York D1EE036, D1EG User Manual

®
036-21411-002-A-0204
TECHNICAL GUIDE
SUNLINE PLUS™
AIR-COOLED
AIR CONDITIONERS
D1EG/D1EE036, 048, & 060
3, 4, AND 5 NOMINAL TONS
FLEXIBLE EASY TO INSTALL SINGLE PACKAGE UNITS.
GENERAL
YORK Model DEE/DEG units are single package air condi­tioners designed for outdoor installation on a rooftop or a slab. These units can be equipped with field installed elec­tric heaters for cooling/heating applications or factory installed gas heat. The units are completely assembled on rigid, permanently attached base rails. All piping, refriger­ant charge, and electrical wiring is factory installed and tested. The units require only electric power and duct con­nections at the point of installation.
FEATURING
COMMON FOOTPRINT / COMMON CABINET
HIGH EFFICIENCY
CONVERTIBLE AIRFLOW DESIGN
OPTIONAL MOTORIZED AIR DAMPER
OPTIONAL MANUAL OUTDOOR DAMPER
FLEXIBLE INDOOR AIRFLOWS
FULL PERIMETER BASE RAILS
INSTALLER FRIENDLY CONTROL CIRCUIT
EASY UTILITY CONNECTIONS
1” OR 2” FILTERS WITH NO MODIFICATIONS
•DIRECT DRIVE
OPTIONAL BELT DRIVE
1 YEAR LIMITED WARRANTY
COMPRESSORS 5 YEAR WARRANTY
10 YEAR LIMITED WARRANTY ON GAS-FIRED HEAT EXCHANGERS
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
TABLE OF CONTENTS
036-21411-002-A-0204
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 4
FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4
MECHANICAL SPECIFICATIONS . . . . . . . . . . . . . 30
LIST OF FIGURES
Fig. Pg.
1 SUNLINE PLUS COMPONENT LOCATION. . . . . . . . . . 5
2 POWER SUPPLY, POWER WIRING THREE PHASE 22
3 CONTROL WIRING - COOLING ONLY . . . . . . . . . . . . 22
4 CONTROL WIRING- COOLING & HEATING
MULTI-STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5 POWER SUPPLY, POWER WIRING SINGLE
PHASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6 CONTROL WIRING - COOLING/HEATING
(24 VOLT THERMOSTAT) . . . . . . . . . . . . . . . . . . . . . . 22
7 CONTROL WIRING - COOLING/HEATING
(ELECTRONIC THERMOSTAT). . . . . . . . . . . . . . . . . . 23
8 UNIT DIMENSIONS WITH ECONOMIZER
RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9 UNIT DIMENSIONS DEE 3, 4, & 5 TON. . . . . . . . . . . . 24
10 ACCESS PANELS AND DISCONNECT . . . . . . . . . . . . 24
11 UNIT DIMENSIONS DEG 3, 4, & 5 TON . . . . . . . . . . . 25
12 DEE/DEG DIMENSIONS REAR VIEW -
3, 4, & 5 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
13 DETAIL B UNIT DIMENSIONS WITH DAMPER/
RAINHOOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
14 UNIT & CURB APPLICATION. . . . . . . . . . . . . . . . . . . . 27
15 ROOF CURB DIMENSIONS DEE & DEG
3, 4, & 5 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
16 CENTER OF GRAVITY. . . . . . . . . . . . . . . . . . . . . . . . .28
17 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 29
18 TYPICAL ROOF TOP INSTALLATION. . . . . . . . . . . . . 29
LIST OF TABLES
3 SOUND POWER RATINGS . . . . . . . . . . . . . . . . . . . . . . 7
4 PHYSICAL DATA - BASIC UNIT . . . . . . . . . . . . . . . . . . 8
5 COOLING CAPACITIES - 3 TON (DEE / DEG036) . . . . 9
6 COOLING CAPACITIES - 4 TON (DEE / DEG048) . . . 10
7 COOLING CAPACITIES - 5 TON (DEE / DEG060) . . . 11
8 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG036 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 12
9 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG048 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 13
10 SUPPLY AIR BLOWER PERFORMANCE -DEE/
DEG060 W/ BELT DRIVE & SIDE DUCT . . . . . . . . . . 14
11 SUPPLY AIR BLOWER PERFORMANCE - DEE/
DEG036-060 W/ DIRECT DRIVE . . . . . . . . . . . . . . . . . 15
12 STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . . . . . . 15
13 MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER 16
14 BASIC UNIT W/ DIRECT-DRIVE ELECTRICAL DATA 16
15 BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA . . 17
16 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE036. . . . . . . . . . . . . . . . . . . . . 18
17 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE048. . . . . . . . . . . . . . . . . . . . . 19
18 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 19
19 FUSE BLOCK ACCESSORY . . . . . . . . . . . . . . . . . . . . 19
20 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ DIRECT DRIVE DEE060. . . . . . . . . . . . . . . . . . . . . 20
21 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ BELT DRIVE DEE036 & 048. . . . . . . . . . . . . . . . . . 21
22 ELECTRICAL DATA COOLING/ELECTRIC HEAT
W/ BELT DRIVE DEE060 . . . . . . . . . . . . . . . . . . . . . . . 22
23 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 25
24 DEE/DEG UNIT CLEARANCES. . . . . . . . . . . . . . . . . . 26
25 ACCESSORY’S WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 29
26 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Tbl. Pg.
1 CAPACITY RATINGS - COOLING / ELECTRIC
HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2 CAPACITY RATINGS - COOLING / GAS HEATING . . . 7
2 Unitary Products Group
036-21411-002-A-0204

DESCRIPTION

YORK Sunline Plus™ units are high efficiency, convertible, single package air conditioners with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame.
All units are self--contained and assembled on rigid full perimeter base rails with fork lift slots on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to provide for a quick and easy field installation.
The units are available in cooling only, and cooling with gas heat. Electric heaters are available as field--installed acces­sories.
Both bottom and side duct connections are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either bottom and side duct applications with no modifications required.
All models include a 5--year limited warranty on compres­sors, a 10--year limited warranty on gas--fired heat exchang­ers and a 1--year limited warranty on other parts.

FEATURES

Adjustable belt drive blowers are available on all models from the factory for complete airflow flexibility.
FIELD--INSTALLED ACCESSORIES -- Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in, and electrical con­nections are made by modular plugs. Electric heaters mount easily, and knockouts are provided in the internal partitions to connect the elements to the control box single point kit.
The motorized air damper includes a slid--in/plug--in damper assembly with a rainhood and filters. The outdoor air damp­ers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.
The manual outdoor damper provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
The 14" high roof curb is shipped knocked down. An insu­lated deck is not required because the bottom of the unit is insulated.
Low ambient controls are available to provide stable unit operation at outdoor temperatures down to 0 ºF.
Propane, high altitude and low NOx kits are also available to cover all gas heating applications.
COMMON FOOTPRINT/COMMON CABINET -- All model sizes and configurations share a common cabinet and a com­mon roof curb. The installer has the flexibility of setting one curb and placing the proper tonnage unit on that curb after the internal load has been determined. He can even decide between gas or electric heat after the curb has been set.
HIGH EFFICIENCY -- All units have a high cooling efficiency of at least 11.0 SEER and gas / electric models have an AFUE as high as 80.9%. All efficiencies exceed legislated minimum levels and provide low operating costs.
CONVERTIBLE AIRFLOW DESIGN -- Both the side and bot­tom duct openings are covered when they leave the factory. If a side supply / side return is desired, you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply / bottom return is desired, you simply remove the two knockout panels from the base of the unit and discard them. No panel cutting or swapping is required! Con­vertible airflow design allows maximum field flexibility and minimum inventory.
FACTORY--INSTALLED OPTIONS -- Economizers can be installed at the factory. The economizers are shipped installed and wired. Only the rain hood needs to be field assembled and installed. Field labor dollars can be saved by having the components arrive already installed.
WIDE RANGE OF INDOOR AIRFLOWS -- All models oper­ate over a wide range of design conditions with a 3--speed direct--drive fan motor. Belt--drive blowers are also available on all models.
FULL PERIMETER BASE RAILS -- The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides, and rigging holes are also pro­vided so that an overhead crane can be used to place the units on a roof.
SYSTEM PROTECTION -- Internal overload protection is standard on all compressors. Every unit has a liquid line filter-
-drier, high and low pressure/loss of charge switches and a suction line freezestat to protect all system components. All units will provide cooling at ambient temperatures down to 45 ºF.
UTILITY CONNECTIONS MADE EASY -- Gas and electric utility knockouts are provided in the unit base as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum amount of field labor.
SIMPLE CONTROL CIRCUIT -- A low voltage printed circuit board contains a compressor lockout indicator light and a low
Unitary Products Group 3
036-21411-002-A-0204
voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external con­trols. Mate--n--lock plug connectors are used where line and low voltage wires pass through internal bulkheads. This allows for easier troubleshooting and component replace­ment. The electrical control box is not located in the compres­sor compartment so the access cover can be removed for troubleshooting without affecting the normal system operat­ing pressures.
AIR FILTERS -- Units are shipped with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications.

