York D1EE036, D1EG User Manual

®
036-21411-002-A-0204
TECHNICAL GUIDE
SUNLINE PLUS™
AIR-COOLED
AIR CONDITIONERS
D1EG/D1EE036, 048, & 060
3, 4, AND 5 NOMINAL TONS
FLEXIBLE EASY TO INSTALL SINGLE PACKAGE UNITS.
GENERAL
YORK Model DEE/DEG units are single package air condi­tioners designed for outdoor installation on a rooftop or a slab. These units can be equipped with field installed elec­tric heaters for cooling/heating applications or factory installed gas heat. The units are completely assembled on rigid, permanently attached base rails. All piping, refriger­ant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct con­nections at the point of installation.
FEATURING
COMMON FOOTPRINT / COMMON CABINET
HIGH EFFICIENCY
CONVERTIBLE AIRFLOW DESIGN
OPTIONAL MOTORIZED AIR DAMPER
OPTIONAL MANUAL OUTDOOR DAMPER
FLEXIBLE INDOOR AIRFLOWS
FULL PERIMETER BASE RAILS
INSTALLER FRIENDLY CONTROL CIRCUIT
EASY UTILITY CONNECTIONS
1” OR 2” FILTERS WITH NO MODIFICATIONS
•DIRECT DRIVE
OPTIONAL BELT DRIVE
1 YEAR LIMITED WARRANTY
COMPRESSORS 5 YEAR WARRANTY
10 YEAR LIMITED WARRANTY ON GAS-FIRED HEAT EXCHANGERS
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TABLE OF CONTENTS
036-21411-002-A-0204
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 4
FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4
MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 30
LIST OF FIGURES
Fig. Pg.
1 SUNLINE PLUS COMPONENT LOCATION. . . . . . . . . . 5
2 POWER SUPPLY, POWER WIRING THREE PHASE 22
3 CONTROL WIRING - COOLING ONLY . . . . . . . . . . . . 22
4 CONTROL WIRING- COOLING & HEATING
MULTI-STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5 POWER SUPPLY, POWER WIRING SINGLE
PHASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 CONTROL WIRING - COOLING/HEATING
(24 VOLT THERMOSTAT) . . . . . . . . . . . . . . . . . . . . . . 22
7 CONTROL WIRING - COOLING/HEATING
(ELECTRONIC THERMOSTAT). . . . . . . . . . . . . . . . . . 23
8 UNIT DIMENSIONS WITH ECONOMIZER
RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9 UNIT DIMENSIONS DEE 3, 4, & 5 TON. . . . . . . . . . . . 24
10 ACCESS PANELS AND DISCONNECT . . . . . . . . . . . . 24
11 UNIT DIMENSIONS DEG 3, 4, & 5 TON . . . . . . . . . . . 25
12 DEE/DEG DIMENSIONS REAR VIEW -
3, 4, & 5 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
13 DETAIL B UNIT DIMENSIONS WITH DAMPER/
RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
14 UNIT & CURB APPLICATION. . . . . . . . . . . . . . . . . . . . 27
15 ROOF CURB DIMENSIONS DEE & DEG
3, 4, & 5 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
16 CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . . . . . . .28
17 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 29
18 TYPICAL ROOF TOP INSTALLATION. . . . . . . . . . . . . 29
LIST OF TABLES
3 SOUND POWER RATINGS . . . . . . . . . . . . . . . . . . . . . . 7
4 PHYSICAL DATA - BASIC UNIT . . . . . . . . . . . . . . . . . . 8
5 COOLING CAPACITIES - 3 TON (DEE / DEG036) . . . . 9
6 COOLING CAPACITIES - 4 TON (DEE / DEG048) . . . 10
7 COOLING CAPACITIES - 5 TON (DEE / DEG060) . . . 11
8 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG036 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 12
9 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG048 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 13
10 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG060 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 14
11 SUPPLY AIR BLOWER PERFORMANCE - DEE/
DEG036-060 W/ DIRECT DRIVE . . . . . . . . . . . . . . . . . 15
12 STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . . . . . . 15
13 MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER 16
14 BASIC UNIT W/ DIRECT-DRIVE ELECTRICAL DATA 16
15 BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA . . 17
16 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE036. . . . . . . . . . . . . . . . . . . . . 18
17 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE048. . . . . . . . . . . . . . . . . . . . . 19
18 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 19
19 FUSE BLOCK ACCESSORY . . . . . . . . . . . . . . . . . . . . 19
20 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE060. . . . . . . . . . . . . . . . . . . . . 20
21 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ BELT DRIVE DEE036 & 048. . . . . . . . . . . . . . . . . . 21
22 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ BELT DRIVE DEE060 . . . . . . . . . . . . . . . . . . . . . . . 22
23 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 25
24 DEE/DEG UNIT CLEARANCES. . . . . . . . . . . . . . . . . . 26
25 ACCESSORY’S WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 29
26 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Tbl. Pg.
1 CAPACITY RATINGS - COOLING / ELECTRIC
HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2 CAPACITY RATINGS - COOLING / GAS HEATING . . . 7
2 Unitary Products Group
036-21411-002-A-0204

