and
the local code authorities. c. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities. d. Ducted fans must always vent to the outdoors. e. If this unit is to be installed over a tub or shower, it must be marked as appropriate for the application and be connected to a GFI
(Ground Fault Interrupter protected branch circuit). g. NEVER place a switch where it can be reached from a tub or shower. h. Make sure the power is off before installing, wiring or maintenancing.
2
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK. NOT FOR USE IN OUTDOOR COOKING ENVIRONMENTS.
CAUTION
To reduce risk of fi re and to properly exhaust air outside - Do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces or garages.
OPERATION
Always leave safety grilles and fi lters in place. Without these components, operating blowers could catch onto hair, fi ngers and loose clothing.
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation, maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to negligence and the warranty of the unit automatically expires due to improper maintenance.
*NOTE: Please check www.zephyronline.com for revisions before doing any custom work.
ELECTRICAL REQUIREMENTS
Important:
Observe all governing codes and ordinances. It is the customer’s responsibility:
- To contact a qualifi ed electrical installer.
- To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 latest edition* or CSA standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualifi ed electrician determine that the ground path is adequate.
Do not ground to a gas pipe. Check with a qualifi ed electrician if you are not sure the range hood is properly grounded. Do not have a fuse in the neutral or ground circuit. *National Fire Protection Association Batterymarch Park, Quincy, Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road, Cleveland, Ohio 44131-5575 This appliance requires a 120V 60Hz electrical supply and connected to an individual properly grounded branch circuit
protected by a 15 or 20 ampere circuit breaker or time delay fuse. Wiring must be 2 wire with ground. Please also refer to Electrical Diagram on product.
A cable locking connector (not supplied) might also be required by local codes. Check with local requirements, purchase and install appropriate connector if necessary.
Important Safety Notice
3
MODEL: CTP-E48BSX, CTP-E54BSX, CTP-E60BSX
1 - Hood 2 - Baffl e Filters 4 - 6W Zephyr Bloom™ HD LED Light Bulbs 2 - Telescopic Duct Covers 4 - Telescopic Support Rod Sets 4 - Telescopic Support Rod Couplers 1 - Duct Cover Ceiling Bracket 2 - Utensil Rails 4 - Angle Brackets (short) 4 - Angle Brackets (long) 1 - 8” Round Starting Collar
List of Materials
1 - AC Power Wiring Box 1 - Remote Blower Wire Harness & Wiring Box 1 - Motor Housing w/ Internal Motor Housing Flange 1 - Remote Blower Motor Housing Flange 1 - Hardware Packet
Hardware Packet Contents
M4 * 2” x 4
M4 * 38 x 4
M4 * 6 x 36
wire cap x 3
www.zephyronline.com
3/16 * 3/8 x 2
M4 * 8 x 12
zip tie x 4
allen key x 1
Internal Blower Hardware Packet Contents
M4 * 8 x 2
M4 * 16 x 4
10x3/16” x 2
M4 * 8 x 2
zip tie holder x 2
washer x 2
washer x 4
M3 * 5 x 2
M4 * 4 set screw x 12
M4 * 4 set screw x 10 (pre-installed in utensil rails)
Parts Not Supplied
- Ducting, conduit and all installation tools
- Cable connector (if required by local codes)
- Internal Blower Kits (CBI-290A / CBI-600A)
- External Blower Kit (CBE-1000)
- In-Line Blower Kit (PBN-1000A)
- Duct Cover Extension Accessory
4
Duct pieces
q
3- 1/ 4” x 10” Rect., straight
Equivalent number length x used =
1 Ft. x ( ) =
To ta l
Ft.
Duct pieces
6”- 8” Round wall cap with damper
Equivalent number length x used =
30 Ft. x ( ) =
To ta l
Ft.
7” Round, straight
8” Round, straight
3- 1/ 4” x 10”
0
Rect. 90 elbow
3- 1/ 4” x 10”
0
Rect. 45 elbow
3- 1/ 4” x 10”
0
Rect. 90 flat elbow
3- 1/ 4” x 10” Rect. wall cap with damper
3- 1/ 4” x 10” Rect. to 6” round transition
3- 1/ 4” x 10” Rect. to 6” round transition
0
elbow
90
6” Round,
0
elbow
90
1 Ft. x ( ) =
1 Ft. x ( ) =
15 Ft. x ( ) =
9 Ft. x ( ) =
24 Ft. x ( ) =
30 Ft. x ( ) =
5 Ft. x ( ) =
15 Ft. x ( ) =
15 Ft. x ( ) =
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
6”- 8” Round, roof cap
6” round to 3- 1/ 4” x 10” rect. transition
6” round to 3- 1/ 4” x 10” rect. transition
0
elbow
90
7” or 8”
Round,
0
90
elbow
7” or 8”
Round,
0
45
elbow
7” or 8”
Round
wall cap with damper
7” or 8” Round, roof cap
7” round to 3 1/ 4” x 10” rect. transition
7” round to 3- 1/ 4” x 10” rect. transition
0
elbow
90
30 Ft. x ( ) =
1 Ft. x ( ) =
16 Ft. x ( ) =
15 Ft. x ( ) =
9 Ft. x ( ) =
30 Ft. x ( ) =
30 Ft. x ( ) =
8 Ft. x ( ) =
15 Ft. x ( ) =
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Ft.