FACTORY-INSTALLED OPTIONS

ECONOMIZERS: Units equipped with a factory-installed economizer option have dampers that are positioned by a spring return, fully modulating damper actuator and are capa­ble of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is determined by a single input electronic enthalpy control or by a dual input electronic enthalpy control. Simulta­neous compressor and economizer operation is also possi­ble.
The single enthalpy system contains a sensor that monitors the outdoor air which automatically operates the damper actuator allowing the dampers to open or close.
The dual enthalpy system contains a second sensor that monitors both the temperature and the humidity of the return air in addition to the outdoor air sensor described for a single enthalpy system. The logic module compares the inputs from both sensors and switches to economizer operation when­ever the outdoor air is cooler than the return air for maximum efficiency of the economizer system.
The economizer is completely wired and installed at the fac­tory. Only the outdoor air hood, including its filters, need be assembled and installed in the field.
BELT DRIVE BLOWERS: Adjustable belt-drive blowers pro­viding maximum flexibility to handle many airflow require­ments, are available on all models.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER ­Includes a slide-in / plug-in damper assembly with fully modu­lating spring return motor actuator capable of introducing up to 100% outdoor air, one outdoor air electronic enthalpy sen­sor and a rain hood with filters. The rain hood is painted to match the basic unit and must be field-assembled before installation. Economizer dampers are 2% low leakage type.
DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER ­Includes the same damper system and rain hood with filters as described for a single enthalpy economizer except this accessory contains two enthalpy sensors. It uses a differen­tial enthalpy control that compares the outdoor air versus the return air. The logic module then optimizes the economizer operation for additional savings over the single input econo­mizer.
MOTORIZED AIR DAMPER - Includes a slid-in/plug-in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.
MANUAL OUTDOOR DAMPER - Provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.
ELECTRIC HEATERS - Include nickel chromium elements, a terminal block, fuses (where required by UL), all the neces­sary connectors and hardware. All heaters utilize single point power supply hookup. Capacities from 5 KW through 30 KW heating are available.
FUSE BLOCK KITS - These kits have a fuse box with a fuse block and fuses. They're available for all 460-3-60 volt heat­ers and 208/230-3-60 volt heaters 7 KW and smaller.
OUTDOOR THERMOSTAT - A 24-volt thermostat providing two stages of control for units equipped with electric heat accessories.
ROOF CURB - This 14" high full perimeter roof curb is shipped knocked down for field assembly and contains duct supports that can easily be shifted for the desired unit duct arrangement. No insulated deck is required because the unit underside is insulated.
START ASSIST KIT - Provides increased starting torque for single phase units in areas with low voltage conditions. It con­tains a 12.5 OHM PTCR temperature resistor with a support clip and hardware for mounting.
LOW AMBIENT KIT - A head pressure controller maintains stable system operation by reducing the speed of the con­denser fan motor when the outdoor temperature is between 45 and 0 ºF. Condenser fan motors with ball bearings and heavier windings are also available for these low ambient applications.
ANTI-RECYCLE TIMER - A timer to prevent the unit com­pressor from short cycling. It assures a 5-minute off-time between compressor cycles.
4 Unitary Products Group
036-21411-002-A-0204
PROPANE CONVERSION KIT - Converts a gas-fired heater from natural gas to propane. It contains main burner orifices, a pilot orifice and a regulator spring.
LOW NOx KIT (natural gas furnaces only) - Contains five stainless steel expanded metal sheets for mounting into the heat exchanger tubes to meet the California low nitrous oxide emission requirements.
HIGH ALTITUDE CONVERSION (NATURAL AND PRO­PANE) - Provides orifices for proper furnace operation at alti­tudes up to 6000 feet. For propane applications, the propane conversion kit will also be required.
2 0 G A U G E A L U M I N I Z E D S T E E L T U B U L A R H E A T E X C H A N G E R
s o m e
E C O N O M I Z E R H O O D
O U T D O O R A I R O P E N I N G F O R S L I D E - I N / P L U G I N I N T
E R N A L E C O N O M I Z E R
S I D E R E T U R N A I R D U C T O P E N I N G
L O W V O L T A G E R E L A Y B O A R D A N D T E R M I N A L S T R I P
E L E C T R I C A L M O U N T I N G L O C A T I O N ( F i e l d I n s t a l l e d )
D I S C O N N E C T
D I R E C T D R I V E B L O W E R M O T O R ( B e l t D r i v e O p t i o n a l s o a v a i l a b l e o n m o d e l s )
GAS PIPING - This kit contains 1/2" pipe nipples, fittings and gas cock (including panel access gaskets) required for bot­tom gas supply connection with external shut-off.
OUTDOOR COIL GUARD - Consists of grille-type sections for installation over the outdoor coil to protect it from damage.
WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
L O N G L A S T I N G P O W D E R P A I N T F I N I S H
E L E C T R I C H E A T A C C E S S O R Y L O C A T I O N ( E l e c / E l e c U n i t s )
P O W E R V E N T E R M O T O R W I T H P O S T P U R G E C Y C L E
C O P P E R T U B E A L U M I N U M F I N C O N D E N S E R C O I L
H I G H E F F I C I E N C Y C O M P R E S S O R S
/
B O T T O M R E T U R N A I R D U C T O P E N I N G
3 / 4 " P V C F E M A L E C O N D E N S A T E D R A
K N O C K O U T S F O R S I D E P O W E R A N D C O N T R O L E N T R Y
I N
T E R M I N A L B L O C K ( F o r S i n g l e P o i n t P o w e r S u p p l y o n E l e c / E l e c U

FIGURE 1 - SUNLINE PLUS COMPONENT LOCATION

K N O C K O U T F O R B O T T O M P O W E R E N T R Y
n i t s )
K N O C K O U T F O R B O T T O M G A S S U P P L Y E N T R Y
F U L L P E R I M E T E R B A S E R A I L S W I T H F O R K L I F T S L O T S A N D L I F T I N G H O L E S
K N O C K O U T F O R S I D E G A S S U P P L Y E N T
M O D E L D E G
( G a s H e a t i n g )
R Y
Unitary Products Group 5
036-21411-002-A-0204
TABLE 1: CAPACITY RATINGS - COOLING / ELECTRIC HEATING
ARI RATINGS
MODEL
DEE036 42.5 11.5
DEE048 49.5 11.0
DEE060 58.5 11.0
1.
Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.
2.
Heaters are available as accessories - all with single point power supply
3.
Rated in accordance with ARI Standard 270.
4.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
COOLING CAPACITY 80 / 67-95°F SOUND
MBH
SEER
4
divided by the total electric power input in watt-hours during the same period.
5.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
1
5
EER
10.10 86.0
10.0 86.0
10.05 86.0
RATING
(dBels)
NOMINAL ELECTRIC HEAT CAPACITY2 (kW)
3
5, 7, 10, 15 &
5, 7, 10, 15 &
5, 7, 10, 15,
Not ARI required
240V 480V 600V
20
20
20, & 30
7, 10, 15 & 20 10, 15, & 20
7, 10, 15 & 20 10, 15, & 20
7, 10, 15, 10,
& 30

TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING

MODEL
DEG036N040 42.5 11.5 10.1 86 50 40 80.9 81.6 15-45 1/2 DEG036N079 42.5 11.5 DEG048N060 49.5 11.0 DEG048N099 49.5 11.0 DEG060N079 58.5 11.0 DEG060N099 58.5 11.0
1.
Ratings are in accordance with ARI Standard 210.
2.
Sound ratings are in accordance with ARI Standard 270.
3.
AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.
4.
S.S.E. = Steady State Efficiency (Percent Output).
5.
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
COOLING CAPACITY 80 /
MBH
ARI RATINGS
67-95°F
5
SEER
1
SOUND
RATING
6
EER
10.1 86 100 79 80.5 80.8 40-70 1/2
10.0 86 75 59 80.9 81.6 25-55 1/2
10.0 86 125 99 80.3 80.6 45-75 1/2
10.05 86 100 79 80.5 80.8 25-55 1/2
10.05 86 125 99 80.3 80.6 35-65 1/2
(dBels)
INPUT
2
(MBH)
OUTPUT
(MBH)
divided by the total electric power input in watt-hours during the same period.
6.
EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).
GAS HEAT CAPACITY
3
(%) S.S.E.4 (%)
AFUE
TEMP.
RISE
(°F)
GASE LINE SIZE
Not ARI required
10, 15, 20 &
30
(in. O.D.)

