Yokogawa YTA510 User Manual

Y
User’s
YTA Series
Manual
Temperature Transmitter (BRAIN Protocol)
IM 01C50T03-01E
okogawa Electric Corporation
5th Edition
CONTENTS
CONTENTS
1. INTRODUCTION..........................................................................................1-1
Regarding This Manual ............................................................................. 1-1
For Safe Use of Product ........................................................................... 1-2
Warranty .................................................................................................... 1-2
ATEX Documentation................................................................................ 1-3
2. CONDITIONS OF COMMUNICATION LINE............................................... 2-1
2.1 Interconnection Between YTA and BT200 ......................................... 2-1
2.2 Communication Line Requirements.................................................... 2-1
3. OPERATION ................................................................................................ 3-1
3.1 Parameters Description....................................................................... 3-1
3.2 Setting Parameters ............................................................................. 3-4
3.2.1 Sensor Configuration .................................................................... 3-4
3.2.2 Process Variables Mapping ......................................................... 3-5
3.2.3 Unit Setting................................................................................... 3-6
3.2.4 Range Setting............................................................................... 3-6
3.2.5 Setting Damping Time Constant .................................................. 3-6
3.2.6 Tag Number and Memo Writing ................................................... 3-6
3.2.7 Forced Output Function ............................................................... 3-7
3.2.8 Integral Indicator Display Function ............................................... 3-7
3.2.9 Burn Out Function ...................................................................... 3-10
3.2.10 Reverse Output Function ........................................................... 3-10
3.2.11 Sensor Backup Function (For Model YTA320).......................... 3-10
3.2.12 Copy the Setting Data................................................................ 3-11
3.2.13 Write Protect Function ................................................................ 3-11
3.2.14 Sensor Trim................................................................................ 3-12
3.2.15 Output Trim ................................................................................ 3-13
3.2.16 CJC Selection............................................................................. 3-14
4. SELF-DIAGNOSTICS .................................................................................. 4-1
4.1 Error Message..................................................................................... 4-1
4.2 Warning ............................................................................................... 4-3
4.3 Logging Function................................................................................. 4-5
4.3.1 Error Log ...................................................................................... 4-5
4.3.2 Min/Max Log................................................................................. 4-5
4.3.3 Operation Time ............................................................................. 4-5
4.3.4 Power Check ................................................................................ 4-5
4.3.5 BRAIN communication BCC error occurrence rate ..................... 4-5
5. LIST OF PARAMETERS ............................................................................. 5-1
FD No. IM 01C50T03-01E 5th Edition: Sep. 2006 (KP) All Rights Reserved, Copyright © 1998, Yokogawa Electric Corporation
i
IM 01C50T03-01E
CONTENTS
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200 ............................. A-1
A.1 Operation Key Arrangement ...............................................................A-1
A.2 Function of Operation Keys ................................................................A-2
A.2.1 Entry of Alphanumeric Characters ...............................................A-2
A.2.2 Function Keys...............................................................................A-3
A.3 Calling of Menu Address..................................................................... A-4
A.3.1 Data Display with BT200 .............................................................. A-5
A.3.2 Data Setting with BT200 .............................................................. A-5
APPENDIX B. THE SENSOR MATCHING FUNCTION ..................................... B-1
B.1 Specifications ......................................................................................B-1
B.2 Operations (The Sensor Matching Function)...................................... B-2
APPENDIX C. SAFETY INSTRUMENTED SYSTEMS INSTALLATION ......... C-1
C.1 Scope and Purpose ............................................................................ C-1
C.2 Using the YTA for an SIS Application ................................................C-1
C.2.1 Safety Accuracy ...........................................................................C-1
C.2.2 Diagnostic Response Time ..........................................................C-1
C.2.3 Setup ............................................................................................C-1
C.2.4 Required Parameter Settings .......................................................C-1
C.2.5 Proof Testing................................................................................ C-1
C.2.6 Repair and Replacement .............................................................C-2
C.2.7 Startup Time .................................................................................C-2
C.2.8 Firmware Update..........................................................................C-2
C.2.9 Reliability Data ............................................................................. C-3
C.2.10 Lifetime Limits ..............................................................................C-3
C.2.11 Environmental Limits ....................................................................C-3
C.2.12 Application Limits .........................................................................C-3
C.3 Terms and Definitions......................................................................... C-3
REVISION RECORD
ii
IM 01C50T03-01E
1. INTRODUCTION

1. INTRODUCTION

Thank you for purchasing the YTA series Temperature Transmitter.
The YTA temperature transmitter is fully factory-tested according to the specifications indicated on your order.
This manual describes BRAIN communication func­tions of the model YTA110, YTA310, and YTA320 temperature transmitters and the various settings for temperature transmitter functions that can be set via the BT200 handheld terminal. The BT200 BRAIN terminal is required to change the settings of internal transmitter parameters.
In order for the YTA temperature transmitter to be fully functional and to operate in an efficient manner, read the instruction manual carefully to become familiar with the functions and operation as well as handling.
See User’s Manual IM 01C00A11-01E for details related to using the BT200 BRAIN terminal. For details of mounting, wiring and maintenance of this transmitter, see the separate User’s Manual IM 01C50B01-01E.

Regarding This Manual

• The following safety symbol marks are used in this Manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
•This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instrument.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
NOTE
Draws attention to information essential for understanding the operation and features.
1-1
IM 01C50T03-01E
1. INTRODUCTION

For Safe Use of Product

For the protection and safety of the operator and the instrument or the system including the instrument, please be sure to follow the instructions on safety described in this manual when handling this instru­ment. In case the instrument is handled in contradiction to these instructions, Yokogawa does not guarantee safety. Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
• In case of high process temperature, care should be taken not to burn yourself because the surface of the case reaches a high temperature.
• All installation shall comply with local installation requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about WIRING are not permitted for operators.
• Please confirm that voltages between the power supply and the instrument before connecting the power cables and that the cables are not powered before connecting.
(c) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact nearest YOKOGAWA office.
•Care should be taken to prevent the build up of drift, dust or other material on the display glass and name plate. In case of its maintenance, soft and dry cloth is used.

Warranty

•The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurred during the warranty period shall basically be repaired free of charge.
• In case of problems, the customer should contact the Yokogawa representative from which the instrument was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• Responsible party for repair cost for the problems shall be determined by Yokogawa based on our investigation.
• The Purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Failure or damage due to improper handling, use or storage which is out of design conditions.
- Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earth­quakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
(d) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
1-2
IM 01C50T03-01E
1. INTRODUCTION

ATEX Documentation

This procedure is only applicable to the countries in European Union.
GB
All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative.
DK
Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk. Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante.
E
Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano.
NL
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä. Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos Ex da ATEX estão disponíveis em Inglês, Alemão e Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die Betriebsanleitungen für Ex-Produkte in Ihrer Landessprache benötigen, setzen Sie sich bitte mit Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant.
Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger.
GR
       ATEX Ex   ,   .        Ex           Yokogawa   .
1-3
IM 01C50T03-01E

2. CONDITIONS OF COMMUNICATION LINE

2. CONDITIONS OF COMMUNICATION
LINE
2.1 Interconnection Between YTA
and BT200
WARNING
Do not attempt to use the BT200 in a dangerous environment where explosive gas or inflammable vapor is generated.
The BRAIN communication signal is superimposed onto the 4 to 20 mA DC analog signal. Since the modulated wave is a communication signal, superim­posing it on the normal signal will, from basic prin­ciples, cause no error in the DC component of the analog signal. Thus, monitoring can be performed via the BT200 while the transmitter is on-line.
As shown in Figure 2.1, there are two methods of connecting the transmitter and the BT200: the first is to use the BT200 connection hook provided in the terminal box and the other is to use a terminal board or relay terminals on the transmission line.
Load impedance : 3.3 mH or less Communication distance: 2 km (1.25 mile), when
CEV cable is used
Distance from the power line:
Output signal line : 15 cm (5.9 inch) or more
(do not use parallel wiring)
Input signal line : 100 cm (39.8 inch) or more
(do not use parallel wiring)
Input impedance of receiver connected to receiving resistor: 10 kmore (at 2.4 kHz)
Rc
Power supply

Figure 2.2 Communication line requirements

cc
YTA
RcR
BT200
F0202.EPS
4 to 20 mA DC signal
Relay
terminals
YTA
BT200
Figure 2.1 Connecting the BT200
transmission line
Control room
Terminal board
Distributor
BT200BT200BT200
F0201.EPS
2.2 Communication Line Re-
quirements
Configure a loop that satisfies the following conditions for mutual communication with the temperature transmitter.
Power supply voltage : 16.4 to 42 V DC Load resistance : R + 2Rc = 250 to 600 (See Figure 2.3 for the relationship between the power supply voltage and load resistance.) Load capacity : 0.22 µF or less
600
E–10.5
R=
Load
resistance
R
250
()
Figure 2.3 Relationship between power supply voltage
and load resistance
0.0236
10.5 16.4 24.7 42 Power supply voltage E (V)
Communication applicable range
F0203.EPS
2-1
IM 01C50T03-01E
3. OPERATION
IMPORTANT
Do not turn off the power to the transmitter immediately after setting the data using the BT200. If the transmitter is turned off less than 30 seconds after parameters have been set, the setting data will not be stored in the transmitter.

