Yokogawa YTA510 User Manual

Y
User’s
YTA Series
Manual
Temperature Transmitter (BRAIN Protocol)
IM 01C50T03-01E
okogawa Electric Corporation
5th Edition
CONTENTS
CONTENTS
1. INTRODUCTION..........................................................................................1-1
Regarding This Manual ............................................................................. 1-1
For Safe Use of Product ........................................................................... 1-2
Warranty .................................................................................................... 1-2
ATEX Documentation................................................................................ 1-3
2. CONDITIONS OF COMMUNICATION LINE............................................... 2-1
2.1 Interconnection Between YTA and BT200 ......................................... 2-1
2.2 Communication Line Requirements.................................................... 2-1
3. OPERATION ................................................................................................ 3-1
3.1 Parameters Description....................................................................... 3-1
3.2 Setting Parameters ............................................................................. 3-4
3.2.1 Sensor Configuration .................................................................... 3-4
3.2.2 Process Variables Mapping ......................................................... 3-5
3.2.3 Unit Setting................................................................................... 3-6
3.2.4 Range Setting............................................................................... 3-6
3.2.5 Setting Damping Time Constant .................................................. 3-6
3.2.6 Tag Number and Memo Writing ................................................... 3-6
3.2.7 Forced Output Function ............................................................... 3-7
3.2.8 Integral Indicator Display Function ............................................... 3-7
3.2.9 Burn Out Function ...................................................................... 3-10
3.2.10 Reverse Output Function ........................................................... 3-10
3.2.11 Sensor Backup Function (For Model YTA320).......................... 3-10
3.2.12 Copy the Setting Data................................................................ 3-11
3.2.13 Write Protect Function ................................................................ 3-11
3.2.14 Sensor Trim................................................................................ 3-12
3.2.15 Output Trim ................................................................................ 3-13
3.2.16 CJC Selection............................................................................. 3-14
4. SELF-DIAGNOSTICS .................................................................................. 4-1
4.1 Error Message..................................................................................... 4-1
4.2 Warning ............................................................................................... 4-3
4.3 Logging Function................................................................................. 4-5
4.3.1 Error Log ...................................................................................... 4-5
4.3.2 Min/Max Log................................................................................. 4-5
4.3.3 Operation Time ............................................................................. 4-5
4.3.4 Power Check ................................................................................ 4-5
4.3.5 BRAIN communication BCC error occurrence rate ..................... 4-5
5. LIST OF PARAMETERS ............................................................................. 5-1
FD No. IM 01C50T03-01E 5th Edition: Sep. 2006 (KP) All Rights Reserved, Copyright © 1998, Yokogawa Electric Corporation
i
IM 01C50T03-01E
CONTENTS
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200 ............................. A-1
A.1 Operation Key Arrangement ...............................................................A-1
A.2 Function of Operation Keys ................................................................A-2
A.2.1 Entry of Alphanumeric Characters ...............................................A-2
A.2.2 Function Keys...............................................................................A-3
A.3 Calling of Menu Address..................................................................... A-4
A.3.1 Data Display with BT200 .............................................................. A-5
A.3.2 Data Setting with BT200 .............................................................. A-5
APPENDIX B. THE SENSOR MATCHING FUNCTION ..................................... B-1
B.1 Specifications ......................................................................................B-1
B.2 Operations (The Sensor Matching Function)...................................... B-2
APPENDIX C. SAFETY INSTRUMENTED SYSTEMS INSTALLATION ......... C-1
C.1 Scope and Purpose ............................................................................ C-1
C.2 Using the YTA for an SIS Application ................................................C-1
C.2.1 Safety Accuracy ...........................................................................C-1
C.2.2 Diagnostic Response Time ..........................................................C-1
C.2.3 Setup ............................................................................................C-1
C.2.4 Required Parameter Settings .......................................................C-1
C.2.5 Proof Testing................................................................................ C-1
C.2.6 Repair and Replacement .............................................................C-2
C.2.7 Startup Time .................................................................................C-2
C.2.8 Firmware Update..........................................................................C-2
C.2.9 Reliability Data ............................................................................. C-3
C.2.10 Lifetime Limits ..............................................................................C-3
C.2.11 Environmental Limits ....................................................................C-3
C.2.12 Application Limits .........................................................................C-3
C.3 Terms and Definitions......................................................................... C-3
REVISION RECORD
ii
IM 01C50T03-01E
1. INTRODUCTION