DESCRIPTION

YORK Sunline Plus™ units are high efficiency, convertible, single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units are self--contained and assembled on rigid full perimeter base rails with fork lift slots on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to provide for a quick and easy field installation.
The units are available in cooling only, and cooling with gas heat. Electric heaters are available as field--installed acces­sories.
Both bottom and side duct connections are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either bottom and side duct applications with no modifications required.
All models include a 5--year limited warranty on compres­sors, a 10--year limited warranty on gas--fired heat exchang­ers and a 1--year limited warranty on other parts.

FEATURES

Adjustable belt drive blowers are available on all models from the factory for complete airflow flexibility.
FIELD--INSTALLED ACCESSORIES -- Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in, and electrical con­nections are made by modular plugs. Electric heaters mount easily, and knockouts are provided in the internal partitions to connect the elements to the control box single point kit.
The motorized air damper includes a slid--in/plug--in damper assembly with a rainhood and filters. The outdoor air damp­ers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.
The manual outdoor damper provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
The 14" high roof curb is shipped knocked down. An insu­lated deck is not required because the bottom of the unit is insulated.
Low ambient controls are available to provide stable unit operation at outdoor temperatures down to 0 ºF.
Propane, high altitude and low NOx kits are also available to cover all gas heating applications.
COMMON FOOTPRINT/COMMON CABINET -- All model sizes and configurations share a common cabinet and a com­mon roof curb. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined. He can even decide between gas or electric heat after the curb has been set.
HIGH EFFICIENCY -- All units have a high cooling efficiency of at least 11.0 SEER and gas / electric models have an AFUE as high as 80.9%. All efficiencies exceed legislated minimum levels and provide low operating costs.
CONVERTIBLE AIRFLOW DESIGN -- Both the side and bot­tom duct openings are covered when they leave the factory. If a side supply / side return is desired, you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply / bottom return is desired, you simply remove the two knockout panels from the base of the unit and discard them. No panel cutting or swapping is required! Con­vertible airflow design allows maximum field flexibility and minimum inventory.
FACTORY--INSTALLED OPTIONS -- Economizers can be installed at the factory. The economizers are shipped installed and wired. Only the rain hood needs to be field assembled and installed. Field labor dollars can be saved by having the components arrive already installed.
WIDE RANGE OF INDOOR AIRFLOWS -- All models oper­ate over a wide range of design conditions with a 3--speed direct--drive fan motor. Belt--drive blowers are also available on all models.
FULL PERIMETER BASE RAILS -- The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides, and rigging holes are also pro­vided so that an overhead crane can be used to place the units on a roof.
SYSTEM PROTECTION -- Internal overload protection is standard on all compressors. Every unit has a liquid line filter-
-drier, high and low pressure/loss of charge switches and a suction line freezestat to protect all system components. All units will provide cooling at ambient temperatures down to 45 ºF.
UTILITY CONNECTIONS MADE EASY -- Gas and electric utility knockouts are provided in the unit base as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
SIMPLE CONTROL CIRCUIT -- A low voltage printed circuit board contains a compressor lockout indicator light and a low
Unitary Products Group 3
036-21411-002-A-0204
voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external con­trols. Mate--n--lock plug connectors are used where line and low voltage wires pass through internal bulkheads. This allows for easier troubleshooting and component replace­ment. The electrical control box is not located in the compres­sor compartment so the access cover can be removed for troubleshooting without affecting the normal system operat­ing pressures.
AIR FILTERS -- Units are shipped with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications.

