Sunline™ 2000 series convertible package rooftop models have two independent refrigerant circuits for efficient
part load operation. Although the units are primarily
designed for curb mounting on a roof, they can also be
slab-mounted at ground level or set on steel beams above
a finished roof.
Technical Guide
SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
D2CE / D2CG 300 CONSTANT VOLUME
25 NOMINAL TONS
8.5 EER
SUNLINE 2000 ™
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factorymounted options and field-installed accessories to make
them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead
rigging.
Every unit is completely piped, wired, charged and tested
at the factory to simplify field installation and to provide
years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt
spray process per ASTM-B117 test standard.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct
connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you
replace the supply and return air panels on the rear of the
unit with a side duct flange accessory.
All models are available with five different outdoor air
damper options:
• Single enthalpy economizer
• Differential (dual) enthalpy economizer
• Single enthalpy economizer with power exhaust
• Differential (dual) enthalpy economizer with
power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly is shipped in the return
air compartment of all units ordered without an economizer
or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10,
15 or 25% outdoor air. With bottom duct connections, the
intake damper assembly should be mounted over the
opening in the return air panel. With horizontal ductwork, it
should be mounted on the return air duct.
FOR DISTRIBUTION USE ONLY - NOT TO BE USEDAT POINT OF RETAIL SALE
036-21359-001-B-0302
All supply air blowers are equipped with a belt drive
that can be adjusted to meet the exact requirements of
the job. A high speed drive accessory is available for
applications with a higher CFM and/or static pressure
requirement.
All compressors include internal pressure relief. Every
refrigerant circuit includes an expansion valve, a liquid
line filter-drier, a discharge line high pressure switch
and a suction line with a freezestat and low pressure/
loss of charge switch. The unit control circuit includes
two 75 VA transformers, two 24-volt circuit breakers
and a relay board with two compressor lockout circuits,
a terminal strip for thermostat wiring, plus an additional
set of pin connectors to simplify the interface of additional field controls.
All 208/230 and 460-volt models are ETL approved. All
208/230 and 575-volt models are CGA approved.
All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized
steel tubular heat exchangers carry an additional 9year warranty.
All gas heat models are built with two heating sections
for two equal stages of capacity control. Each section
includes a durable heat exchanger with aluminized
steel tubes, a redundant gas valve, spark ignition,
power venting, an ignition module for 100% shut-off
and all of the safety controls required to meet the latest
ANSI standards.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
All electric heat models are wired for a single power
source and include a bank of nickel chromium elements mounted at the discharge of the supply air
blower to provide a high velocity and uniform distribution of air across the heating elements. Every element
is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base
pan of the unit or through a knockout in the wiring
panel on the front of the unit.
All internal factory wiring is color coded and numbered
for ease in servicing and troubleshooting.
FACTORY-INSTALLED OPTIONS
ECONOMIZERS
Interlocked outdoor and return air dampers are positioned by a fully modulating, spring return damper actuator capable of introducing up to 100% outdoor air with
nominal 1% leakage type dampers. As the outdoor air
intake dampers open, the return air dampers close.
The changeover from compressor to economizer cooling is determined by one or two solid state enthalpy
controls.
On single enthalpy, an outdoor air sensor determines
when the outdoor air is cool and dry enough to provide
“free” cooling. On differential enthalpy, one sensor
monitors the outdoor air while a second sensor monitors the return air. Whenever the outdoor air is cooler
and drier than the return air, the unit will switch to economizer operation. For either option, the first compressor stage can provide additional cooling during
economizer operation if the room thermostat calls for
second stage.
The dampers and controls are installed and wired at
the factory. Only the accessory rain hood needs to be
assembled and installed in the field.
These economizer options can be used on all duct configurations.
POWER EXHAUST
Both the single and differential economizer options are
available with power exhaust. Whenever the outdoor
air intake dampers are opened for free cooling, the
exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The exhaust fan, motor and controls are installed and
wired at the factory. Only the back-draft damper
assembly needs to be field installed and the accessory
rain hoods need to be assembled and installed in the
field.
