York DY036 User Manual

TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
343615-YTG-D-0708

DESCRIPTION

YORK Sunline Magnumunits are convertible single pack­age air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units include:
AND SINGLE PACKAGE AIR CONDITIONERS
DY 036, 048 & 060
3, 4 & 5 NOMINAL TONS
14.00 SEER
Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
Permanently lubricated motors
Bottom or side air discharge configuration capability (field convertible)
Manufactured under the quality standards of ISO9001
®
Simplicity
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units

WARRANTY

Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and electric heat elements.
Control Board
Ten-year parts warranty on the gas-fired heat exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
343615-YTG-D-0708

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 6
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 7
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 32
LIST OF FIGURES
Fig. # Pg. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 TYPICAL FIELD POWER & CONTROL WIRING . . . .25
3 UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . 26
4 UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . .27
6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . .27
7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . .28
8 DISCONNECT/BLOWER ACCESS LOCATION . . . . . 28
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . .29
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . .30
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . .31
LIST OF TABLES
Tbl. # Pg. #
1 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . . . 8
2 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . .8
3 2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . .8
4 DY036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . . .9
5 DY036 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . .9
6 DY036 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
7 DY036 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . .10
Tbl. # 8 DY048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 11
9 DY048 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 11
10 DY048 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
11 DY048 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 12
12 DY060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED INLET) . . . . . . . . . . . . . . . . 13
13 DY060 INDOOR SOUND POWER LEVELS
(HORIZONTAL DUCTED DISCHARGE) . . . . . . . . . . . 13
14 DY060 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED INLET) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
15 DY060 INDOOR SOUND POWER LEVELS (VERTICAL
DUCTED DISCHARGE) . . . . . . . . . . . . . . . . . . . . . . . 14
16 DY036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 15
17 DY048 COOLING CAPACITIES (4 TON) 1 . . . . . . . . . . 6
18 DY060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 17
19 SUPPLY AIR BLOWER PERFORMANCE (DY036,
048, & 060 DIRECT DRIVE) SIDE DUCT
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
20 SUPPLY AIR BLOWER PERFORMANCE (DY036,
048, & 060 DIRECT DRIVE) BOTTOM DUCT
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
21 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 19
22 ELECTRIC HEAT CFM LIMITATIONS . . . . . . . . . . . . 19
23 ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE
W/O POWERED CONVENIENCE OUTLET . . . . . . . . 20
24 ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE
W/ POWERED CONVENIENCE OUTLET . . . . . . . . . 22
25 DY PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . 24
26 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 24
27 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 24
28 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
29 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 28
30 DY 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 30
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 31
Pg. #
2 Johnson Controls Unitary Products

PRODUCT NOMENCLATURE

3-5 Ton Sunline Magnum™ Model Number Nomenclature
D Y 048 N04 A 2 A AA 2 0 1 2 4 A
343615-YTG-D-0708
Product Category
D = A/C, Single Pkg., R-22
Product Identifier
Y = 14.0 SEER
Nominal Cooling Capacity
036 = 3.0 Ton 048 = 4.0 Ton 060 = 5.0 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. Suitable for Field
Installed Electric Heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel, 1 Stage (036) N06 = 60 MBH Output Aluminized Steel, 1 Stage (048) N08 = 80 MBH Output Aluminized Steel, 1 Stage
(036, 060)
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(048, 060)
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(036, 048, 060)
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(036*, 048, 060) S04 = 40 MBH Output Stainless Steel, 1 Stage (036) S06 = 60 MBH Output Stainless Steel, 1 Stage (048) S08 = 80 MBH Output Stainless Steel, 1 Stage
(036, 060)
S10 = 100 MBH Output Stainless Steel, 1 Stage
(048, 060) T06 = 60 MBH Output Stainless Steel, 2 Stage
(036, 048, 060)
T10 = 100 MBH Output Stainless Steel, 2 Stage
(036*, 048, 060)
Electric Heat Options
E05 = 5 KW E07 = 7 KW E10 = 10 KW E15 = 15 KW E20 = 20 KW E30 = 30 KW
*(D, T)10 = 92 MBH Output on 036 Models
Airflow
A = Direct Drive B = Direct Drive/Single Input Economizer D = Direct Drive/Motorized Damper
1 = 208/230-1-60 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Voltage
Product Style
A = Style A
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
2" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
2 = Second Generation
Standard Cabinet
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch AS = Bottom Drain Connection RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator and Condenser Coil
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
Configuration Options (not required for all units)
Additional Options
Hinged Filter Door & Toolless Access Cabinet
BA = Hinged Filter Door & Toolless Access Panels BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
Options
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products 3
343615-YTG-D-0708

