Yokogawa YTA70 User Manual

User’s Manual
YTA70 Temperature Transmitter
IM 01C50C03-01EN
7th Edition: July 2011 (YK) All Rights Reserved, Copyright © 1999, Yokogawa Electric Corporation
IM 01C50C03-01EN
7th Edition
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Branch Sales Offices
YOKOGAWA CORPORATION OF AMERICA
2 Dart Road, Newnan, Georgia 30265-1094, U.S.A. Phone : 1-800-888-6400 Fax : 1-770-254-0928
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS Phone : 31-88-4641000 Fax : 31-88-4641111
Branch Sales Offices / Wien (Austria), Zaventem (Belgium), Ratingen (Germany), Madrid (Spain), Runcorn (United Kingdom), Milano (Italy), Velizy-Villacoublay (France), Budapest (Hungary), Stockholm (Sweden), Sola (Norway), Warszawa (Poland), Vila Nova de Gaia (Portugal), Bucharest (Romania), Dublin (Ireland)
YOKOGAWA AMERICA DO SUL LTDA.
Praca Acapulco, 31 - Santo Amaro. Sao Paulo/SP - BRAZIL Phone : 55-11-5681-2400 Fax : 55-11-5681-4434
YOKOGAWA ELECTRIC ASIA PTE. LTD.
5 Bedok South Road, 469270 SINGAPORE Phone : 65-6241-9933 Fax : 65-6241-2606
YOKOGAWA ELECTRIC KOREA CO., LTD.
14-1, Yangpyongdong-4Ga, Youngdeungpo-Gu, Seoul, 150-866 KOREA Phone : 82-2-2628-6000 Fax : 82-2-2628-6400
YOKOGAWA AUSTRALIA PTY. LTD.
Tower A, 112-118 Talavera Road, Macquarie Park, N.S.W.2113, AUSTRALIA Phone : 61-2-8870-1100 Fax : 61-2-8870-1111
YOKOGAWA INDIA LTD.
Plot No.96 Electronic City Complex, Hosur Road, Bangalore 560100, INDIA Phone : 91-80-4158-6000 Fax : 91-80-2852-1442
YOKOGAWA CHINA CO., LTD.
3F TowerD Cartelo Crocodile Building No.568 West Tianshan Road, Shanghai 200335, CHINA Phone : 86-21-62396262 Fax : 86-21-62387866
June '10
SAFETY INSTRUCTIONS
Ex/I.S. installation:
• For correct use and installation the manufacturer’s manual must be followed. When programming the Transmitter by PC and communication interface or a
HART® terminal the intrinsically safe data shall be observed.
• The designation galvanic isolation between the transducer input and the loop supply indicates signal isolation only. It shall not be interpreted as an Intrinsically Safe galvanic isolation like an isolating barrier. Therefore ordinary care in selecting barrier and grounding shall be considered.
• The apparatus must be installed in an enclosure with an Ingress Protection of at least IP 20.
• The terminals 1 and 2 of the equipment have to be electrically connected to a linear barrier located in the non hazardous area.
• For Ex/I.S. data, see chapter 7. Approvals Options.
The YTA70 is a head mount type of temperature transmitter that accepts thermocouple or RTD input and converts it to a 4 to 20 mA DC signal for transmission. The YTA70 species HART communication protocol for remote conguration. It is imperative that usres observe the instructions in this manual to ensure the protection and safety of operators.
1. Model and Sufx Codes
Model Sufx code Descriptions
YTA70 . . . . . . . . . . Temperature Transmitter
Output Signal -E . . . . . . . . 4 to 20mA DC with digital communication
(HART protocol)
Optional Specications
/KS2 CENELEC ATEX (KEMA) intrinsically safe
approval
/DS2 FM intrinsically safe/Nonincendive and CENELEC
ATEX (KEMA) intrinsically safe approval combination
/SS2 IECEx intrinsically safe, FM intrinsically safe/
Nonincendive, and CENELEC ATEX (KEMA) intrinsically safe approval combination
2. Warranty
The warranty period of the instrument is as of condition shown when purchasing. Any trouble arising during the warranty period shall be replaced at free of charge. The following problems or troubles shall not be eligible of charge-exempt repair.
• Caused by improper usage or storage of the customer which exceeds the specication requirements.
• Caused by mishandling or modication.
• Caused by re, earthquake or other acts of God that are not directly a result of problems of the instrument.
