York D2CE, D2CG User Manual

®
DESCRIPTION
Sunline™ 2000 series convertible package rooftop mod­els have two independent refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
Technical Guide
SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS
D2CE / D2CG 300 CONSTANT VOLUME 25 NOMINAL TONS
8.5 EER
SUNLINE 2000 ™
Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory­mounted options and field-installed accessories to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the factory to simplify field installation and to provide years of dependable operation. Powder paint cabinets pro­vide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.
All models (including those with an economizer) are suit­able for either bottom or horizontal duct connections. Mod­els with power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
All models are available with five different outdoor air damper options:
• Single enthalpy economizer
• Differential (dual) enthalpy economizer
• Single enthalpy economizer with power exhaust
• Differential (dual) enthalpy economizer with power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly is shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
FOR DISTRIBUTION USE ONLY - NOT TO BE USEDAT POINT OF RETAIL SALE
036-21359-001-B-0302
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement.
All compressors include internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch. The unit control circuit includes two 75 VA transformers, two 24-volt circuit breakers and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of addi­tional field controls.
All 208/230 and 460-volt models are ETL approved. All 208/230 and 575-volt models are CGA approved.
All models include a 1-year limited warranty on the complete unit. Compressors and electric heater ele­ments carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9­year warranty.
All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
All electric heat models are wired for a single power source and include a bank of nickel chromium ele­ments mounted at the discharge of the supply air blower to provide a high velocity and uniform distribu­tion of air across the heating elements. Every element is fully protected against excessive current and temper­ature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
All internal factory wiring is color coded and numbered for ease in servicing and troubleshooting.
FACTORY-INSTALLED OPTIONS
ECONOMIZERS
Interlocked outdoor and return air dampers are posi­tioned by a fully modulating, spring return damper actu­ator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. As the outdoor air intake dampers open, the return air dampers close. The changeover from compressor to economizer cool­ing is determined by one or two solid state enthalpy controls.
On single enthalpy, an outdoor air sensor determines when the outdoor air is cool and dry enough to provide “free” cooling. On differential enthalpy, one sensor monitors the outdoor air while a second sensor moni­tors the return air. Whenever the outdoor air is cooler and drier than the return air, the unit will switch to econ­omizer operation. For either option, the first compres­sor stage can provide additional cooling during economizer operation if the room thermostat calls for second stage.
The dampers and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled and installed in the field.
These economizer options can be used on all duct con­figurations.
POWER EXHAUST
Both the single and differential economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi­tioned space from being over-pressurized during econ­omizer operation.
The exhaust fan, motor and controls are installed and wired at the factory. Only the back-draft damper assembly needs to be field installed and the accessory rain hoods need to be assembled and installed in the field.
The power exhaust option can only be used on bottom duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Interlocked outdoor and return air dampers are con­trolled by a 2-position, spring return damper actuator. The outdoor damper will open to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower shuts down.
The damper and controls are installed and wired at the factory. Only the accessory rain hood needs to be assembled in the field.
This damper option can be used on all duct configura-
2 Unitary Products Group
tions.
036-21359-001-B-0302
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS
ANTI-RECYCLE TIMERS
Two solid state timers prevent the compressors from short-cycling. Once a compressor is de-energized, it will remain de-energized for approximately five min-
Includes a slide-in/plug-in damper assembly with fully
utes.
modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is
HIGH ALTITUDE NATURAL GAS
Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
PROPANE
cool enough and dry enough to provide “free” cooling.
Burner orifices, pilot orifices and gas valve parts are
The rainhood is painted to match the basic unit and
provided to convert a natural gas furnace to propane.
must be field-assembled before installing. Power exhaust is not available as a field installed
option.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully modulating spring-return monitor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
This enthalpy system contains one sensor that moni­tors the outdoor air and one sensor that monitors the return air. The logic module compares these two val­ues and modulates the dampers providing the maxi­mum efficiency of economizer system.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
Power exhaust is not available as a field installed option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Includes a slide-in/plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
Power exhaust is not available as a field installed option.
ROOF CURBS
Fourteen inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full
HIGH ALTITUDE PROPANE
Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
SIDE DUCT FLANGES
One inch flanges replace the supply and return air pan­els on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used indi­vidually for bottom supply/horizontal return or horizon­tal supply/bottom return. They cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER
This damper accessory can be used to relieve internal air pressure on units with an economizer but no power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
ECONOMIZER / POWER EXHAUST RAIN HOODS
A rain hood accessory must be used on units with an economizer, a motorized damper, or a combined econ­omizer with power exhaust option. These accessories include all the hood panels, the necessary components and hardware for field assembly.
HIGH SPEED DRIVE
A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirement.
perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger sup­ports.
Unitary Products Group 3
LOW AMBIENT CONTROLS TO 0°F
An autotransformer and a thermostat maintain stable system operation by reducing the speed of the con­denser fan motor at low outdoor temperatures. The kit
036-21359-001-B-0302
O
also includes a 1-phase motor to replace the unit's standard 3-phase condenser fan motor. Standard units can operate down to 45°F.
COIL GUARD KIT
LO NG LASTING POW DER PAIN T FINISH
ECONOMIZER HOOD
2" DISPOSA BLE FILTER S
UTDOOR AIR OPENING FOR SLIDE-IN /PLUG-IN INTERNAL ECONOM IZER (OPTION)
SIDE AN D B O TTO M SUPPLY & RETUR N AIR D U C T O P E N IN G S ( S ID E X S ID E )
ELEC TR IC H EA TER LOC A TIO N (O P T IO N A L E L E C T R IC /E L E C T R IC U N IT S )
20 G AU G E ALUM IN IZED STEEL TUBULAR HEAT EXCHANGERS
NPT
I
1" N P T I CONDENSATE DRAIN
FULL PER IM ETER 14 G UAG E BASE R A IL S W IT H L IF T IN G H O L E S
Provides coil guard and fastners.