The power exhaust option can only be used on bottom
duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Interlocked outdoor and return air dampers are controlled by a 2-position, spring return damper actuator.
The outdoor damper will open to some pre-set position
whenever the supply air blower is operating and will
drive fully closed when the blower shuts down.
The damper and controls are installed and wired at the
factory. Only the accessory rain hood needs to be
assembled in the field.
This damper option can be used on all duct configura-
2Unitary Products Group
tions.
036-21359-001-B-0302
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS
ANTI-RECYCLE TIMERS
Two solid state timers prevent the compressors from
short-cycling. Once a compressor is de-energized, it
will remain de-energized for approximately five min-
Includes a slide-in/plug-in damper assembly with fully
utes.
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
The enthalpy system contains one sensor that
monitors the outdoor air and determines when the air is
HIGH ALTITUDE NATURAL GAS
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet.
PROPANE
cool enough and dry enough to provide “free” cooling.
Burner orifices, pilot orifices and gas valve parts are
The rainhood is painted to match the basic unit and
provided to convert a natural gas furnace to propane.
must be field-assembled before installing.
Power exhaust is not available as a field installed
option.
DUAL INPUT ELECTRONIC ENTHALPY
ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
This enthalpy system contains one sensor that monitors the outdoor air and one sensor that monitors the
return air. The logic module compares these two values and modulates the dampers providing the maximum efficiency of economizer system.
The rainhood is painted to match the basic unit and
must be field-assembled before installing.
Power exhaust is not available asa field installed
option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Includes a slide-in/plug-in damper assembly with a
2-position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower
is operating and will drive fully closed when the blower
unit shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed
option.
ROOF CURBS
Fourteen inch high roof curbs provide a water-tight seal
between the unit and the finished roof. These full
HIGH ALTITUDE PROPANE
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet. This
accessory supplements the basic propane conversion
kit.
SIDE DUCT FLANGES
One inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal
duct connections. These flanges can also be used individually for bottom supply/horizontal return or horizontal supply/bottom return. They cannot be used on units
with power exhaust.
BAROMETRIC RELIEF DAMPER
This damper accessory can be used to relieve internal
air pressure on units with an economizer but no power
exhaust. This accessory includes a rain hood, a bird
screen and a fully assembled damper. With bottom
duct connections, the damper should be mounted over
the opening in the return air panel. With horizontal
ductwork, the accessory should be mounted on the
return air duct.
ECONOMIZER / POWER EXHAUST RAIN HOODS
A rain hood accessory must be used on units with an
economizer, a motorized damper, or a combined economizer with power exhaust option. These accessories
include all the hood panels, the necessary components
and hardware for field assembly.
HIGH SPEED DRIVE
A smaller blower pulley and a shorter belt increase the
speed of the supply air blower for applications with a
higher CFM and/or static pressure requirement.
perimeter curbs meet the requirements of the National
Roofing Contractors Association (NRCA) and are
shipped knocked-down for field assembly. They're
designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger supports.
Unitary Products Group3
LOW AMBIENT CONTROLS TO 0°F
An autotransformer and a thermostat maintain stable
system operation by reducing the speed of the condenser fan motor at low outdoor temperatures. The kit
036-21359-001-B-0302
O
also includes a 1-phase motor to replace the unit's
standard 3-phase condenser fan motor. Standard units
can operate down to 45°F.
COIL GUARD KIT
LO NG LASTING
POW DER PAIN T FINISH
ECONOMIZER HOOD
2" DISPOSA BLE
FILTER S
UTDOOR AIR OPENING
FOR SLIDE-IN /PLUG-IN
INTERNAL ECONOM IZER (OPTION)
SIDE AN D B O TTO M
SUPPLY & RETUR N AIR
D U C T O P E N IN G S ( S ID E X S ID E )
ELEC TR IC H EA TER LOC A TIO N
(O P T IO N A L E L E C T R IC /E L E C T R IC U N IT S )
20 G AU G E ALUM IN IZED STEEL
TUBULAR HEAT EXCHANGERS
NPT
I
1" N P T I
CONDENSATE DRAIN
FULL PER IM ETER 14 G UAG E BASE
R A IL S W IT H L IF T IN G H O L E S
Provides coil guard and fastners.