3.1 Parameters Description

The following outlines the function of the BRAIN parameters for the YTA.
• Sensor configuration See Page 3-4
When changing the sensor type from the current setting to another, it is necessary to change param­eter settings.
D10: SENSOR1 TYPE D20: SENSOR1 WIRE E10: SENSOR2 TYPE(YTA320 only) E20: SENSOR2 WIRE(YTA320 only)
•Process variable mapping See Page 3-5
Process variables can be assigned as the primary variable(PV), the secondary variable(SV), the tertiary variable(TV), and the quaternary variable(4V). The following items can be mapped as the process variables.
Sensor1, Sensor2*2, DIFFERENCE*2, AVERAGE*2, Sensor1-Term, Sensor2-Term*2, Terminal Temp (*2: These items are displayed for the model YTA320 only.)
B10: PV is, B20: SV is, B30: TV is, B40: 4V is
• Unit setting See Page 3-6
Choose the engineering unit for the process variables assigned as the PV, SV, TV, and 4V from degree C and Kelvin. When mV or ohm is specified as an input type, the unit is automatically set to mV or ohm.
B11: PV UNIT, B21: SV UNIT, B31: TV UNIT, B41: 4V UNIT
• Range setting See Page 3-6
Changing the range of the PV as a 4 to 20mA DC output. There are two ways to set the range value.
F10: LRV , F20: URV F30: AUTO LRV , F35: AUTO URV
.............
.............
.......................
.........................
Sensor type setting Wire connections setting
Setting by keypad
.
Setting by applying value

3. OPERATION

Damping time constant setting
See Page 3-6
Setting the response time of the transmitter smooths the output with rapid changes in input. The damping time constant can be set between 1 and 99 seconds.
B12: PV DAMPING, B22: SV DAMPING, B32: TV DAMPING, B42: 4V DAMPING
• Tag Number, Memo, Description and Date See Page 3-6
C10: TAG NO. ............... Tag number (16 characters)
O10: MEMO1, O20: MEMO2
...... MEMO (16 characters)
O30: DESCRIPTOR ...... DESCRIPTION (16 characters)
O40: DATE ..................... DATE (6 characters)
• Forced Output Function (Manual Output mode) See Page 3-7
Setting the transmitter to output a fixed current from -2.5 to 110 % in 0.1% increments for loop checks.
G10: OUTPUT MODE, G20: OUPUT VALUE
•Integral Indicator Display Function
See Page 3-7
The input and output values can be displayed, as can the type of temperature sensor and the number of wire connections.
M10: PROCESS DISP ...... Process variable display
selection
M20: %/mA DISP ................ Output display selection
M30: MATRIX DISP ............ Sensor type/wire connec-
tions display selection
M40: BAR GRAPH ..............Output bar graph display
setting
M50: DISP UPDATE ........... Selection of a cycle speed
for display
M55: Err- NO DISP ............. Error code display
• Burn Out Function See Page 3-10
Configure the current output value in sensor failure. Selectable from High, Low, and User setting values.
F40: BURN OUT, F41: BURN OUT VAL, F50: TX FAILURE
• Reverse Output Function See Page 3-10
To reverse the direction for a 4 to 20 mA DC output relative to input.
H10: REVERSE OUT
3-1
IM 01C50T03-01E
• Sensor Backup Function (YTA320 only) See Page 3-10
Configure the transmitter to automatically transfer the input from Sensor1 to Sensor2 when Sensor1 fails.
H20: SNSR BACKUP, H21: RETURN SNS1
• Copy the Setting Data to the BT200 See Page 3-11
Copy the setting data of one temperature transmitter to another via the BT200. (Uploading & Download­ing)
H30: UPLOAD SELCT
•Write Protect See Page 3-11
Configure the transmitter to enable/disable write protection parameters
H40: WRITE PROTCT
•Sensor Trim See Page 3-12
Adjust the integral characterization curve stored in memory.
J05: SNSR1 CLR, J10: SNSR1 ZERO, J20: SNSR1
GAIN ..... Sensor1 Trim
K05: SNSR2 CLR, K10: SNSR2 ZERO, K20: SNSR2 GAIN ... Sensor2 Trim (YTA320 only) J07: IN TRIM MODE
3. OPERATION
• Output Trim See Page 3-13
Used for fine adjustment of a 4 to 20 mA DC output.
L05: OUT CLR, J10: OUTPUT MODE, J20: OUT ZERO, J30: OUT GAIN
• Error Messages See Page 4-1
To show that the transmitter has malfunctioned.
A60: SELF CHECK
• Warnings See Page 4-3
To show that incorrect settings entered for a particular usage of the transmitter.
I59: WARNING, H50: WARNING ENBL
• Logging Function See Page 4-5
Store the errors and min/max process values.
3-2
IM 01C50T03-01E
Menu tree for YTA110 & YTA310
3. OPERATION
HOME
A:VARIABLE
B:SET VAR CON.
Menu tree for YTA320
HOME
A:VARIABLE
B:SET VAR CON.
A10:PV A11:mA of RANGE A12:% of RANGE A20:SV A30:TV A40:4V A50: TERM A60:SELF CHECK
B10:PV is B11:PV UNIT B12:PV DAMPING B13:PV DMP POINT B20:SV is B21:SV UNIT B22:SV DAMPING B30:TV is B31:TV UNIT B32:TV DAMPING B40:4V is B41:4V UNIT B42:4V DAMPING B51:TERM UNIT B60:SELF CHECK
A10:PV A11:mA of RANGE A12:% of RANGE A20:SV A30:TV A40:4V A50: TERM A60:SELF CHECK
B05:SET DIFF B10:PV is B11:PV UNIT B12:PV DAMPING B13:PV DMP POINT B20:SV is B21:SV UNIT B22:SV DAMPING B30:TV is B31:TV UNIT B32:TV DAMPING B40:4V is B41:4V UNIT B42:4V DAMPING B51:TERM UNIT B60:SELF CHECK
SET
C:SET TA G
D:SET SENSOR1
F:SET OUTPUT
G:FORCED OUT
H:SET MODE
I:INFORMATION
SET
C:SET TA G
D:SET SENSOR1
E:SET SENSOR2
F:SET OUTPUT
G:FORCED OUT
H:SET MODE
I:INFORMATION
C10:TAG NO. C60:SELF CHECK
D10:SENSOR1 TYPE D20:SENSOR1 WIRE D40:SENSOR1 D41:SNSR1 UNIT D60:SELF CHECK
F10:LRV F20:URV F30:AUTO LRV F35:AUTO URV F40:BURN OUT
F41:BURN OUT VAL F50:TX FAILURE F60:SELF CHECK
G10:OUTPUT MODE
G20:OUTPUT VALUE G60:SELF CHECK
H01:CJC SELECT
H02: CNST CJC TMP H10:REVERSE OUT H30:UPLOAD SELCT H40:WRITE PROTCT H50:WARNING ENBL H60:SELF CHECK
I10:PV LRL I11:PV URL I12:PV MIN SPAN I20:SNSR1 LSL I21:SNSR1 USL I40:TERM LSL I41:TERM USL I59:WARNING I60:SELF CHECK
C10:TAG NO. C60:SELF CHECK
D10:SENSOR1 TYPE D20:SENSOR1 WIRE D40:SENSOR1 D41:SNSR1 UNIT D60:SELF CHECK
E10:SENSOR2 TYPE E20:SENSOR2 WIRE E40:SENSOR2 TEMP E41:SNSR2 UNIT E60:SELF CHECK
F10:LRV F20:URV F30:AUTO LRV F35:AUTO URV F40:BURN OUT
F41:BURN OUT VAL F50:TX FAILURE F60:SELF CHECK
G10:OUTPUT MODE
G20:OUTPUT VALUE G60:SELF CHECK
H01:CJC SELECT
H02: CNST CJC TMP H10:REVERSE OUT H20:SNSR BACKUP
H21:RETURN SNSR1 H30:UPLOAD SELCT H40:WRITE PROTCT H50:WARNING ENBL H60:SELF CHECK
I10:PV LRL I11:PV URL I12:PV MIN SPAN I20:SNSR1 LSL I21:SNSR1 USL I30:SNSR2 LSL I31:SNSR2 USL I40:TERM LSL I41:TERM USL I59:WARNING I60:SELF CHECK
ADJ
J:CAL SENSOR1
L:CAL OUTPUT
M:SET METER
O:MEMO
P:RECORDS
ADJ
J:CAL SENSOR1
K:CAL SENSOR2
L:CAL OUTPUT
M:SET METER
O:MEMO
P:RECORDS
J05:SNSR1 CLR J07:IN TRIM MODE J10:SNSR1 ZERO J20:SNSR1 GAIN J30:SNSR1 SERIAL J60:SELF CHECK
L05:OUT CLR L10:OUTPUT MODE
L20:OUT ZERO L30:OUT GAIN
L60:SELF CHECK M10:PROCESS DISP
M20:%/mA DISP M30:MATRIX DISP M40:BAR GRAPH M50:DISP UPDATE M55:Err-NO DISP M60:SELF CHECK
O10:MEMO1 O20:MEMO2 O30:DESCRIPTOR O40:DATE O60:SELF CHECK
P05:LOG CLEAR P10:PV MIN LOG P11:PV MAX LOG P12:SV MIN LOG P13:SV MAX LOG P14:TV MIN LOG P15:TV MAX LOG P16:4V MIN LOG P17:4V MAX LOG P18:TERM MIN LOG P19:TERM MAX LOG P20:ERR LOG 1 P21:ERR LOG 2 P22:ERR LOG 3 P23:ERR LOG 4 P24:ERR LOG CLR P30:OPERATE TIME P31:POWER CHECK P40:BCC ERROR % P60:SELF CHECK
J05:SNSR1 CLR J07:IN TRIM MODE J10:SNSR1 ZERO J20:SNSR1 GAIN J30:SNSR1 SERIAL J60:SELF CHECK
K05:SNSR2 CAL CLR K10:SNSR2 ZERO K20:SNSR2 GAIN K30:SNSR2 SERIAL K60:SELF CHECK
L05:OUT CLR L10:OUTPUT MODE
L20:OUT ZERO L30:OUT GAIN
L60:SELF CHECK M10:PROCESS DISP
M20:%/mA DISP M30:MATRIX DISP M40:BAR GRAPH M50:DISP UPDATE M55:Err-NO DISP M60:SELF CHECK
O10:MEMO1 O20:MEMO2 O30:DESCRIPTOR O40:DATE O60:SELF CHECK
P05:LOG CLEAR P10:PV MIN LOG P11:PV MAX LOG P12:SV MIN LOG P13:SV MAX LOG P14:TV MIN LOG P15:TV MAX LOG P16:4V MIN LOG P17:4V MAX LOG P18:TERM MIN LOG P19:TERM MAX LOG P20:ERR LOG 1 P21:ERR LOG 2 P22:ERR LOG 3 P23:ERR LOG 4 P24:ERR LOG CLR P30:OPERATE TIME P31:POWER CHECK P40:BCC ERROR % P60:SELF CHECK
F0300.EPS
3-3
IM 01C50T03-01E
3. OPERATION