3. Handling Precautions
(1) Read this manual throughly and carefully before handling the instruments.
Observe the instructions.
(2) Store the product in location that meets the following requirements.
• No exposure to rain or water
• No major mechanical vibration or shock
• Humidity and Temperature limitations
• Ordinary conditions(25°C, 65%) is preferable.
Otherwise, as of specied in “Standard Specications.” (3) Avoid corrosive atmosphere for storage and installation. (4) For safe installation of the transmitter in hazardous area, the following must be observed. The module must only be installed by qualied
personnels who are familiar with the national and international laws, directives, and standards that apply to this area.
(5) Yokogawa will not be liable for malfunctions or damage resulting from any
modication made to this instrument by the customer.
4. Standard Specications
Accuracy (see table below)
Sensor
Standard
type
<T/C> B IEC584 400 to 1820 752 to 3308 200 360 ±0.1% of span or ±1.0°C E -100 to 1000 -148 to 1832 50 90 ±0.1% of span or ±0.5°C J -100 to 1200 -148 to 2192 50 90 K -180 to 1372 -292 to 2502 50 90 N -180 to 1300 -292 to 2372 100 180 R -50 to 1760 -58 to 3200 200 360 ±0.1% of span or ±1.0°C S -50 to 1760 -58 to 3200 200 360 T -200 to 400 -328 to 752 50 90 ±0.1% of span or ±0.5°C L DIN43710 -100 to 900 -148 to 1652 50 90 U -200 to 600 -328 to 1112 75 135 W3 ASTM 0 to 2300 32 to 4172 200 360 ±0.1% of span or ±1.0°C W5 0 to 2300 32 to 4172 200 360 <RTD> Pt100 IEC751 -200 to 850 -328 to 1562 10 18 ±0.1% of span or ±0.1°C Ni100 DIN43760 -60 to 250 -76 to 482 10 18 ±0.1% of span or ±0.2°C DC Voltage -800 to 800 [mV] 2.5 [mV] ±0.1% of span or
Resistance 0 to 7000 [Ω] 25 [Ω] ±0.1% of span or ±0.1Ω
Input ranges
°C °F °C °F
Cold Junction Compensation Accuracy(For T/C only)
±1°C (±1.8°F)
Ambient Temperature Effects (per 10°C Change)
For E, J, K, L, N, T and U thermocouple inputs: ±0.05% of span or ±0.25°C, whichever is greater For R, S, B, W3 and W5 thermocouple inputs: ±0.05% of span or ±1°C, whichever is greater For Pt100 and Ni100 RTD inputs: ±0.05% of span or ±0.05°C, whichever is greater For DC voltage input: ±0.05% of span or ±5µV, whichever is greater For Resistance(ohm) input: ±0.05% of span or ±0.05Ω, whichever is greater
Power Supply Effects
±0.005% of FS per Volt
RFI Effects
Tested per EN 61326, eld intensity up to 10 V/m.
EMC Conformity
EN 61326
Maximum Zero Offset
±50% of the maximum temperature
Input Signal Source Resistance (for T/C input)
10 MΩ, or 3 kΩ at power-off
Input Lead Wire Resistance (for RTD input)
5 Ω per wire or lower
Burnout
High(NAMUR NE43 upscale) , Low(NAMUR NE43 downscale) or value within
3.5 to 20 mA
Output
Two wire 4 to 20 mA DC
Response Time
1 to 60 sec programmable
Ambient Temperature Limits (Option code may affect limit)
–40 to 85°C (–40 to 185°F)
Ambient Humidity Limits
5 to 90% RH at 40°C (104°F)
Supply Voltage
8 to 35 V DC 8 to 30 V DC for Intrinsically safe type
13.8 to 35 V DC for digital communication
Load Resistance
Limitation: 0 to (E–8)/0.0236 [Ω], where E is power supply voltage.
Isolation
Input/output isolated to 1500 V AC.
Mounting
DIN form B head mounting
Terminals
M3 screws
Weight
50 g (0.11 lb)
Minimum
span
Accuracy
(value whichever is greater)
±0.01mV
5. Block Diagram
0_16
mA
1
2
supply +
8–35VDC
supply -
4–20 mA
A
F01E.ai
mV
mV
RTD.lin.R
+
-
-
Wire
4 3 2
TC
6
5
+
Int.
MUX
CJC
-
4
3
PGA
A/D
CPU
EEPROM
4 mA
HART
Comm.