HIGH EFFICIENCY SCROLL COM PRESSORS
COPPER TUBE/ALUM INUM FIN
BELT-DR IVE
BLOW ER MOTOR
CONDENSER COILS
HOLE FOR BOTTOM
GAS SUPPLY ENTRY
POW ER VENTOR M O TO R
W ITH POST PURGE CYCLE
LOW VO LTAGE RELAY BOAR D
A N D T E R M IA N L S T R IP
ELECTRIC AL D ISCO N NECT
M O U N T IN G L O C A T IO N
(F ie ld in s t a lle d )
KNOCKOUT FOR
S ID E C O N T R O L W IR IN G E N T R Y
KNOCKOUT FOR
S ID E P O W E R W IR IN G E N T R Y S ID E
T E R M IN A L B L O C K
(F or S ingle P oint P ow er Supp ly
w ith E le c tric H e a t)
ELECTRIC/ELECTRIC UNITS
Outside the scope of ARI Standard 340/360.
EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
IPLV - Integrated part load value.
Note: All gas units are two-stage heating. First stage is 50% of total.
All models are 80% Steady State Efficiency (S.S.E.).
Sound Power (db 10-
12
Watts)
@10Ft.
*
30010,000 1.30 1,160 12.5 108 1089891938681769865
*.
At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation,
measuring the indoor ambient sound levels ten feet from the source. The dBA
values provided are for reference only. Calculation of dBA values cover matters
of system design and application. This constitutes an exception to any specifi-
cation or guarantee requiring a dBA value or sound data in any other form than
sound power level ratings.
1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower
Per form ance Ta ble for the KW of the sup ply air blower mo tor.
2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.
- BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM8750 CFM10000 CFM11250 CF
STANDARD DRIVE:
ACCESSORY DRIVE:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
- 25 TON (DCE/DCG300)
- BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM8750 CFM10000 CFM11250 CFM12500 CFM
STANDARD DRIVE:
ACCESSORY DRIVE:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
CEN TRIFU GAL BLOWER (Dia. x Wd. in.)18 x 15
FAN MO TOR HP15
ROWS DEEP4
FINS PER INCH13.5
FACE AREA (Sq. Ft.)25.0
PRO PEL LER DIA. (in.) (Each)30
FAN MO TOR HP (Each)1
NOM. CFM TO TAL (Each)7200
ROWS DEEP3
FINS PER INCH15
FACE AREA (Sq. Ft.)43.3
12.5 TON, SCROLL, HER METIC,
TAN DEM (2 STAGE, 50% ea.)
QUAN TITY PER UNIT (16" X 20" X 2")2
QUAN TITY PER UNIT (16" X 25" X 2")4
QUAN TITY PER UNIT (14" X 20" X 2")3
TO TAL FACE AREA (sq. ft.)21.4
RE FRIG ER ANT
22 (lbs./oz.)
DCE/DCG/DCV
300
SYS TEM NO. 120/8
SYS TEM NO. 220/0
OP ER AT ING WEIGHTS
MODEL SIZE (MBH)300
DCE (Cool ing only)2730
DCV (Cool ing only)2795
Ba sic Unit
DCG (Gas / Elec tric)
DCV (Gas / Elec tric)
Econo mizer160
Econo mizer with
Power Ex haust
Op tions Mo tor ized Damper150
Elec tric Heater
2
(Elec/Elec only)
Roof Curb185
Ba ro met ric Damper45
Ac ces so -
Econo mizer/Mo tor ized Damper
Rain Hood
ries
Econo mizer/Power Ex haust Rain
Hood
Wood Skid220
N2402930
N3202970
N2402995
N3203035
245
18 KW25
36 KW30
54 KW35
72 KW40
55
90
Unitary Products Group7
036-21359-001-B-0302
A
t
BLOWER MO TOR AND DRIVE DATA
1
MODEL
SIZE
25 TON
1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, up stream
of any heat ing de vice.