3.2 Setting Parameters

3.2.1 Sensor Configuration

When the sensor type or the number of wire connec­tions changes, the following parameters must be reset.
Sensor type setting;
D10: SENSOR1 TYPE, E10: SENSOR2 TYPE
Wire connections setting;
D20: SENSOR1 WIRE, E20: SENSOR2 WIRE
Figure 3.1 diagram shows the wire connections to the input terminals of the transmitter and sensor type selections for the parameters in each connection case. Note that TCs and mV are categorized as Group A and RTDs and ohm as Group B.
Check the connections between the input terminals and temperature sensors and set the correct sensor type and the number of wire connections for the parameters.
Sensor type selection
Thermocouple TYPE W3, W5 (ASTM988)
TYPE B, E, J, K, N, R, S, T (IEC 584) TYPE L, U (DIN 43710)
Resistance thermometer
Pt100, Pt200, Pt500 (IEC 751)
[2-, 3- or 4-wire] JPt100 (JIS)
Ni120 (STI INC), Cu
(SAMA RC21-4) DC voltage mV Resistance ohm [2- or 3-wire]
1-input model YTA110, YTA310, and YTA320
Thermocouple and DC voltage (TC & mV)
1
(+)
2
Sensor1
3
(–)
4 5
Resistance thermometer(RTD) and resistance (2-wire type)
Resistance thermometer(RTD) and resistance (3-wire type)
Resistance thermometer(RTD) (4-wire type)
(A)
1
Sensor1
2
(B)
3 4 5
(A)
1
(B) (B)
(A) (A) (B) (B)
Sensor1
2 3 4 5
1 2
Sensor1
3 4 5
Group A
Group B
Group B
Group B
* : Without ohm
Thermocouple and DC voltage (TC & mV)
Resistance thermometer(RTD) and resistance (2-wire type)
Resistance thermometer(RTD) and resistance (3-wire type)
Thermocouple(TC) & Resistance thermometer(RTD) and resistance (3-wire type)
*
2-input model YTA320
(+)
1 2
(–)
3 4
(+)
5
(A1)
1
(B1)
2 3
(B2)
4
(A2)
5
(A1)
1
(B1)
2
(B1)
3
(B2)
4
(B2)
5
(A2)
(+)
1
(–)
2
(B)
3 4
(B)
5
(A)
Figure 3.1 Input terminal wire connection diagram and sensor type categories
Sensor1
Sensor2
Sensor1
Sensor2
Sensor1 Sensor2
Sensor1 Sensor2
Group A Group A
Group B Group B
Group B Group B
Group A Group B
Group A
TYPE B (IEC584) TYPE W3 (ASTM988) TYPE W5 (ASTM988) TYPE E (IEC584) TYPE J (IEC584 TYPE K (IEC584) TYPE L (DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U (DIN43710)
Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4) ohm
mV
Group B
TYPE B (IEC584) TYPE W3 (ASTM988) TYPE W5 (ASTM988) TYPE E (IEC584) TYPE J (IEC584 TYPE K (IEC584) TYPE L (DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U (DIN43710)
Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4)
* Only for 2 or 3-wire type]
ohm [
mV
F0301.EPS
3-4
IM 01C50T03-01E
3. OPERATION
Example: Set Pt 100 and 4-wire type to Sensor1. (model YTA320)
<1>
PARAM D10:SENSOR1 TYPE Pt200 (IEC751) D20:SENSOR WIRE 3 WIRE D40:SENSOR1 TEMP
23.56 degC DATA DIAG PRNT ESC
<2>
SET D10:SENSOR1 TYPE Pt200 (IEC751) <Pt100 (IEC751) > <Pt200 (IEC751) > <Pt500 (IEC751) > <JPt100 (JIS ) >
<3>
SET D20:SENSOR1 WIRE 3 WIRE <3 WIRE > <4 WIRE > <2 WIRE >
TYPE B (IEC584) TYPE W3(ASTM988) TYPE W5(ASTM988) TYPE E (IEC584) TYPE J (IEC584) TYPE K (IEC584) TYPE L(DIN43710) TYPE N (IEC584) TYPE R (IEC584) TYPE S (IEC584) TYPE T (IEC584) TYPE U(DIN43710) Pt100 (IEC751) Pt200 (IEC751) Pt500 (IEC751) JPt100 (JIS) Ni120 (STI INC) Cu (SAMA RC21-4) ohm mV Non Connection
1. Select D: SET SENSOR1 to go to the screen (1).
2. Select “D10” and press [ENTER] to go to the
screen (2).
3. Select “Pt100” and press [ENTER] twice.
4. Check that “Pt100” has been set and press [OK].
ESC
5. To set the number of wire connections, select
D20 and press [ENTER].
6. Select “4 WIRE” and press
ESC
[ENTER] twice.
7. Press [OK].
Note: D40 indicates input values of
the sensor based on the settings at D10 and D20.
F0302.EPS

3.2.2 Process Variables Mapping

Process variable mapping;
B10: PV is, B20: SV is, B30: TV is, B40: 4V is
Process variables can be assigned as the primary variable(PV), the secondary variable(SV), the tertiary variable(TV), and the quaternary variable(4V). The PV always outputs a 4 to 20mA DC analog signal corre­sponding to Lower Range Value and Upper Range Value. Mapping process variables to the SV, TV, and 4V is optional.
The following items can be mapped as the process variables.
Sensor1 : Sensor1 input value. Sensor2 : Sensor2 input value. DIFFERENCE
*1,*2,*4
: Difference between
Sensor1 and Sensor2.
(Sensor1-Sensor2 or
Sensor2-Sensor1; speci­fied in B05: SET DIFF)
AVERAGE
*1,*4
: Average of Sensor1 and Sensor2. [(Sensor1 + Sensor2)/2]
Sensor1-Term
*4,*5
: Difference between
Sensor1 and terminal temperature
Sensor2-Term
*1,*4,*5
: Difference between
Sensor2 and terminal
temperature Terminal Temp : Terminal temperature Not used
*3
: Showing that a process
variable is not assigned.
*1: This item is displayed only when the YTA320 2-input
temperature transmitter is used. *2: The setting in B05 applies to the PV, SV, TV, and 4V. *3: “Not used” is not displayed for B10 since the PV
requires process variable mapping. *4: When this item is selected, the sensor types to be set
for D10(Sensor1) and E10(Sensor2) should be
selected from any one of the following three groups;
Temperature sensor(T/C and RTD), DC voltage or
resistance. The combination(for example, temperature
sensor and DC voltage input) would cause an incorrect
computation due to the different unit system and is not
allowed. *5: When this item is selected, DC voltage and resistance
input should not be set for D10(Sensor1) or
E10(Sensor2).
Example: Use two temperature sensors to map the difference (Sensor2-Sensor1) between Sensor1 and Sensor2 to the PV (the primary variable). Before mapping the process variable, complete the setting of the temperature sensor to be connected to Sensor1 and Sensor2.
Sensor1 setting: D10: SENSOR1 TYPE, D20:
SENSOR1 WIRE
Sensor2 setting: E10: SENSOR2 TYPE, E20:
SENSOR2 WIRE
PARAM B05:SET DIFF Sensor1-Sensor2 B10:PV is Sensor1 B11:PV UNIT degC
DATA DIAG PRNT ESC
SET B05:SET DIFF Sensor1-Sensor2 <Sensor1-Sensor2 > <Sensor2-Sensor1 >
SET B10:PV is Sensor1 <Sensor1 > <Sensor2 > <DIFFERENCE > <AVERAGE >
If the temperature sensor is correctly connected to Sensor1 and Sensor2, the setting content is reflected on A10: PV.
1. Set the content of “DIFFERENCE” for the
difference between Sensor1
and Sensor2.
Select B05: SET DIFF and
press [ENTER]
2. Select “Sensor2 - Sensor1” and press [ENTER] twice.
3. Press [OK].
ESC
4. Select B10: PV is and press [ENTER] for PV mapping.
5. Select “DIFFERENCE” and
ESC
press [ENTER] twice.
6. Press [OK].
F0303.EPS
3-5
IM 01C50T03-01E
3. OPERATION

3.2.3 Unit Setting

B11: PV UNIT, B21: SV UNIT, B31: TV UNIT, B41: 4V UNIT
Select the engineering unit for the process variables assigned as PV, SV, TV, and 4V from degree C, Kelvin, degree F* and degree R*. When mV or ohm is specified as an input type, the unit is automatically set to mV or ohms.
*: Degree F and degree R are available only when
optional code /D2 is specified.