1. INTRODUCTION

Thank you for purchasing the YTA series Temperature Transmitter.
The YTA temperature transmitter is fully factory-tested according to the specifications indicated on your order.
This manual describes BRAIN communication func­tions of the model YTA110, YTA310, and YTA320 temperature transmitters and the various settings for temperature transmitter functions that can be set via the BT200 handheld terminal. The BT200 BRAIN terminal is required to change the settings of internal transmitter parameters.
In order for the YTA temperature transmitter to be fully functional and to operate in an efficient manner, read the instruction manual carefully to become familiar with the functions and operation as well as handling.
See User’s Manual IM 01C00A11-01E for details related to using the BT200 BRAIN terminal. For details of mounting, wiring and maintenance of this transmitter, see the separate User’s Manual IM 01C50B01-01E.

Regarding This Manual

• The following safety symbol marks are used in this Manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
•This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instrument.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
NOTE
Draws attention to information essential for understanding the operation and features.
1-1
IM 01C50T03-01E
1. INTRODUCTION

For Safe Use of Product

For the protection and safety of the operator and the instrument or the system including the instrument, please be sure to follow the instructions on safety described in this manual when handling this instru­ment. In case the instrument is handled in contradiction to these instructions, Yokogawa does not guarantee safety. Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
• In case of high process temperature, care should be taken not to burn yourself because the surface of the case reaches a high temperature.
• All installation shall comply with local installation requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about WIRING are not permitted for operators.
• Please confirm that voltages between the power supply and the instrument before connecting the power cables and that the cables are not powered before connecting.
(c) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact nearest YOKOGAWA office.
•Care should be taken to prevent the build up of drift, dust or other material on the display glass and name plate. In case of its maintenance, soft and dry cloth is used.

Warranty

•The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurred during the warranty period shall basically be repaired free of charge.
• In case of problems, the customer should contact the Yokogawa representative from which the instrument was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• Responsible party for repair cost for the problems shall be determined by Yokogawa based on our investigation.
• The Purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Failure or damage due to improper handling, use or storage which is out of design conditions.
- Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earth­quakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
(d) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
1-2
IM 01C50T03-01E
1. INTRODUCTION

ATEX Documentation

This procedure is only applicable to the countries in European Union.
GB
All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative.
DK
Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk. Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante.
E
Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano.
NL
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä. Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos Ex da ATEX estão disponíveis em Inglês, Alemão e Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die Betriebsanleitungen für Ex-Produkte in Ihrer Landessprache benötigen, setzen Sie sich bitte mit Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant.
Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger.
GR
       ATEX Ex   ,   .        Ex           Yokogawa   .
1-3
IM 01C50T03-01E

2. CONDITIONS OF COMMUNICATION LINE

2. CONDITIONS OF COMMUNICATION
LINE
2.1 Interconnection Between YTA
and BT200
WARNING
Do not attempt to use the BT200 in a dangerous environment where explosive gas or inflammable vapor is generated.
The BRAIN communication signal is superimposed onto the 4 to 20 mA DC analog signal. Since the modulated wave is a communication signal, superim­posing it on the normal signal will, from basic prin­ciples, cause no error in the DC component of the analog signal. Thus, monitoring can be performed via the BT200 while the transmitter is on-line.
As shown in Figure 2.1, there are two methods of connecting the transmitter and the BT200: the first is to use the BT200 connection hook provided in the terminal box and the other is to use a terminal board or relay terminals on the transmission line.
Load impedance : 3.3 mH or less Communication distance: 2 km (1.25 mile), when
CEV cable is used
Distance from the power line:
Output signal line : 15 cm (5.9 inch) or more
(do not use parallel wiring)
Input signal line : 100 cm (39.8 inch) or more
(do not use parallel wiring)
Input impedance of receiver connected to receiving resistor: 10 kmore (at 2.4 kHz)
Rc
Power supply