BLOWER
DRIVE
RANGE
(RPM)
Stan-
975/1165
dard
High
Speed
1140/13651B5V949.79.5 1-7/16 5VX840 84.01
Ac cess
MO TOR
HP FRAME
15 254T91
AD JUST ABLE MO TOR PUL LEYFIXED BLOWER PUL LEY
OUT-
EFF.
(%)
DESIG-
NATION
1LVP58B70
A
SIDE
DIA.
(IN.)
7.5
PITCH
DIA.
(IN.)
6.2-
7.4
BORE
(IN.)
1 5/8
OUT SIDE
DESIG NATION
1B5V11011.311.1 1-7/16 5VX860 86.01
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIG-
NATION
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
QTY.
STATIC RE SIS TANCES*
DESCRIPTION
DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL:0.100.100.100.100.10
ECONOMIZER (RETURN DUCT): 0.060.090.110.140.18
18kW ELECTRIC HEAT:0.310.430.560.710.87
36kW ELECTRIC HEAT:0.380.520.680.871.07
54kW ELECTRIC HEAT:0.620.841.101.391.72
72kW ELECTRIC HEAT:0.680.931.211.541.90
ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
*Fac tory Set ting
Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent pro tec tion.
0.20.30.40.50.6
CFMKWCFMKWCFMKWCFMKWCFMKW
ELEC TRI CAL DATA
ELECTRICAL DATA - Cooling Only Units & Units With Gas Hea
MODEL NO.
D2CE300 208/230-3-6041.431214.21538.6139.5175
& D2CG300460-3-6020.015012.11519.368.380
POWER
SUPPLY
575-3-6016.410812.01515.456.170
STATIC RE SIS TANCE OF RE TURN DUCT WORK, IWG
-
Cool ing Only Units and Units With Gas Heat
COMPRESSORS
(QTY. 2)
RLALRAHPFLAAMPACITYDEVICE (1)
(ea.)(ea.)(ea.)(ea.)(AMPS)(AMPS)
COND. FAN
(#1 & #2)
SUPPLY AIRMINIMUMMAXIMUM
BLOWER MOTOR
HPRLA
CIRCUITOVERCURRENT
VOLT AGE
LIMI TA TIONS**
**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.
POWER SUP PLY
208/230- 3- 60187253
460- 3- 6 0414506
575- 3- 6 0518630
VOLT AGE
MIN.MAX.
8Unitary Products Group
036-21359-001-B-0302
FIELD WIRING - DCE/DCG ELECTRIC/ELECTRIC AND GAS/ELECTRIC UNITS
CONTROL W IRING
C O O L IN G O N L Y (2 4 V O L T T H E R M O S T A T )
THERM OSTAT
TER M IN ALS
1
UNIT TERMINAL
BLO CK 1TB
R
R
Y1
Y2
Y1
Y2
W1
W2
G
G
B
X
A1
1
24 V olt T herm ostat 2TH 04701224.
2
Term inal block 1TB - located on relay board in 24-volt section
of the unit control box.
A2
2
24 V O LT
TRAN SFO R M ER
C O O L IN G / H E A T IN G (2 4 V O L T T H E R M O S T A T )
THERM OSTAT
TER M IN ALS
RH
RC
1
UNIT TERMINAL
BLO CK 1TB
Y1
Y2
W1
ADD
JU M P E R
Y1
W2
G
Y2
W1
W2
3
A1
A2
G
R
B
X
24 V O LT
TRAN SFO R M ER
2
C O O L IN G / H E A T IN G (E L E C T R O N IC T H E R M O S T A T )
ADD
JUM PER
THERM OSTAT
TER M IN ALS
RC
RH
Y1
Y2
W1
W2
G
B
LED 1
LED 2
COM
1
NOT
USED
3
4
4
UNIT TERMINAL
BLO CK 1TB
2
R
Y1
Y2
W1
W2
24 V O LT
G
TRAN SFO R M ER
B
X
A1
A2
A1
A2
T
T
TO R EM OTE SENSO R
2TH 04702224 IF U SE D
1
Electronic program m able Therm ostat 2E T 04700224 (includes subbase).