HIGH EFFICIENCY SCROLL COM PRESSORS
COPPER TUBE/ALUM INUM FIN
BELT-DR IVE BLOW ER MOTOR
CONDENSER COILS
HOLE FOR BOTTOM GAS SUPPLY ENTRY
POW ER VENTOR M O TO R W ITH POST PURGE CYCLE
LOW VO LTAGE RELAY BOAR D A N D T E R M IA N L S T R IP
ELECTRIC AL D ISCO N NECT M O U N T IN G L O C A T IO N (F ie ld in s t a lle d )
KNOCKOUT FOR S ID E C O N T R O L W IR IN G E N T R Y
KNOCKOUT FOR S ID E P O W E R W IR IN G E N T R Y S ID E
T E R M IN A L B L O C K (F or S ingle P oint P ow er Supp ly w ith E le c tric H e a t) ELECTRIC/ELECTRIC UNITS
BOTTOM POW ER & CO NTROL W IRING ENTRY
KNO CKO U TS FOR SIDE GAS SUPPLY ENTRY
CAPACITY RATINGS - (ARI 360)
*
MODEL MBH EER IPLV MODEL MBH EER IPLV
COOLING WITH GAS HEAT COOLING WITH ELECTRIC HEAT
D2CG300N240 290 8.5 8.3 D2CE300E018 290 8.5 8.6 D2CG300N320 290 8.5 8.3 D2CE300E036 290 8.5 8.6 COOLING ONLY D2CE300E054 287 8.5 8.2 D2CE300 290 8.5 8.7 D2CE300E072 284 8.5 8.2
*.
Outside the scope of ARI Standard 340/360. EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). IPLV - Integrated part load value.
NOTE: All cooling is three stage.
GAS HEAT RATINGS
MBH Input MBH Output
MODEL
D2CG300N240 300 150 240 120 D2CG300N320 400 200 320 160
Unit
Size
CFM
)
Stage
1&2
Stage 1
ESP Blower
Stage
1&2
Stage 1
Octave Band Centerline Frequency (Hz) SWL db(A)
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 db(A)
Note: All gas units are two-stage heating. First stage is 50% of total. All models are 80% Steady State Efficiency (S.S.E.).
Sound Power (db 10-
12
Watts)
@10Ft.
*
300 10,000 1.30 1,160 12.5 108 108 98 91 93 86 81 76 98 65
*.
At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for reference only. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specifi-
cation or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
4 Unitary Products Group
036-21359-001-B-0302
COOL ING CA PACI TIES -
Air On
Evapo ra tor
CFM
12,000
11,000
10,000
9,000
8,000
6,000
Coil
WB
?F 72 371 27.1 277 240 203 167 130 - - 354 28.8 268 231 195 158 122 - -
67 340 26.1 335 299 262 226 189 152 116 325 27.7 324 288 251 214 178 141 105 62 329 25.5 329 329 329 293 256 219 183 315 27.1 315 315 315 278 241 205 168 57 329 25.5 329 329 329 292 256 219 183 314 27.1 314 314 314 278 241 205 168 72 365 27.0 260 226 193 159 125 - - 348 28.6 257 223 189 155 122 - ­67 336 25.9 317 283 249 216 182 148 114 321 27.5 312 279 245 211 178 144 110 62 324 25.3 324 324 313 279 245 212 178 309 26.9 309 309 307 273 239 206 172 57 324 25.3 324 324 315 281 247 214 180 309 26.9 309 309 309 275 242 208 174 72 359 26.8 244 213 182 151 120 - - 342 28.5 245 214 184 153 122 - ­67 332 25.7 298 268 237 206 175 144 113 317 27.4 301 270 239 208 177 146 115 62 318 25.2 318 318 296 265 235 204 173 304 26.8 304 304 299 268 237 207 176 57 318 25.1 318 318 301 270 239 208 177 304 26.7 304 304 304 273 242 211 180 72 354 26.6 229 201 173 145 117 - - 338 28.2 228 200 172 144 116 - ­67 326 25.5 280 252 224 196 168 141 113 312 27.1 279 251 223 195 167 139 111 62 314 25.0 314 306 282 254 226 198 170 300 26.5 300 295 280 253 225 197 169 57 314 25.0 314 308 286 258 230 203 175 300 26.5 300 297 285 257 229 201 173 72 349 26.4 215 190 165 140 115 - - 334 28.0 211 186 161 136 111 - ­67 321 25.3 262 237 212 187 162 137 112 307 26.9 257 232 207 182 157 132 107 62 310 24.8 310 293 268 243 218 193 168 297 26.3 297 287 262 237 212 187 162 57 310 24.8 310 297 272 247 222 197 172 297 26.3 297 291 266 241 216 191 166 72 318 25.2 186 167 148 129 110 - - 304 26.8 177 158 138 119 100 - ­67 290 24.0 226 206 187 168 149 130 111 277 25.5 213 194 175 156 137 118 99 62 282 23.7 277 258 240 221 201 192 163 270 25.2 262 243 225 206 187 167 148 57 282 23.7 281 262 243 224 205 186 167 270 25.2 266 247 228 209 190 171 152
To tal
Cap.
MBH
1
Power
In put
KW
2
86 83 80 77 74 71 68 86 83 80 77 74 71 68
25 TON (DCE / DCG300)
Tem pera ture of Air on Con denser Coil
85 ?F95?F
Sen si ble Ca pac ity
En ter ing Dry Bulb, ?F En ter ing Dry Bulb, ?F
1
, MBH
To tal
Cap.