Figure 2.2 Communication line requirements

cc
YTA
RcR
BT200
F0202.EPS
4 to 20 mA DC signal
Relay
terminals
YTA
BT200
Figure 2.1 Connecting the BT200
transmission line
Control room
Terminal board
Distributor
BT200BT200BT200
F0201.EPS
2.2 Communication Line Re-
quirements
Configure a loop that satisfies the following conditions for mutual communication with the temperature transmitter.
Power supply voltage : 16.4 to 42 V DC Load resistance : R + 2Rc = 250 to 600 (See Figure 2.3 for the relationship between the power supply voltage and load resistance.) Load capacity : 0.22 µF or less
600
E–10.5
R=
Load
resistance
R
250
()
Figure 2.3 Relationship between power supply voltage
and load resistance
0.0236
10.5 16.4 24.7 42 Power supply voltage E (V)
Communication applicable range
F0203.EPS
2-1
IM 01C50T03-01E
3. OPERATION
IMPORTANT
Do not turn off the power to the transmitter immediately after setting the data using the BT200. If the transmitter is turned off less than 30 seconds after parameters have been set, the setting data will not be stored in the transmitter.

3.1 Parameters Description

The following outlines the function of the BRAIN parameters for the YTA.
• Sensor configuration See Page 3-4
When changing the sensor type from the current setting to another, it is necessary to change param­eter settings.
D10: SENSOR1 TYPE D20: SENSOR1 WIRE E10: SENSOR2 TYPE(YTA320 only) E20: SENSOR2 WIRE(YTA320 only)
•Process variable mapping See Page 3-5
Process variables can be assigned as the primary variable(PV), the secondary variable(SV), the tertiary variable(TV), and the quaternary variable(4V). The following items can be mapped as the process variables.
Sensor1, Sensor2*2, DIFFERENCE*2, AVERAGE*2, Sensor1-Term, Sensor2-Term*2, Terminal Temp (*2: These items are displayed for the model YTA320 only.)
B10: PV is, B20: SV is, B30: TV is, B40: 4V is
• Unit setting See Page 3-6
Choose the engineering unit for the process variables assigned as the PV, SV, TV, and 4V from degree C and Kelvin. When mV or ohm is specified as an input type, the unit is automatically set to mV or ohm.
B11: PV UNIT, B21: SV UNIT, B31: TV UNIT, B41: 4V UNIT
• Range setting See Page 3-6
Changing the range of the PV as a 4 to 20mA DC output. There are two ways to set the range value.
F10: LRV , F20: URV F30: AUTO LRV , F35: AUTO URV
.............
.............
.......................
.........................
Sensor type setting Wire connections setting
Setting by keypad
.
Setting by applying value