Installation – Ducting Calculation Sheet
Ft.
6” Round,
0
elbow
45
9 Ft. x ( ) =
Subtotal column 1 =
Maximum Duct Length: For satisfactory air movement,
the total duct length of a 3 1/ 4” x 10” rectangular6”, 7” or 8” diameter round duct should not exceed 100 e
uivalent feet.
Ft.
Ft.
Subtotal column 2 =
Subtotal column 1 =
Total ductwork =
Ft.
Ft.
Ft.
5
min. A
max. B
www.zephyronline.com
long reducer instead of a pancake reducer. Reduce duct size as far away from opening as possible.
If turns or transitions are required; install as far away from opening and as far apart, between 2, as possible.
Minimum mount height between range top and hood bottom should be no less than 26”.
min. C
max. D
26” min. 36” max.
36”
Standard Extension
Hood Heights Duct Cover Duct Cover
minimum (A) 34” 47“ maximum (B) 51
Ceiling Heights
minimum (C) 96” (8’) 109“ (9‘ 1”) maximum (D) 123
1/2 72”
1/2” (10’ 3 1/2“) 144” (12’)
Maximum mount height should be no higher than 36”.
It is important to install the hood at the proper mounting height. Hoods mounted too low could result in heat damage and fi re hazard; while hoods mounted too high will be hard to reach and will lose its performance and effi ciency.
If available, also refer to range manufacturer’s height clearance requirements and recommended hood mounting height above range.
Vertical Ducting:
6” round minimum (internal blower) 10” to 8” round minimum (remote blower)
Horizontal Ducting:
N/A
Installation – Mounting Height & Clearance
DUCTING
A minimum of 6” round duct work must be used to maintain maximum air fl ow effi ciency with the 290/600 cfm internal blower. A minimum of 10” to 8” round duct work must be used with the 1000 cfm remote blower.
Always use rigid type metal ducts only. Flexible ducts could restrict air fl ow by up to 50%.
Use calculation (on page 5) to compute total available duct run when using elbows, transitions and caps.
ALWAYS, when possible, reduce the number or transitions and turns. If long duct run is required, increase the duct size.. If a reducer is used, install a
DAMAGE-SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage before
• If the unit is damaged in shipment, return the unit
• If the unit is damaged by the customer, repair or
• If the unit is damaged by the installer (if other
installation.
to the store in which it was bought for repair or replacement.
replacement is the responsibility of the customer.
than the customer), repair of replacement must be made by arrangement between customer and installer.
6
WARNING FIRE HAZARD
NEVER exhaust air or terminate duct work into spaces between walls, crawl spaces, ceiling, attics or garages. All exhaust must be ducted to the outside.
Use metal ductwork only.
Fasten all connections with sheet metal screws and tape all joints with certifi ed Silver Tape or Duct Tape.
Some Ducting Options
External Blower
side wall cap w/ gravity damper
Soit or crawl space
Roof Pitch w/ Flashing & Cap
Installation – Ducting Options
External
Blower
Soit or crawl space
7
www.zephyronline.com
6-13/16”
Installation – Hood Specifi cations
Side View
15-3/4”
Front View
1/2”
Standard Duct Cover Min 34” - Max 51 1/2”
Z1C-00TP Extension Min 47” - Max 72”
2-3/8”
12-1/8”
13/16”
5/8”
8-7/8”
Top View
32”
Ceiling Bracket
11-3/4”
10”
9”
26-7/8”
25-3/16”
Min 21-5/8” Max 41”
2-1/8”
6-9/16”
47-15/16”, 53-15/16”, 59-1/8”
8
8-15/16”
9-1/2”
10-7/16”
3-1/8”
1-3/8”
FRONT
INTERNAL BLOWER PREPARATION
1. Remove internal blower fl ange from motor
housing by (6) screws.
3. Secure AC power wiring box to internal blower
fl ange by (2) M4*8 screws.