FEATURES

All models are available with a wide variety of factory­mounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over­head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon­tal duct, remove the supply and return air panels on the rear of the unit.
All models are available with these “factory mounted” outdoor air damper options:
Single enthalpy economizer
Motorized outdoor air damper Supply air blowers are equipped with a 5 speed direct drive
motor that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo­nents.
®
Simplicity standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
Anti-Short Cycle Protection - To aid compressor
Fan Delays - Fan on and fan off delays are fully pro-
Safety Monitoring - The control board monitors the
Controls - Simplicity® control boards have
allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis­tance. Optionally , the control board can be pro­grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
All units have long lasting powder paint cabinets with 1 000 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA listed.
Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each sec­tion includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni­form distribution of air across the heating elements. Every element is fully protected against excessive tem­perature by thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.
BAS Controls - York’s Sunline™ series units of fer factory mounted BAS controls such as Simplicity
®
INTELLI-Com­fort™, Novar, Honeywell , Johnson, York Commercial Comfort System (YCCS) and CPC.
4 Johnson Controls Unitary Products
Gas/Electric
Knockout for side power entry
economizer
Economizer
hood
Slide-in
Smoke
detector
3/4" PVC female condensate drain
HACR
breaker
GFCI
convenience outlet
Knockout for side control entry
Direct drive
blower
20 Gauge aluminized
steel tubular heat exchanger
Simplicity® Lite™
control board
Electric heat
accessory location
Knockout for side
gas supply entry
Power ventor motor with
post purge cycle
Full perimeter baserails
with forklift slots and
lifting holes
343615-YTG-D-0708
High efficiency
compressor
Copper tube/ aluminum fin
condensing coil
Electric/Electric and Heat Pump
Economizer
hood
Slide-in
economizer
Smoke
detector
3/4" PVC female condensate drain
convenience outlet
Knockout
for side
power entry
GFCI
HACR
breaker
Knockout for side control entry
Direct drive
blower
Simplicity® Lite™
control board
Electric Heat
accessory location
Full perimeter baserails
with forklift slots and
lifting holes
High efficiency
compressor
Copper tube/ aluminum fin
condensing coil
FIGURE 1 - UNIT CUTAWAY
Johnson Controls Unitary Products 5
343615-YTG-D-0708

FACTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa­ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper­ating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes
T echnicoat 10-1 immersion of the complete coil for maximum protection.
ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are pro­vided with limit and automatic reset capability to prevent operation at excessive temperatures.
FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.
TM
processes. Coating is applied by total
using CO2 sensors. It uses an inside CO2 sensor to per­form Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to pro­vide comfortable ventilation air temperature. The pat­ented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy sav­ings by recovering the building from the Unoccupied Set­points to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity
®
INTELLI-Comfort™ balances space temperature, venti­lation air temperature, CO2 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with MOD LINK CON­TROL - The York® Simplicity® INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi­tional control to translate communications from MOD­BUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system con­troller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air prov­ing switch.
CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
BAS - Building Automation System Controls
Simplicity Simplicity
®
INTELLI-Comfort™ CONTROL - The Y ork®
®
INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sen­sor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand
HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
YORK COMMERCIAL COMFORT SYSTEM (YCCS) ­Provides rooftop system integration for YCCS single zone and change-over bypass systems.
SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
ventilation are achieved through the INTELLI-Comfort™
6 Johnson Controls Unitary Products
Factory installed Smoke Detectors in the Return Air, may be subjected to freezing temperatures during "off" times due to Out Side Air infiltration. These Smoke Detectors have an operational limit of 32°F to 131°F. Smoke Detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
STAINLESS STEEL DRAIN PAN - An optional rust- proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environ­ments.
BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connec­tions for applications in cold environments to reduce freezing drain lines.
PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of­phase condition.
DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.
343615-YTG-D-0708
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
ELECTRIC HEATERS wired for single point power sup- ply. These nickel chromium heater elements are pro­vided with limit and automatic reset capability to prevent operation at excessive temperatures.
ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti­tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
LOW NOX KIT - Required to reduce the emission of nitrogen oxides below 40 nano grams per joule.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa­ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
Johnson Controls Unitary Products 7
POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi­tioned space from being over-pressurized during econo­mizer operation.
The power exhaust option can only be used on bot­tom duct configurations.
BAROMETRIC RELIEF DAMPER - This damper acces­sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
343615-YTG-D-0708
ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
CFM
1
SOUND RATING
(Db)

TABLE 1: CAPACITY RATINGS - (ARI 210/240)