3. OPERATION

Damping time constant setting
See Page 3-6
Setting the response time of the transmitter smooths the output with rapid changes in input. The damping time constant can be set between 1 and 99 seconds.
B12: PV DAMPING, B22: SV DAMPING, B32: TV DAMPING, B42: 4V DAMPING
• Tag Number, Memo, Description and Date See Page 3-6
C10: TAG NO. ............... Tag number (16 characters)
O10: MEMO1, O20: MEMO2
...... MEMO (16 characters)
O30: DESCRIPTOR ...... DESCRIPTION (16 characters)
O40: DATE ..................... DATE (6 characters)
• Forced Output Function (Manual Output mode) See Page 3-7
Setting the transmitter to output a fixed current from -2.5 to 110 % in 0.1% increments for loop checks.
G10: OUTPUT MODE, G20: OUPUT VALUE
•Integral Indicator Display Function
See Page 3-7
The input and output values can be displayed, as can the type of temperature sensor and the number of wire connections.
M10: PROCESS DISP ...... Process variable display
selection
M20: %/mA DISP ................ Output display selection
M30: MATRIX DISP ............ Sensor type/wire connec-
tions display selection
M40: BAR GRAPH ..............Output bar graph display
setting
M50: DISP UPDATE ........... Selection of a cycle speed
for display
M55: Err- NO DISP ............. Error code display
• Burn Out Function See Page 3-10
Configure the current output value in sensor failure. Selectable from High, Low, and User setting values.
F40: BURN OUT, F41: BURN OUT VAL, F50: TX FAILURE
• Reverse Output Function See Page 3-10
To reverse the direction for a 4 to 20 mA DC output relative to input.
H10: REVERSE OUT
3-1
IM 01C50T03-01E
• Sensor Backup Function (YTA320 only) See Page 3-10
Configure the transmitter to automatically transfer the input from Sensor1 to Sensor2 when Sensor1 fails.
H20: SNSR BACKUP, H21: RETURN SNS1
• Copy the Setting Data to the BT200 See Page 3-11
Copy the setting data of one temperature transmitter to another via the BT200. (Uploading & Download­ing)
H30: UPLOAD SELCT
•Write Protect See Page 3-11
Configure the transmitter to enable/disable write protection parameters
H40: WRITE PROTCT
•Sensor Trim See Page 3-12
Adjust the integral characterization curve stored in memory.
J05: SNSR1 CLR, J10: SNSR1 ZERO, J20: SNSR1
GAIN ..... Sensor1 Trim
K05: SNSR2 CLR, K10: SNSR2 ZERO, K20: SNSR2 GAIN ... Sensor2 Trim (YTA320 only) J07: IN TRIM MODE
3. OPERATION
• Output Trim See Page 3-13
Used for fine adjustment of a 4 to 20 mA DC output.
L05: OUT CLR, J10: OUTPUT MODE, J20: OUT ZERO, J30: OUT GAIN
• Error Messages See Page 4-1
To show that the transmitter has malfunctioned.
A60: SELF CHECK
• Warnings See Page 4-3
To show that incorrect settings entered for a particular usage of the transmitter.
I59: WARNING, H50: WARNING ENBL
• Logging Function See Page 4-5
Store the errors and min/max process values.
3-2
IM 01C50T03-01E
Menu tree for YTA110 & YTA310
3. OPERATION
HOME
A:VARIABLE
B:SET VAR CON.
Menu tree for YTA320
HOME
A:VARIABLE
B:SET VAR CON.
A10:PV A11:mA of RANGE A12:% of RANGE A20:SV A30:TV A40:4V A50: TERM A60:SELF CHECK
B10:PV is B11:PV UNIT B12:PV DAMPING B13:PV DMP POINT B20:SV is B21:SV UNIT B22:SV DAMPING B30:TV is B31:TV UNIT B32:TV DAMPING B40:4V is B41:4V UNIT B42:4V DAMPING B51:TERM UNIT B60:SELF CHECK
