York Hu12mb Installation Guide

This product must be installed by a qualified heating and air conditioning contractor. Failure to do so could result in serious injury from electrical shock.
This product must be installed in compliance with all local, state and federal codes.
ATTENTION INSTALLER:
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING
MODEL 7000 FAN POWERED HUMIDIFIER
INSTALLATION OPTIONS
Typical Installation Alternate Installation
COOLING COILS IN
WARM AIR PLENUM
Humidifier to be installed as shown in relation to cooling coils.
WIRING DIAGRAM
90-922
90-921
Orientation of Humidifier
to Cooling Coils
WARNING
1. ELECTRICAL SHOCK HAZARD.
Disconnect electrical power to the furnace before starting installation. Failure to do so could result in serious injury from electrical shock.
2.
SHARP EDGES HAZARD. Sharp
edges may cause serious injury from cuts. Use care when making plenum openings and handling ductwork.
3.
RISK OF SCALDING. Water
temperature over 125°F can cause severe burns and scald instantly. Shut off the hot water supply before disconnecting or tapping into any hot water supply line.
SPECIFICATIONS
HUMIDIFIER DIMENSIONS
Width 15
29
32
Height
(including solenoid valve
and drain spud)
18”
Depth 10
11
32
PLENUM OPENING
14
3
4”W x 145⁄16”H
WATER FEED RATE
6 gph
ELECTRICAL DATA
120 VAC-60 Hz, 0.8 AMP
CAUTION
1. Do not install humidifier where freezing temperatures could occur. The water line could freeze and crack causing water damage to the home.
2. Do not install humidifier on the furnace cabinet.
3. Do not install humidifier on a plenum face where the blanked off ends of the cooling coil will restrict air movement through the humidifier.
4. Do not set humidity level above recommended or to recommended level if condensation exists on inside windows of any unheated space, as condensation damage may result. Excess humidity can cause moisture accumulation which can allow the possibility for mold growth in the home.
5. Do not connect the humidifier power cord to multi-speed furnace blower motors or blower motors other than 120 VAC. Premature component failure may result. Use Model S1-HURELAY24VAA Current Sensing Relay.
6. When installing Manual Humidifier Control on a downflow furnace, ensure blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Control.
7. Do not install humidifier where water pressure exceeds 125 psi, since damage to the humidifier may result. Follow codes in effect concerning pressure reduction.
8. Do not install humidifier on the supply plenum where static pressure exceeds 0.4 in. wg.
RISK OF PROPERTY AND EQUIPMENT DAMAGE.
BLANKED OFF
END OF COIL
NOTES
1. The humidifier is not suitable for installation on ducts with horizontal airflow. Performance will be reduced.
2. When installing humidifier on a heat pump system, use hot water. The heated water supplements the reduced supply air temperature as added heat for evaporation.
TEMPLATE MUST BE LEVEL
RETURN
RETURN
HOT WATER
SUPPLY
SUPPLY
90-1109Y
Automatic Humidifier Control
For detailed Automatic Humidifier Control
installation and wiring instructions,
see separate sheet included with Control.
IMPORTANT
WHEN MODEL S1-HURELAY24VAA CURRENT SENSING RELAY IS USED:
WIRE CURRENT SENSING RELAY INTO 24 VAC HUMIDIFIER CONTROL CIRCUIT ONLY! DO NOT
INSTALL IN TRANSFORMER PRIMARY CIRCUIT.
IMPORTANT
USE 120 VAC POWER SOURCE OTHER THAN FURNACE MOTOR CIRCUIT. HOWEVER, THE TRANSFORMER CAN BE POWERED OFF THE HOT 120 VAC LINE BEFORE IT ENTERS THE FURNACE.
• DO NOT WIRE TRANSFORMER INTO FURNACE BLOWER CIRCUIT.
SHUT-OFF
(SADDLE VALVE)
HUMIDIFIER CONTROL
WATER SUPPLY
120 VAC OUTLET
CONNECT DRAIN LINE HERE
COMMON
BROWN WIRES
MODEL S1-HURELAY24VAA
CURRENT SENSING RELAY (IF REQUIRED)
FURNACE
BLOWER MOTOR
6
5
7
1
3
9
11
13
12
14
15
8
10
4
2
16
17
READ COMPLETE SAFETY INSTRUCTIONS AND INSTALLATION TEMPLATE BEFORE STARTING
TEMPLATE MUST BE LEVEL
– TOP –
READ REVERSE SIDE FIRST! READ REVERSE SIDE FIRST!
Form 358009 10007597 B2204318A 1.08
90-888
FURNISHED ITEMS
24 VAC Manual Humidifier Control
Saddle Valve
Humidifier Installation Template
Mounting screws
(sheet metal screws)
Water supply line (1⁄4” copper)
Drain line (1⁄2” I.D. hose)
Low voltage wire
Manual Humidifier Control
Adapter Plate Part No. S1-4039
Model S1-HURELAY24VAA Current
Sensing Relay (if required)
ITEMS NOT FURNISHED
IMPORTANT! Be sure owner’s manual containing instructions for
operation and warranty information is given to owner in order to avoid unnecessary
calls. Warranty is void unless humidifier is installed by qualified heating and air
conditioning contractor due to possible misapplication of product.