TABLE 3: SOUND POWER RATINGS

UNIT SIZE
036 1200 0.60 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43
CFM
1.
These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The
ESP BLOWER
IWG SPEED kW 63 125 250 500 1000 2000 4000 8000
1
-12
OCTAVE BAND CENTERLINE FREQUENCY (Hz)
SOUND POWER (dB 10
WATTS )
SWL
dB(A)
dBA
@ 10Ft
2
dBA values provided are to be used fro reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2.
At a distance of 10 feet from the blower.
6 Unitary Products Group
036-21411-002-A-0204

TABLE 4: PHYSICAL DATA - BASIC UNIT

MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FAN
CONDENSER
COIL
AIR FILTERS
SYSTEM CHARGE Refrigerant 22 (Lbs./Oz.) 9/12 9/8 9/8
COMPRESSOR Quantity Per Unit: (Hermetic Type) 1 / Recpt 1 / Recpt 1 / Scroll
1.
Filter racks are adapted for 1” or 2” thick filters.
Centrifugal Blower (Dia. x Wd. in.) Fan Motor HP (Direct - Drive) Fan Motor HP (Belt - Drive)
Rows Deep Fins Per Inch Face Area (Sq. Ft.)
Propeller Dia. (in.) Fan Motor HP Nom. CFM. Total
Rows Deep Fins Per Inch Face Area (Sq. Ft.)
Quantity Per Unit (15” x 20” x 1”)
1
Quantity Per Unit (14” x 25” x 1”) Total Face ARea (Sq. Ft.)
036 048 060
12 x 10
1/2
1.5 3
13
3.6
22 1/2
4,500
2
18
17.1 2
1
6.6
DEE/DEG
12 x 10
4,200
17.1
3/4
1.5
13
4.3 22
1/2
18
6.6
3
2
2 1
12 x 10
1
1.5 3
13
5.1
22
1/2
4,500
2
18
17.1 2
1
6.6
Unitary Products Group 7

TABLE 5: COOLING CAPACITIES - 3 TON (DEE / DEG036)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F
72 55 3.4 35 31 26 22 18 - - 51 3.7 35 30 26 21 17 - -
1500
67 52 3.3 47 42 38 33 29 24 20 48 3.6 45 41 36 32 28 23 19 62 42 3.2 57 42 3.2 72 51 3.3 32 28 24 20 16 - - 49 3.6 32 28 24 20 16 - -
1350
67 49 3.3 42 38 34 30 26 22 18 47 3.5 42 38 34 30 26 22 18 62 39 3.2 57 40 3.2 72 48 3.2 28 24 21 17 14 - - 48 3.6 29 25 22 18 15 - -
1200
67 46 3.3 37343027231916 46 3.5 39 36 32 38 25 21 18 62 36 3.2 57 37 3.2 72 46 3.3 26 23 19 16 13 - - 45 3.6 26 23 20 16 13 - -
1050
67 44 3.3 34 31 28 25 22 18 15 43 3.5 35 32 28 25 22 19 16 62 35 3.2 57 36 3.2 72 45 3.3 24 21 18 15 13 - - 43 3.5 23 20 17 15 12 - -
900
67 42 3.2 31 29 26 23 20 17 15 40 3.5 30 28 25 22 19 16 14 62 34 3.2 57 35 3.1
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
42 42 42 37 33 28 24 39 3.5 39 39 39 34 30 25 21 42 42 42 38 33 29 24 39 3.5 39 39 39 35 30 26 21
39 39 37 33 29 25 21 37 3.5 37 37 37 33 29 25 21 40 40 38 34 30 26 22 38 3.5 38 38 38 34 30 26 22
36 36 33 29 26 22 19 36 3.5 36 36 35 31 28 24 21 37 37 35 31 27 24 20 37 3.4 37 37 37 33 30 26 22
35 34 31 28 24 21 18 34 3.4 34 33 31 28 25 22 19 36 35 32 29 26 23 20 35 3.4 35 34 33 30 27 23 20
34 32 26 26 23 20 18 32 3.4 32 30 28 25 22 19 17 35 33 30 27 25 22 19 33 3.4 33 32 29 26 24 21 18
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
036-21411-002-A-0204
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 47 3.9 33 29 25 20 16 - - 43 4.1 32 28 23 19 14 - -
1500
67 44 3.8 43 39 35 30 26 22 17 40 4.1 40 38 33 29 24 20 16 62 36 3.7 57 36 3.7
36 36 36 31 27 22 18 33 4.0 33 33 33 28 24 19 15 36 36 36 31 27 23 18 33 3.9 33 33 33 28 24 20 15
72 44 3.9 30 26 22 18 14 - - 39 4.1 28 24 20 16 12 - -
1350
67 42 3.8 39 36 32 28 24 20 16 37 4.0 36 33 29 25 21 17 13 62 34 3.7 57 34 3.7
34 34 33 29 25 21 17 30 4.0 30 30 30 26 22 18 14 34 34 34 30 26 22 18 30 3.9 30 30 31 27 23 19 15
72 42 3.8 27 23 20 16 12 - - 36 4.1 24 21 17 14 10 - -
1200
67 40 3.8 36 32 29 25 22 18 14 34 4.0 33 29 25 22 18 15 11 62 32 3.7 57 32 3.7
32 32 31 28 24 20 17 27 3.9 27 27 28 24 20 17 13 32 32 33 29 26 22 19 28 3.9 28 28 29 26 22 18 15
72 40 3.8 24 21 18 15 12 - - 35 4.1 22 19 16 13 10 - -
1050
67 38 3.7 32 29 26 23 19 16 13 33 4.0 30 26 23 20 17 14 11 62 30 3.7 57 31 3.6
30 30 28 25 22 19 16 27 3.9 27 27 26 22 19 16 13 31 31 30 27 24 20 17 27 3.9 27 27 27 24 21 17 14
72 38 3.8 22 19 16 13 11 - - 34 4.0 20 18 15 12 9 - -
900
67 36 3.7 29 26 23 20 17 15 12 32 4.0 27 24 21 18 16 13 10 62 29 3.6 57 30 3.6
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 8 or 11, multiply
29 28 26 23 20 17 15 26 3.9 26 26 24 21 18 15 13 30 29 27 24 21 19 16 26 3.9 26 26 25 22 19 17 14
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Table 8 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING
ALL SENSIBLE CAPACITY
8 Unitary Products Group
036-21411-002-A-0204

TABLE 6: COOLING CAPACITIES - 4 TON (DEE / DEG048)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F 72 64 3.9 45 39 33 27 21 - - 60 4.2 44 38 32 26 20 - -
2000
67 57 3.8 55494337312519 53 4.1 62 54 3.8 57 54 3.8 72 62 3.9 42 36 31 25 20 - - 58 4.2 41 35 30 24 19 - -
1800
67 55 3.8 51 46 40 35 30 24 19 52 4.1 50 44 39 34 28 23 18 62 52 3.8 57 52 3.8 72 59 3.9 38 33 29 24 19 - - 57 4.2 38 33 28 23 18 - -
1600
67 54 3.8 48433833292419 52 4.2 47 42 37 32 28 23 18 62 50 3.7 57 50 3.7 72 58 3.8 35 31 27 23 18 - - 55 4.2 34 30 26 22 17 - -
1400
67 52 3.8 44 39 35 31 27 22 18 49 4.2 42 38 34 30 26 21 17 62 49 3.7 48474339343026 46 4.1 57 49 3.7 72 57 3.8 32 29 25 21 17 - - 53 4.2 31 28 24 20 16 - -
1200
67 50 3.8 40 36 32 29 25 21 17 47 4.2 38 35 31 27 23 20 16 62 48 3.7 47444036332925 45 4.1 57 48 3.7
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
54 54 53 47 41 35 29 50 4.0 50 50 50 44 38 32 26 54 54 54 48 42 36 30 50 4.0 50 50 50 46 40 34 28
52 52 49 44 39 33 28 49 4.1 49 49 47 42 37 31 26 52 52 51 45 40 35 29 49 4.1 49 49 49 44 38 33 27
50 50 46 41 36 32 27 47 4.1 47 47 45 40 35 31 26 50 50 47 42 38 33 28 47 4.1 47 47 46 41 37 32 27
49 48 44 40 36 31 27 46 4.1 46 46 43 38 34 30 26
48 45 41 37 34 30 26 45 4.1 45 43 39 35 32 28 24
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
53 47 41 35 29 23 17
46 45 42 37 33 29 25
45 42 38 34 31 27 23
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 56 4.7 42 36 30 25 19 - - 53 5.2 41 35 29 23 17 - -
2000
67 50 4.6 62 47 4.5 57 47 4.5
50 45 39 33 28 22 16 47 5.1 47 44 38 32 26 20 14 47 47 47 41 35 29 23 44 5.0 44 44 44 38 32 26 20 47 47 47 44 38 32 26 44 5.0 44 44 44 42 36 30 24
72 54 4.7 39 34 29 23 17 - - 51 5.1 38 33 27 22 17 - -
1800
67 49 4.6 47 43 37 32 27 21 16 46 5.1 45 41 36 31 25 20 14 62 46 4.5 57 46 4.5
46 46 45 40 34 29 23 43 5.0 43 43 43 37 32 26 21 46 46 46 42 36 31 26 43 5.0 43 43 43 40 34 29 24
72 53 4.7 36 31 27 22 17 - - 49 5.1 35 30 25 21 16 - -
1600
67 48 4.6 45 40 35 31 26 21 16 44 5.1 43 39 34 29 24 19 15 62 44 4.6 57 44 4.5
44 44 43 38 33 29 24 41 5.0 41 41 41 36 31 26 22 44 44 44 39 34 30 25 41 5.0 41 41 41 37 32 28 23
72 51 4.7 33 29 25 21 16 - - 48 5.1 32 28 24 20 15 - -
1400
67 46 4.6 41 37 33 28 24 20 16 43 5.0 40 35 31 27 23 19 14 62 43 4.5 57 43 4.5
43 42 40 36 31 27 23 40 5.0 40 40 38 34 30 25 21 43 43 41 37 32 28 24 40 5.0 40 40 39 35 31 26 22
72 50 4.7 30 27 23 19 16 - - 47 5.1 30 26 22 18 15 - -
1200
67 44 4.6 37 33 30 26 22 19 15 42 5.0 36 32 29 25 21 18 14 62 42 4.5 57 42 4.5
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 9 or 11, multiply
42 41 37 33 29 26 22 39 5.0 39 39 35 32 28 24 21 42 41 38 34 30 27 23 39 5.0 39 39 36 33 29 25 22
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Tables 9 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING ALL SENSIBLE CAPACITY
Unitary Products Group 9