A10:PV A11:mA of RANGE A12:% of RANGE A20:SV A30:TV A40:4V A50: TERM A60:SELF CHECK
B05:SET DIFF B10:PV is B11:PV UNIT B12:PV DAMPING B13:PV DMP POINT B20:SV is B21:SV UNIT B22:SV DAMPING B30:TV is B31:TV UNIT B32:TV DAMPING B40:4V is B41:4V UNIT B42:4V DAMPING B51:TERM UNIT B60:SELF CHECK
SET
C:SET TA G
D:SET SENSOR1
F:SET OUTPUT
G:FORCED OUT
H:SET MODE
I:INFORMATION
SET
C:SET TA G
D:SET SENSOR1
E:SET SENSOR2
F:SET OUTPUT
G:FORCED OUT
H:SET MODE
I:INFORMATION
C10:TAG NO. C60:SELF CHECK
D10:SENSOR1 TYPE D20:SENSOR1 WIRE D40:SENSOR1 D41:SNSR1 UNIT D60:SELF CHECK
F10:LRV F20:URV F30:AUTO LRV F35:AUTO URV F40:BURN OUT
F41:BURN OUT VAL F50:TX FAILURE F60:SELF CHECK
G10:OUTPUT MODE
G20:OUTPUT VALUE G60:SELF CHECK
H01:CJC SELECT
H02: CNST CJC TMP H10:REVERSE OUT H30:UPLOAD SELCT H40:WRITE PROTCT H50:WARNING ENBL H60:SELF CHECK
I10:PV LRL I11:PV URL I12:PV MIN SPAN I20:SNSR1 LSL I21:SNSR1 USL I40:TERM LSL I41:TERM USL I59:WARNING I60:SELF CHECK
C10:TAG NO. C60:SELF CHECK
D10:SENSOR1 TYPE D20:SENSOR1 WIRE D40:SENSOR1 D41:SNSR1 UNIT D60:SELF CHECK
E10:SENSOR2 TYPE E20:SENSOR2 WIRE E40:SENSOR2 TEMP E41:SNSR2 UNIT E60:SELF CHECK
F10:LRV F20:URV F30:AUTO LRV F35:AUTO URV F40:BURN OUT
F41:BURN OUT VAL F50:TX FAILURE F60:SELF CHECK
G10:OUTPUT MODE
G20:OUTPUT VALUE G60:SELF CHECK
H01:CJC SELECT
H02: CNST CJC TMP H10:REVERSE OUT H20:SNSR BACKUP
H21:RETURN SNSR1 H30:UPLOAD SELCT H40:WRITE PROTCT H50:WARNING ENBL H60:SELF CHECK
I10:PV LRL I11:PV URL I12:PV MIN SPAN I20:SNSR1 LSL I21:SNSR1 USL I30:SNSR2 LSL I31:SNSR2 USL I40:TERM LSL I41:TERM USL I59:WARNING I60:SELF CHECK
ADJ
J:CAL SENSOR1
L:CAL OUTPUT
M:SET METER
O:MEMO
P:RECORDS
ADJ
J:CAL SENSOR1
K:CAL SENSOR2
L:CAL OUTPUT
M:SET METER
O:MEMO
P:RECORDS
J05:SNSR1 CLR J07:IN TRIM MODE J10:SNSR1 ZERO J20:SNSR1 GAIN J30:SNSR1 SERIAL J60:SELF CHECK
L05:OUT CLR L10:OUTPUT MODE
L20:OUT ZERO L30:OUT GAIN
L60:SELF CHECK M10:PROCESS DISP
M20:%/mA DISP M30:MATRIX DISP M40:BAR GRAPH M50:DISP UPDATE M55:Err-NO DISP M60:SELF CHECK
O10:MEMO1 O20:MEMO2 O30:DESCRIPTOR O40:DATE O60:SELF CHECK
P05:LOG CLEAR P10:PV MIN LOG P11:PV MAX LOG P12:SV MIN LOG P13:SV MAX LOG P14:TV MIN LOG P15:TV MAX LOG P16:4V MIN LOG P17:4V MAX LOG P18:TERM MIN LOG P19:TERM MAX LOG P20:ERR LOG 1 P21:ERR LOG 2 P22:ERR LOG 3 P23:ERR LOG 4 P24:ERR LOG CLR P30:OPERATE TIME P31:POWER CHECK P40:BCC ERROR % P60:SELF CHECK
J05:SNSR1 CLR J07:IN TRIM MODE J10:SNSR1 ZERO J20:SNSR1 GAIN J30:SNSR1 SERIAL J60:SELF CHECK
K05:SNSR2 CAL CLR K10:SNSR2 ZERO K20:SNSR2 GAIN K30:SNSR2 SERIAL K60:SELF CHECK
L05:OUT CLR L10:OUTPUT MODE
L20:OUT ZERO L30:OUT GAIN
L60:SELF CHECK M10:PROCESS DISP
M20:%/mA DISP M30:MATRIX DISP M40:BAR GRAPH M50:DISP UPDATE M55:Err-NO DISP M60:SELF CHECK
O10:MEMO1 O20:MEMO2 O30:DESCRIPTOR O40:DATE O60:SELF CHECK
P05:LOG CLEAR P10:PV MIN LOG P11:PV MAX LOG P12:SV MIN LOG P13:SV MAX LOG P14:TV MIN LOG P15:TV MAX LOG P16:4V MIN LOG P17:4V MAX LOG P18:TERM MIN LOG P19:TERM MAX LOG P20:ERR LOG 1 P21:ERR LOG 2 P22:ERR LOG 3 P23:ERR LOG 4 P24:ERR LOG CLR P30:OPERATE TIME P31:POWER CHECK P40:BCC ERROR % P60:SELF CHECK
F0300.EPS
3-3
IM 01C50T03-01E
3. OPERATION