2. Secure internal blower to internal blower fl ange by (4) M4*16 screws from internal blower hardware.
Installation – Blower Preparation
4. Secure ground wire to underside of internal blower fl ange by (1) 3/16*3/8 screw and (1) washer.
5. Connect 9 pin molex connector from capacitor cable to 9 pin molex connector from internal blower.
6. Re-install internal blower fl ange to motor housing by (6) screws previously removed from step 1.
9
INTERNAL BLOWER PREPARATION CONT.
www.zephyronline.com
7. Secure motor housing to hood body by (12) M4*6 screws.
Installation – Blower Preparation
9. Secure capacitor box to internal hood body by (2) M4*8 screws and secure ground wire by (1) 3/16*3/8 screws.
REMOTE BLOWER PREPARATION
8. Connect 6 pin molex connector from capacitor cable to 6 pin molex connector from control box. Connect 2 pin plug from AC power cable to 2 pin plug from control box. Secure cables to hood interior with zip ties and zip tie holders.
1. Remove internal blower fl ange from motor housing by (6) screws.
2. Secure AC power box and remove blower wiring box to remote blower fl ange by (2) M4*8 screws each.
10
REMOTE BLOWER PREPARATION CONT.
3. Secure AC power ground wire and remote blower ground wire to underside of remote blower fl ange by (1) 3/16*3/8 screw and (1) washer each.
5. Secure remote blower fl ange to motor housing using (6) screws previously removed from step 1.
4. Secure remote blower 8” round collar to remote blower fl ange by (8) M4*8 screws.
Installation – Blower Preparation
6. Secure motor housing to hood body by (12) M4*6 screws.
NOTE: For instructions on mounting the remote blower please refer to the CBE-1000 or PBN­1000A remote blower manual included in the remote blower packaging or on our website at www.zephyronline.com
7. Connect 6 pin molex connector from remote blower wiring box to 6 pin molex connector from control box. Connect 2 pin plug from AC power cable to 2 pin plug from control box. Secure cables to hood interior with zip ties and zip tie holders.
11
Add Blockings
Tabs
Tabs
Ceiling Bracket
FIG. 1
www.zephyronline.com
Ceiling
CL
Mounting
Holes
FIG. 2
FRONT
Electrical wiring
passage
Marking for Coupler
CL
Set screw mounting
hole
1. Determine the location for mounting the hood. Mark centerlines front to back and left to right of hood placement. Place supplied paper template on ceiling and center marked center lines with template center lines. Mark mounting holes for ceiling bracket and telescopic rod couplers.
2. Cut out hole in ceiling for the duct work and electrical wiring passage.
Installation – Mounting the Range Hood
3. Add and secure wook blockings (minimum 2x4 studs) between ceiling joists for celing bracket and telescopic rod couplers if needed. FIG. 1.
4. Center, mark and fasten ceiling bracket onto ceiling using (4) M4*38 screws and (4) washers. Make sure the word “FRONT” displayed on the ceiling bracket is facing the front of the hood where the controls will be located. FIG. 2.
5. Attach telescopic rod couplers to marked locations on ceiling using (1) M4*2” wood screw for each coupler. Make sure the set screw mounting hole is toward the bottom of the coupler during mounting. FIG. 2.
6. Prepair and position electrical wiring and duct work through ceiling bracket.
ELECTRICAL WARNING All Electrical work must by performed by qualifi ed electrician or person with similar technical know how and background.
For personal safety, remove house fuse or open circuit breaker before beginning installation. Do not use extension cord or adapter plug with this appliance.
Follow national electrical codes or prevailing local codes and ordinances.
Electrical Supply: This appliance requires a 120V 60Hz electrical supply, and connected to an individual, properly grounded branch
circuit, protected by a 15 or 20 ampere circuit breaker or time delay fuse. Wiring must be 2 wire w/ ground. Please also refer Electrical Diagram labeled on product.
Cable Lock: A cable locking connector (not supplied) might also be required by local codes. Check with local requirements and codes, purchase and install appropriate connector if necessary.
12
Tab
A
B
B
A
A
A
B
A
B
FIG. 4
FIG. 3
7. Determine desired height of hood, measure and select either 27 3/8” or 35 3/8” angle brackets. Position and attach angle brackets type A and B to the motor housing as shown using (8) M4*6 screws, (2) for each angle bracket. FIG. 3.
8. Slide duct covers over motor housing. Make sure bottom duct cover with cut-out is facing the front and back of hood. FIG. 3.
9. Lift assembled unit and attach all (4) angle brackets to ceiling bracket. Make sure the tabs on each angle bracket fi t between the slots on the ceiling bracket. One half of the angle bracket will be outside the ceiling bracket and the other half outside the ceiling bracket. Attach angle brackets to ceiling brakcet using (16) M4*6 screws, (4) for each angle bracket. FIG. 4.
10. Connect duct work and electrical wiring.
11. Slide up upper duct cover and attach to ceiling bracket using (2) M3*5 screws.
Installation – Mounting the Range Hood
13
Loading...
+ 35 hidden pages