TABLE 7: COOLING CAPACITIES - 5 TON (DEE / DEG060)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F 72 75 4.6 53 46 38 31 23 - - 73 5.0 53 46 38 31 23 - -
2500
67 67 4.5 64 56 49 41 34 26 19 65 4.9 64 56 49 41 34 26 19 62 62 4.5 57 56 4.4 72 74 4.6 51 44 37 31 24 - - 72 5.0 50 43 37 30 23 - -
2250
67 67 4.5 62 55 48 42 35 28 21 64 5.0 61 54 47 41 34 27 20 62 61 4.5 57 55 4.4 72 73 4.5 49 43 37 31 25 - - 70 5.0 47 41 35 29 23 - -
2000
67 66 4.5 60544842363024 63 5.0 58 52 46 40 34 28 22 62 60 4.4 57 55 4.4 72 72 4.5 45 40 34 29 24 - - 68 5.0 43 38 33 27 22 - -
1750
67 65 4.5 55 50 44 39 34 29 23 61 4.9 53 47 42 37 32 26 21 62 60 4.4 57 54 4.4 72 71 4.5 41 37 32 27 23 - - 66 5.0 40 35 30 26 21 - -
1500
67 63 4.5 50 46 41 36 32 27 22 58 4.9 48 43 39 34 29 25 20 62 59 4.4 57 53 4.4
TOTAL
CAP.
MBH
85°F
POWER
1
INPUT
kW
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83
62 62 62 54 47 39 32 60 4.9 60 60 60 53 46 38 31 56 56 56 48 41 33 26 55 4.8 55 55 55 47 40 32 25
61 61 61 54 47 40 34 59 4.9 59 59 59 52 45 38 32 55 55 55 48 41 35 28 53 4.8 53 53 53 46 39 33 26
60 60 60 54 48 42 36 58 4.9 58 58 57 51 45 39 33 55 55 54 48 42 36 30 52 4.8 52 52 61 45 39 33 27
60 59 56 50 45 40 35 56 4.9 56 56 53 48 42 27 32 54 53 50 45 40 34 29 50 4.8 50 50 48 42 37 32 27
59 57 52 47 43 38 34 54 4.9 54 54 49 44 40 35 31 53 52 47 42 38 33 28 49 4.8 49 49 44 40 35 30 26
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
036-21411-002-A-0204
95°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
80 77 74 71 68
1
, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
TOTAL
CAP
MBH
105°F 115°F
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
TEMPERATURE OF AIR ON CONDENSER COIL
1
, MBH
TOTAL
CAP
MBH
POWER
.1
INPUT
kW.
2
SENSIBLE CAPACITY
72 66 5.5 51 44 36 29 21 - - 60 6.0 49 41 34 26 19 - -
2500
67 59 5.5 58544639312416 53 6.0 62 55 5.4 57 49 5.4
55 55 55 47 40 32 25 49 5.9 49 49 49 42 34 27 19 49 49 49 42 35 27 20 44 5.9 44 44 44 37 29 22 15
53 51 43 36 28 21 13
72 65 5.5 48 42 35 28 21 - - 58 6.0 46 40 33 26 20 - -
2250
67 58 5.5 57524538312518 52 6.0 62 54 5.4 57 48 5.4
54 54 54 48 41 34 28 48 5.9 48 48 48 44 37 30 24 48 48 48 42 36 29 22 44 5.9 44 44 44 39 32 25 19
52 49 43 36 29 22 16
72 63 5.5 45 39 33 28 22 - - 57 6.0 44 38 32 26 20 - -
2000
67 58 5.5 55504438322620 52 6.0 62 52 5.4 57 47 5.4
52 52 52 48 42 36 30 47 5.9 47 47 47 46 40 34 28 47 47 47 43 37 31 25 43 5.9 43 43 43 41 35 29 23
52 48 42 36 30 24 18
72 62 5.5 42 36 31 26 21 - - 55 6.1 40 35 30 24 19 - -
1750
67 55 5.5 50 45 40 35 30 24 19 50 6.0 48 43 38 33 28 22 17 62 51 5.4 57 46 5.4
51 51 50 45 40 35 29 46 6.0 46 46 46 43 37 32 27 46 46 45 40 35 30 24 41 5.9 41 41 41 38 33 27 22
72 60 5.5 38 33 29 24 19 - - 53 6.1 36 32 27 23 18 - -
1500
67 53 5.5 46 41 37 32 27 23 18 47 6.1 44 39 35 30 25 21 16 62 49 5.4 57 44 5.4
1.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from Table 10 or 11, multiply
49 49 47 42 37 33 28 44 6.0 44 44 44 39 35 30 25 44 44 42 37 33 28 23 40 6.0 40 40 40 35 30 26 21
this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to Tables 10 or 11 for the kW of the supply air blower motor.
1
, MBH
NOMINAL RATING ALL SENSIBLE CAPACITY
10 Unitary Products Group
036-21411-002-A-0204
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG036 W/ BELT DRIVE & SIDE DUCT1
MODEL
DEE/DEG
036
MODEL
DEE/DEG
036
1.
2.
3.
AIR
FLOW
CFM
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730
AIR
FLOW
CFM
200011031270-----------­190010851210-----------­18001064114511021180---------­1700 1040 1075 1081 1115 1121 1140 - - - - - - - ­1600 1020 1005 1060 1050 1100 1085 - - - - - - - ­1500 1003 945 1044 995 1086 1035 - - - - - - - ­1400 982 880 1024 920 1067 965 1107 1000 - - - - - ­1300 970 835 1010 870 1053 920 1099 960 - - - - - ­1200 953 780 992 815 1034 855 1080 905 - - - - - -
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
230/460/575 Volts
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
other than gas / electric units with side duct airflows.
3
3
2
Unitary Products Group 11
036-21411-002-A-0204
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG048 W/ BELT DRIVE & SIDE DUCT1
MODEL
DEE/DEG
048
MODEL
DEE/DEG
048
1.
2.
3.
AIR
FLOW
CFM
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730
AIR
FLOW
CFM
200011031270-----------­190010851210-----------­18001064114511021180---------­1700104010751081111511211140-------­1600102010051060105011001085-------­15001003945104499510861035-------­14009828801024920106796511071000-----­1300970835101087010539201099960-----­120095378099281510348551080905------
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
230/460/575 Volts
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
other than gas / electric units with side duct airflows.
3
3
2
12 Unitary Products Group
036-21411-002-A-0204
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE -DEE/DEG060 W/ BELT DRIVE & SIDE DUCT1
MODEL
DEE/DEG
060
MODEL
DEE/DEG
060
1.
2.
3.
AIR
FLOW
CFM
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440 2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340 2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225 1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095 1800 - - - - 855 815 903 860 950 905 988 940 1022 970 1700 - - - - - - 884 815 925 850 964 880 1001 910 1600 - - - - - - 864 770 908 805 948 835 987 870 1500 - - - - - - - - 882 740 926 780 965 830
AIR
FLOW
CFM
2500-------------­240011931665-----------­23001170158012021620---------­22001148148011801530---------­2100 1121 1385 1155 1425 1190 1475 - - - - - - - ­2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - ­1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - ­1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - ­1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - ­1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
0.20 0.30 0.40 0.50 0.60 0.70 0.80
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
230/460/575 Volts
For 208 Volts multiply values by 0.95.
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance values on applications
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
other than gas / electric units with side duct airflows.
3
3
2
Unitary Products Group 13
036-21411-002-A-0204

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - DEE/DEG036-060 W/ DIRECT DRIVE