3.2.4 Range Setting

(a) Changing the range with keypad
Lower range value setting;
F10: LRV, Upper range value setting; F20: URV
The range for the PV corresponding to the 4 to 20mA output signal is set at the factory before shipment. The procedure to rerange is as follows.
Example: Changing the measurement range from 0 to 100°C to 0 to 150°C .
PARAM F10:LRV 0 degC F20:URV 100 degC F30:AUTO LRV DISABLE
DATA DIAG PRNT ESC
PARAM F20:URV 0 degC + 150
DEL CLR ESC
Note : The unit selected in B11: PV UNIT is applied to the units used
for F10 and F20.
NOTE
When entering numeric values at the range setting, the value of URV must be greater than that of LRV. Range Setting Condition: URV > LRV
1. Select F20: URV and press [ENTER].
2. Input “150” and press [ENTER] twice.
3. Press [OK].
F0304.EPS

3.2.5 Setting Damping Time Constant

B12: PV DAMPING, B22: SV DAMPING, B32: TV DAMPING, B42: 4V DAMPING
Setting the response time of each Process Variable to make the output change very slowly with a rapid change in input. Set the value from 0 to 99 seconds.
If the time constant is set to 2 seconds, the transmitter calculates a reading every cycle using the damping equation, in order to make the output 63 percent of the input range after 2 seconds.
This damping time constant is normally set to work when the temperature make a step change within 2 percent of the output range. The damping can be changed using the “B13: PV DMP POINT” parameter.
Setting Damping Holding Point
B13: PV DMP POINT
This parameter is used to set the point where the transmitter conducts the PV damping operation, depending on a magnitude of the change in the input value. When the change value in percent exceeds the setting value, the transmitter outputs the signal without the damping operation. Set the value as a percent of span.
Example: Output pattern for the setting value of 10%
•Change value less then 10%
(C)
Input
10
0
(%)
Output
10
0
3 sec.
•Change value 10% or above
(C)
Input
10
0
(%)
Output
10
0
Time
9%
Assumed setting Renge: 0 to 100 C Damping time: 3 sec.
14%
(b) Changing the range while applying an
actual input
F30: AUTO LRV F35: AUTO URV
This feature allows the lower and upper range values to be setup automatically with the actual input applied.
3 sec.
Time

3.2.6 Tag Number and Memo Writing

Tag number (See Appendix A. Section A.3.2)
C10: TAG NO.
Up to sixteen alphanumeric characters can be entered. The tag number is as specified upon shipment.
3-6
IM 01C50T03-01E
F0325.EPS
3. OPERATION
Memo
O10: MEMO1, O20: MEMO2
Up to sixteen alphanumeric characters can be entered.
Description
O30: DESCRIPTOR
Up to sixteen alphanumeric characters can be entered.
Date
O40: DATE
Six numeric values can be entered. Only a date recording function is provided; no internal clock function is provided, thus the date is not updated.

3.2.7 Forced Output Function

G10: OUTPUT MODE, G20: OUPUT VALUE
This feature can be used to output a fixed current from
3.6 mA (-2.5%) to 21.6 mA (110%) for loop checks.
Example: Outputting 16 mA (75%) constant current
PARAM G10:OUTPUT MODE AUTOMATIC MODE G60:SELF CHECK GOOD
DATA DIAG PRNT ESC
SET G10:OUTPUT MODE AUTOMATIC MODE <AUTOMATIC MODE > <MANUAL MODE mA > <MANUAL MODE % >
PARAM G10:OUTPUT MODE MANUAL MODE mA G20:OUTPUT VALUE 4 mA C60:SELF CHECK GOOD
DATA DIAG PRNT ESC
SET G20:OUTPUT VALUE 4 mA + 16
DEL CLR ESC
SET G20:OUTPUT VALUE 16 mA
FEED NO OK
1. Select G10: OUTPUT MODE
and press [ENTER].
2. Set "MANUAL MODE mA."
ESC
3. G20: OUTPUT VALUE is
displayed.
Select G20: OUTPUT VALUE
and press [ENTER].
4. Set "16."
5. Pressing [ENTER] twice outputs
a constant current.
If the transmitter is equipped
with the integral indicator, the LCD displays F.O.
6. Press [OK].
IMPORTANT
• Manual mode output is held for approximately 10 minutes and then released automatically after the time has elapsed. Even if the BT200 power supply is turned off or the communica­tion connector is disconnected during the test, it is held for approximately 10 minutes.
• To release the test output immediately, set “AUTOMATIC MODE” at G10 as seen in the figure above or turn off the transmitter.

3.2.8 Integral Indicator Display Function

If the transmitter is equipped with the integral indica­tor, the following items can be displayed in parameter settings.
(a) Display process variable
M10: PROCESS DISP
Displays PV value.
Also, if the output value is selected at M20, the process variable and output value are displayed alternately.
PV : Displays PV value SV : Displays SV value TV : Displays TV value 4V : Displays 4V value PV, SV : Displays PV and SV
PV, SV, TV : Displays PV, SV and TV
PV, SV, TV, 4V : Displays PV, SV, TV, and
INHIBIT : The process variable is
Used to select the process variable to be displayed on the LCD indicator. If more than one process is selected, they are displayed in sequence as the display update cycles. The appropriate unit is also
F03291
displayed for each process variable.
value alternately
value alternately
4V value alternately
not displayed.
"F.O." lit on.
F0305.EPS
(b) Display output value
M20: %/mA DISP
Displays output value.
Used to select the output indica­tions to be displayed on the LCD indicator. If two output indications are selected, they are displayed in sequence as the display update cycles.
F03292
3-7
IM 01C50T03-01E
3. OPERATION
mA : Displays output value in mA %: Displays output value in % mA, % : Displays output value in
mA and % alternately
INHIBIT : The output value is not
displayed
(c) Display sensor type/number of wire
connections
M30: MATRIX DISP
Displays PV value and
sensor type
Used to select the input sensor type and the number of wire connec­tions to be displayed on the LCD indicator. The displays of these items are synchronized with the process variable displays selected
F03293
at M10. Specifying “INHIBIT” under M10 disables the function of M30 for the display.
PROCESS : Displays process variables
(PV, SV, TV, or 4V.) TYPE : Displays sensor type WIRE : Displays number of wire
connections PROCESS, TYPE : Displays process and
sensor type alternately TYPE, WIRE : Displays sensor type and
number of wire
connections alternately INHIBIT : the sensor type and the
number of wire
connections is not
displayed
FAST : 1/2 of the normal cycle
speed NORMAL : Normal cycle speed SLOW : 1.5 times of the normal
cycle speed
NOTE
When operating under –10°C(14°F), the display response time may be reduced. In such a case, set the display cycle speed to “NORMAL” or “SLOW.”
(d) Display output bar graph
M40: BAR GRAPH
Displays bar graph.
Used to select output bar graph display ON/OFF.
F03292
SHOW : Displays analog output bar
graph
INHIBIT : No bar graph display
(e) Select a cycle speed for display
M50: DISP UPDATE
Used to select the update rate for the display on the LCD indicator. Process variables, output values, and error codes are displayed using this cycle speed.
3-8
IM 01C50T03-01E
(f) Display error code
M55: Err-NO DISP
If an error occurs, the error code is displayed on the LCD indicator.
SHOW : Error code is displayed INHIBIT : Error code is not displayed
Example of LCD display cycle The example of the LCD indicator is based on the following settings.
3. OPERATION
Integral indicator display parameter setting
M10: PROCESS DISP = PV, SV M20: %/mA DISP = mA M30: MATRIX DISP = PROCESS, TYPE M40: BAR GRAPH = SHOW
Process variable display PV value PV value SV value SV value %/mA display: mA Matorix display: Process variable Sensor type Process variable Sensor type Bar graph ON
Assumed current status and parameter settings
A10: PV = 50.0 degC A11: mA of RANGE = 12.00 mA A20: SV = 25.16 degC B10: PV is = Sensor1 B20: SV is = Sensor1-Term D10: SENSOR1 TYPE = TYPE B
F0306.EPS
3-9
IM 01C50T03-01E

3.2.9 Burn Out Function

(a) Sensor burn out
Configure the burn out mode in the case of sensor failure or disconnection. When the sensor failure is detected, the transmitter will output one of the follow­ing values.
F40: BURN OUT
Select from the followings:
LOW : Outputs 3.6 mA (-2.5%) HIGH : Outputs 21.6 mA (110%) USER mA : Output user set value in mA.
Settable 3.6 to 21.6 mA in F41
USER % : Output user set value in %.
Settable -2.5 to 110 % in F41
OFF : The burn out output is NOT
defined
F41: BURN OUT VAL
When “USER mA” or “USER %” is selected at F40:BURN OUT, F41:BURN OUT VAL is displayed. The output value setting range is 3.6 to 21.6 mA (-2.5 to 110%).
3. OPERATION
Displays "Abn." Displays "OUT."
F0308.EPS
Figure 3.2 Integral Indicator Display in Sensor Burn Out
(b) Confirming the output direction if Hard-
ware error occurs
F50: TX FAILURE
The output status of the transmitter in hardware failure is set by using a jumper on the CPU assembly. (See IM 01C50B01-01E section 3.2) The current setting can be checked in parameter D50: TX FAILURE.
HIGH : When an error occurs,
110%(21.6mA) or higher is output.
LOW : When an error occurs,
-5%(3.2mA) or lower is output.

3.2.10 Reverse Output Function

Example: Setting output to 20.8 mA in the event of sensor burn out
PARAM F40:BURN OUT HIGH F50:TX FAILURE HIGH F60:SELF CHECK GOOD
DIAG PRNT ESC
DATA
SET F40:BURN OUT HIGH <HIGH > <USER mA > <USER % > <OFF >
PARAM F40:BURN OUT USER mA F41:BURN OUT VAL
21.6 mA F50:TX FAILURE HIGH
DIAG PRNT ESC
DATA
SET F41:BURN OUT VAL
21.6 mA + 20.8
DEL CLR ESC
1. Select F40: BURN OUT and press [ENTER].
2. Select "USER mA" and press [ENTER] twice.
3. Press [OK].
ESC
4. Select F40: BURN OUT VAL and press [ENTER].
5. Set “20.8” and press [ENTER] twice.
6. Press [OK].
F0307.EPS
During sensor burn out time, the Sensor1 failure or the Sensor2 failure error message is generated. (See Section 4.1.1 for details.)
If the transmitter is equipped with the integral indica­tor, the LCD displays “Abn.” and “OUT” as shown in Figure 3.2.
H10: REVERSE OUT
To reverse the direction for a 4 to 20 mA DC output relative to input.