3.2 Setting Parameters

3.2.1 Sensor Configuration

When the sensor type or the number of wire connec­tions changes, the following parameters must be reset.
Sensor type setting;
D10: SENSOR1 TYPE, E10: SENSOR2 TYPE
Wire connections setting;
D20: SENSOR1 WIRE, E20: SENSOR2 WIRE
Figure 3.1 diagram shows the wire connections to the input terminals of the transmitter and sensor type selections for the parameters in each connection case. Note that TCs and mV are categorized as Group A and RTDs and ohm as Group B.
Check the connections between the input terminals and temperature sensors and set the correct sensor type and the number of wire connections for the parameters.
Sensor type selection
Thermocouple TYPE W3, W5 (ASTM988)
TYPE B, E, J, K, N, R, S, T (IEC 584) TYPE L, U (DIN 43710)
Resistance thermometer
Pt100, Pt200, Pt500 (IEC 751)
[2-, 3- or 4-wire] JPt100 (JIS)
Ni120 (STI INC), Cu
(SAMA RC21-4) DC voltage mV Resistance ohm [2- or 3-wire]
1-input model YTA110, YTA310, and YTA320
Thermocouple and DC voltage (TC & mV)
1
(+)
2
Sensor1
3
(–)
4 5
Resistance thermometer(RTD) and resistance (2-wire type)
Resistance thermometer(RTD) and resistance (3-wire type)
Resistance thermometer(RTD) (4-wire type)
(A)
1
Sensor1
2
(B)
3 4 5
(A)
1
(B) (B)
(A) (A) (B) (B)
Sensor1
2 3 4 5
1 2
Sensor1
3 4 5
Group A
Group B
Group B
Group B
* : Without ohm
Thermocouple and DC voltage (TC & mV)
Resistance thermometer(RTD) and resistance (2-wire type)
Resistance thermometer(RTD) and resistance (3-wire type)
Thermocouple(TC) & Resistance thermometer(RTD) and resistance (3-wire type)
*
2-input model YTA320
(+)
1 2
(–)
3 4
(+)
5
(A1)
1
(B1)
2 3
(B2)
4
(A2)
5
(A1)
1
(B1)
2
(B1)
3
(B2)
4
(B2)
5
(A2)
(+)
1
(–)
2
(B)
3 4
(B)
5
(A)
Figure 3.1 Input terminal wire connection diagram and sensor type categories
Sensor1
Sensor2
Sensor1
Sensor2
Sensor1 Sensor2
Sensor1 Sensor2
Group A Group A
Group B Group B
Group B Group B
Group A Group B
Group A
TYPE B (IEC584) TYPE W3 (ASTM988) TYPE W5 (ASTM988) TYPE E (IEC584) TYPE J (IEC584 TYPE K (IEC584) TYPE L (DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U (DIN43710)
Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4) ohm
mV
Group B
TYPE B (IEC584) TYPE W3 (ASTM988) TYPE W5 (ASTM988) TYPE E (IEC584) TYPE J (IEC584 TYPE K (IEC584) TYPE L (DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U (DIN43710)
Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4)
* Only for 2 or 3-wire type]
ohm [
mV
F0301.EPS
3-4
IM 01C50T03-01E
3. OPERATION
Example: Set Pt 100 and 4-wire type to Sensor1. (model YTA320)
<1>
PARAM D10:SENSOR1 TYPE Pt200 (IEC751) D20:SENSOR WIRE 3 WIRE D40:SENSOR1 TEMP
23.56 degC DATA DIAG PRNT ESC
<2>
SET D10:SENSOR1 TYPE Pt200 (IEC751) <Pt100 (IEC751) > <Pt200 (IEC751) > <Pt500 (IEC751) > <JPt100 (JIS ) >
<3>
SET D20:SENSOR1 WIRE 3 WIRE <3 WIRE > <4 WIRE > <2 WIRE >
TYPE B (IEC584) TYPE W3(ASTM988) TYPE W5(ASTM988) TYPE E (IEC584) TYPE J (IEC584) TYPE K (IEC584) TYPE L(DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U(DIN43710) Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4) ohm mV Non Connection
1. Select D: SET SENSOR1 to go to the screen (1).
2. Select “D10” and press [ENTER] to go to the
screen (2).
3. Select “Pt100” and press [ENTER] twice.
4. Check that “Pt100” has been set and press [OK].
ESC
5. To set the number of wire connections, select
D20 and press [ENTER].
6. Select “4 WIRE” and press
ESC
[ENTER] twice.
7. Press [OK].
Note: D40 indicates input values of
the sensor based on the settings at D10 and D20.
F0302.EPS