2
Term inal block 1TB - located on relay board in 24-volt section of the unit control box.
3
Second stage heating is not required on units w ith a single stage electric heater.
4
Term inals A 1 and A 2 provide a relay output to close the outdoor econom izer dam pers
w hen the therm ostat sw itches to the set-back position.
Fan switch m ust be in "O N " position for m inim um ventilation during heater operation.
1
24 V olt T herm ostat 2TH 04701024 or 2TH 04701524
(w ith subbase 2TB 04700224 or 2TB 04700324).
2
Term inal block 1TB - located on relay board in 24-volt section
o f th e u n it c o n tro l b o x .
3
Second stage heating is not required on units w ith a single stage
electric heater.
POW ER W IRING
LINE VOLTAGE
TER M IN AL
BLO CK 2TB
IN U N IT
CONTROL BOX
GROUND LUG
L1
L2
L3
R e fe r to th e
ELECTRICAL
DATA
ta b le s to s iz e th e
power wiring, the
fuses an d th e
disconnect
sw itch.
O
Unitary Products Group9
BLOWER
R
R
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
FRONT
VIEW
UNIT BASE WITH RAILS
Shown separate ly to illustrate
Bottom Duct openings and Power
Connection locations
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
ACCESS
125-1/4" (15 TON)
136-1/4" (20 TON)
ELECTRIC HEAT
ACCESS
CONTROL BOX
ACCESS
24-1/4" (15 TON)
36-1/4" (20 TON)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
35"
33"
21"
5"
9-3/4"
5-7/8"
RETURN
AIR
2-3/4" 21-1/2"
12-1/2"
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
92"
11-1/2"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
SUPPLY
AIR
8-1/8"
9-1/4"
9-3/4"
COMPRESSOR
ACCESS
(See detail "X")
OPTIONAL COIL
GUARD KIT
48-5/8" (15TON)
52-5/8" (20TON)
CONDENSER
COILS
(A)
CONTROL WIRING
ENTRY
(B)
POWER WIRING
ENTRY
3-3/4"
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
036-21359-001-B-0302
All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.
UTILITIES ENTRY DATA
HOLE
11" pip ing MPT re quired
2 Open ing in the bot tom of the unit can be lo cated by the slice
in the in su la tion.
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
OUTDOOR AIR
(Economizer)
OPEN ING
SIZE
(DIA.)
1-1/8" KOCon trol
A
3/4" NPS (Fem.)Bot tom
3-5/8" KO
B
3" NPS (Fem.)Bot tom
USED FOR
Wir ing
Power
Wir ing
Front
Front
C2-3/8" KOGas Pip ing (Front)
D1-11/16" Hole
Gas Pip ing (Bot -
1,2
tom)
1
BLOWER
ACCESS
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
GAS HEAT
ACCESS
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET
HOOD
(C)
GAS SUPPLY
ENTRY
FRONT
VIEW
UNIT BASE WITH RAILS
Shown separately to illu s t ra te
Bottom Duct openings, Power
and Gas Piping Connection
locations
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
136-1/4
CONTROL BOX
ACCESS
(D)
GAS SUPPLY
ENTRY
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
6-3/8"
35"
35-1/4
11-1/8"
46-5/8"
7-1/8"
5-7/8"
RETURN
33"
2-3/4" 21-1/2"
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
21"
5"
9-3/4"
46-5/8"
BOTTOM SUPPLY
AIR
SUPPLY
AIR
9-1/4"
12-1/2"
92"
11-1/2"
AND RETURN
AIR OPENINGS
(See Note)
8-1/8"
9-3/4"
COMPRESSOR
ACCESS
(See detail "X")
OPTIONAL
COIL GUARD
KIT
52-5/8
CONDENSER
COILS
(A)
CONTROL WIRING
ENTRY
(B)
POWER WIRING
ENTRY
3-3/4"
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
CLEARANCES
Front36"
Back
Left Side (Fil ter Ac cess)
Right Side (Cond. Coil)36"
Be low Unit
Above Unit
1U nits (ap pli ca ble in U.S.A. only) may be in stalled on com bus ti ble floors
made from wood or class A, B or C roof cov er ing ma te rial.