3.2.11 Sensor Backup Function (For Model YTA320)

IMPORTANT
To use sensor backup function, the following conditions must be met.
• “Sensor1” is mapped as the PV at B10: PV is.
• “Sensor2” is mapped as the SV at B20: SV is.
• “Sensor1” and “Sensor2” are both correct input status.
• “HIGH, LOW, User mA, or User %” is se­lected in the sensor burnout parameter setting at F40: BURN OUT
The sensor backup command sets the transmitter to automatically use Sensor2 as PV if Sensor1 fails. When the transmitter is in the Sensor Backup operation and switches to Sensor2, there will be no disruption in the 4 to 20 mA output. The error code for Sensor1 failure is shown on the integral indicator, and also the error message is sent to the BT200 that the Sensor1 failed and the sensor backup has been in operation. In case Sensor2 fails during the backup operation, the
3-10
IM 01C50T03-01E
3. OPERATION
transmitter will send the error code for Sensor2 failure to the integral indicator and the BT200, and outputs the “Sensor burnout” value.
(a) Setting of backup mode
H20: SNSR BACKUP
Set “ENABLE” at H20: SNSR BACKUP.
ENABLE : Activates backup mode, and
transmitter starts to observe.
DISABLE : Cancels backup mode.
IMPORTANT
Do not change the PV and SV mapping data when the sensor backup mode is active. Cancel the sensor backup mode to alter the mapping data.
(b) Returning from Sensor2 to Sensor1 during
the sensor backup operation
H21: RETURN SNS1
Once the transmitter enters the sensor backup opera­tion, H21:RETURN SNS1 appears on the BT200. This parameter is used to retrieve the output to the Sensor1 input value. Ensure that Sensor1 and Sensor2 are both correct input status, then;
Set “ENABLE” at H21:RETURN SNS1.
ENABLE : Switches to Sensor1 output. DISABLE : Maintains Sensor2 output status.
SET PRAM ONLY : Uploads the parameters
with respect to the opera­tion settings such as LRV and the sensor type.
ALL PRAM : Uploads the all param-
eters.
See the parameter list at the end of this manual for classification of the operation setting parameter groups and the parameter group unique to the equipment. See also the BT200 instruction manual, IM 1C0A11-01E, for the setting procedure.

3.2.13 Write Protect Function

(a) Software Write Protect Function
H40: WRITE PROTCT
The write protect function is used to prevent unautho­rized configuration data changes in the transmitter.
YES : Disables writing of all parameters
other than H40.
NO : Enables writing of all param-
eters.
If the transmitter is equipped with the integral indica­tor, the LCD displays “W.P.” when setting H40 to YES.
Example: Setting write protect on
SET H40:WRIT PROTCT NO <NO > <YES >
1. Select “YES” and press [ENTER] twice to enter the setting.
ESC
"W. P." lit on
IMPORTANT
In the sensor backup operation, even if the Sensor1 recovers, the Sensor2 input value continues to be output until “ENABLE” is set at H21: RETURN SNS1 or the transmitter's power is turned off and then on again.

3.2.12 Copy the Setting Data

H30: UPLOAD SELCT
This function is used to copy the setting data of one temperature transmitter to another.
Connect the temperature transmitter with the BT200 and record (UPLOAD) the setting data to the BT200 nonvolatile memory. By connecting the BT200 to other temperature transmitters, recorded data can be over­written (DOWNLOAD) on the transmitters.
The YTA series temperature transmitter handles the uploading data at two levels. It is necessary to specify the desired one before uploading data.
(b) Hardware Write Protect Function
Hardware write protect function is set up by Switch (SW2) on the CPU assembly. Under write protect status, any change operation is denied. If the transmit­ter is equipped with the integral indicator, the LCD displays “W.P.” when setting SW2 to “Y”.
3-11
IM 01C50T03-01E
F0309.EPS
3. OPERATION
Pin position of SW2
W P
Y
SW2
N
W P
Y
SW2
N
SW1 Burnout output direction upon hardware failure
CPU Assembly
Figure 3.3 SW2 setting
Write Protect Status
No
Yes
SW2 Hardware Write Protect
F0355.EPS

3.2.14 Sensor Trim

Each YTA transmitter is factory-characterized based on the standard sensor curve and uses the information to produce a process variable output. The sensor trim function is used to adjust to the transmitters internal interpretation of the input signal.
ZERO
Output
Input
One point trim
Figure 3.4 Trim function images
ZERO
Output
Input
Two points trim
(a) Zero/Gain Point Adjustment
J07: IN TRIM MODE J10: SNSR1 ZERO, J20: SNSR1 GAIN K10: SNSR2 ZERO, K20: SNSR2 GAIN ...YTA320 only
1) Connect the temperature transmitter and the calibration device as shown in Figure 3.5 and warm up for at least three minutes.
GAIN
F0310.EPS
a. Wiring of power supply and output
+ Output signal –
Load resistance
Voltmeter
b. Example of wiring of thermocouple or DC voltage input (1-input type)
1 2 3 4 5
c. Example of wiring of thermometer resistor 4-wire type (1-input type)
1 2 3 4 5
Figure 3.5 Example of wiring for calibration equipment
(+) (–)
DC voltage generator
or thermocouple
(A) (A) (B) (B)
Variable resistor
or thermometer resistor
F0311.EPS
2) Check the sensor type with the D: parameter.
3) Select the input trimming mode in J07:IN TRIM MODE. The following selections are offered.
V.R./ZERO&GAIN V.R./ZERO TEMP/ZERO&GAIN
TEMP/ZERO Select “V.R./ZERO&GAIN” or “V.R./ZERO” when the calibration device is DC voltage generator or Variable resistor, or select “TEMP/ZERO&GAIN” or “TEMP/ZERO” when the device is Temperature sensor.
4) Perform zero-point adjustment.
•When the input trimming mode is “V.R./
ZERO&GAIN” or “V.R./ZERO”, apply the value for the zero-point shown in the Table 3.1 depend­ing on the specified sensor type. Wait until the input from the calibration device becomes stable.
•When the input trimming mode is “TEMP/
ZERO&GAIN” or “TEMP/ZERO”, expose the temperature sensor to calibration temperature for the zero-point. Wait until the input from the temperature sensor becomes stable.
3-12
IM 01C50T03-01E
3. OPERATION
Table 3.1 Zero and Gain point value for Sensor trim
Sensor type
TC B,R,S,T +0[mV] +25[mV] E,J,K,N,W3,W5,L,U, mV +0[mV] +75[mV] RTD Pt100,JPt100,NI120,Cu +40[ohm] +330[ohm] Pt200, Pt500, ohm +40[ohm] +1600[ohm]
Setting value
Zero-point Gain-point
T0301.EPS
5) Enter the current input value in J10: SNSR1 ZERO (or K10: SNSR2 ZERO for YTA320).
6) Press [ENTER] twice and press [OK].
7) Perform gain-point adjustment if “V.R./ ZERO&GAIN” or “TEMP/ZERO&GAIN” is selected in J07:IN TRIM MODE.
•When the input trimming mode is “V.R./
ZERO&GAIN” apply the value for the gain-point shown in the Table 3.1 depending on the speci­fied sensor type. Wait until the input from the calibration device becomes stable.
•When the input trimming mode is “TEMP/
ZERO&GAIN”, expose the temperature sensor to calibration temperature for the gain-point. Wait until the input from the temperature sensor becomes stable.
8) Enter the current input value in J20: SNSR1 GAIN (or K20: SNSR2 GAIN for YTA320).
9) Press [ENTER] twice and press [OK].
NOTE
• First correct the ZERO point, then correct the GAIN point in two points calibration. When the GAIN point is adjusted, the ZERO point correction amount is also updated and written into the EEPROM.
• The calibration unit is changed to “mV” or “ohm” depending on the type of connected sensor when the input trimming mode is “V.R./ ZERO&GAIN” or “V.R./ZERO” or to tempera­ture unit selected at D41:SNSR1 UNIT.
(b) Returning to the factory set value
J05: SNSR1 CLR K05: SNSR2 CLR ...YTA320 only
To return to the factory set value, set “USER CAL CLEAR” or “USER CAL IGNORE” at J05: SNSR1 CLR for the Sensor1 and K05: SNSR2 CLR for the Sensor2.
USER CAL CLEAR : Clear user trim value
and return to the factory set value.
USER CAL IGNORE : Ignore user trim value
and return to the factory set value.
USER CAL ACT : Use user trim value.
NOTE
Regardless of restarting the transmitter, the “USER CAL ACT” is always set and the user trim value is used as the input signal unless it is cleared by “USER CAL CLEAR.”