3.2.2 Process Variables Mapping

Process variable mapping;
B10: PV is, B20: SV is, B30: TV is, B40: 4V is
Process variables can be assigned as the primary variable(PV), the secondary variable(SV), the tertiary variable(TV), and the quaternary variable(4V). The PV always outputs a 4 to 20mA DC analog signal corre­sponding to Lower Range Value and Upper Range Value. Mapping process variables to the SV, TV, and 4V is optional.
The following items can be mapped as the process variables.
Sensor1 : Sensor1 input value. Sensor2 : Sensor2 input value. DIFFERENCE
*1,*2,*4
: Difference between
Sensor1 and Sensor2.
(Sensor1-Sensor2 or
Sensor2-Sensor1; speci­fied in B05: SET DIFF)
AVERAGE
*1,*4
: Average of Sensor1 and Sensor2. [(Sensor1 + Sensor2)/2]
Sensor1-Term
*4,*5
: Difference between
Sensor1 and terminal temperature
Sensor2-Term
*1,*4,*5
: Difference between
Sensor2 and terminal
temperature Terminal Temp : Terminal temperature Not used
*3
: Showing that a process
variable is not assigned.
*1: This item is displayed only when the YTA320 2-input
temperature transmitter is used. *2: The setting in B05 applies to the PV, SV, TV, and 4V. *3: “Not used” is not displayed for B10 since the PV
requires process variable mapping. *4: When this item is selected, the sensor types to be set
for D10(Sensor1) and E10(Sensor2) should be
selected from any one of the following three groups;
Temperature sensor(T/C and RTD), DC voltage or
resistance. The combination(for example, temperature
sensor and DC voltage input) would cause an incorrect
computation due to the different unit system and is not
allowed. *5: When this item is selected, DC voltage and resistance
input should not be set for D10(Sensor1) or
E10(Sensor2).
Example: Use two temperature sensors to map the difference (Sensor2-Sensor1) between Sensor1 and Sensor2 to the PV (the primary variable). Before mapping the process variable, complete the setting of the temperature sensor to be connected to Sensor1 and Sensor2.
Sensor1 setting: D10: SENSOR1 TYPE, D20:
SENSOR1 WIRE
Sensor2 setting: E10: SENSOR2 TYPE, E20:
SENSOR2 WIRE
PARAM B05:SET DIFF Sensor1-Sensor2 B10:PV is Sensor1 B11:PV UNIT degC
DATA DIAG PRNT ESC
SET B05:SET DIFF Sensor1-Sensor2 <Sensor1-Sensor2 > <Sensor2-Sensor1 >
SET B10:PV is Sensor1 <Sensor1 > <Sensor2 > <DIFFERENCE > <AVERAGE >
If the temperature sensor is correctly connected to Sensor1 and Sensor2, the setting content is reflected on A10: PV.
1. Set the content of “DIFFERENCE” for the
difference between Sensor1
and Sensor2.
Select B05: SET DIFF and
press [ENTER]
2. Select “Sensor2 - Sensor1” and press [ENTER] twice.
3. Press [OK].
ESC
4. Select B10: PV is and press [ENTER] for PV mapping.
5. Select “DIFFERENCE” and
ESC
press [ENTER] twice.
6. Press [OK].
F0303.EPS
3-5
IM 01C50T03-01E
3. OPERATION