2
Units must be in stalled ou doors. Over hang ing struc tures or shrubs should
not ob struct con denser air dis charge out let.
NOTE:
ELEC/ELEC Mod els
RETURN AIR
com bus ti ble ma te ri als when equipped with elec tric heat ers.
SUPPLY AIR
GAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any
com bus ti ble ma te rial and the sup ply air duct work for a dis tance of 3 feet
OUTDOOR AI
from the unit.
OUTDOOR AI
The prod ucts of com bus tion must not be al lowed to ac cu mu late within a
(Economizer)
con fined space and re cir cu late.
Lo cate unit so that the vent air out let hood is at least:
? Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (ex -
clud ing those in te gral to the unit).
? Four (4) feet be low, 4 hori zon tal feet from, or 1 foot above any door or grav ity
air in let into the build ing.
1
2
: Units and duct work are ap proved for zero clear ance to
24" (Less Econo mizer)
49" (With Econo mizer)
24" (Less Econo mizer)
36" (With Econo mizer)
20"
72" With 36" Maxi mum
Ho ri zon tal Ov er hang
(For Con denser Air
Dis charge)
10Unitary Products Group
036-21359-001-B-0302
e
GAUGE LINE
ACCESS
COMPRESSOR
ACCESS
SUPPLY AIR
ACCESS
40-3/8"
5-1/2"
CONDENSER
SECTION
RETURN AIR
ACCESS
REAR
VIEW
SUPPLY AIR
CO M PAR TM ENT
SUPPLY
AIR
18-5/8"
5-1/8"
RETURN
AIR
OUTDOOR
AIR
27-3/4"
29-5/8" (15 TON)
39-5/8" (20 TON)
POW ER
RAIN
HOOD
Return Air C om partm ent)
(o n
EXHAU ST
EVAPORATOR
SECTION
DOT PLUG
(For pressur
drop reading)
FILTER
ACCESS
40-1/2"
1" NPT FEMALE
COND. DRAIN
CONNECTION
OUTDOOR AIR
COMPARTMENT
ACCESS
ECONOMIZER
MOTORIZED
DAMPER
RAIN HOO D
(on O utdoor A ir C om partm ent)
DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for
connecting side ducts.
For bottom
duct applications:
1Remove the side panels from the supply and returnair
compartments to gain access to the bottom supply and
return air duct covers.
2Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper c omposition.)
3Replace the side supply and return air compartment
panels.
For side duct applications;
1Replace the s ide panels o n the supply and return air
compartments with the accessory flange kit panels.
2Connect ductwork to the duct flanges on the rear ofthe
unit.
ECONOMIZER
AND
MOTORIZED DAM PER
/
POW ER EXHAUST RAIN HOODS
REAR VIEW
66-1/2"
34-1/4"
36"
2"
UNIT W ITH RAIN HOO DS
5"
D E T A IL " Y "
36-1/4"
16-1/8"
FIX ED
OUTDOOR
HOOD
IN T A K E
(located on
R e tu r n A ir
C om partm ent)
AIR
L H V IE W
1" C O N D EN STA TE
DRAIN
(M ust be trapped)
92"
Unitary Products Group11
036-21359-001-B-0302
B
F
A
FRO N T
D
C
A
B
E
C
4 Point Loads6 Point Loads
DCE
UNIT
TOTALABCD
4 - POINT LOADS (LBS)
3002,890487619646508
DCE
DCE
UNIT
TOTALABCDEF
6 - POINT LOADS (LBS)
3002,890415471528551492433
NOTE: These weights are with economizerand 24kW electric heat.