3.2.15 Output Trim

(a) Zero/Gain Point Adjustment
L10: OUTPUT MODE, L20: OUT ZERO, L30: OUT GAIN
The output adjustment function can match the 4 mA and 20 mA output of the temperature transmitter to the reference meter such as a voltmeter.
1) Connect the temperature transmitter, 250
resistance and the voltmeter as shown in Figure 3.2.
2) Select L10: OUTPUT MODE and press [OK].
3) Select “MANUAL MODE 4mA” and press [ENTER] twice. (4 mA output status continues for 10 minutes.) Press [OK].
4) Select L20: OUT ZERO and press [OK].
5) Write the indicated value of the voltmeter to L20: OUT ZERO and press [ENTER] twice. (The temperature transmitter automatically corrects the difference between this value and the operation output.) Press [OK].
6) Select L10: OUTPUT MODE and press [OK].
7) Select “MANUAL MODE 20mA” and press [ENTER] twice. (20 mA output status continues for 10 minutes.) Press [OK].
8) Write the indicated value of the voltmeter at L30: OUT GAIN and Press [ENTER] twice. (The temperature transmitter automatically corrects the difference between this value and the operation output.) Press [OK].
Note 1: First correct the ZERO point, then correct the GAIN
point. If the ZERO point is not adjusted, GAIN point is not corrected.
(b) Returning to the factory set value
L05: OUT CLR
To return to the factory set value;
USER CAL CLEAR : Clear user trim value
and return to the factory set value.
3-13
IM 01C50T03-01E
USER CAL IGNORE : Ignore user trim value
and return to the factory set value.
USER CAL ACT : Use user trim value.
NOTE
Regardless of restarting the transmitter, the “USER CAL ACT” is always set and the user trim value is used as the input signal unless it is cleared by “USER CAL CLEAR.”

3.2.16 CJC Selection

For thermocouple input, terminal temperature measured by an internal sensor is used for Cold Junction Com­pensation function. In YTA, a constant value set by users can be used for the compensation function in place of the terminal temperature. If the constant value is set to “0", the compensation is not applied.
3. OPERATION
H01 : CJC SELECT
Select “Constant CJC” to use the constant value in place of terminal temperature;
INTERNAL CJC : Use the terminal tempera-
ture measured by an internal sensor.
CONSTANT CJC : Use the constant value set
by users.
H02 : CNST CJC TMP
This parameter appears only when “CONSTANT CJC” is selected for H01. Enter designated temperature value used for CJC function. This value is a constant and not incremented.
3-14
IM 01C50T03-01E
4. SELF-DIAGNOSTICS
The temperature transmitter continually monitors its own performance during normal operation. If an error occurs, it displays and records the error to the logging parameters, and with the integral indicator, an error code corresponding to the error is displayed.

4.1 Error Message

An error message is displayed on the BT200 when there is a problem with functions. The error message can be checked with the parameter number of each item 60:SELF CHECK. In addition, the error code is displayed when the transmitter is equipped with the integral indicator. See Table 4.1 below for the error contents corresponding to the error messages, error codes, and their countermeasures.

4. SELF-DIAGNOSTICS

Example: Checking by the BT200
PARAM A10:PV
125.06 degC A11:mA of RANGE
16.51 mV A12:% of RANGE
50.25 % DATA DIAG PRNT ESC
HOME A60:SELF CHECK ERROR <ERROR > <SENSOR1 FAILURE > <Sns Backup Start> <SENSOR2 FAILURE >
FEED PRNT ESC
1. Press [F2] (DIAG) to go to the diagnostics panel
(A60: SELF CHECK).
2. Error messages are shown when the error occurs.
Example: Checking by the integral indicator
Error codes are shown when the errors occur.
F0401.EPS
Note : To display the error code, set M55: Err-NO DISP to SHOW.
F0402.EPS
4-1
IM 01C50T03-01E
Table 4.1 List of Error Codes
Indicator
N/A GOOD Er-01 Output Too Low
Er-02 Output Too High
Er-03 Sensor1 Failure
Er-04 Sensor2 Failure (YTA320 only)
Er-05 S1 Signal Error
Er-06 S2 Signal Error (only YT A320)
Er-07 Amb Temp Low
Er-08 Amb Temp High
Er-09 Sns Backup Start (only YT A320)
Er-10 Illegal PV MAP
Er-11 Term Sns Failure
Er-12 EEPROM Failure
Er-13 CPU Failure
Er-14 AD Conv Failure
Er-15 Reverse Cal Fail
*1: See subsection 3.2.9 (a) ‘Sensor burn out.’ *2: See subsection 3.2.9 (b) ‘Confirming the output direction if Hardware error occurs.’
BT200 display Cause Output operation upon error Action
Input value is lower than the PV low range value.
Input value is higher than the PV Upper range value.
Sensor1 fails or disconnects from the terminal box.
Sensor2 fails or disconnects from the terminal box.
Outputs goes to minimum value. (3.68 mA, –2.0%)
Outputs goes maximum value. (20.8 mA, 105%)
If sensor1 is set as PV, burnout value is output. When sensor backup mode is set in YTA320, sensor2 input is used as PV.
If sensor1 value is set as PV, and the sensor backup mode is effect, the sensor burnout value is output.
Sensor1 input value greatly exceeds sensor measurement range. Sensor
Outputs goes to minimum value (3.68 mA) or
maximum value (20.8 mA). type or connection polarity may be incorrect.
Sensor2 input value greatly exceeds sensor measurement range. Sensor
Outputs goes to minimum
value (3.68 mA) or
maximum value (20.8 mA). type or connection polarity may be incorrect.
The ambient temperature exceeds the lower ambient
Continues to operate and
output. temperature limit of the transmitter.
The ambient temperature exceeds the upper ambient
Continues to operate and
output. temperature limit of the transmitter.
Sensor backup mode is in effect.
Sensor2 input is used as
PV. If sensor2 fails, the
transmitter operates with
burnout setting. There is a problem with the
PV mapping setting.
Check output status
immediately before error is
stored. Terminal block sensor has
failed. EEPROM failed.
Continues operate and
output.
The output goes to the
value set by the hardware
error mode jumper. Output circuit hardware
failure.
The output goes to the
value set by the hardware
error mode jumper. Input circuit hardware failure.
The output goes to the
value set by the hardware
error mode jumper. Confirmation calculation
result is bad.
The output goes to the
value set by the hardware
failure mode jumper.
4. SELF-DIAGNOSTICS
Check the LRV and adjust.
Check the URV and adjust.
• Check sensor for damage.
*1
• Check terminal connection.
• If in sensor backup mode refer to “Er-09.”
• Check sensor for damage.
• Check terminal connection.
• If sensor backup mode is set,
*1
repair wiring or replace damage sensors.
• Check sensor connections.
• Check sensor type selected.
• Check sensor connections.
• Check sensor type selected.
Use a heat source to raise the temperature of the transmitter.
Use a cooling source to lower the temperature of the transmitter.
Repair or replace sensor1 then enable sensor1 normal connection parameters, or repower the transmitter.
Correct the PV mapping.
Contact Service personnel.
Contact Service personnel.
*2
Contact Service personnel.
*2
Contact Service personnel.
*2
Contact Service personnel.
*2
T0401.EPS
4-2
IM 01C50T03-01E
4. SELF-DIAGNOSTICS

4.2 Warning

1) Warning and contents
The YTA series has a warning display function. The warning display function displays a warning when
there is an incorrect use status such that a setting is out of the specified range. Also, when the instrument is operated in other than standard operation mode, that status is displayed as a warning. Factory default setting is to not display the warning. To display the warning, set parameter H55: WARNING ENBL. Use parameter I59: WARNING to confirm the warning. See Table 4.2 for contents corresponding to warnings and counter­measures.
2) Setting warning display
Classified warnings can be displayed with H55: WARNING ENBL. The warning is classified as follows.
Setting : Occurs when an inappropriate
parameter setting is used such as out of the specification range of the transmitter.
Operation : Occurs when the input value for
the parameter setting is out of the setting range.
Special : Occurs when the parameter of a
function unique to the YTA is set during forced output operation or reverse output operation.
Setting Operation status Special Data to set
× × × 00000000
× × 3F1C0000
×
× ×
×
×
= display, × = no display
× C0030800 × FF1F0800
00E00108 3FFC0108 C0E30908 FFFF0908
T0403.EPS
Example: Displaying “Setting” and “Special” warning
SET H50:WARNING ENBL 00000000 3FFC0108
DEL CLR ESC
SET I59:WARNING GOOD
SET I59:WARNING WARNING < WARNING > <Out Manual Mode > <Can Write data >
1. Set “3FFC0108” in the Data to set column for F combination in the table above.
2. Press [ENTER] twice.
Warning can be checked with I59: WARNING.
ESC
ESC
F0403.EPS
4-3
IM 01C50T03-01E
Table 4.2 List of warnings
Parameter StatusClass
LRV Too Low
LRV Too High
URV Too Low
URV Too High
Setting
LRV>=URV setting
The LRV setting is lower than the temperature range (GS stated value).
The LRV setting is higher than the temperature range (GS stated value).
The URV setting is lower than the temperature range (GS stated value).
The URV setting is higher than the temperature range (GS stated value).
The LRV and URV settings are reversed.
4. SELF-DIAGNOSTICS
Countermeasure
Check the LRV setting.
Check the LRV setting.
Check the LRV setting.
Check the URV setting.
Set LRV < URV.
Operation
status
Special
Span Too Small
Illegal SV MAP
Illegal TV MAP
Illegal 4V MAP
Snsr1 Temp Low
Snsr1 Temp High
Snsr2 Temp Low
Snsr2 Temp High
Last SUM Area
Out Reverse Mode
Out Manual Mode
Snsr Backup Mode Soft Not Protect
The setting is lower than the recommended minimum span.
There is a problem with input (setting status) specified to SV map.
There is a problem with input (setting status) specified to TV map.
There is a problem with input (setting status) specified to 4V map.
Sensor1 input temperature is lower than the temperature range. The measurement range is a YTA series specification but not a range defined by sensor type.
Sensor1 input temperature is higher than the temperature range. The measurement range is a YTA series specification but not a range defined by sensor type.
Sensor2 input temperature is lower than the temperature range. The measurement range is a YTA series specification but not a range defined by sensor type.
Sensor2 input temperature is higher than the temperature range. The measurement range is a YTA series specification but not a range defined by sensor type.
The EEPROM checksum field is using the spare 4 (the last area). This means there is no spare area for writing the EEPROM checksum.
Output reverse mode operation is ongoing.
Forced output mode is on. In this case, the forced output is active or the output adjustment is performed.
The sensor backup mode is set. This is the parameter write enable status.
Unexpected write cannot be prevented.
Set URV-LRV to be set to greater than minimum span.
Correct SV mapping
Correct TV mapping
Correct 4V mapping
Check process temperature and set new LRV and URV values. Verify correct sensor selection for temperature range.
Check process temperature and set new LRV and URV values. Verify correct sensor selection for temperature range.
Check process temperature and set new LRV and URV values. Verify correct sensor selection for temperature range.
Check process temperature and set new LRV and URV values. Verify correct sensor selection for temperature range.
There is no problem with current operation. If EEPROM is damaged an EEPROM FAILURE will be indicated.
Turning output reverse mode OFF causes normal output .
The transmitter is in manual output mode. Return to normal operation if desired.
Turn the sensor backup mode OFF. Set the protect parameter to YES to enable write
protect mode and prevent unexpected changes.
T0402.EPS
4-4
IM 01C50T03-01E
4. SELF-DIAGNOSTICS

4.3 Logging Function

The YTA series has the capability to store useful information for trouble shooting.