FACTORY-INSTALLED OPTIONS

ECONOMIZERS: Units equipped with a factory-installed economizer option have dampers that are positioned by a spring return, fully modulating damper actuator and are capa­ble of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is determined by a single input electronic enthalpy control or by a dual input electronic enthalpy control. Simulta­neous compressor and economizer operation is also possi­ble.
The single enthalpy system contains a sensor that monitors the outdoor air which automatically operates the damper actuator allowing the dampers to open or close.
The dual enthalpy system contains a second sensor that monitors both the temperature and the humidity of the return air in addition to the outdoor air sensor described for a single enthalpy system. The logic module compares the inputs from both sensors and switches to economizer operation when­ever the outdoor air is cooler than the return air for maximum efficiency of the economizer system.
The economizer is completely wired and installed at the fac­tory. Only the outdoor air hood, including its filters, need be assembled and installed in the field.
BELT DRIVE BLOWERS: Adjustable belt-drive blowers pro­viding maximum flexibility to handle many airflow require­ments, are available on all models.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER ­Includes a slide-in / plug-in damper assembly with fully modu­lating spring return motor actuator capable of introducing up to 100% outdoor air, one outdoor air electronic enthalpy sen­sor and a rain hood with filters. The rain hood is painted to match the basic unit and must be field-assembled before installation. Economizer dampers are 2% low leakage type.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER ­Includes the same damper system and rain hood with filters as described for a single enthalpy economizer except this accessory contains two enthalpy sensors. It uses a differen­tial enthalpy control that compares the outdoor air versus the return air. The logic module then optimizes the economizer operation for additional savings over the single input econo­mizer.
MOTORIZED AIR DAMPER - Includes a slid-in/plug-in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.
MANUAL OUTDOOR DAMPER - Provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
ELECTRIC HEATERS - Include nickel chromium elements, a terminal block, fuses (where required by UL), all the neces­sary connectors and hardware. All heaters utilize single point power supply hookup. Capacities from 5 KW through 30 KW heating are available.
FUSE BLOCK KITS - These kits have a fuse box with a fuse block and fuses. They're available for all 460-3-60 volt heat­ers and 208/230-3-60 volt heaters 7 KW and smaller.
OUTDOOR THERMOSTAT - A 24-volt thermostat providing two stages of control for units equipped with electric heat accessories.
ROOF CURB - This 14" high full perimeter roof curb is shipped knocked down for field assembly and contains duct supports that can easily be shifted for the desired unit duct arrangement. No insulated deck is required because the unit underside is insulated.
START ASSIST KIT - Provides increased starting torque for single phase units in areas with low voltage conditions. It con­tains a 12.5 OHM PTCR temperature resistor with a support clip and hardware for mounting.
LOW AMBIENT KIT - A head pressure controller maintains stable system operation by reducing the speed of the con­denser fan motor when the outdoor temperature is between 45 and 0 ºF. Condenser fan motors with ball bearings and heavier windings are also available for these low ambient applications.
ANTI-RECYCLE TIMER - A timer to prevent the unit com­pressor from short cycling. It assures a 5-minute off-time between compressor cycles.
4 Unitary Products Group
036-21411-002-A-0204
PROPANE CONVERSION KIT - Converts a gas-fired heater from natural gas to propane. It contains main burner orifices, a pilot orifice and a regulator spring.
LOW NOx KIT (natural gas furnaces only) - Contains five stainless steel expanded metal sheets for mounting into the heat exchanger tubes to meet the California low nitrous oxide emission requirements.
HIGH ALTITUDE CONVERSION (NATURAL AND PRO­PANE) - Provides orifices for proper furnace operation at alti­tudes up to 6000 feet. For propane applications, the propane conversion kit will also be required.
2 0 G A U G E A L U M I N I Z E D S T E E L T U B U L A R H E A T E X C H A N G E R
s o m e
E C O N O M I Z E R H O O D
O U T D O O R A I R O P E N I N G F O R S L I D E - I N / P L U G I N I N T
E R N A L E C O N O M I Z E R
S I D E R E T U R N A I R D U C T O P E N I N G
L O W V O L T A G E R E L A Y B O A R D A N D T E R M I N A L S T R I P
E L E C T R I C A L M O U N T I N G L O C A T I O N ( F i e l d I n s t a l l e d )
D I S C O N N E C T
D I R E C T D R I V E B L O W E R M O T O R ( B e l t D r i v e O p t i o n a l s o a v a i l a b l e o n m o d e l s )
GAS PIPING - This kit contains 1/2" pipe nipples, fittings and gas cock (including panel access gaskets) required for bot­tom gas supply connection with external shut-off.
OUTDOOR COIL GUARD - Consists of grille-type sections for installation over the outdoor coil to protect it from damage.
WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
L O N G L A S T I N G P O W D E R P A I N T F I N I S H
E L E C T R I C H E A T A C C E S S O R Y L O C A T I O N ( E l e c / E l e c U n i t s )
P O W E R V E N T E R M O T O R W I T H P O S T P U R G E C Y C L E
C O P P E R T U B E A L U M I N U M F I N C O N D E N S E R C O I L
H I G H E F F I C I E N C Y C O M P R E S S O R S
/
B O T T O M R E T U R N A I R D U C T O P E N I N G
3 / 4 " P V C F E M A L E C O N D E N S A T E D R A
K N O C K O U T S F O R S I D E P O W E R A N D C O N T R O L E N T R Y
I N
T E R M I N A L B L O C K ( F o r S i n g l e P o i n t P o w e r S u p p l y o n E l e c / E l e c U