MODEL
DEE/DEG
036
048
060
MODEL
DEE/DEG
036
048
060
1.
2.
MOTOR
SPEED
HI - - - - 1699 825 1650 785 MED 1684 800 1631 780 1582 750 1524 720 LOW 1487 710 1464 690 1421 670 1367 650
HI 1996 960 1933 936 1868 910 1795 880 MED 1804 838 1765 810 1714 785 1650 765 LOW 1681 760 1640 738 1604 715 1541 695
HI 2400 1155 2338 1125 2274 1095 2167 1045 MED 2290 1105 2214 1065 2145 1030 2071 990 LOW 2150 1020 2100 990 2029 950 1965 910
MOTOR
SPEED
HI 1570 755 1430 725 1360 700 1280 680 1180 655 MED 1410 690 1324 650 1260 630 1185 610 1100 590 LOW 1315 620 1246 605 1185 590 1110 570 1020 545
HI 1722 845 1635 820 1544 790 1419 765 1300 740 MED 1589 735 1508 705 1407 675 1306 645 1195 625 LOW 1490 670 1416 645 1337 620 1230 595 1120 575
HI 2096 1010 1990 980 1887 945 1771 905 1629 855 MED 1990 950 1911 920 1828 885 1724 835 1604 798 LOW 1905 880 1816 838 1724 800 1644 770 1531 710
0.20 0.30 0.40 0.50
CFM WATTS CFM WATTS CFM WATTS CFM WATTS
0.6 0.70 0.80 0.90 1.00
CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS
Side Duct application (230/460/575 Volts)
Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to Table 12 for resistance val-
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
ues on applications other than gas / electric units with side duct airflows.
2
1
1

TABLE 12: STATIC RESISTANCES

DESCRIPTION
ECONOMIZER
ELECTRIC HEATERS
BOTTOM DUCT CONNECTIONS
COOLING ONLY
1.
2.
3.
1 2
1
3
5 - 15 kW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22 20 - 30 kW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26
1
Deduct these resistance values from the available external static pressure shown on Tables 8, 9, 10, and 11.
The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Add these resistance values to the available static resistance in the respective Blower Performance Table (see Tables 8, 9, 10, and 11).
RESISTANCE, IWG
CFM
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30
0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22
0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32
14 Unitary Products Group
036-21411-002-A-0204

TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER

1
MODEL
DEE / DEG 036 780 - 1120 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.7 1 37.3 A36 DEE / DEG 048 790 - 1120 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.7 1 37.3 A36 DEE / DEG 060 850 - 1220 1-1/2 1725 56 1.15 2.4-3.4 7/8 5.2 1 37.3 A36
1.
All motors have a solid base and are inherently protected. These motors can be selected to operate into their service fac-
BLOWER
RANGE
RPM
HP RPM
MOTOR
FRAME
SIZE
SERVICE
FAC TOR
ADJUSTABLE
MOTOR PULLEY PITCH
DIA.
(in.)
BORE
(in.)
tor because they are located in the moving air, upstream of any heating device.
FIXED
BLOWER PULLEY
PITCH
DIA. (in.)
BORE
(in.)
PITCH
LENGTH
(in.)
BELT
NATION

TABLE 14: BASIC UNIT W/ DIRECT-DRIVE ELECTRICAL DATA

MODEL
DEE/
DEG
036
048
060
1.
Rated in accordance with ARI Standard 110, utilization range “A”.
2.
Dual element, time delay type.
3.
DEE models only.
POWER
SUPPLY
208/230-1-60 187 253 16.7 87 2.3 4.4 27.5 40 40 208/230-3-60 187 253 13.1 110 2.3 4.4 23.1 35 35
460-3-60 414 504 6.7 54 1.4 2.2 12.0 15 15
3
575-3-60 208/230-1-60 187 253 18.7 135 2.3 5.0 38.6 60 60 208/230-3-60 187 253 11.9 130 2.3 5.0 25.7 40 40
460-3-60 414 504 6.3 64 1.4 2.2 13.2 20 20
3
575-3-60 208/230-1-60 187 253 32.1 169 2.3 6.6 49.0 80 80 208/230-3-60 187 253 19.3 123 2.3 6.6 33.0 50 50
460-3-60 414 504 10.0 62 1.4 3.3 17.2 25 25
3
575-3-60
VOLTAGE
LIMITATIONS
MIN MAX RLA LRA
518 630 5.1 44 1.4 2.2 10.7 15 -
518 630 4.9 52 1.4 2.2 11.4 15 -
518 630 7.9 50 1.4 3.3 14.6 20 -
1
COMPRESSOR
CON.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE SIZE
AMPS
2
DESIG-
HACR
BREAKER
AMPS
MAX.
SIZE,
Unitary Products Group 15

TABLE 15: BASIC UNIT W/ BELT-DRIVE ELECTRICAL DATA

MODEL
DEE/ DEG
POWER
SUPPLY
VOLTAGE
LIMITATIONS
MIN MAX RLA LRA
1
COMPRESSOR
208/230-1-60 187 253 16.7 87 2.3 7.6 30.1 45 45
036
208/230-3-60 187 253 13.1 110 2.3 5.3 23.9 35 35
460-3-60 414 504 6.7 54 1.4 2.6 12.4 20 20
3
575-3-60
518 630 5.1 44 1.4 2.0 9.8 15 15
208/230-1-60 187 253 18.7 135 2.3 8.6 42.6 60 60
048
208/230-3-60 187 253 11.9 130 2.3 5.2 26.3 40 40
460-3-60 414 504 6.3 64 1.4 2.6 14.3 20 20
3
575-3-60
518 630 4.9 52 1.4 2.0 11.4 15 15
208/230-1-60 187 253 32.1 169 2.3 8.6 51.0 80 80
060
1.
2.
3.
208/230-3-60 187 253 19.3 123 2.3 6.0 32.4 50 50
460-3-60 414 504 10.0 62 1.4 3.0 16.9 25 25
3
575-3-60
518 630 7.9 50 1.4 2.4 13.7 20 20
Rated in accordance with ARI Standard 110, utilization range “A”.
Dual element, time delay type.
= DEE models only.
CON.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
036-21411-002-A-0204
MAX. FUSE
SIZE
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
16 Unitary Products Group
036-21411-002-A-0204

TABLE 16: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE036

SUPPLY
AIR
BLOWER
MOTOR
FLA
MODEL
DEE
POWER SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
2CE04500506 2CE04500706 5.6 1 27.1 39.4 45 45
208-1-60
2CE04501006 8.0 1 38.3 53.4 60 60
4.4 2CE04501506 11.9 2 57.4 77.3 80 80 2CE04502006 15.9 2 76.6 101.2 110 110 2CE04500506 2CE04500706 7.5 1 31.3 44.6 45 45
230-1-60
2CE04501006 10.6 1 44.2 60.7 70 70
4.4 2CE04501506 15.9 2 66.0 88.3 90 90 2CE04502006 21.2 2 88.3 115.9 125 125
3
3
4.4
3
3
4.4
036
208-3-60
230-3-60
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 33.1 35 35 2CE04501525 11.9 2 33.1 46.9 50 50 2CE04502025 15.9 2 44.2 60.7 70 70
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 37.4 40 40 2CE04501525 15.9 2 38.2 53.3 60 60 2CE04502025 21.2 2 51.0 69.2 70 70
3
3
2.2
3
3
460-3-60
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04501058
575-3-60
2CE04501558 15.9 1 15.3 21.9 25 25
2.2 2CE04502058 21.2 2 20.4 28.2 30 30
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse block accessories are available for field installation (see Table 19).
ELECTRIC HEATERS
MINIMUM
kW STAGES
TOTAL
AMPS
CIRCUIT
AMPACITY
4.0 1 19.1 30.7 45 45
5.3 1 22.1 33.1 45 45
4.0 1 11.0 24.3 35 35
5.6 1 15.6 25.0 35 35
5.3 1 12.7 24.3 35 35
7.5 1 18.0 28.1 35 35
6.8 1 8.2 13.0 15 15
10.1 1 12.1 17.9 20 20
13.6 1 16.4 23.2 25 25
19.5 2 23.5 32.1 35 35
10.6 1 10.2 15.5 20 20
MAX
FUSE SIZE
AMPS
MAX.
1
SIZE
HACR
2
Unitary Products Group 17

TABLE 17: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE048

3
3
3
3
3
3
3
3
SUPPLY
AIR
BLOWER
MOTOR
FLA
5.0
5.0
5.0
5.0
2.2
2.2
MODEL
DEE
048
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse
POWER SUPPLY
208-1-60
230-1-60
208-3-60
230-3-60
460-3-60
575-3-60
HEATER
ACCESSORY
MODEL
NUMBER
2CE04500506 2CE04500706 5.6 1 27.1 39.9 60 60 2CE04501006 8.0 1 38.3 54.3 60 60 2CE04501506 11.9 2 57.4 77.8 80 80 2CE04502006 15.9 2 76.6 101.8 110 110 2CE04500506 2CE04500706 7.5 1 31.3 45.3 60 60 2CE04501006 10.6 1 44.2 61.5 70 70 2CE04501506 15.9 2 66.3 89.1 90 90 2CE04502006 21.2 2 88.3 116.7 125 125
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 34.0 40 40 2CE04501525 11.9 2 33.1 47.5 50 50 2CE04502025 15.9 2 44.2 61.4 70 70
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 38.0 40 40 2CE04501525 15.9 2 38.2 54.0 60 60 2CE04502025 21.2 2 51.0 70.0 70 70
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04501058 2CE04501558 15.9 1 15.3 21.9 25 25 2CE04502058 21.2 2 20.4 28.2 30 30
block accessories are available for field installation (see Table 19).
ELECTRIC HEATERS
kW STAGES
4.0 1 19.1 38.6 60 60
5.3 1 22.1 38.6 60 60
4.0 1 11.0 25.7 40 40
5.6 1 15.6 25.7 40 40
5.3 1 12.7 25.7 40 40
7.5 1 18.0 28.8 40 40
6.8 1 8.2 13.2 20 20
10.1 1 12.1 17.9 20 20
13.6 1 16.4 23.2 25 25
19.5 2 23.5 32.1 35 35
10.6 1 10.2 15.5 20 20
TOTAL
AMPS
MINIMUM
CIRCUIT
AMPACITY
036-21411-002-A-0204
MAX
FUSE SIZE
AMPS
1
MAX.
SIZE
HACR
2