4.3.1 Error Log

Up to four error histories are stored in the transmitter memory. The transmitter records an error that contin­ues to occur for more than 6 minutes.
P20:ERR LOG 1
This parameter records the latest errors that occurred.
P21:ERR LOG 2
This parameter records the last errors that have occurred.
P22:ERR LOG 3
This parameter records the 2nd to last error.
P23:ERR LOG 4
This parameter records the 3rd to last error.
P24: ERR LOG CLR ...... Error log clear processing
Clears all error logging data.
The % value is calculated from the number of BCC errors that occurred in BRAIN communication recep­tion frame and the number of transmissions/receptions.
Turning the power off clears the data.
*1 : This parameter should display the 0 % in normal operation. If
it consistently displays other than that, check the cable wiring for the transmitter.
*2 : BBC = BRAIN Communication Check.

4.3.2 Min/Max Log

Minimum and Maximum values of the process vari­ables and terminal temperature are stored in the transmitter memory. The logged data for the process variables except for the terminal temperature is reset at every power off.
To clear the logging data for process variables, select “ENABLE” at P05: ERR LOG CLR.

4.3.3 Operation Time

P30: OPERATE TIME
The transmitter’s operation time from the last power up is counted. The information is reset at every power off. The accuracy of time counting is not guaranteed. It is simply a reference.

4.3.4 Power Check

P31: POWER CHECK
By setting this parameter to START after power up, the transmitter can be checked to see if a temporary loss of power has occurred. This parameter is always reset to STOP at power off.

4.3.5 BRAIN communication BCC error occurrence rate

P40: BCC ERROR %
Displays the BCC error occurrence rate of BRAIN communication.
4-5
IM 01C50T03-01E
5. LIST OF PARAMETERS
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ●
● ● ● ● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ● ●