D
FRO NT
DCG
UNIT
TOTALABCD
4-POINTLOADS(LBS)
3003,130615671962882
DCG
UNIT
TOTALABCDEF
6 - POINT LOADS (LBS)
3003,130418438533658603510
NOTE: These weights are with economizer, high heat and oversized motor.
12Unitary Products Group
036-21359-001-B-0302
3.69"
3.56"
BASE RAIL
Unitary Products Group13
036-21359-001-B-0302
14Unitary Products Group
036-21359-001-B-0302
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged,
(DCG Electric Cooling/Gas Heat, DCE Electric Cooling/
Optional Electric Heat), designed for outdoor mounted
installation. Units shall have minimum EER ratings of
8.5. They shall have built in field convertible duct connections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories.
The units shall be factory wired, piped, charged with R22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded.
Enclosed in each unit shall be a factory test log sheet
consisting of the unit tested pressures, temperatures
and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to
ISO 9001 standards and the cooling performance shall
be rated in accordance with DOE and ARI test procedures. Units shall be ETL & CGA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236M90 conditions.
UNIT CABINET
7.Condensate pan shall be internally sloped and
conform to ASHARE 62-89 self-draining standards.
Condensate connection shall be a minimum of 1"
I.D. female and be a ridged mount connection.
8.Unit shall incorporate a fixed outdoor air damper
with an outdoor air intake opening covered with a
bird screen and a rain hood painted to match the
exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1.Fan shall be a belt drive assembly and include an
adjustable-pitch motor pulley. Job site selected
(B.H.P.) brake horse power shall not exceed the
motors nameplate horse power rating, plus the service factor. Units shall be designed not to operate
above service factor.
2.Fan wheel shall be double-inlet type with forwardcurved blades, dynamically balanced to operate
smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
3.Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
1.Unit cabinet shall be constructed of G90 galva-
OUTDOOR (CONDENSER) FAN ASSEMBLY
nizedsteel,withexteriorsurfacescoatedwitha
non-chalking, powered paint finish, certified at 750
hours salt spray test per ASTM-B117 standards.
1.The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have blades
riveted to corrosion resistant steel spider brackets
2.Indoor blower section shall be insulated with up to
1" thick insulation, coated on the air side. Alumi-
and shall be dynamically balanced for smooth
operation.
num foil faced insulation shall be used in the furnace compartment and be fastened with ridged
fasteners to prevent insulation from entering the air
stream.
2.The 2 outdoor fan motors shall be totally enclosed
with permanently lubricated bearings, internally
protected against overload conditions and staged
independently.
3.Cabinet panels shall be “large” size, easily removable for servicing and maintenance.
REFRIGERANT COMPONENTS
1. Compressors:
4.Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications.
5.Disposable 2" filters shall be furnished and be
accessible through a removable access door,
sealed air tight. Units filter track shall be designed
to accommodate either 1" or 2" filters.
A. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
B. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be externallyisolatedonadedicated,independent
mounting.
6.Fan performance measuring ports shall be provided on the outside of the cabinet to allow accu-
2Coils:
rateairmeasurementsofevaporatorfan
performance without removing panels or creating
air by-pass of the coils.
Unitary Products Group15
A. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
036-21359-001-B-0302
B. Evaporator and Condenser coils s hall be of the
direct expansion, draw-thru, design.
C. Condenser coils shall be protected with factory
installed coil guards
3.Refrigerant Circuit and Refrigerant Safety Components shall include:
A. Balance-port thermostatic expansion valve with
independent circuit feed system.
B. Filter drier/strainer to eliminate any moisture or for-
eign matter.
C. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
D. The refrigeration system shall provide at least 15 °F
of sub-cooling at design conditions.
E. All Models shall have two independent circuits..
4.Unit Controls:
A. Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24 volt transformer side.
resistance and allowing minimum mixed air entering temperature of 25 °F.
3.Burners shall be of the in-shot type, constructed of
aluminum coated steel and contain air mixture
adjustments.