PARTS LIST
1. Front Cover
2. Base
3. Orifice Plate
4. Motor Mount Bridge
5. Scale Control Insert
6. Humidifier Pad
7. Water Distribution Tray
8. Fan Blade
9. Motor
10. Motor Mount Gasket
11. Control Circuit Board
12. Power Cord
13. Strain Relief Bushing
14. Solenoid Valve
15. Connector Plug
16. Feed Tube
NOTE: BEFORE LEAVING THE JOB SITE, MAKE SURE:
1. Saddle valve is fully open.
2. All plumbing connections are watertight.
3. Humidifier functions properly.
1. Place the humidifier on a flat surface.
Unlatch humidifier cover assembly from base assembly at the bottom of the cover, lift and set aside. Pull out the evaporative assembly by grasping at the top and tipping out. (See Figure 1)
2. Using a level, position this template at
least 1
1
2 inches above the furnace housing or cooling coil if applicable, for clearance of the drain line. Trace around template edges. When there is insufficient space on the supply plenum, the humidifier can be installed on the return duct provided the humidifier is supplied with hot water. Remove the template and accurately cut the plenum opening 14
3
4”W x 145⁄16“H, being careful
to avoid injury from sharp edges.
3. Position the two plastic hooks on the
top of base along the top edge of the plenum opening. Push base up to engage the two hooks and sheet metal along the top edge opening. Push base in and slide down so that the bottom four hooks engage the sheet metal at the bottom edge of the opening. Secure base to
opening using top three screw holes in housing. An additional hole is provided at the bottom for securing the base to the plenum. (See Figure 2)
4. While pressing the base against the
plenum, reach through the center opening and turn left and right swing latches down to secure the base onto the plenum.
(See Figure 3)
5. Reinstall the evaporative assembly into
the base, with the bottom of the scale control insert (5) sitting firmly in the inside of the drain spud attached to the base. Push the evaporative assembly in at the top between the retaining ribs that hold the assembly in place in a vertical position. Reinstall cover assembly by hooking at the top of base assembly and latching at the bottom.
6. Locate and install the Manual Humidifier
Control by following the instructions shown in step #6A. For Automatic Humidifier Control installation instructions, see separate sheet included with the Automatic Control. DISCONNECT ELECTRICAL POWER
TO FURNACE BEFORE PROCEEDING!
6A. MANUAL HUMIDIFIER CONTROL INSTALLATION INSTRUCTIONS:
The Manual Humidifier Control is designed for low voltage service to control humidification equipment. An increase in relative humidity expands the nylon ribbon that opens the control switch to stop operation of the humidifier. A decrease in relative humidity reverses the process and closes the control switch.
LOCATION
1. Locate on inside wall of living area approximately 5 feet above floor, or in the furnace return air plenum. Adapter Plate Part No. S1-4039 (not included) is required for return plenum air installation. If humidifier is mounted on return duct, Humidifier Control must be at least 6” upstream of humidifier.
2. Do not locate Control in the direct path of furnace discharge air or drafts from open doors and windows.
3. Do not install where operation might be affected by lamps, sunlight, fireplace registers, radiators, concealed air ducts and pipes, or room occupants.
4. The basic rules for location of thermostats also apply to humidifier controls.
GENERAL INSTRUCTIONS
1. Do not attempt to repair or recalibrate
Humidifier Control. Humidifier Controls requiring service should be returned to your distributor.
2. Use Humidifier Control in low voltage (24 VAC) applications only. Install 24 VAC wiring to Humidifier Control as shown in Wiring Diagram, opposite side.
3. Make sure no bare wires are exposed or insulation damaged. Insulation on wire should extend to head of screws.
4. Make sure all splices are mechanically and electrically secure.
5. To remove dirt or other foreign matter from nylon ribbon and control interior, dust lightly with a fine, soft brush.
7. The humidifier power cord must be
plugged into a 120 VAC outlet. Wire an electric outlet box to power source other than furnace fan motor circuit. Outlet box can be powered off of the 120 VAC line before it enters furnace. If furnace accessory terminals are 120 VAC, outlet box can be wired from this location. See manufacturer’s recommendations for wiring. Do not use an extension cord. Do not power 120 VAC outlet from the furnace blower circuit.
In order for the humidifier to turn on, the furnace blower must be operating and the Humidifier Control must be calling for humidity. The interface between the humidifier and the furnace to detect blower operation can be accomplished several different ways:
A. If the humidifier is plugged into a 120 VAC outlet that is powered only when the furnace is on, then the brown wires from the humidifier can be connected directly to the Manual Humidifier Control.
B. If the humidifier is plugged into a continuously powered 120 VAC outlet, then a Model S1-HURELAY24VAA Current Sensing Relay (not included) must be installed in the humidifier circuit. (Brown wires connected to Manual Humidifier Control.)
8. Tap into water supply line with the saddle valve
furnished. See instructions on saddle valve package. The humidifier will function with cold, hot, softened or unsoftened water. The use of service hot water (140°F MAX.) and constant blower operation will provide maximum evaporative capacity. When installing
humidifier on heat pump system, humidifier must be supplied with service hot water.
NOTE: The saddle valve is designed to be fully opened or closed. Do not use it to regulate water flow.
9. Connect tubing from the saddle valve to the inlet side
of the solenoid valve using
1
4” O.D. copper tubing (not
furnished). DOUBLE WRENCH TO PREVENT LEAKING!
(See Figure 4)
10. Drain spud is designed to accept
1
2” I.D. plastic hose (not furnished). Run drain line from drain spud to floor drain. CAUTION: If hose clamp is used, do not
overtighten, drain spud could crack. Be sure drain line has continuous slope. NOTE: Do not sweat or directly attach metal drain line to fitting. Do not use solvent type adhesives when connecting plastic drain line, since damage to fitting could result.
11. Open saddle valve completely and turn on furnace.
Turn up Humidifier Control so that humidifier will turn on. Allow humidifier to run until water is observed coming out of the drain line. Check to see if humidifier and saddle valve are watertight. Check operation to make sure that all electrical components function properly. Set Humidifier Control to level recommended in Owner’s Manual.
Figure 1
90-923 90-924 90-925 90-926
Figure 2 Figure 3 Figure 4
Loading...