D/A
YTA70
6. Wiring
See wiring diagram. For output signal, use twisted pair or cables with performance equivalent to 600V vinyl insulate cable. For wiring in high or low temperature, use a wire or cable suitable for such temperature. Use cables and wires which meet atmospheric conditions. Take necessary measure to avoid corrosion or damage of cables and wires.
IMPORTANT
When mounting on a sensor head, do not overtighten the screws.
Wiring Diagram
n
1
SUPPLY
2
3
(–)
4
5
(+)
6
T/C or
DC milivolts
Dimensions
n
+
3
3
2
33 (1.30)
(+)
(–)
+
5 4
1
1
2
3
4
5
6
RTD or ohm
Ø6
6
(0.24)
SUPPLY
(B)
(A)
Two-wire
(+)
(–)
Ø 44 (1.73)
20.2
(0.80)
1
2
3
4
5
6
(+)
SUPPLY
(–)
(B)
(B)
(A)
Three-wire
RTD or ohm
Unit : mm (approx. inch)
1
2
3
(B)
4
(B)
5
(A)
6
(A)
Four-wire
RTD or ohm
F03E.ai
(+)
SUPPLY
(–)
F02E.ai
7. Approvals Options
7.1 CENELEC ATEX (KEMA) Intrinsically safe model (/KS2, /DS2, /SS2)
ATEX Certicate: KEMA 10 ATEX0027 Applicable Standard: EN 60079-0: 2006, EN 60079-11: 2007,
EN 60079-26: 2007, EN 61241-0: 2006, EN 61241-11: 2006
[ Installation diagram ]
Zone 0, 1, 2, 20, 21, 22
T4: -40 ≤ Ta ≤ 85°C T6: -40 ≤ Ta ≤ 60°C
Terminal: 3, 4, 5, 6 Uo: 9.6 VDC Io: 28 mA Po: 67 mW Lo: 35 mH Co: 3.5 μF
6
5
4
3
YTA70
Terminal: 1, 2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W Li: 10 μ H Ci: 1.0 nF
Non-hazardous AreaHazardous Area
1 +
2 -
Barrier
F04E.ai
1
Maximum Ambient Temperature for gas-proof
For T4: 85°C, For T6: 60°C
Maximum Surface Temperature for dust-proof
For T4: T105°C (Ambient Temperature: –40 to 85°C) For T6: T85°C (Ambient Temperature: –40 to 60°C)
7.2 FM Intrinsically safe/Nonincendive model (/DS2, /SS2)
Applicable Standard: FM 3600, FM 3610, FM 3611, FM 3810 Installation diagram
[ Intrinsically safe ]
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D Class II Division 1 Groups E,F,G or Class I, Zone 0, IIC
Ambient temperature limits T4: -40 to +85 deg. Celcius T6: -40 to +60 deg. Celcius
Terminal 3,4,5,6 Vt or Uo: 9.6 V It or Io: 28 mA Pt or Po: 67.2 mW Ca or Co: 3.5 uF La or Lo: 35 mH
sensor
6
5
YTA70
4
3
Terminal: 1 , 2 Vmax or Ui: 30 V Imax or Ii: 120 mA Pmax or Pi: 0.84 W Ci: 1 nF Li: 10 uH
Non-hazardous Location
Associated Apparatus
1 +
2 -
entity Parameters:
UM ≤ 250V Voc or Uo ≤ Vmax or Ui Isc or Io ≤ Imax or Ii Po ≤ Pi Ca or Co ≥ Ci + C cable La or Lo ≥ Li + L cable
This device must not be
connected to any associated apparatus which uses or generates more than 250 VRMS
or Barrier
with
[ Nonincendive ]
Hazardous (Classified) Location
Class I,Division2, Groups, A,B,C,D Class I, Zone 2, IIC
Ambient temperature limits T4: -40 to +85 deg. Celcius T6: -40 to +60 deg. Celcius
6
5
4
sensor
3
YTA70
Terminal: 1 , 2 Vmax: 35 V
Ci: 0 μ F
Li: 10 uH
Non-hazardous Location
Associated Apparatus
1 +
Voc or Vt ≤ Vmax
2 -
Ca ≥ Ci + C cable La ≥ Li + L cable
This device must not be
connected to any associated apparatus which uses or generates more than 250 VRMS
or Barrier
F05E.ai
7.3 IECEx Scheme Intrinsically safe model (/SS2)
Certicate No.: IECEx KEM 10.0086 Applicable Standard: IEC 60079-0:2007-10, IEC 60079-11:2006,
IEC 60079-26:2006, IEC 61241-11:2005
[ Installation diagram ]
Zone 0, 1, 2, 20, 21, 22
T4: -40 ≤ Ta ≤ 85°C T6: -40 ≤ Ta ≤ 45°C
Terminal: 3, 4, 5, 6 Uo: 9.6 VDC Io: 28 mA Po: 67 mW Lo: 35 mH Co: 3.5 μF
6
5
4
3
YTA70
Terminal: 1, 2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W Li: 10 μ H Ci: 1.0 nF
Non-hazardous AreaHazardous Area
1 +
2 -
Barrier
F06E.ai
8. HART Communication
8.1 Connection and Requirements
A standard HART communicator can be used for programming the YTA70. The HART communicator must be loaded with the appropriate DDL driver for YTA70.