4.All gas piping shall enter the unit cabinet at a single
location through either the side or curb, without any
field modifications.
5.An integrated control board shall provide timed
control of evaporator fan functioning and burner
ignition.
6.Heating section shall be provided with the following
minimum protection:
A. Primaryandauxiliaryhigh-temperaturelimit
switches.
B. Induced draft motor speed sensor.
C. Flame roll out switch (manual reset).
D. Flame proving controls.
7Unit shall have two independent stages of capacity.
B. Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor:
1.Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
3.Freeze-protection thermostat, evaporator coil.
If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall illuminate.
C. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
D. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
GAS HEATING SECTION (DCG MODELS)
1.Shall be designed with induced draft combustion
with post purge logic and energy saving direct
spark ignition, redundant main gas valve. Ventor
wheel shall be constructed of stainless steel for
corrosion resistance.
ELECTRIC HEATING (DCE MODELS)
1.Nickel chromium electric heating elements shall be
provided as required by the application with 1 or 2
stage control, as required, from 13.5 KW to 72 KW
capacity.
2.The heating section shall have a primary limit control(s) and automatic reset to prevent the heating
element system from operating at an excessive
temperature.
3. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing
(where required).
UNIT OPERATING CHARACTERISTICS
1.Unit shall be capable of starting and running at 125
°F outdoor temperature, exceeding maximum load
criteria of ARI Standard 210/240.
2.The compressor, with standard controls, shall be
capable of operation down to 25 °F outdoor temperature. Accessory low ambient kit shall be available for operation to 0 °F.
2.The heat exchanger shall be of the tubular type,
constructed of T1-40 aluminized steel for corrosion
3. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms
up. (Gas heat only)
16Unitary Products Group
036-21359-001-B-0302
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single
factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit
field modifications. Separate side and bottom openings
shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
Compressor- 5 Years
Heat Exchanger - 10 Years
Elect. Heat. Elem.- 5 Years
Parts- 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available
by either/or):
1ELECTRONIC ENTHALPY AUTOMATIC ECON-
OMIZER - Outdoor and return air dampers that are
interlocked and positioned by a fully-modulating,
spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall
not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5
IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper
assembly to take in CFM of outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from compressor to economizer operation shall be provided
by an integral electronic enthalpy control that feeds
input into the basic module. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.
2.DUAL INPUTDIFFERENTIALELECTRONICENTHALPY AUTOMATIC ECONOMIZER -Outdoor and return air dampers that are interlocked
and positioned by a fully-modulating, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unit
mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the minimum ventilation requirement of the conditioned
space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from compressor to economizer operation shall be provided
by two integral electronic enthalpy controls - one
that senses outdoor air and one that senses indoor
air. Both enthalpy sensors supply input to the logic
module which modulates both sets of dampers for
maximum economizer savings. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.
3MOTORIZED OUTDOOR AIR DAMPERS -Out-
door and return air dampers that are interlocked
and positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unitmounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during
normal operation. Whenever the indoor fan motor
is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor
air enthalpy. Dampers return to the fully closed
position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
1.
ROOF CURB - 14" high, full perimeter curb with
wood nailer (shipped knocked-down).
2.
BAROMETRIC RELIEF DAMPER -Containsarain
hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure
through the unit during economizer operation.
3.
PROPANE CONVERSION KIT - Contains new ori-
fices and gas valve parts to convert from natural to
L.P. gas. One per unit required.
4.
HIGH ALTITUDE - NATURAL GAS -Containsorifices
required for applications between 2000 and 6000
feet altitude.
Unitary Products Group17
036-21359-001-B-0302
5.HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000
feet altitude. Must be used with propane conversion kit.
6.
BURGLAR BARS -Designedtoworkwithabove
roofcurbs, depending on unit model. Fits duct
openings of curb supply and return air openings.
7.
SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on
units with power exhaust.
8.
HIGH SPEED DRIVE - Includes blower pulley and
belt for higher CFM and/or static pressure requirements.