Young 41382LF2 User Manual

MODEL 41382LF2
RELATIVE HUMIDITY / TEMPERATURE PROBE with CURRENT OUTPUTS
SPECIFICATIONS
RELATIVE HUMIDITY: Measuring range: 0-100% RH Accuracy at 23°C: ±1% Stability: Better than ±1%RH per year Response Time: 10 seconds (Without Filter) Sensor type: Rotronic Hygromer
TEMPERATURE: Measuring Range: -50 to +150°F Accuracy at 23°C: ±0.5°F Response Time: 10 seconds (Without Filter) Sensor type: Platinum RTDW
Output signal: 4-20 mA Power Required: 5-30 VDC, 46 mA max Recommended Cable: 2 Pair shielded 22AWG, Young 18723 Recommended Shields: Young Model 43502 Aspirated Radiation Shield Young Model 41003P Multi-Plate Radiation Shield
INSTRUCTION SHEET 41382LF2-90
REV B102613
Declaration of Conformity
INTRODUCTION
INSTALLATION
Install the probe in a naturally ventilated or fan aspirated radiation shield. Mount probe and shield in a location with good air circulation clear of large thermal masses (buildings, pavement, solar panels, etc.), exhaust vents, electrical machinery and motors, water fountains and sprinklers. Typical wiring diagrams appear on next page.
MAINTENANCE
The probe provides years of service with minimal maintenance. Humidity calibration, which may drift slightly with time, can be checked or restored at the factory.
Periodically clean the humidity sensor lter when used in areas of high dust or contamination (smokestacks, seawater, etc.) Soak in
clean water or use a mild soap solution. DO NOT USE SOLVENTS.
CE COMPLIANCE
This product complies with the European CE directive on EMC compatibility. Shielded cable must be used.
WARRANTY
R. M. Young Company 2801 Aero Park Drive Traverse City, MI 49686 USA
Model 41382LF2 RH/Temp Probe The undersigned hereby declares on behalf of R. M. Young Company that the above-referenced product, to which this declaration relates, is in conformity with the provisions of:
Council Directive 2004/108/EC (December 15, 2004) on Electromagnetic Compatibility
David Poinsett R&D Manager
FILTER
3.4in
86.5mm
5.4in
136mm
7.4in
188mm
.94in
24mm
Thi s product is warra nted to b e free of defects in mate rials and construc tion for a period of 12 mon ths from date of initial purc hase. Lia bility is limited to repair or repla cement of defective it em. A copy of the warra nty polic y may be obtained fro m R. M. Young Company.
R. M. YOUNG COMPANY 2801 Aero Park Drive , Traverse City, Michigan 49686 USA
TEL (231) 946-3980 FAX (231) 946-4772
2.5in
62mm
TYPICAL WIRING
4-20 mA CURRENT INPUT
MEASURING INSTRUMENT
CURRENT INPUT 1 (+)
CURRENT INPUT 2 (+)
R R
250 Ohms Typical
CURRENT INPUT COMMON
VOLTAGE INPUT MEASURING INSTRUMENT
+24VDC PWR
+24VDC PWR
PWR COMMON
SHIELDED CABLE
EARTH GROUND
SHIELDED CABLE
(WHT)
(BLK)
(GRN)
(RED)
(WHT)
SENSOR TERMINALS
+PWR
GND
RH
T
SENSOR TERMINALS
+PWR
PWR COMMON
VOLTAGE INPUT 1 (+)
VOLTAGE INPUT 2 (+)
VOLTAGE INPUT COMMON
(BLK)
(GRN)
(RED)
R R
EARTH GROUND
50 to 250 Ohms Typical
30VDC at 46 mA Max Supply Total Current Consumption = T mA + RH mA + 6 mA
Min Supply V = 4 + 0.02R Max Load R = (Vsupply - 4) / 0.02
GND
RH
T
Loading...