MBH
1
Power
In put
KW
2
Sen si ble Ca pac ity
1
, MBH
Air On
Evapo ra tor
Coil
WB
CFM
105?F 115?F
To tal
Power
1
Cap.
In put
MBH
?F
KW
Sen si ble Ca pac ity
2
En ter ing Dry Bulb, ?F En ter ing Dry Bulb, ?F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
Tem pera ture of Air on Con denser Coil
1
, MBH
To tal
Cap.
MBH
1
Power
In put
KW
2
Sen si ble Ca pac ity
1
, MBH
72 337 30.7 264 228 191 155 118 - - 320 32.6 261 224 188 151 114 - -
12,000
67 310 29.5 309 283 246 210 173 137 100 294 31.3 294 278 242 205 169 132 95 62 300 28.8 300 300 300 263 226 190 153 285 30.5 285 285 285 248 212 175 138 57 299 28.8 299 299 299 263 226 190 153 285 30.5 285 285 285 248 211 175 138 72 331 30.5 254 221 187 153 119 - - 315 32.3 252 218 185 151 117 - -
11,000
67 306 29.3 302 276 242 208 174 141 107 291 31.0 291 273 239 205 171 138 104 62 295 28.5 295 295 294 260 226 192 159 280 30.3 280 280 280 246 213 179 145 57 294 28.5 294 294 294 261 227 193 160 280 30.3 280 280 280 246 213 179 145 72 326 30.2 244 213 183 152 121 - - 310 32.1 243 212 181 151 120 - -
10,000
67 302 29.0 294 268 237 206 176 145 114 287 30.8 287 267 236 205 174 143 112 62 290 28.3 290 290 287 256 226 195 164 276 30.0 276 276 276 245 214 183 152 57 290 28.2 290 290 290 259 228 197 166 275 29.9 275 275 275 244 214 183 152 72 322 30.0 228 200 172 144 116 - - 306 31.8 228 200 172 144 116 - ­67 297 28.8 276 251 223 195 167 139 111 283 30.5 274 251 223 195 167 139 111
9,000
62 286 28.1 286 284 271 243 215 187 159 272 29.8 272 272 262 234 206 178 150 57 286 28.1 286 285 273 245 217 189 161 272 29.7 272 272 261 234 206 178 150 72 319 29.8 212 187 162 137 112 - - 303 31.6 213 188 163 138 113 - ­67 293 28.6 259 234 209 184 159 134 109 278 30.3 260 235 210 185 160 135 110
8,000
62 283 28.0 283 278 255 230 205 180 155 269 29.6 269 269 248 223 198 173 148 57 283 28.0 283 280 257 232 207 182 157 269 29.6 269 269 248 223 198 173 148 72 290 28.3 180 161 141 122 103 - - 276 30.0 183 164 145 125 106 - ­67 264 26.9 224 200 181 162 142 123 104 251 28.5 222 203 194 165 146 127 108
6,000
62 258 26.6 258 241 223 204 184 165 146 245 28.2 245 239 220 201 182 163 144 57 258 26.6 258 242 224 205 186 167 148 245 28.2 245 240 221 202 182 163 144
1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower Per form ance Ta ble for the KW of the sup ply air blower mo tor.
2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.
All Sen si ble Ca pac ityNomi nal Rat ing
Unitary Products Group 5
BLOWER PER FORM ANCE - 25 TON (DCE/DCG300)
M
M
036-21359-001-B-0302
DCE300
BLOWER PULLEY
SPEED TURNS ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT
(rpm) OPEN: (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)
975 6.0* 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2 - - - - - ­1005 5.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6 0.1 10.9 8.9 - - ­1040 4.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0 0.3 11.4 9.4 - - ­1070 3.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3 0.6 11.9 9.8 - - ­1100 2.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7 0.8 12.4 10.2 0.2 14.3 11.7 1135 1.0 2.4 7.7 6.3 2.0 9.3 7.6 1.6 11.1 9.1 1.0 13.0 10.6 0.4 14.9 12.2 1165 0.0 2.6 8.0 6.6 2.2 9.7 8.0 1.8 11.6 9.5 1.3 13.5 11.0 0.7 15.5 12.7
1140 6.0 2.4 7.7 6.3 2.1 9.4 7.7 1.6 11.2 9.2 1.1 13.1 10.7 0.5 15.0 12.3 1180 5.0 2.7 8.2 6.7 2.3 9.9 8.1 1.9 11.8 9.7 1.4 13.7 11.2 0.8 15.8 12.9 1215 4.0 2.9 8.6 7.0 2.6 10.4 8.5 2.2 12.3 10.1 1.7 14.3 11.7 1 .1 16.4 13.5 1255 3.0 3.2 9.1 7.4 2.9 11.0 9.0 2.5 12.9 10.6 2.0 15.0 12.3 1 .4 17.2 14.1 1290 2.0 3.4 9.5 7.8 3.1 11.5 9.4 2.7 13.5 11.1 2.2 15.6 12.8 - - ­1330 1.0 3.7 10.0 8.2 3.4 12.0 9.9 3.0 14.1 11.6 2.6 16.4 13.4 - - ­1365 0.0 3.9 10.5 8.6 3.7 12.6 10.3 3.3 14.7 12.1 2.9 17.0 13.9 - - -