MODEL MBH
DY036 DY048
DY060
35.6 12 14 1200 84
46.0 12 14 1600 83
5
59.0 11.6 14 1750 81
EER
2
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
4. Rated in accordance with ARI 270 Standard.
5. Models are 3Ø only.
SEER
3
CO
SENSOR - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the present limits.
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
HAIL GUARD - Hail Guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.
GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.
TABLE 2: GAS HEAT RATINGS
MODEL
4
DY036N04 DY036N08
DY048N06 DY048N10
DY060N08 DY060N10
1. All units are single-stage heating.
MBH
INPUT
50
100
75
125 100
125
1
MBH
OUTPUT
40 80
60
100
80
100
AFUE
(%)
80.9
80.5
80.9
80.3
80.5
80.3
TEMP
RISE ºF
15 - 45 45 - 75
25 - 70 45 - 75
25 - 55 30 - 75
TABLE 3: 2 STAGE GAS HEAT RATINGS
1
MODEL
DY036D06 DY036D10 DY048D06 DY048D10 DY060D06 DY060D10
1. Models are 3 Ø only.
MBH INPUT MBH OUTPUT STEADY STATE EFFICIENCY RISE
ST
1
STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE MIN. MAX.
45 75 35.8 60.8 79.4 81.1 35 70 790 69 115 55.2 92 80.0 80.2 55 90 950 45 75 35.7 60.8 79.4 81.1 25 70 790 75 125 60.4 100.6 80.5 80.5 45 75 1230 45 75 35.8 60.8 79.4 81.1 20 55 1010 75 125 60.4 100.6 80.5 80.5 35 75 1230
MINIMUM HEATING
AIRFLOW (CFM)
8 Johnson Controls Unitary Products
TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
343615-YTG-D-0708
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
630 631 879 885
0.2 0.3 0.2 0.7
1116 928 1979 1020
0.41 0.37 0.76 0.53
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY036 / 3 Ton
Horizontal Ducted Inlet
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
63 80 82 80 82 78 83 81 85 125 767776 77 82838182 250 565956 60 60615860 500 505049 50 54545152
1000 404339 42 49 5044 45 2000 414240 42 49 4943 44 4000 41 41 41 41
49 49 41 41
8000 45 45 45 45 47 47 45 45
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 5: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
630 631 879 885
0.2 0.3 0.2 0.7
1116 928 1979 1020
0.41 0.37 0.76 0.53
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY036 / 3 Ton
Horizontal Ducted Discharge
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Operation
Cooling
(dB)
ID Blower
2
Only (dB)
63 80 84 80 83 85 87 84 87
125 747774 76 80828083 250 586158 61 68686365
500 485147 50 58585354 1000 414539 43 55 5549 50 2000 394137 39 53 5346 47 4000 414138 38 55 5549 49 8000 454544 44 52 5347 47
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
(dB)
Cooling
Operation
(dB)
2
2
Johnson Controls Unitary Products 9
343615-YTG-D-0708
TABLE 6: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
632 632 881 883
0.2 0.3 0.2 0.7
1069 870 1903 917
0.36 0.33 0.71 0.49
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY036 / 3 Ton
Vertical Ducted Inlet
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
63 78 82 78 82 80 85 80 84 125 70 75 70 74 71 80 71 79 250 55 60 55 60 59 61 58 62 500 47 50 47 50 52 53 49 52
1000 4043394350514546 2000 3740373945464143 4000 3637363745464040 8000 4444444445474444
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
(dB)
2
TABLE 7: DY036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
632 632 881 883
0.2 0.3 0.2 0.7
1069 870 1903 917
0.36 0.33 0.71 0.49
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY036 / 3 Ton
Vertical Ducted Discharge
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
63 80 83 80 83 83 86 82 85 125 787977 78 80837982 250 556054 59 63635862 500 485146 50 58595253
1000 414439 43 54 5548 49 2000 374035 38 50 5042 44 4000 383936 37 52 5344 44 8000 444544 44 49 5045 45
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
(dB)
2
10 Johnson Controls Unitary Products
TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
766 769 1077 1087
0.2 0.5 0.4 1.0
1484 993 2270 1406
0.67 0.54
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY048 / 4 Ton
Horizontal Ducted Inlet
1.24 0.90
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
63 74 97 74 95 77 90 77 90 125 70 86 69 86 73 78 72 77 250 53 58 52 57 60 61 58 61 500 49 55 47 54 54 56 51 53
1000 4242383950554545 2000 4044384348514546 4000 3844364148524345 8000 4243424445484445
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
343615-YTG-D-0708
Cooling
Operation
2
(dB)
TABLE 9: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL CONFIGURATION
Indoor Blower Speed (RPM) Blower Static Pressure (IWG) Airflow (CFM) Blower Motor BHP
Octave Center Freq.
ID Blower Only (dB)
Horizontal Ducted Discharge
766 769 1077 1087
0.2 0.5 0.4 1.0
1484 993 2270 1406
0.67 0.54 1.24 0.90
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
DY048 / 4 Ton
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
Cooling
Operation
(dB)
ID Blower
2
Only (dB)
63 77 97 75 95 84 91 82 91 125 72 86 69 85 81 83 78 80 250 60 62 57 59 71 71 66 67 500 53 56 49 54 60 61 55 56
1000 4747424358595252 2000 4546404354555050 4000 4647404257585252 8000 4747454554544849
1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2. Cooling Operation – ID blower, compressor and outdoor fan operating.
3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4. Test duct termination is flush with reverberation room wall.
5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Cooling
Operation
(dB)
2
Johnson Controls Unitary Products 11