FIGURE 1 - SUNLINE PLUS COMPONENT LOCATION

K N O C K O U T F O R B O T T O M P O W E R E N T R Y
n i t s )
K N O C K O U T F O R B O T T O M G A S S U P P L Y E N T R Y
F U L L P E R I M E T E R B A S E R A I L S W I T H F O R K L I F T S L O T S A N D L I F T I N G H O L E S
K N O C K O U T F O R S I D E G A S S U P P L Y E N T
M O D E L D E G
( G a s H e a t i n g )
R Y
Unitary Products Group 5
036-21411-002-A-0204
TABLE 1: CAPACITY RATINGS - COOLING / ELECTRIC HEATING
ARI RATINGS
MODEL
DEE036 42.5 11.5
DEE048 49.5 11.0
DEE060 58.5 11.0
1.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2.
Heaters are available as accessories - all with single point power supply
3.
Rated in accordance with ARI Standard 270.
4.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
COOLING CAPACITY 80 / 67-95°F SOUND
MBH
SEER
4
divided by the total electric power input in watt-hours during the same period.
5.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
1
5
EER
10.10 86.0
10.0 86.0
10.05 86.0
RATING
(dBels)
NOMINAL ELECTRIC HEAT CAPACITY2 (kW)
3
5, 7, 10, 15 &
5, 7, 10, 15 &
5, 7, 10, 15,
Not ARI required
240V 480V 600V
20
20
20, & 30
7, 10, 15 & 20 10, 15, & 20
7, 10, 15 & 20 10, 15, & 20
7, 10, 15, 10,
& 30

TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING

MODEL
DEG036N040 42.5 11.5 10.1 86 50 40 80.9 81.6 15-45 1/2 DEG036N079 42.5 11.5 DEG048N060 49.5 11.0 DEG048N099 49.5 11.0 DEG060N079 58.5 11.0 DEG060N099 58.5 11.0
1.
Ratings are in accordance with ARI Standard 210.
2.
Sound ratings are in accordance with ARI Standard 270.
3.
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
4.
S.S.E. = Steady State Efficiency (Percent Output).
5.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
COOLING CAPACITY 80 /
MBH
ARI RATINGS
67-95°F
5
SEER
1
SOUND
RATING
6
EER
10.1 86 100 79 80.5 80.8 40-70 1/2
10.0 86 75 59 80.9 81.6 25-55 1/2
10.0 86 125 99 80.3 80.6 45-75 1/2
10.05 86 100 79 80.5 80.8 25-55 1/2
10.05 86 125 99 80.3 80.6 35-65 1/2
(dBels)
INPUT
2
(MBH)
OUTPUT
(MBH)
divided by the total electric power input in watt-hours during the same period.
6.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
GAS HEAT CAPACITY
3
(%) S.S.E.4 (%)
AFUE
TEMP.
RISE
(°F)
GASE LINE SIZE
Not ARI required
10, 15, 20 &
30
(in. O.D.)

TABLE 3: SOUND POWER RATINGS

UNIT SIZE
036 1200 0.60 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
CFM
1.
These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The
ESP BLOWER
IWG SPEED kW 63 125 250 500 1000 2000 4000 8000
1
-12
OCTAVE BAND CENTERLINE FREQUENCY (Hz)
SOUND POWER (dB 10
WATTS )
SWL
dB(A)
dBA
@ 10Ft
2
dBA values provided are to be used fro reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2.
At a distance of 10 feet from the blower.
6 Unitary Products Group
036-21411-002-A-0204

TABLE 4: PHYSICAL DATA - BASIC UNIT

MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FAN
CONDENSER
COIL
AIR FILTERS
SYSTEM CHARGE Refrigerant 22 (Lbs./Oz.) 9/12 9/8 9/8
COMPRESSOR Quantity Per Unit: (Hermetic Type) 1 / Recpt 1 / Recpt 1 / Scroll
1.
Filter racks are adapted for 1” or 2” thick filters.
Centrifugal Blower (Dia. x Wd. in.) Fan Motor HP (Direct - Drive) Fan Motor HP (Belt - Drive)
Rows Deep Fins Per Inch Face Area (Sq. Ft.)
Propeller Dia. (in.) Fan Motor HP Nom. CFM. Total
Rows Deep Fins Per Inch Face Area (Sq. Ft.)
Quantity Per Unit (15” x 20” x 1”)
1
Quantity Per Unit (14” x 25” x 1”) Total Face ARea (Sq. Ft.)
036 048 060
12 x 10
1/2
1.5 3
13
3.6
22 1/2
4,500
2
18
17.1 2
1
6.6
DEE/DEG
12 x 10
4,200
17.1
3/4
1.5
13
4.3 22
1/2
18
6.6
3
2
2 1
12 x 10
1
1.5 3
13
5.1
22
1/2
4,500
2
18
17.1 2
1
6.6
Unitary Products Group 7