NOTES:
BLOWER PERFORMANCE
DCG300
BLOWER PULLEY
SPEED TURNS ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT ESP OUTPUT INPUT
(rpm) OPEN: (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)
975 6.0* 1.2 5.9 4.9 0.5 7.3 6.0 - - - - - - - - ­1005 5.0 1.4 6.2 5.1 0.7 7.7 6.3 - - - - - - - - ­1040 4.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0 - - - - - ­1070 3.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3 - - - - - ­1100 2.0 2.0 7.3 6.0 1.3 8.9 7.3 0.6 10.6 8.7 - - - - - ­1135 1.0 2.2 7.7 6.3 1.6 9.3 7.6 0.8 11.1 9.1 - - - - - ­1165 0.0 2.4 8.0 6.6 1.8 9.7 8.0 1.0 11.6 9.5 0.2 13.5 11.0 - - -
1140 6.0 2.2 7.7 6.3 1.6 9.4 7.7 0.9 11.2 9.2 - - - - - ­1180 5.0 2.5 8.2 6.7 1.9 9.9 8.1 1.2 11.8 9.7 0.3 13.7 11.2 - - ­1215 4.0 2.7 8.6 7.0 2.1 10.4 8.5 1.4 12.3 10.1 0.6 14.3 11.7 - - ­1255 3.0 3.0 9.1 7.4 2.4 11.0 9.0 1.7 12.9 10.6 0.9 15.0 12.3 - - ­1290 2.0 3.2 9.5 7.8 2.7 11.5 9.4 2.0 13.5 11.1 1.2 15.6 12.8 - - ­1330 1.0 3.5 10.0 8.2 3.0 12.0 9.9 2.3 14.1 11.6 1.5 16.4 13.4 - - ­1365 0.0 3.7 10.5 8.6 3.2 12.6 10.3 2.6 14.7 12.1 1.8 17.0 13.9 - - -
NOTES:
- BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM 8750 CFM 10000 CFM 11250 CF
STANDARD DRIVE:
ACCESSORY DRIVE:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances. ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * FACTORY SETTING
- 25 TON (DCE/DCG300)
- BOT TOM DUCT CON NEC TIONS (COOL ING AP PLI CA TIONS)
7500 CFM 8750 CFM 10000 CFM 11250 CFM 12500 CFM
STANDARD DRIVE:
ACCESSORY DRIVE:
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil. Refer to page 7 for additional static resistances. ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * FACTORY SETTING
12500 CF
6 Unitary Products Group
036-21359-001-B-0302
-
ELEC TRI CAL DATA
MODEL POWER CIRCUIT OVERCURRENT
D2CE SUPPLY AMPACITY DEVICE (1)
300A25 208-3-60 E018 13.5 1 37.5 139.5 175 300A25 208-3-60 E036 27.0 2 75.1 142.1 175 300A25 208-3-60 E054 40.6 2 112.6 189.0 200 300A25 208-3-60 E072 54.1 2 150.1 198.4 225 300A25 230-3-60 E018 18.0 1 43.3 139.5 175 300A25 230-3-60 E036 36.0 2 86.6 156.5 175 300A25 230-3-60 E054 54.0 2 129.9 178.2 200 300A25 230-3-60 E072 72.0 2 173.2 221.5 250 300A46 460-3-60 E018 18.0 1 21.7 68.3 80 300A46 460-3-60 E036 36.0 2 43.3 78.3 80 300A46 460-3-60 E054 54.0 2 65.0 89.1 10 0 300A46 460-3-60 E072 72.0 2 86.6 110.7 125 300A58 575-3-60 E018 18.0 1 17.3 56.1 70 300A58 575-3-60 E036 36.0 2 34.6 62.6 70 300A58 575-3-60 E054 54.0 2 52.0 71.2 80 300A58 575-3-60 E072 72.0 2 69.3 88.5 10 0
1
NOMI NAL VOLT AGE VOLT AGE KW CAP. MUL TI PLIER
ELECTRIC HEATER OPTION
MODEL kW(1) STAGES AMPS
208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92
Units With Elec tric Heat
MINIMUM MAXIMUM
(AMPS) (AMPS)
PHYSI CAL DATA BA SIC UNITS
MOD ELS
EVAPO RA TOR
BLOWER
EVAPO RA TOR
COIL
CON DENSER
FAN
(Two Per Unit)
CON DENSER
COIL
COM PRES SOR
(Qty. Per Unit)
AIR
FIL TERS
CHARGE
CEN TRIFU GAL BLOWER (Dia. x Wd. in.) 18 x 15 FAN MO TOR HP 15 ROWS DEEP 4 FINS PER INCH 13.5 FACE AREA (Sq. Ft.) 25.0 PRO PEL LER DIA. (in.) (Each) 30 FAN MO TOR HP (Each) 1 NOM. CFM TO TAL (Each) 7200 ROWS DEEP 3 FINS PER INCH 15 FACE AREA (Sq. Ft.) 43.3
12.5 TON, SCROLL, HER METIC, TAN DEM (2 STAGE, 50% ea.) QUAN TITY PER UNIT (16" X 20" X 2") 2
QUAN TITY PER UNIT (16" X 25" X 2") 4 QUAN TITY PER UNIT (14" X 20" X 2") 3 TO TAL FACE AREA (sq. ft.) 21.4 RE FRIG ER ANT
22 (lbs./oz.)