Minimum loop resistance is 250Ω. If the receiving equipment has a lower resistance, a serial resistor must be inserted to communicate with the HART communicator.
Control room
Relaying terminals
+
YTA70
HART
communicator
communicator
Connection
600
E-8
R=
External load resistance
(Ω)
R
0.0236
250
8.0
Power supply voltage E (V DC)
Communication requirement
8.2 Parameters
Online Menu
1.Device setup
2.PV
3.Electr
4.Snsr1
5.PV AO
6.PV %rnge
(Device setup)
1.Process Variable
2.Diag/ Service
3.Basic Setup
4.Detailed Setup
5.Review
(Process Variables)
1.PV
2.Electr
3.Snsr1
4.PV AO
5.PV % rnge
(Diag/Service)
1.Status
2.Loop test
3.Calibration
4.Write Protection
5.Read max/min log
6.Reset max/min
(Basic Setup)
1.Tag
2.Range values
3.Sensor config
4.PV Damp
5.Snsr s/n
(Detailed setup)
1.Sensors
2.Signal condition
3.Output condition
4.Device information
HART
13.8
Terminal board
communicator
Digital
Communication
range
21.8
(Status)
1.Sensor errors
2.ADC errors
3.Misc. errors
(Calibration)
1.Range values
2.D/A trim
3.Scaled D/A trim
4.Override D/A trim
1.Write protect
2.New password
(Range values)
1.PV LRV
2.PV URV
3.PV unit
4.LSL
5.USL
(Sensors)
1.Process sensor
2.Electr
(Signal condition)
1.PV LRV
2.PV URV
3.PV unit
4.PV % rnge
5.PV Damp
(Output condition)
1.Analog output
2.HART output
Distributor
HART
35.0
F08E.EPS
(Range values)
1.PV LRV
2.PV URV
3.PV unit
4.LSL
5.USL
(Process sensor)
1.PV
2.Snsr1
3.PV unit
4.Sensor setup
5.Sensor info
(Analog output)
1.PV AO
2.Output rnge
3.Sensor error values
4.Loop test
5.Scaled D/A trim
6.D/A trim
7.Override D/A trim
(HART output)
1.Poll addr
2.Num req preams
3.Num resp preams
F07E.ai
(Cable resistance)
1.Enter value
2.Measure value
(Sensor setup)
1.Sensor config
2.Error detection
3.Cable resistance
4.Snsr s/n
1.USL
2.LSL
3.Min span
(Output range)
1.AO 0%
2.AO 100%
3.AO lo lim
4.AO up lim
(Sensor error values)
1.Broken sensor
2.Shorted sensor
(Broken/shorted sensor)
1.Br(Sh) sensor
2.NAMUR down
3.NAMUR up
F09E.ai
Parameters List
HART
Communicator
PV Measured variables in engineering
Process Variable
Item
Process Variable
Electr Terminal temperature
Output value
PV AO Output value in mA
PV % rnge Output value with respect to the
PV Log Read max/min log Reads the maximum/minimum PV
Reset max/min Clears the PV maximum/minimum
Signal Condition
Range value
PV LRV/PV URV Lower/upper range value to
Range Limit LSL/USL Shows the max./min. usable value
Unit PV unit Engineering unit to be displayed
Damping PV Damp Damping time constant in seconds
Sensor Setup
Sensor cong
Sensor type (wire, unit)
RTD factor For RTD only. Leave it to “1.” 1
Cold Junction Compensation
Sensor Errors
Cable resistance
Error detection Type of sensor errors to be
Enter value Enter new value of the RTD/ohm
Measure value Actually measure the cable
Output Condition
Minimum span limit
Analog Output range
Min.span Minimum settable span
AO 0%(100%) Output value for 0%(100%) in mA. 4(0%)
AO lo(up) lim Output lower(upper) limit in mA.