TABLE 5: COOLING CAPACITIES - 3 TON (DEE / DEG036)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F
72 55 3.4 35 31 26 22 18 - - 51 3.7 35 30 26 21 17 - -
1500
67 52 3.3 47 42 38 33 29 24 20 48 3.6 45 41 36 32 28 23 19 62 42 3.2 57 42 3.2 72 51 3.3 32 28 24 20 16 - - 49 3.6 32 28 24 20 16 - -
1350
67 49 3.3 42 38 34 30 26 22 18 47 3.5 42 38 34 30 26 22 18 62 39 3.2 57 40 3.2 72 48 3.2 28 24 21 17 14 - - 48 3.6 29 25 22 18 15 - -
1200
67 46 3.3 37343027231916 46 3.5 39 36 32 38 25 21 18 62 36 3.2 57 37 3.2 72 46 3.3 26 23 19 16 13 - - 45 3.6 26 23 20 16 13 - -
1050
67 44 3.3 34 31 28 25 22 18 15 43 3.5 35 32 28 25 22 19 16 62 35 3.2 57 36 3.2 72 45 3.3 24 21 18 15 13 - - 43 3.5 23 20 17 15 12 - -
900
67 42 3.2 31 29 26 23 20 17 15 40 3.5 30 28 25 22 19 16 14 62 34 3.2 57 35 3.1
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
42 42 42 37 33 28 24 39 3.5 39 39 39 34 30 25 21 42 42 42 38 33 29 24 39 3.5 39 39 39 35 30 26 21
39 39 37 33 29 25 21 37 3.5 37 37 37 33 29 25 21 40 40 38 34 30 26 22 38 3.5 38 38 38 34 30 26 22
36 36 33 29 26 22 19 36 3.5 36 36 35 31 28 24 21 37 37 35 31 27 24 20 37 3.4 37 37 37 33 30 26 22
35 34 31 28 24 21 18 34 3.4 34 33 31 28 25 22 19 36 35 32 29 26 23 20 35 3.4 35 34 33 30 27 23 20
34 32 26 26 23 20 18 32 3.4 32 30 28 25 22 19 17 35 33 30 27 25 22 19 33 3.4 33 32 29 26 24 21 18
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
036-21411-002-A-0204
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 47 3.9 33 29 25 20 16 - - 43 4.1 32 28 23 19 14 - -
1500
67 44 3.8 43 39 35 30 26 22 17 40 4.1 40 38 33 29 24 20 16 62 36 3.7 57 36 3.7
36 36 36 31 27 22 18 33 4.0 33 33 33 28 24 19 15 36 36 36 31 27 23 18 33 3.9 33 33 33 28 24 20 15
72 44 3.9 30 26 22 18 14 - - 39 4.1 28 24 20 16 12 - -
1350
67 42 3.8 39 36 32 28 24 20 16 37 4.0 36 33 29 25 21 17 13 62 34 3.7 57 34 3.7
34 34 33 29 25 21 17 30 4.0 30 30 30 26 22 18 14 34 34 34 30 26 22 18 30 3.9 30 30 31 27 23 19 15
72 42 3.8 27 23 20 16 12 - - 36 4.1 24 21 17 14 10 - -
1200
67 40 3.8 36 32 29 25 22 18 14 34 4.0 33 29 25 22 18 15 11 62 32 3.7 57 32 3.7
32 32 31 28 24 20 17 27 3.9 27 27 28 24 20 17 13 32 32 33 29 26 22 19 28 3.9 28 28 29 26 22 18 15
72 40 3.8 24 21 18 15 12 - - 35 4.1 22 19 16 13 10 - -
1050
67 38 3.7 32 29 26 23 19 16 13 33 4.0 30 26 23 20 17 14 11 62 30 3.7 57 31 3.6
30 30 28 25 22 19 16 27 3.9 27 27 26 22 19 16 13 31 31 30 27 24 20 17 27 3.9 27 27 27 24 21 17 14
72 38 3.8 22 19 16 13 11 - - 34 4.0 20 18 15 12 9 - -
900
67 36 3.7 29 26 23 20 17 15 12 32 4.0 27 24 21 18 16 13 10 62 29 3.6 57 30 3.6
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 8 or 11, multiply
29 28 26 23 20 17 15 26 3.9 26 26 24 21 18 15 13 30 29 27 24 21 19 16 26 3.9 26 26 25 22 19 17 14
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Table 8 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING
ALL SENSIBLE CAPACITY
8 Unitary Products Group
036-21411-002-A-0204