DCE/DCG/DCV
300
SYS TEM NO. 1 20/8
SYS TEM NO. 2 20/0
OP ER AT ING WEIGHTS
MODEL SIZE (MBH) 300 DCE (Cool ing only) 2730 DCV (Cool ing only) 2795
Ba sic Unit
DCG (Gas / Elec tric)
DCV (Gas / Elec tric)
Econo mizer 160 Econo mizer with Power Ex haust
Op tions Mo tor ized Damper 150
Elec tric Heater
2
(Elec/Elec only)
Roof Curb 185 Ba ro met ric Damper 45
Ac ces so -
Econo mizer/Mo tor ized Damper Rain Hood
ries
Econo mizer/Power Ex haust Rain Hood
Wood Skid 220
N240 2930 N320 2970 N240 2995 N320 3035
245
18 KW 25 36 KW 30 54 KW 35 72 KW 40
55
90
Unitary Products Group 7
036-21359-001-B-0302
A
t
BLOWER MO TOR AND DRIVE DATA
1
MODEL
SIZE
25 TON
1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, up stream of any heat ing de vice.
BLOWER
DRIVE
RANGE
(RPM)
Stan-
975/1165
dard High
Speed
1140/1365 1B5V94 9.7 9.5 1-7/16 5VX840 84.0 1
Ac cess
MO TOR
HP FRAME
15 254T 91
AD JUST ABLE MO TOR PUL LEY FIXED BLOWER PUL LEY
OUT-
EFF.
(%)
DESIG-
NATION
1LVP58B70
A
SIDE
DIA. (IN.)
7.5
PITCH
DIA. (IN.)
6.2-
7.4
BORE
(IN.)
1 5/8
OUT SIDE
DESIG­ NATION
1B5V110 11.3 11.1 1-7/16 5VX860 86.0 1
DIA. (IN.)
PITCH
DIA. (IN.)
BORE
(IN.)
DESIG-
NATION
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
QTY.
STATIC RE SIS TANCES*
DESCRIPTION
DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL: 0.10 0.10 0.10 0.10 0.10 ECONOMIZER (RETURN DUCT): 0.06 0.09 0.11 0.14 0.18 18kW ELECTRIC HEAT: 0.31 0.43 0.56 0.71 0.87 36kW ELECTRIC HEAT: 0.38 0.52 0.68 0.87 1.07 54kW ELECTRIC HEAT: 0.62 0.84 1.10 1.39 1.72 72kW ELECTRIC HEAT: 0.68 0.93 1.21 1.54 1.90
ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
HORIZONTAL (SIDE) SUPPLY DUCT: 0.31 0.26 0.27 0.31 0.41 HORIZONTAL (SIDE) RETURN DUCT: 0.05 0.05 0.05 0.05 0.05
7500 8750 10000 11250 12500
ESP ESP ESP ESP ESP
(IWG) (IWG) (IWG) (IWG) (IWG)
IRFLOW (CFM)
POWER EX HAUST PER FORM ANCE
MO TOR
SPEED
HIGH* 5250 0.83 4500 0.85 4200 0.88 3750 0.93 3000 0.99
ME DIUM 4900 0.77 3900 0.79 3500 0.82 2900 0.85 - -
LOW 4400 0.72 3700 0.74 3000 0.78 - - - -
*Fac tory Set ting Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent pro tec tion.
0.2 0.3 0.4 0.5 0.6
CFM KW CFM KW CFM KW CFM KW CFM KW
ELEC TRI CAL DATA
ELECTRICAL DATA - Cooling Only Units & Units With Gas Hea
MODEL NO.
D2CE300 208/230-3-60 41.4 312 1 4.2 15 38.6 139.5 175
& D2CG300 460-3-60 20.0 150 1 2.1 15 19.3 68.3 80
POWER
SUPPLY
575-3-60 16.4 108 1 2.0 15 15.4 56.1 70
STATIC RE SIS TANCE OF RE TURN DUCT WORK, IWG
-
Cool ing Only Units and Units With Gas Heat
COMPRESSORS
(QTY. 2)
RLA LRA HP FLA AMPACITY DEVICE (1)
(ea.) (ea.) (ea.) (ea.) (AMPS) (AMPS)
COND. FAN
(#1 & #2)
SUPPLY AIR MINIMUM MAXIMUM BLOWER MOTOR
HP RLA
CIRCUIT OVERCURRENT
VOLT AGE
LIMI TA TIONS**
**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.
POWER SUP PLY
208/230- 3- 60 187 253
460- 3- 6 0 414 506
575- 3- 6 0 518 630
VOLT AGE
MIN. MAX.
8 Unitary Products Group
036-21359-001-B-0302
FIELD WIRING - DCE/DCG ELECTRIC/ELECTRIC AND GAS/ELECTRIC UNITS
CONTROL W IRING
C O O L IN G O N L Y (2 4 V O L T T H E R M O S T A T )
THERM OSTAT
TER M IN ALS
1
UNIT TERMINAL
BLO CK 1TB
R
R
Y1
Y2
Y1 Y2
W1
W2
G
G
B X
A1
1
24 V olt T herm ostat 2TH 04701224.
2
Term inal block 1TB - located on relay board in 24-volt section
of the unit control box.
A2
2
24 V O LT TRAN SFO R M ER
C O O L IN G / H E A T IN G (2 4 V O L T T H E R M O S T A T )
THERM OSTAT
TER M IN ALS
RH
RC
1
UNIT TERMINAL
BLO CK 1TB
Y1 Y2
W1
ADD JU M P E R
Y1
W2
G
Y2
W1
W2
3
A1 A2
G
R
B X
24 V O LT TRAN SFO R M ER
2
C O O L IN G / H E A T IN G (E L E C T R O N IC T H E R M O S T A T )
ADD JUM PER
THERM OSTAT
TER M IN ALS
RC RH
Y1
Y2 W1 W2
G B
LED 1
LED 2
COM
1
NOT USED
3
4
4
UNIT TERMINAL
BLO CK 1TB
2
R Y1 Y2
W1 W2
24 V O LT
G
TRAN SFO R M ER
B
X A1 A2
A1 A2
T T
TO R EM OTE SENSO R 2TH 04702224 IF U SE D
1
Electronic program m able Therm ostat 2E T 04700224 (includes subbase).