Sensor Error values
Loop test Change the output manually for
Diagnostics Error status Sensor errors Show error status related to a
ADC errors Show error status related to
Misc. errors Show error status related to a
Selection/Setting Range
unit.
range in %
stored in the memory
log and restart logging
denes the 0%/100% value of the measurement
for upper/lower range value
with such digital value as PV, URV, LRV, USL, LSL,min.span, etc.
applied to the digital value. 0 to
62.5(s)
Sensor type and related settings. [When T/C or milivolts is selected] Always select “single” for a measurement type. [When RTD or ohm is selected] Always select 2-, 3- or 4-wire but others for the number of sensor wires.
For T/C only. Always leave it to “1.internal sensor.”
detected for burnout operation. (1)No test performed, (2)broken sensor, (3)shorted sensor*3, or (4)broken & shorted*3
cable resistance for compensation.
resistance of 2-wire RTD/ohm for compensation.
NAMUR, or 3.8 to 23mA
Enter or select the output value when sensor error is detected. NAMUR upscale, NAMUR downscale, or value within 3.5 to 23mA
testing the loop. 4mA, 20mA, or value within 3.5 to 23mA
sensor. When any one of the errors turns "ON", check the sensor and wiring.
analog to digital conversion. When any one of the errors turns "ON", Repower the device. If error remains, replace the device.
device. When any one of the errors turns "ON", Re-power the device. If error remains, replace the device.
Initial
Setting
LRV: 0 URV:100 *1
°C
0.43(s) *1
Pt100 3-wire °C *1
Internal sensor
broken sensor
5 (ohm)
20(100%)
NAMUR
NAMUR upscale [high] *1
Item
Calibration Write
protection
Apply trim D/A trim Allows the calibration of a selected
Clear trim Override D/A trim Overrides any previous
HART
Communicator
Write protect Write-protects the device, if correct
New password Sets a new password for wirte
Scaled D/A trim Allows the calibration of the analog
Selection/Setting Range
password is entered. *2
protection, if correct password is entered.
analog output with an external reference at the operating endpoint.
output with the external reference which is scaled at 0 to 100%.
D/A trimming by restoring factory calibration values.
Initial
Setting
Not protected
Device information Manufacturer Manufacturer identication code Yokogawa
Model Model name YTA70-E
TAG Tag number, up to 8
Descriptor Text which can be used by user in
Message Text which can be used by user in
Date Date information. MM/DD/YY. Not
Write protect Indicates whether the device is
alphanumerical characters.
any way. Up to 16 alpha-numerical characters
any way. Up to 32 alpha-numerical characters
inclemented. The date is updated whenever changing conguration via PC congurator.
write-proteced.
Factory calibration date
Not protected
Snsr s/n Not used. 0
Final assembly number
Not used. 0
Distributor Yokogawa
Revision #'s Software/hardware revision
Status Error stauts (see “Error status” in
number
this table.)
Review Input info List of input variables
Output info List of output variables
Device information See “Device information” in this
table.
*1: Or as specied upon ordering. *2: The initial setting of password upon shipment is "********". *3: With T/C or milivolts for sensor type, the alarm is generated when the input
signal drops down below 2.5 mV.
Revision Record
● Manual No. : IM 01C50C03-01EN
● Title : YTA70 Temperature Transmitter
Edition Date Page Revised item
1st Mar. 1999 New Publication.
2nd June 1999 1
3rd Feb. 2000 2,3
4th Mar. 2002 12Change Optional code KS1 and DS1 to KS2 and DS2
5th July 2003 1,5,6 Delete code "/KS1" and "/DS1".
6th Feb. 2007 2,3,6 Add handling precaution.
7th July 2011 Change marking for KS2 and DS2.
Add code "/DS1" in the table Add "7.2 FM intrinsically safe model"
6
Add "note 2" .
10
Revise accuracy & temperature effect. Correct "Isolation".
4
Add explanation
9
Add "Note".
11
respectively. Add description(4) based on ATEX directives.
Change specications of FM Intrinsically safe model.
Change Certicate number and applicable standard. Change electrical data. Add 7.3 IECEx scheme approval.
2
Loading...