TABLE 18: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92

TABLE 19: FUSE BLOCK ACCESSORY

PART NUMBER VOLTS
2FB04700425 208/240 Volts 2FB04700546 460 Volts
18 Unitary Products Group
036-21411-002-A-0204

TABLE 20: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE060

SUPPLY
AIR
BLOWER
MOTOR
FLA
MODEL
DEE
POWER SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
2CE04500506 2CE04500706 5.6 1 27.1 49.0 80 80
208-1-60
2CE04501006 8.0 1 38.3 56.1 80 80 2CE04501506 11.9 2 57.4 80.0 90 90
8.6
2CE04502006 15.9 2 76.6 103.9 110 110 2CE04503006 22.2 2 106.9 141.9 150 150 2CE04500506 2CE04500706 7.5 1 31.3 49.0 80 80
230-1-60
2CE04501006 10.6 1 44.2 63.5 80 80 2CE04501506 15.9 2 66.3 91.1 100 100
8.6
2CE04502006 21.2 2 88.3 118.7 125 125 2CE04503006 29.6 2 123.3 162.4 175 175
3
3
6.0
3
3
6.0
060
208-3-60
230-3-60
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 35.9 50 50 2CE04501525 11.9 2 33.1 49.7 50 50 2CE04502025 15.9 2 44.2 63.5 70 70 2CE04503025 22.2 2 61.7 85.4 90 90
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 40.1 50 50 2CE04501525 15.9 2 38.2 56.1 60 60 2CE04502025 21.2 2 51.0 72.0 80 80 2CE04503025 29.6 2 71.2 97.3 100 100
3
3
3
3.0
3
3
460-3-60
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04503046
2CE04501058
575-3-60
2CE04501558 15.9 1 15.3 23.2 25 25 2CE04502058 21.2 2 20.4 29.6 30 30
2.4
2CE04503058 30.4 2 29.3 40.7 45 45
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse block accessories are available for field installation (see Table 19).
ELECTRIC HEATERS
MINIMUM
kW STAGES
TOTAL
AMPS
CIRCUIT
AMPACITY
4.0 1 19.1 49.0 80 80
5.3 1 22.1 49.0 80 80
4.0 1 11.0 33.0 50 50
5.6 1 15.6 33.0 50 50
5.3 1 12.7 33.0 50 50
7.5 1 18.0 33.0 50 50
6.8 1 8.2 17.2 25 25
10.1 1 12.1 19.3 25 25
13.6 1 16.4 24.6 25 25
19.5 2 23.5 33.4 35 35
28.8 2 34.6 47.4 50 50
10.6 1 10.2 16.9 20 20
MAX.
FUSE SIZE
AMPS
1
MAX.
SIZE
2
HACR
BREAKER
AMPS
Unitary Products Group 19
036-21411-002-A-0204

TABLE 21: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE036 & 048

SUPPLY
AIR
BLOWER
MOTOR
FLA
MODEL
DEE
POWER SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
2CE04500506 2CE04500706 5.6 1 27.1 44.6 50 50
208-1-60
2CE04501006 8.0 1 38.3 58.6 60 60
5.3 2CE04501506 11.9 2 57.4 82.5 90 90 2CE04502006 15.9 2 76.6 106.4 110 110 2CE04500506 2CE04500706 7.5 1 31.2 49.8 50 50
230-1-60
2CE04501006 10.6 1 44.2 66.0 70 70
5.3 2CE04501506 15.9 2 66.3 93.6 100 100 2CE04502006 21.2 2 88.3 121.2 125 125
3
3
5.3
3
3
5.3
036
208-3-60
230-3-60
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 34.2 35 35 2CE04501525 11.9 2 33.1 48.1 50 50 2CE04502025 15.9 2 44.2 61.9 70 70
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 38.5 40 40 2CE04501525 15.9 2 38.2 54.4 60 60 2CE04502025 21.2 2 51.0 70.4 80 80
3
3
3
3
3.1
460-3-60
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04501058
575-3-60
2CE04501558 15.9 1 15.3 23.0 25 25
3.1 2CE04502058 21.2 2 20.4 29.4 30 30 2CE04500506 2CE04500706 5.6 1 27.1 44.4 60 60
208-1-60
2CE04501006 8.0 1 38.3 58.8 60 60
8.6 2CE04501506 11.9 2 57.4 82.3 90 90 2CE04502006 15.9 2 76.6 106.3 110 110 2CE04500506 2CE04500706 7.5 1 31.2 49.8 60 60
230-1-60
2CE04501006 10.6 1 44.2 66.0 70 70
8.6 2CE04501506 15.9 2 66.3 93.6 100 100 2CE04502006 21.2 2 88.3 121.2 125 125
3
3
5.2
3
3
5.2
048
208-3-60
230-3-60
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 34.3 40 40 2CE04501525 11.9 2 33.1 47.8 50 50 2CE04502025 15.9 2 44.2 61.7 70 70
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 38.4 40 40 2CE04501525 15.9 2 38.2 54.3 60 60 2CE04502025 21.2 2 51.0 70.2 80 80
3
3
3
3
2.6
460-3-60
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04501058
575-3-60
2CE04501558 15.9 1 15.3 21.6 25 25
2.0 2CE04502058 21.2 2 20.4 28.0 30 30
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for fuse block accessories available for field installation.
ELECTRIC HEATERS
MINIMUM
kW STAGES
TOTAL
AMPS
CIRCUIT
AMPACITY
4.0 1 19.1 34.9 50 50
5.3 1 22.1 38.4 50 50
4.0 1 11.0 25.2 35 35
5.6 1 15.6 26.2 35 35
5.3 1 12.7 25.2 35 35
7.5 1 18.0 29.2 35 35
6.8 1 8.2 14.1 20 20
10.1 1 12.1 19.1 20 20
13.6 1 16.4 24.3 25 25
19.5 2 23.5 33.2 35 35
10.6 1 10.2 16.6 20 20
4.0 1 19.1 42.2 60 60
5.3 1 22.1 42.2 60 60
4.0 1 11.0 25.9 40 40
5.6 1 15.6 25.9 40 40
5.3 1 12.7 25.9 40 40
7.5 1 18.0 29.1 40 40
6.8 1 8.2 13.6 20 20
10.1 1 12.1 18.4 20 20
13.6 1 16.4 23.7 25 25
19.5 2 23.5 32.6 35 35
10.6 1 10.2 15.2 20 20
MAX. FUSE
SIZE
AMPS
1
MAX.
SIZE
2
HACR
BREAKER
AMPS
20 Unitary Products Group
036-21411-002-A-0204