2
Term inal block 1TB - located on relay board in 24-volt section of the unit control box.
3
Second stage heating is not required on units w ith a single stage electric heater.
4
Term inals A 1 and A 2 provide a relay output to close the outdoor econom izer dam pers
w hen the therm ostat sw itches to the set-back position.
Fan switch m ust be in "O N " position for m inim um ventilation during heater operation.
1
24 V olt T herm ostat 2TH 04701024 or 2TH 04701524
(w ith subbase 2TB 04700224 or 2TB 04700324).
2
Term inal block 1TB - located on relay board in 24-volt section
o f th e u n it c o n tro l b o x .
3
Second stage heating is not required on units w ith a single stage
electric heater.
POW ER W IRING
LINE VOLTAGE TER M IN AL BLO CK 2TB IN U N IT CONTROL BOX
GROUND LUG
L1 L2 L3
R e fe r to th e ELECTRICAL DATA ta b le s to s iz e th e power wiring, the fuses an d th e disconnect sw itch.
O
Unitary Products Group 9
BLOWER
R
R
BLOWER MOTOR ACCESS
BLOWER COMPARTMENT ACCESS (Auxiliary)
DOT PLUG (For pressure Drop Reading)
FRONT VIEW
UNIT BASE WITH RAILS Shown separate ly to illustrate Bottom Duct openings and Power Connection locations
NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for the proper size of the supply and return air duct connections.
ACCESS
125-1/4" (15 TON) 136-1/4" (20 TON)
ELECTRIC HEAT ACCESS
CONTROL BOX ACCESS
24-1/4" (15 TON) 36-1/4" (20 TON)
FIELD-SUPPLIED DISCONNECT SWITCH LOCATION
35"
33"
21"
5"
9-3/4"
5-7/8"
RETURN
AIR
2-3/4" 21-1/2"
12-1/2"
ECONOMIZER / MOTORIZED DAMPER, FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail "Y")
92"
11-1/2"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
SUPPLY
AIR
8-1/8"
9-1/4"
9-3/4"
COMPRESSOR ACCESS (See detail "X")
OPTIONAL COIL GUARD KIT
48-5/8" (15TON) 52-5/8" (20TON)
CONDENSER COILS
(A) CONTROL WIRING ENTRY
(B) POWER WIRING ENTRY
3-3/4"
(B) POWER WIRING ENTRY
(A) CONTROL WIRING ENTRY
036-21359-001-B-0302
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
UTILITIES ENTRY DATA
HOLE
11" pip ing MPT re quired
2 Open ing in the bot tom of the unit can be lo cated by the slice in the in su la tion.
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
OUTDOOR AIR (Economizer)
OPEN ING
SIZE
(DIA.)
1-1/8" KO Con trol
A
3/4" NPS (Fem.) Bot tom
3-5/8" KO
B
3" NPS (Fem.) Bot tom
USED FOR
Wir ing Power
Wir ing
Front
Front
C 2-3/8" KO Gas Pip ing (Front)
D 1-11/16" Hole
Gas Pip ing (Bot -
1,2
tom)
1
BLOWER ACCESS
BLOWER MOTOR ACCESS
BLOWER COMPARTMENT ACCESS (Auxiliary)
DOT PLUG (For pressure Drop Reading)
GAS HEAT ACCESS
VENT AIR OUTLET HOODS
COMBUSTION AIR INLET HOOD
(C) GAS SUPPLY ENTRY
FRONT VIEW
UNIT BASE WITH RAILS Shown separately to illu s t ra te Bottom Duct openings, Power and Gas Piping Connection locations
NOTE: For curb mounted units, refer to the curb hanger dimensions of the curb for the proper size of the supply and return air duct connections.
136-1/4
CONTROL BOX ACCESS
(D) GAS SUPPLY ENTRY
FIELD-SUPPLIED DISCONNECT SWITCH LOCATION
6-3/8"
35"
35-1/4
11-1/8"
46-5/8"
7-1/8"
5-7/8"
RETURN
33"
2-3/4" 21-1/2"
ECONOMIZER / MOTORIZED DAMPER, FIXED OUTDOOR INTAKE AIR AND POWER EXHAUST RAIN HOODS (See detail "Y")
21"
5"
9-3/4"
46-5/8"
BOTTOM SUPPLY
AIR
SUPPLY
AIR
9-1/4"
12-1/2"
92"
11-1/2"
AND RETURN
AIR OPENINGS
(See Note)
8-1/8"
9-3/4"
COMPRESSOR ACCESS (See detail "X")
OPTIONAL COIL GUARD KIT
52-5/8
CONDENSER COILS
(A) CONTROL WIRING ENTRY
(B) POWER WIRING ENTRY
3-3/4"
(B) POWER WIRING ENTRY
(A) CONTROL WIRING ENTRY
CLEARANCES
Front 36"
Back
Left Side (Fil ter Ac cess)
Right Side (Cond. Coil) 36" Be low Unit
Above Unit
1U nits (ap pli ca ble in U.S.A. only) may be in stalled on com bus ti ble floors made from wood or class A, B or C roof cov er ing ma te rial.
2
Units must be in stalled ou doors. Over hang ing struc tures or shrubs should
not ob struct con denser air dis charge out let.
NOTE: ELEC/ELEC Mod els
RETURN AIR
com bus ti ble ma te ri als when equipped with elec tric heat ers.