3.2.3 Unit Setting

B11: PV UNIT, B21: SV UNIT, B31: TV UNIT, B41: 4V UNIT
Select the engineering unit for the process variables assigned as PV, SV, TV, and 4V from degree C, Kelvin, degree F* and degree R*. When mV or ohm is specified as an input type, the unit is automatically set to mV or ohms.
*: Degree F and degree R are available only when
optional code /D2 is specified.

3.2.4 Range Setting

(a) Changing the range with keypad
Lower range value setting;
F10: LRV, Upper range value setting; F20: URV
The range for the PV corresponding to the 4 to 20mA output signal is set at the factory before shipment. The procedure to rerange is as follows.
Example: Changing the measurement range from 0 to 100°C to 0 to 150°C .
PARAM F10:LRV 0 degC F20:URV 100 degC F30:AUTO LRV DISABLE
DATA DIAG PRNT ESC
PARAM F20:URV 0 degC + 150
DEL CLR ESC
Note : The unit selected in B11: PV UNIT is applied to the units used
for F10 and F20.
NOTE
When entering numeric values at the range setting, the value of URV must be greater than that of LRV. Range Setting Condition: URV > LRV
1. Select F20: URV and press [ENTER].
2. Input “150” and press [ENTER] twice.
3. Press [OK].
F0304.EPS

3.2.5 Setting Damping Time Constant

B12: PV DAMPING, B22: SV DAMPING, B32: TV DAMPING, B42: 4V DAMPING
Setting the response time of each Process Variable to make the output change very slowly with a rapid change in input. Set the value from 0 to 99 seconds.
If the time constant is set to 2 seconds, the transmitter calculates a reading every cycle using the damping equation, in order to make the output 63 percent of the input range after 2 seconds.
This damping time constant is normally set to work when the temperature make a step change within 2 percent of the output range. The damping can be changed using the “B13: PV DMP POINT” parameter.
Setting Damping Holding Point
B13: PV DMP POINT
This parameter is used to set the point where the transmitter conducts the PV damping operation, depending on a magnitude of the change in the input value. When the change value in percent exceeds the setting value, the transmitter outputs the signal without the damping operation. Set the value as a percent of span.
Example: Output pattern for the setting value of 10%
•Change value less then 10%
(C)
Input
10
0
(%)
Output
10
0
3 sec.
•Change value 10% or above
(C)
Input
10
0
(%)
Output
10
0
Time
9%
Assumed setting Renge: 0 to 100 C Damping time: 3 sec.
14%
(b) Changing the range while applying an
actual input
F30: AUTO LRV F35: AUTO URV
This feature allows the lower and upper range values to be setup automatically with the actual input applied.
3 sec.
Time

3.2.6 Tag Number and Memo Writing

Tag number (See Appendix A. Section A.3.2)
C10: TAG NO.
Up to sixteen alphanumeric characters can be entered. The tag number is as specified upon shipment.
3-6
IM 01C50T03-01E
F0325.EPS
Loading...
+ 28 hidden pages