TABLE 22: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ BELT DRIVE DEE060

ELECTRIC HEATERS
MINIMUM
kW STAGES
TOTAL
AMPS
CIRCUIT
AMPACITY
4.0 1 19.1 51.0 80 80
5.6 1 27.1 51.0 80 80
5.3 1 22.1 51.0 80 80
7.5 1 31.3 51.0 80 80
4.0 1 11.0 32.4 50 50
5.6 1 15.6 32.4 50 50
5.3 1 12.7 32.4 50 50
7.5 1 18.0 32.4 50 50
6.8 1 8.2 16.4 25 25
10.1 1 12.1 18.9 25 25
13.6 1 16.4 24.2 25 25
19.5 2 23.5 33.1 35 35
28.8 2 34.6 47.1 50 50
10.6 1 10.2 15.7 20 20
3
3
SUPPLY
AIR
BLOWER
MOTOR
FLA
8.6
MODEL
DEE
POWER SUPPLY
208-1-60
HEATER
ACCESSORY
MODEL
NUMBER
2CE04500525
2CE04500725
2CE04501025 8.0 1 38.3 58.6 80 80 2CE04501525 11.9 2 57.4 82.5 90 90 2CE04502025 15.9 2 76.6 106.4 110 110 2CE04503025 22.2 2 106.9 144.4 150 150
3
3
8.6
230-1-60
2CE04500525
2CE04500725
2CE04501025 10.6 1 44.2 66.0 80 80 2CE04501525 15.9 2 66.3 93.6 100 100 2CE04502025 21.2 2 88.3 121.1 125 125 2CE04503025 29.6 2 123.3 164.9 175 175
3
3
6.0
060
208-3-60
2CE04500525
2CE04500725
2CE04501025 8.0 1 22.1 35.1 50 50 2CE04501525 11.9 2 33.1 48.9 50 50 2CE04502025 15.9 2 44.2 62.7 70 70 2CE04503025 22.2 2 61.7 84.6 90 90
3
3
6.0
230-3-60
2CE04500525
2CE04500725
2CE04501025 10.6 1 25.5 39.4 50 50 2CE04501525 15.9 2 38.2 55.3 60 60 2CE04502025 21.2 2 51.0 71.2 80 80 2CE04503025 29.6 2 71.2 96.5 100 100
3
3
3
3.0
3
3
460-3-60
2CE04500746
2CE04501046
2CE04501546
2CE04502046
2CE04503046
2CE04501058
575-3-60
2CE04501558 15.9 1 15.3 22.1 25 25 2CE04502058 21.2 2 20.4 28.5 30 30
2.4
2CE04503058 30.4 2 29.3 39.6 40 40
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago) see Table 19 for fuse block accessories available for field installation.
MAX.
FUSE SIZE
AMPS
1
MAX.
SIZE
2
HACR
BREAKER
AMPS
Unitary Products Group 21
036-21411-002-A-0204
REFER TO THE ELECTRI­CAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTECTION AND WIRING
T T S
/
)
FIGURE 2 - POWER SUPPLY, POWER WIRING
SINGLE PHASE
T H E R M O S T A T
T E R M I N A L S
A D D
J U M P E R
4
L E D 1
L E D 2
C O M
A D D
J U M P E R
1
E L E C T R O N I C P R O G R A M M A B L E T H E R M O S T A T 2 E T 0 4 7 0 0 2 2 4 ( I N C L U D E S S U B B A S E
2
S E C O N D S T A G E C O O L I N G I S N O T R E Q U I R E D O N U N I T S L E S S E C O N O M I Z E R .
3
S E C O N D S T A G E H E A T I N G I S O N L Y R E Q U I R E D O N U N I T S W I T H A T W O S T A G E
E L E C T R I C H E A T E R .
4
R E M O V E J U M B E R J 2 F R O M T E R M I N A L S 4 A N D 9 O N J U M P E R P L U G C O N N E C T O R P 6 O N U N I T S W I T H E C O N M I Z E R . T E R M I O U T - P U T T O C L O S E T H E O U T D O O R E C O N O M I Z E R D A M P E R S W H E N T H E T H E R M O S T A T
S W I T C H E S T O T H E S E T - B A C K P O S I T I O N .
1
U N I T T E R M I N A L
R C
R H
Y 1
Y 2
W 1
W 2
G
B
N O T U S E D
A 1
A 2
T
T
S T R I P T B 1
R
2
3
4
T O R E M O T E S E N S O R 2 T H 0 4 0 7 0 2 2 2 4 I F U S E D
Y 1
Y 2
W 1
W 2
G
B
X
N
N A L S A 1 A N D A 2 P R O V I D E A R E L A Y
2 4 V O L T
T R A N S F O R M E R
FIGURE 5 - CONTROL WIRING- COOLING &
HEATING MULTI-STAGE
FIGURE 3 - POWER SUPPLY, POWER WIRING
THREE PHASE
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
1
24 VOLT THERMOSTAT 2TH07701024 IF THE UNIT HAS AN ECONOMIZER,
REMOVE JUMPER J1 FROM TERMINALS 8 AND 10 ON THE RELAY BOARD
O PREVENT SIMULTANEOUS OPERATION OF THE COMPRESSOR AND HE ECONOMIZER. IF YOU WANT TO CONTROL THE ECONOMIZER ON A ECOND STAGE OF COOLING, USE THE THERMOSTAT 2TH04701224.
1
UNIT TERMINAL
STRIP TB1
48
;+
/.
4
;
;
*
24 VOLT
TRANSFORMER

FIGURE 4 - CONTROL WIRING - COOLING ONLY

C O O L I N G / H E A T I N G ( 2 4 V O L T T H E R M O S T A T )
T H E R M O S T A T
1
T E R M I N A L S
A D D
J U M P E R
1
R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D
T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D
T H E E C O N O M I Z E R . I F Y O U W
S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C H E A T A C C E S S O R Y
W I T H T W
R H
R C
Y
W
G
2 4 V O L T T H E R M O S T A T 2 T H 0 7 7 0 1 0 2 4 . I F T H E U N I T H A S A N E C O N O M I Z E R ,
O S T A G E S O F H E A T , U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4
U N I T T E R M I N A L
S T R I P T B 1
R
Y 1
Y 2
W 1
W 2
G
B
A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A
2 4 V O L T
T R A N S F O R M E R
1 0 O N T H E R E L A Y B O A R D
FIGURE 6 - CONTROL WIRING - COOLING/
HEATING (24 VOLT THERMOSTAT)
22 Unitary Products Group
036-21411-002-A-0204
C O O L I N G / H E A T I N G ( E L E C T R O N I C T H E R M O S T A T )
S I N G L E S T A G E
1
U N I T T E R M I N A L
S T R I P T B 1
R
Y 1
W 1
G
B
A D D
J U M P E R
T H E R M O S T A T
T E R M I N A L S
R H
R C
Y
W
G
2 4 V O L T
T R A N S F O R M E R
1
E L E C T R O N I C P R O G R A M M A B L E T H E R M O S T A T 2 E T 0 7 7 0 1 0 2 4 ( I N C L U D E S S U B B A S E ) . I F T H I S U N I T H A S A N D E C O N O M I Z E R , R 1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C
O M P R E S S O R A N D T H E E C O N O M I Z E R . I F Y O U W A N T T O C O N T R O L T H E
E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G , U S
E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D
E T H E R M O S T A T 2 E T 0 4 7 0 0 2 2 4 .

FIGURE 7 - CONTROL WIRING - COOLING/HEATING (ELECTRONIC THERMOSTAT)

2 7 - 1 / 2
1 - 5 / 8
2 7 - 1 / 2

FIGURE 8 - UNIT DIMENSIONS WITH ECONOMIZER RAINHOOD

1 9 - 1 / 2
1 9 - 3 / 4
4 4 - 7 / 8
Unitary Products Group 23
DEE UNITS
(
)
3-5 TON
R E T U R N A I R
S U P P L Y A I R
O U T D O O R A I R
O U T D O O R A I R
E c o n o m i z e r
036-21411-002-A-0204

FIGURE 9 - UNIT DIMENSIONS DEE 3, 4, & 5 TON

TABLE 23: UTILITIES ENTRY DATA

HOLE
A
B2
C 1-5/8” Gas Piping (Front) D 1-1/2” Gas Piping (Bottom)
1.
Knockouts in the bottom of the unit can be located by the slice in the insulation.
2.
DO NOT remove the 2” knockout ring.
KNOCKOUT
SIZE (DIA.)
1
7/8”
USED FOR
Control Wiring (Side or
Power Wiring (Side or
Bottom)
Bottom)
2
All dimensions are in inches. They are subject to change without notice. Cer­tified dimensions will be provided upon request.

FIGURE 10 -ACCESS PANELS AND DISCONNECT

24 Unitary Products Group
036-21411-002-A-0204
(
)
DEG UNITS 3-5 TON
R E T U R N A I R
S U P P L Y A I R
O U T D O O R A I R
O U T D O O R A I R
E c o n o m i z e r

FIGURE 11 -UNIT DIMENSIONS DEG 3, 4, & 5 TON

TABLE 24: DEE/DEG UNIT CLEARANCES

FRONT
BACK
LEFT SIDE (Filter Access)
RIGHT SIDE (Cond. Coil) 24”
BELOW UNIT
ABOVE UNIT
1.
1
2
Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2.
Units must be installed outdoors. Overhanging struc­tures or shrubs should not obstruct condenser air dis­charge outlet.
DEE UNITS 24” DEG UNITS 32”
12” (Less Economizer)
36” (With Economizer or
Fixed Air/Motorized
Damper)
24” (Less Economizer) 36” (With Economizer)
72” (For Condenser Air
Discharge)
0”
Note: DEE Models and ductwork are approved for zero
clearance to combustible materials when equipped with electric heaters.
Note: EG Models must have a 1” clearance between any
combustible material and the supply air ductwork for a distance of 3 feet from the unit.
The products of combustion must not be allowed to accumu­late within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least:
Three feet above any forced air inlet located within 10 horizontal feet (excluding those integral to the unit).
Four feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet into the building.
Four feet from electric meters, gas meters, regulators and relief equipment.
Unitary Products Group 25
11-1/2
036-21411-002-A-0204
3
17-1/2
6-1/2
17-1/2

FIGURE 12 -DEE/DEG DIMENSIONS REAR VIEW - 3, 4, & 5 TON

Duct covers - units are shipped with all air duct openings covered.
For side duct applications:
Remove and discard the supply and return air duct covers.
Connect ductwork to duct flanges on the rear of the unit.
For bottom duct applications:
Remove the side supply air duct cover to gain access to the bottom supply air knockout panel.
Remove and discard the bottom knockout panel.
Replace the side duct cover.
With filter section access panel removed from the unit, remove and discard the bottom return air knockout panel.
Replace the filter Access panel.
11-1/2
4-5/8
7-7/8
26 Unitary Products Group
036-21411-002-A-0204
2 7 - 1 / 2
7 - 1 / 4
2 7 - 1 / 2
1 9 - 1 / 8
" A "
R E A R V I E W
D I M E N S I O N " A "
F I X E D
O U T D O O R
1 2
A I R D A M P E R
M O T O R I Z E D
D A M P E R
1 6 - 1 / 2