SUPPLY AIR
GAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any com bus ti ble ma te rial and the sup ply air duct work for a dis tance of 3 feet
OUTDOOR AI
from the unit.
OUTDOOR AI
The prod ucts of com bus tion must not be al lowed to ac cu mu late within a
(Economizer)
con fined space and re cir cu late.
Lo cate unit so that the vent air out let hood is at least: ? Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (ex -
clud ing those in te gral to the unit).
? Four (4) feet be low, 4 hori zon tal feet from, or 1 foot above any door or grav ity
air in let into the build ing.
1
2
: Units and duct work are ap proved for zero clear ance to
24" (Less Econo mizer) 49" (With Econo mizer)
24" (Less Econo mizer) 36" (With Econo mizer)
20" 72" With 36" Maxi mum
Ho ri zon tal Ov er hang (For Con denser Air Dis charge)
10 Unitary Products Group
036-21359-001-B-0302
e
GAUGE LINE ACCESS
COMPRESSOR ACCESS
SUPPLY AIR ACCESS
40-3/8"
5-1/2"
CONDENSER SECTION
RETURN AIR ACCESS
REAR VIEW
SUPPLY AIR CO M PAR TM ENT
SUPPLY AIR
18-5/8"
5-1/8"
RETURN AIR
OUTDOOR AIR
27-3/4"
29-5/8" (15 TON) 39-5/8" (20 TON)
POW ER RAIN
HOOD
Return Air C om partm ent)
(o n
EXHAU ST
EVAPORATOR SECTION
DOT PLUG (For pressur drop reading)
FILTER ACCESS
40-1/2"
1" NPT FEMALE COND. DRAIN CONNECTION
OUTDOOR AIR COMPARTMENT ACCESS
ECONOMIZER MOTORIZED DAMPER RAIN HOO D (on O utdoor A ir C om partm ent)
DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom
duct applications:
1 Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and return air duct covers.
2 Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper c omposition.)
3 Replace the side supply and return air compartment
panels.
For side duct applications; 1 Replace the s ide panels o n the supply and return air
compartments with the accessory flange kit panels.
2 Connect ductwork to the duct flanges on the rear of the
unit.
ECONOMIZER AND
MOTORIZED DAM PER
/
POW ER EXHAUST RAIN HOODS
REAR VIEW
66-1/2"
34-1/4"
36"
2"
UNIT W ITH RAIN HOO DS
5"
D E T A IL " Y "
36-1/4"
16-1/8"
FIX ED OUTDOOR
HOOD
IN T A K E (located on R e tu r n A ir C om partm ent)
AIR
L H V IE W
1" C O N D EN STA TE DRAIN (M ust be trapped)
92"
Unitary Products Group 11
036-21359-001-B-0302
B
F
A
FRO N T
D
C
A
B
E
C
4 Point Loads 6 Point Loads
DCE
UNIT
TOTAL A B C D
4 - POINT LOADS (LBS)
300 2,890 487 619 646 508
DCE
DCE
UNIT
TOTAL A B C D E F
6 - POINT LOADS (LBS)
300 2,890 415 471 528 551 492 433
NOTE: These weights are with economizerand 24kW electric heat.
D
FRO NT
DCG UNIT
TOTAL A B C D
4-POINTLOADS(LBS)
300 3,130 615 671 962 882
DCG UNIT
TOTAL A B C D E F
6 - POINT LOADS (LBS)
300 3,130 418 438 533 658 603 510
NOTE: These weights are with economizer, high heat and oversized motor.
12 Unitary Products Group
036-21359-001-B-0302
3.69"
3.56"
BASE RAIL
Unitary Products Group 13
036-21359-001-B-0302
14 Unitary Products Group
036-21359-001-B-0302
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged, (DCG Electric Cooling/Gas Heat, DCE Electric Cooling/ Optional Electric Heat), designed for outdoor mounted installation. Units shall have minimum EER ratings of
8.5. They shall have built in field convertible duct con­nections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories.
The units shall be factory wired, piped, charged with R­22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. Enclosed in each unit shall be a factory test log sheet consisting of the unit tested pressures, temperatures and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test proce­dures. Units shall be ETL & CGA listed, classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236­M90 conditions.
UNIT CABINET
7. Condensate pan shall be internally sloped and conform to ASHARE 62-89 self-draining standards. Condensate connection shall be a minimum of 1" I.D. female and be a ridged mount connection.
8. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1. Fan shall be a belt drive assembly and include an adjustable-pitch motor pulley. Job site selected (B.H.P.) brake horse power shall not exceed the motors nameplate horse power rating, plus the ser­vice factor. Units shall be designed not to operate above service factor.
2. Fan wheel shall be double-inlet type with forward­curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
3. Bearings shall be sealed and permanently lubri­cated for longer life and no maintenance.
1. Unit cabinet shall be constructed of G90 galva-
OUTDOOR (CONDENSER) FAN ASSEMBLY
nizedsteel,withexteriorsurfacescoatedwitha non-chalking, powered paint finish, certified at 750 hours salt spray test per ASTM-B117 standards.
1. The outdoor fans shall be of the direct-driven pro­peller type, discharge air vertically, have blades riveted to corrosion resistant steel spider brackets
2. Indoor blower section shall be insulated with up to 1" thick insulation, coated on the air side. Alumi-
and shall be dynamically balanced for smooth operation.
num foil faced insulation shall be used in the fur­nace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream.
2. The 2 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
3. Cabinet panels shall be “large” size, easily remov­able for servicing and maintenance.
REFRIGERANT COMPONENTS
1. Compressors:
4. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rig­ging and proper sealing on roof curb applications.
5. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed air tight. Units filter track shall be designed to accommodate either 1" or 2" filters.
A. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
B. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter­nally isolated on a dedicated, independent mounting.
6. Fan performance measuring ports shall be pro­vided on the outside of the cabinet to allow accu-
2Coils:
rate air measurements of evaporator fan performance without removing panels or creating air by-pass of the coils.
Unitary Products Group 15
A. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless internally-enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
036-21359-001-B-0302
B. Evaporator and Condenser coils s hall be of the
direct expansion, draw-thru, design.
C. Condenser coils shall be protected with factory
installed coil guards
3. Refrigerant Circuit and Refrigerant Safety Compo­nents shall include:
A. Balance-port thermostatic expansion valve with
independent circuit feed system.
B. Filter drier/strainer to eliminate any moisture or for-
eign matter.
C. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
D. The refrigeration system shall provide at least 15 °F
of sub-cooling at design conditions.
E. All Models shall have two independent circuits..
4. Unit Controls:
A. Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit breaker on the 24 volt transformer side.
resistance and allowing minimum mixed air enter­ing temperature of 25 °F.
3. Burners shall be of the in-shot type, constructed of aluminum coated steel and contain air mixture adjustments.
4. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications.
5. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition.
6. Heating section shall be provided with the following minimum protection:
A. Primary and auxiliary high-temperature limit
switches. B. Induced draft motor speed sensor. C. Flame roll out switch (manual reset). D. Flame proving controls.
7 Unit shall have two independent stages of capacity.
B. Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor:
1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
3. Freeze-protection thermostat, evaporator coil. If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall illuminate.
C. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
D. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy hook-up.
GAS HEATING SECTION (DCG MODELS)
1. Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redundant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance.
ELECTRIC HEATING (DCE MODELS)
1. Nickel chromium electric heating elements shall be provided as required by the application with 1 or 2 stage control, as required, from 13.5 KW to 72 KW capacity.
2. The heating section shall have a primary limit con­trol(s) and automatic reset to prevent the heating element system from operating at an excessive temperature.
3. Units with Electric Heating shall be wired for a sin­gle point power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
1. Unit shall be capable of starting and running at 125 °F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240.
2. The compressor, with standard controls, shall be capable of operation down to 25 °F outdoor tem­perature. Accessory low ambient kit shall be avail­able for operation to 0 °F.
2. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion
3. Unit shall be provided with fan time delay to pre­vent cold air delivery before heat exchanger warms up. (Gas heat only)
16 Unitary Products Group
036-21359-001-B-0302
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bot­tom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
Compressor- 5 Years Heat Exchanger - 10 Years Elect. Heat. Elem.- 5 Years Parts- 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by either/or):
1 ELECTRONIC ENTHALPY AUTOMATIC ECON-
OMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leak­age rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be pro­vided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from com­pressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/ filters shall be provided. Simultaneous economizer/ compressor operation is also possible. Dampers shall fully close on power loss.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER -Out­door and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the mini­mum ventilation requirement of the conditioned
space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from com­pressor to economizer operation shall be provided by two integral electronic enthalpy controls - one that senses outdoor air and one that senses indoor air. Both enthalpy sensors supply input to the logic module which modulates both sets of dampers for maximum economizer savings. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/ filters shall be provided. Simultaneous economizer/ compressor operation is also possible. Dampers shall fully close on power loss.
3 MOTORIZED OUTDOOR AIR DAMPERS -Out-
door and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit­mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the venti­lation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-ener­gized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL­ABLE
1.
ROOF CURB - 14" high, full perimeter curb with
wood nailer (shipped knocked-down).
2.
BAROMETRIC RELIEF DAMPER -Containsarain
hood, air inlet screen, exhaust damper and mount­ing hardware. Used to relieve internal air pressure through the unit during economizer operation.
3.
PROPANE CONVERSION KIT - Contains new ori-
fices and gas valve parts to convert from natural to L.P. gas. One per unit required.
4.
HIGH ALTITUDE - NATURAL GAS -Containsorifices
required for applications between 2000 and 6000 feet altitude.
Unitary Products Group 17
036-21359-001-B-0302
5. HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conver­sion kit.
6.
BURGLAR BARS -Designedtoworkwithabove
roofcurbs, depending on unit model. Fits duct openings of curb supply and return air openings.
7.
SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on units with power exhaust.
8.
HIGH SPEED DRIVE - Includes blower pulley and
belt for higher CFM and/or static pressure require­ments.
9.
WOOD SKID - Allows unit to be handled with 90"
forks.
10.
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD (DCE/CG300 only)
- Contains all hood panels and
the hardware for assembling.
12.
ANTI-RECYCLE TIMER - Assures 5-minute off-time
between compressor cycles.
13.
LOW AMBIENT KIT - Provides unit cooling opera-
tion down to 0°F.
OTHER FACTORY INSTALLED OPTIONS
1 POWER EXHAUST OPTION - To work in conjunc-
tion with economizers.
2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
4. DUAL INPUT ELECTRONIC ENTHALPY ECON­OMIZER
THERMOSTATS - Multiple models available from
11. A.C.O., M.C.O., Electronic or Electrical Mechanical versions.
18 Unitary Products Group
036-21359-001-B-0302
Unitary Products Group 19
036-21359-001-B-0302
20 Unitary Products Group
036-21359-001-B-0302
Unitary Products Group 21
036-21359-001-B-0302
22 Unitary Products Group
036-21359-001-B-0302
Unitary Products Group 23
Subject to change without notice. Printed in U.S.A. CD: 6-21359 036-21359-001-B-0302 Copyright © by Unitary Products Group 2002. All rights reserved. Supersedes: 036-21359-001-A-0302
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...