TABLE 6: COOLING CAPACITIES - 4 TON (DEE / DEG048)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F 72 64 3.9 45 39 33 27 21 - - 60 4.2 44 38 32 26 20 - -
2000
67 57 3.8 55494337312519 53 4.1 62 54 3.8 57 54 3.8 72 62 3.9 42 36 31 25 20 - - 58 4.2 41 35 30 24 19 - -
1800
67 55 3.8 51 46 40 35 30 24 19 52 4.1 50 44 39 34 28 23 18 62 52 3.8 57 52 3.8 72 59 3.9 38 33 29 24 19 - - 57 4.2 38 33 28 23 18 - -
1600
67 54 3.8 48433833292419 52 4.2 47 42 37 32 28 23 18 62 50 3.7 57 50 3.7 72 58 3.8 35 31 27 23 18 - - 55 4.2 34 30 26 22 17 - -
1400
67 52 3.8 44 39 35 31 27 22 18 49 4.2 42 38 34 30 26 21 17 62 49 3.7 48474339343026 46 4.1 57 49 3.7 72 57 3.8 32 29 25 21 17 - - 53 4.2 31 28 24 20 16 - -
1200
67 50 3.8 40 36 32 29 25 21 17 47 4.2 38 35 31 27 23 20 16 62 48 3.7 47444036332925 45 4.1 57 48 3.7
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
54 54 53 47 41 35 29 50 4.0 50 50 50 44 38 32 26 54 54 54 48 42 36 30 50 4.0 50 50 50 46 40 34 28
52 52 49 44 39 33 28 49 4.1 49 49 47 42 37 31 26 52 52 51 45 40 35 29 49 4.1 49 49 49 44 38 33 27
50 50 46 41 36 32 27 47 4.1 47 47 45 40 35 31 26 50 50 47 42 38 33 28 47 4.1 47 47 46 41 37 32 27
49 48 44 40 36 31 27 46 4.1 46 46 43 38 34 30 26
48 45 41 37 34 30 26 45 4.1 45 43 39 35 32 28 24
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
53 47 41 35 29 23 17
46 45 42 37 33 29 25
45 42 38 34 31 27 23
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 56 4.7 42 36 30 25 19 - - 53 5.2 41 35 29 23 17 - -
2000
67 50 4.6 62 47 4.5 57 47 4.5
50 45 39 33 28 22 16 47 5.1 47 44 38 32 26 20 14 47 47 47 41 35 29 23 44 5.0 44 44 44 38 32 26 20 47 47 47 44 38 32 26 44 5.0 44 44 44 42 36 30 24
72 54 4.7 39 34 29 23 17 - - 51 5.1 38 33 27 22 17 - -
1800
67 49 4.6 47 43 37 32 27 21 16 46 5.1 45 41 36 31 25 20 14 62 46 4.5 57 46 4.5
46 46 45 40 34 29 23 43 5.0 43 43 43 37 32 26 21 46 46 46 42 36 31 26 43 5.0 43 43 43 40 34 29 24
72 53 4.7 36 31 27 22 17 - - 49 5.1 35 30 25 21 16 - -
1600
67 48 4.6 45 40 35 31 26 21 16 44 5.1 43 39 34 29 24 19 15 62 44 4.6 57 44 4.5
44 44 43 38 33 29 24 41 5.0 41 41 41 36 31 26 22 44 44 44 39 34 30 25 41 5.0 41 41 41 37 32 28 23
72 51 4.7 33 29 25 21 16 - - 48 5.1 32 28 24 20 15 - -
1400
67 46 4.6 41 37 33 28 24 20 16 43 5.0 40 35 31 27 23 19 14 62 43 4.5 57 43 4.5
43 42 40 36 31 27 23 40 5.0 40 40 38 34 30 25 21 43 43 41 37 32 28 24 40 5.0 40 40 39 35 31 26 22
72 50 4.7 30 27 23 19 16 - - 47 5.1 30 26 22 18 15 - -
1200
67 44 4.6 37 33 30 26 22 19 15 42 5.0 36 32 29 25 21 18 14 62 42 4.5 57 42 4.5
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 9 or 11, multiply
42 41 37 33 29 26 22 39 5.0 39 39 35 32 28 24 21 42 41 38 34 30 27 23 39 5.0 39 39 36 33 29 25 22
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Tables 9 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING ALL SENSIBLE CAPACITY
Unitary Products Group 9