FIGURE 13 -DETAIL B UNIT DIMENSIONS WITH DAMPER/RAINHOOD

4 4 - 7 / 8
L . H . E N D V I E W
1 0 - 1 / 4
3 - 1 / 2
8 - 1 / 4
4 - 3 / 8

FIGURE 14 -UNIT & CURB APPLICATION

Unitary Products Group 27
036-21411-002-A-0204
C O N D E N S E R C O I L E N D O F U N I T
A P P R O X I M A T E C E N T E R O F G R A V I T Y
F R O N T
B A C K
4 4 - 7 / 8
8 2 - 1 / 2
4 0 - 3 / 4
1 9 - 3 / 4
C O R N E R " A "
C O R N E R " B "
C O R N E R " C "
C O R N E R " D "

FIGURE 15 -ROOF CURB DIMENSIONS DEE & DEG 3, 4, & 5 TON

TABLE 25: UNIT WEIGHTS

UNIT
WEIGHT
(lbs.)
DEG036 665 188 185 145 147 DEG048 705 199 196 154 156 DEG060 730 206 203 159 162 DEE036 565 160 157 123 125 DEG048 615 173 170 135 137 DEG060 640 180 177 140 143
UNIT
CORNER WEIGHTS
(location, lbs.)
“A” “B” “C” “D”

TABLE 26: ACCESSORY’S WEIGHT

MOTORIZED OUTDOOR AIR DAMPER 26
ELECTRIC
HEAT (nom. kW DEE only)
ROOF MOUNTING CURB 92
RELIEF/FIXED AIR DAMPER 10

FIGURE 16 -CENTER OF GRAVITY

DESCRIPTION
ECONOMIZER 50
5-7 kW 18 10 - 15 kW 23
10 - 30 kW 28
BELT-DRIVE BLOWER 5
28 Unitary Products Group
036-21411-002-A-0204
ROOF JACK INSTALLATION
ROOF CURB INSTALLATION
SLAB ON GROUND INSTALLATION

FIGURE 17 -TYPICAL APPLICATIONS

FIGURE 18 -TYPICAL ROOF TOP INSTALLATION

Unitary Products Group 29
036-21411-002-A-0204

MECHANICAL SPECIFICATIONS

GENERAL DESCRIPTION

Units shall be High Efficiency factory-assembled, single pack­aged, (DUS Electric Cooling/Gas Heat, DHC Electric Cooling/ Optional Electric Heat), designed for outdoor mounted instal­lation. Units shall have minimum SEER ratings of 11.0. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories.
The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. Enclosed in each unit shall be a factory test log sheet consisting of the unit tested pressures, temperatures and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be UL listed and classified to ANSIZ21.47 standards and UL 1995/CAN/CSA No. 236-M90 conditions.

UNIT CABINET

8. Condensate pan shall be internally sloped and conform to ASHARE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4" I.D. female and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

1. Fan shall be direct drive, multi-speed, or a factory installed belt drive, adjustable-pitch motor pulley option. Job site selected (B.H.P.) brake horse power shall not exceed the motors nameplate horse power rating, plus the service factor. Units shall be designed not to operate above service factor.
2. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
3. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

1. The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riv­eted to corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation.
1. Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powered paint finish, certified at 750 hours salt spray test per ASTM-B117 standards.
2. Indoor blower section shall be insulated with up to 1” thick insulation, coated on the air side. Aluminum foil faced insulation shall be used in the furnace compart­ment and be fastened with ridged fasteners to prevent insulation from entering the air stream.
3. Cabinet panels shall be large size, easily removable for servicing and maintenance.
4. Full perimeter base rails shall be provided to assure reli­able transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications.
5. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed air tight. Units filter track shall be designed to accommodate either 1 or 2" filters.
6. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measure­ments of evaporator fan performance without removing panels or creating air by-pass of the coils.
7. Units vertical discharge and return duct configuration shall be designed to fit between standard 24" O.C. beams without modification to building structure, duct work and base unit.
2. The outdoor fan motor shall be totally enclosed with per­manently lubricated bearings and internally protected against overload conditions.

REFRIGERANT COMPONENTS

1. Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter­nally isolated on a dedicated, independent mounting.
2. Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless internally-enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-through design.
3. Refrigerant Circuit and Refrigerant Safety Components shall include:
30 Unitary Products Group
036-21411-002-A-0204
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15 ºF
of liquid sub-cooling at design conditions.
4. Unit Controls:
a. Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit breaker fuse on the 24 volt transformer side.
b. Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor:
I. Loss-of-charge/Low-pressure switch.
II. High-pressure switch.
III.Freeze-protection thermostat, evaporator coil.
If any of the above safety devices trip, an LED (light-emitting diode) indicator shall illuminate.
6. Heating section shall be provided with the following mini­mum protection:
a. Primary and auxiliary high-temperature limit
switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch (automatic reset).
d. Flame proving controls.

ELECTRIC HEATING SECTION (DEE MODELS)

1. An electric heating section, with nickel chromium ele­ments, shall be provided in a range of 5 through 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters.
2. The heating section shall have a primary limit control(s) and automatic reset, to prevent the heating element sys­tem from operating at an excessive temperature.
3. The Heating Section assembly shall slide out of the unit for easy maintenance and service.
4. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

c. Unit shall incorporate AUTO RESET compressor
over temperature, over current protection.
d. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for easy hook-up.

GAS HEATING SECTION (DEG MODELS)

1. Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition and redundant main gas valve. Ventor wheel shall be con­structed of stainless steel for corrosion resistance.
2. The heat exchanger shall be of the tubular type, con­structed of T1-40 aluminized steel for corrosion resis­tance and allowing minimum mixed air entering temperature of 25 ºF.
3. Burners shall be of the in-shot type, constructed of alu­minum coated steel and contain air mixture adjustments.
4. All gas piping shall enter the unit cabinet at a single loca­tion, through either the side or bottom, without any field modifications.
5. An integrated control board shall provide timed control of evaporator fan functioning and burner ignition.
1. Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240.
2. The compressor, with standard controls, shall be capable of operation down to 45 ºF outdoor temperature. Acces­sory low ambient kit shall be available for operation down to 0 ºF.
3. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only.)

ELECTRICAL REQUIREMENTS

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES

Compressor- 5 Years
Heat Exchanger- 10 Years
Elect. Heat. Elem.- 5 Years
Parts - 1 Year
Unitary Products Group 31
K

OPTIONAL OUTDOOR AIR

(Shall be made available by either/or):
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO­MIZER - Outdoor and return air dampers that are inter­locked and positioned by a fully-modulating, spring­return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti­ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi­tioned space during normal operation. During econo­mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer oper­ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out­door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil­ters shall be provided. Simultaneous economizer/com­pressor operation is also possible. Dampers shall fully close on power loss.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake damp­ers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the minimum ven­tilation requirement of the conditioned space during nor­mal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be pro­vided by two integral electronic enthalpy controls - one that senses outdoor air and one that senses indoor air. Both enthalpy sensors supply input to the logic module which modulates both sets of dampers for maximum economizer savings. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simul­taneous economizer/compressor operation is also possi­ble. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL­ABLE
1. ROOF CURB - 14" AND 8" high, full perimeter knock­down curb with hinged design for quick assembly.
2. MANUAL OUTDOOR DAMPER - Provides 0% through 35% or 0% through 100% outdoor air capability (field adjustable). Designed for duct mounted side supply/ return applications. Includes a hood and a screen assembly.
3. OUTDOOR COIL GUARD - Prevents coil damage.
4. BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.
5. PROPANE CONVERSION KIT - Contains new orifices and gas valve regulator to convert from natural to L.P. gas.
6. LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nano grams per joule.
7. HIGH ALTITUDE - NATURAL GAS - Required for appli­cations between 2000 and 6000 feet altitude.
8. HIGH ALTITUDE - PROPANE GAS - Required for appli­cations between 2000 and 6000 feet altitude. Must be used with propane conversion kit.
9. GAS PIPING - Contains pipe nipples, fittings and gas cock (including panel assess gaskets) required for bot­tom gas supply connection with external shut-off.
10. BURGLAR BARS - Designed to work with above roofcurbs. Fits duct openings of curb supply and return air openings.
11. THERMOSTATS - Multiple models available from A.C.O., M.C.O., Electronic or Electrical Mechanical ver­sions.
12. ANTI-RECYCLE TIMER - Assures 5-minute off-time between compressor cycles.
13. LOW AMBIENT KIT - Provides unit cooling operation down to 0 ºF.
14. ELECTRIC HEAT - Slide-in design, provides single point power and ranges from 5 to 30 KW.

OTHER FACTORY INSTALLED OPTIONS

1. HIGH PERFORMANCE BELT DRIVE MOTOR
2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
4. DUAL INPUT ELECTRONIC ENTHALPY ECONO­MIZER
Subject to change without notice. Printed in U.S.A. 036-21411-002-A-0204 Copyright © 2004 by Unitary Products Group. All rights reserved. Supersedes: 036-21411-001-A-0502