TABLE 7: COOLING CAPACITIES - 5 TON (DEE / DEG060)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F 72 75 4.6 53 46 38 31 23 - - 73 5.0 53 46 38 31 23 - -
2500
67 67 4.5 64 56 49 41 34 26 19 65 4.9 64 56 49 41 34 26 19 62 62 4.5 57 56 4.4 72 74 4.6 51 44 37 31 24 - - 72 5.0 50 43 37 30 23 - -
2250
67 67 4.5 62 55 48 42 35 28 21 64 5.0 61 54 47 41 34 27 20 62 61 4.5 57 55 4.4 72 73 4.5 49 43 37 31 25 - - 70 5.0 47 41 35 29 23 - -
2000
67 66 4.5 60544842363024 63 5.0 58 52 46 40 34 28 22 62 60 4.4 57 55 4.4 72 72 4.5 45 40 34 29 24 - - 68 5.0 43 38 33 27 22 - -
1750
67 65 4.5 55 50 44 39 34 29 23 61 4.9 53 47 42 37 32 26 21 62 60 4.4 57 54 4.4 72 71 4.5 41 37 32 27 23 - - 66 5.0 40 35 30 26 21 - -
1500
67 63 4.5 50 46 41 36 32 27 22 58 4.9 48 43 39 34 29 25 20 62 59 4.4 57 53 4.4
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
62 62 62 54 47 39 32 60 4.9 60 60 60 53 46 38 31 56 56 56 48 41 33 26 55 4.8 55 55 55 47 40 32 25
61 61 61 54 47 40 34 59 4.9 59 59 59 52 45 38 32 55 55 55 48 41 35 28 53 4.8 53 53 53 46 39 33 26
60 60 60 54 48 42 36 58 4.9 58 58 57 51 45 39 33 55 55 54 48 42 36 30 52 4.8 52 52 61 45 39 33 27
60 59 56 50 45 40 35 56 4.9 56 56 53 48 42 27 32 54 53 50 45 40 34 29 50 4.8 50 50 48 42 37 32 27
59 57 52 47 43 38 34 54 4.9 54 54 49 44 40 35 31 53 52 47 42 38 33 28 49 4.8 49 49 44 40 35 30 26
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
036-21411-002-A-0204
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 66 5.5 51 44 36 29 21 - - 60 6.0 49 41 34 26 19 - -
2500
67 59 5.5 58544639312416 53 6.0 62 55 5.4 57 49 5.4
55 55 55 47 40 32 25 49 5.9 49 49 49 42 34 27 19 49 49 49 42 35 27 20 44 5.9 44 44 44 37 29 22 15
53 51 43 36 28 21 13
72 65 5.5 48 42 35 28 21 - - 58 6.0 46 40 33 26 20 - -
2250
67 58 5.5 57524538312518 52 6.0 62 54 5.4 57 48 5.4
54 54 54 48 41 34 28 48 5.9 48 48 48 44 37 30 24 48 48 48 42 36 29 22 44 5.9 44 44 44 39 32 25 19
52 49 43 36 29 22 16
72 63 5.5 45 39 33 28 22 - - 57 6.0 44 38 32 26 20 - -
2000
67 58 5.5 55504438322620 52 6.0 62 52 5.4 57 47 5.4
52 52 52 48 42 36 30 47 5.9 47 47 47 46 40 34 28 47 47 47 43 37 31 25 43 5.9 43 43 43 41 35 29 23
52 48 42 36 30 24 18
72 62 5.5 42 36 31 26 21 - - 55 6.1 40 35 30 24 19 - -
1750
67 55 5.5 50 45 40 35 30 24 19 50 6.0 48 43 38 33 28 22 17 62 51 5.4 57 46 5.4
51 51 50 45 40 35 29 46 6.0 46 46 46 43 37 32 27 46 46 45 40 35 30 24 41 5.9 41 41 41 38 33 27 22
72 60 5.5 38 33 29 24 19 - - 53 6.1 36 32 27 23 18 - -
1500
67 53 5.5 46 41 37 32 27 23 18 47 6.1 44 39 35 30 25 21 16 62 49 5.4 57 44 5.4
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 10 or 11, multiply
49 49 47 42 37 33 28 44 6.0 44 44 44 39 35 30 25 44 44 42 37 33 28 23 40 6.0 40 40 40 35 30 26 21
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Tables 10 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING ALL SENSIBLE CAPACITY
10 Unitary Products Group