5. LIST OF PARAMETERS

*1 *2
NO. Parameter name Content R/W Remarks
01 MODEL Model R 02 TAG No. Tag number R 03 SELF CHECK Self-diagnostics R
Data initial value
YTA110 YTA310 YTA320
YTA110 YTA310 YTA320 Specified upon order GOOD
Applicable model
110 310 320 SET ALL
A VARIABLE Variable R A10 PV Primary variable R Unit specified in B11 A11 mA of RANGE Output in mA R 3.6 to 21.6 mA A12 % of RANGE Output in % R -2 to 110%
A20 SV Secondary variable R Unit specified in B21
A30 TV Tertiary variable R Unit specified in B31
A40 4V Fourth variable R Unit specified in B41 A50 TERM Terminal temperature R Unit specified in B51 A60 SELF CHECK Self-diagnostics R
GOOD, ERROR, Lower Output, Upper Output, Sensor1 Failure, Sensor2 Failure, S1 Signal Error, S2 Signal Error, Lower Amb TEMP, Upper Amb TEMP, Sns Backup Start, Illegal PV MAP, Term Sns Failure, EEPROM Failure, CPU
Failure, AD Conv Failure, Reverse Cal Fail B SET VAR CON. Set process variable condition R B05 SET DIFF Set differential direction W Sensor1-Sensor2, Sensor2-Sensor1 B10 PV is PV mapping W Sensor1, Sensor2*, DIFFERENCE*,
B11 PV UNIT PV engineering unit W degC, kelvin, degF
AVERAGE*, Sensor1-Term, Sensor2-Term*,
Terminal Temp
(* item can be selected only with YTA320)
*4
, degR
*4
B12 PV DAMPING PV damping time constant W 0 to 99 seconds B13 PV DMP POINT PV damping holding point W 0 to 99% B20 SV is SV mapping W Sensor1, Sensor2*, DIFFERENCE*,
B21 SV UNIT SV engineering unit W degC, kelvin, degF
B22 SV DAMPING SV damping time constant W 0 to 99 seconds B30 TV is TV mapping W Same as B20
B31 TV UNIT TV engineering unit W degC, kelvin, degF
B32 TV DAMPING TV damping time constant W 0 to 99 seconds B40 4V is 4V mapping W Same as B20
B41 4V UNIT 4V engineering unit W degC, kelvin, degF
B42 4V DAMPING 4V damping time constant W 0 to 99 seconds B51 TERM UNIT Terminal temperature unit W degC, kelvin, degF
AVERAGE*, Sensor1-Term, Sensor2-Term*,
Terminal Temp Not Used
(* item can be selected only with YTA320)
*4
, degR
*4
, degR
*4
, degR
*4
, degR
*4
*4
*4
*4
B60 SELF CHECK Self-diagnostics R Same as A60 C SET TAG Set Tag number R C10 TAG NO. Tag number W 16 alphanumeric characters C60 SELF CHECK Self-diagnostics R Same as A60 D SET SENSOR1 Set Sensor1 R
SENSOR1 TYPE
D10
D20 SENSOR1 WIRE Sensor1 wire connection W 2 WIRE, 3 WIRE, 4 WIRE
D40 SENSOR1 Sensor1 input value R Unit specified in D20
D41 SENSOR1 UNIT Sensor1 engineering unit W degC, kelvin, degF
D50 SNSR1 MATCH Sensor1 RTD sensor matching W DISABLE, ENABLE
D51 SNSR1 R0 Sensor1-specific constant (R0) W
D52 SNSR1 A IEC co-efficient W
D53 SNSR1 B IEC co-efficient W
D54 SNSR1 C IEC co-efficient W
D55 SNSR1 ALPHA Callendar-Van-Dusen co-efficient A W
D56 SNSR1 DELTA Callendar-Van-Dusen co-efficient B W
D57 SNSR1 BETA Callendar-Van-Dusen co-efficient C W
Sensor1 sensor type W TYPE B, E, J, K, L, N, R, S, T, U, W3, W5,
Pt100, Pt200, Pt500, JPt100, Ni120, Cu,
ohm, mV, Non Connection
*4
*4
, degR
D60 SELF CHECK Self-diagnostics R Same as A60
*1: indicates parameters which may be displayed depending on the setting for other parameters. indicates parameters available on the model with optional code /CM1. *2: RW: R = Read only, W = Read & Write *3: Indicates the parameter selected by H30: UPLOAD SELCT.
SET = SET PRAM ONLY parameters ALL = ALL PRAM parameters
*4: degF and degR can be selected only when optional code /D2 is specified. *5: This parameter will not be printed at PRINTOUT upon UPLOAD/DOWNLOAD, although the parameter itself is UPLOADED/DOWNLOADED.
5-1
Operation Operation Operation Operation Operation Operation Operation GOOD
Sensor1-Sensor2 Sensor1
degC 2 seconds 2 % Not Used
Sensor2
degC 2 seconds Not Used degC 2 seconds Not Used degC 2 seconds degC GOOD
Specified upon order GOOD
Pt100
3 WIRE Operation degC DISABLE +100 +3.9083 E-3
-5.7749 E-7
-4.183 E-12 +3.8505 E-3 +1.4998 E0 +1.0862 E-1 GOOD
IM 01C50T03-01E
*3
UPLOAD DATA
*5
5. LIST OF PARAMETERS
● ●
● ●
● ●
● ● ●
● ● ●
● ●
● ●
● ● ●
● ● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
*1 *2
NO. Parameter name Content R/W Remarks
Data initial value
YTA110 YTA310 YTA320
Applicable model
110 310 320 SET ALL
E SET SENSOR2 Set Sensor2 R
SENSOR2 TYPE
E10
SENSOR2 WIRE
E20
SENSOR2 TEMP
E40
E41 SENSOR2 UNIT Sensor2 engineering unit W degC, kelvin, degF
E50 SNSR2 MATCH Sensor1 RTD sensor matching W DISABLE, ENABLE
E51 SNSR2 R0 Sensor1-specific constant (R0) W
E52 SNSR2 A IEC co-efficient W E53 SNSR2 B IEC co-efficient W
E54 SNSR2 C IEC co-efficient W
E55 SNSR2 ALPHA Callendar-Van-Dusen co-efficient A W
E56 SNSR2 DELTA Callendar-Van-Dusen co-efficient B W
E57 SNSR2 BETA Callendar-Van-Dusen co-efficient C W
E60 SELF CHECK Self-diagnostics R Same as A60 F SET OUTPUT Set output R F10 LRV Lower range value W -5000 to +5000°C F20 URV Upper range value W -5000 to +5000°C F30 AUTO LRV F35 AUTO URV F40 BURN OUT Sensor error burn-out output W LOW, HIGH, USER mA, USER %, OFF
F41 BURN OUT VAL Sensor error burn-out value W 3.6 to 21.6mA (-2.5 to 110%) F50 TX FAILURE Hardware error burn-out R LOW, HIGH F60 SELF CHECK Self-diagnostics R Same as A60 G FORCED OUT Forced output R G10 OUTPUT MODE Output mode W AUTOMATIC MODE, MANUAL MODE mA,
OUTPUT VALUE
G20 G60 SELF CHECK Self-diagnostics R Same as A60 H SET MODE Set Modes R H01 CJC SELECT CJC Selection W Internal CJC, Constant CJC
H02 CNST CJC TMP Constant for CJC function W -5000 to +5000°C H10 REVERSE OUT Reverse output W DISABLE, ENABLE H20 SNSR BACKUP Sensor backup W DISABLE, ENABLE
RETURN SNS1
H21
UPLOAD SELCT
H30
WRITE PROTCT
H40
WARNING ENBL
H50
H60 SELF CHECK Self-diagnostics R Same as A60 IINFORMATION Information R I10 PV LRL PV lower range limit R I11 PV URL PV upper range limit R I12 PV MIN SPAN PV minimum span R
I20 SNSR1 LSL Sensor1 lower sensor limit R
I21 SNSR1 USL Sensor1 upper sensor limit R
I30 SNSR2 LSL Sensor2 lower sensor limit R
I31 SNSR2 USL Sensor2 upper sensor limit R I40 TERM LSL Terminal lower sensor limit R I41 TERM
USL
I59 WARNING Warning R GOOD/Warning, LRV Low Limited, LRV Upp
I60 SELF CHECK Self-diagnostics R Same as A60
*1: indicates parameters which may be displayed depending on the setting for other parameters. indicates parameters available on the model with optional code /CM1. *2: RW: R = Read only, W = Read & Write *3: Indicates the parameter selected by H30: UPLOAD SELCT.
SET= SET PRAM ONLY parameters ALL = ALL PRAM parameters
*4: degF and degR can be selected only when optional code /D2 is specified.
Sensor2 sensor type W TYPE B, E, J, K, L, N, R, S, T, U, W3, W5,
Pt100, Pt200, Pt500, JPt100, Ni120, Cu,
ohm, mV, Non Connection Sensor2 wire connection W 2 WIRE, 3 WIRE Sensor2 input value R Unit specified in E20
Automatic setting of lower range value Automatic setting of upper range value
WDISABLE, ENABLE(-5000 to +5000°C) WDISABLE, ENABLE(-5000 to +5000°C)
*4
, degR
*4
MANUAL MODE % Forced output value W 3.6 to 21.6mA (-2.5 to 110%)
Return Sensor1 W ENABLE, DISABLE Upload parameter select W SET PRAM ONLY, ALL PRAM Write protect W YES, NO Warning function W
00000000, 3F1C0000, C0030800, FF1F0800,
00E00108, 3FFC0108, C0E30908, FFFF0908
Terminal upper sensor limit R
Limited, URV Low Limited, URV Upp Limited,
LRV>=URV set, SPAN Below, Sns1 TEMP
Little, Sns1 TEMP Large, Sns2 TEMP Little,
Sns2 TEMP Large, Illegal SV MAP, Illegal TV
MAP, Illegal 4V MAP, Out Reverse Mode,
Out Manual Mode
Pt100
—3 WIRE
Operation
degC
DISABLE
+100
+3.9083 E-3
-5.7749 E-7
-4.183 E-12 +3.8505 E-3 +1.4998 E0 +1.0862 E-1
GOOD
+0(degC) +100(degC) DISABLE DISABLE
High
110(%)
High
GOOD
AUTOMATIC MODE
Operation
GOOD
Internal CJC
0 DISABLE DISABLE DISABLE
SET PRAM ONLY
NO
00000000
GOOD
-200(degC) +850(degC) +25(degC)
-200(degC) +850(degC)
— —
-40(degC) +85(degC)
GOOD
GOOD
-200(degC) +850(degC)
*3
UPLOAD DATA
5-2
IM 01C50T03-01E
5. LIST OF PARAMETERS
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ● ●
● ● ●
● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
● ● ●
*1 *2
NO. Parameter name Content R/W Remarks
J CAL SENSOR1 Sensor1 sensor trim R
J05 SNSR1 CLR Sensor1 trim value clear W USER CAL ACT, USER CAL IGNORE,
J07 IN TRIM MODE Input Sensor Trimming Mode W V.R/ZERO&GAIN, V.R/ZERO,
J10 SNSR1 ZERO Sensor1 zero point adjustment W
J20 SNSR1 GAIN Sensor1 gain point adjustment W
J30 SNSR1 SERIAL Sensor1 serial number W 000000 to 999999
USER CAL CLEAR
TEMP/ZERO&GAIN, TEMP/ZERO
J60 SELF CHECK Self-diagnostics R Same as A60 K CAL SENSOR2 Sensor2 sensor trim R
SNSR2 CLR
K05
K10 SNSR2 ZERO Sensor2 zero point adjustment W
K20 SNSR2 GAIN Sensor2 gain point adjustment W
K30 SNSR2 SERIAL Sensor2 serial number W 000000 to 999999
Sensor2 trim value clear W USER CAL ACT, USER CAL IGNORE,
USER CAL CLEAR
K60 SELF CHECK Self-diagnostics R Same as A60 L CAL OUTPUT Analog output trim R L05 OUT CLR Output trim value clear W USER CAL ACT, USER CAL IGNORE,
L10 OUTPUT MODE Output mode W AUTOMATIC MODE, MANUAL MODE 4mA,
L20 OUT ZERO Output zero point adjustment W 0.6V to 1.4V
L30 OUT GAIN Output gain point adjustment W 4.6V to 5.4V
USER CAL CLEAR
MANUAL MODE 20mA
L60 SELF CHECK Self-diagnostics R Same as A60
M SET METER Set Meter R
M10 PROCESS DISP Process variable display W PV, SV, TV, 4V, PV-SV, PV-SV-TV,
M20 %/mA DISP Output in % / mA display W mA, %, mA-%, INHIBIT
M30 MATRIX DISP Dot matrix display W PROCESS, TYPE, WIRE, PROCESS-TYPE, TYPE-WIRE, INHIBIT
M40 BAR GRAPH Output bar graph display W SHOW, INHIBIT
M50 DISP UPDATE Display update speed W FAST, NORMAL, SLOW
M55 Err-NO DISP Error number display W SHOW, INHIBIT
M60 SELF CHECK Self-diagnostics R Same as A60
PV-SV-TV-4V, INHIBIT
O MEMO Memo R O10 MEMO1 Memo 1 W 16 alphanumeric characters O20 MEMO2 Memo 2 W 16 alphanumeric characters O30 DESCRIPTOR Description W 16 alphanumeric characters O40 DATE Date W 6 alphanumeric characters O60 SELF CHECK Self-diagnostics R Same as A60 P RECORDS Records R P05 LOG CLEAR Log clear R DISABLE, ENABLE P10 PV MIN LOG PV minimum log R P11 PV MAX LOG PV maximum log R
P12 SV MIN LOG SV minimum log R
P13 SV MAX LOG SV maximum log R
P14 TV MIN LOG TV minimum log R
P15 TV MAX LOG TV maximum log R
P16 4V MIN LOG 4V minimum log R P17 4V MAX LOG 4V maximum log R P18 TERM MIN LOG P19
TERM MAX LOG Terminal maximum log R
Terminal minimum log R
P20 ERR LOG1 Error log 1 R Error message display P21 ERR LOG2 Error log 2 R Error message display P22 ERR LOG3 Error log 3 R Error message display P23 ERR LOG4 Error log 4 R Error message display P24 ERR LOG CLR Error log clear W DISABLE, ENABLE P30 OPERATE TIME Transmitter operation time (after R
instantaneous interrupt detection operation starts)
POWER CHECK
P31 history & detection start
P40 BCC ERROR % BRAIN communication BCC error R generation rate
Instantaneous interrupt detection W STOP, START
P60 SELF CHECK Self-diagnosis R Same as A60
*1: indicates parameters which may be displayed depending on the setting for other parameters. *2: RW: R = Read only, W = Read & Write *3: Indicates the parameter selected by H30: UPLOAD SELCT.
SET = SET PRAM ONLY parameters ALL = ALL PRAM parameters
*4: degF and degR can be selected only when optional code /D2 is specified. *5: This parameter will not be printed at PRINTOUT upon UPLOAD/DOWNLOAD, although the parameter itself is UPLOADED/DOWNLOADED.
5-3
Data initial value
YTA110 YTA310 YTA320
USER CAL ACT
V.R/ZERO&GAIN
0 0 0 GOOD
USER CAL ACT
0 0 0 GOOD
USER CAL ACT
AUTOMATIC MODE
0 0 GOOD
PV
mA PROCESS
SHOW NORMAL SHOW GOOD
(Blank) (Blank) (Blank) (Blank) GOOD
DISABLE Operation Operation Operation Operation Operation Operation Operation Operation 15°C 35°C GOOD GOOD GOOD GOOD DISABLE Operation
STOP
0 %
GOOD
Applicable model
110 310 320 SET ALL
*3
UPLOAD DATA
*5
*5
*5
IM 01C50T03-01E

APPENDIX A. OPERATION OF BRAIN TERMINAL BT200

APPENDIX A. OPERATION OF BRAIN
TERMINAL BT200

A.1 Operation Key Arrangement

Figure 5.3 shows the key pad layout of the BT200.
POWER
BT200
MENU A:VARIABLE B:SET VAR CON.
HOME SET ADJ ESC
BRAIN TERMINAL
LCD
8 lines with 21 characters each
Functions keys
Executes the commands displayed at the bottom of the screen.
Arrow keys
• Selects an item
•Moves the cursor
ENT keys
•Goes to the selected item
• Sets the entry data to the object communication instrument
Alphanumeric keys
• Enters a number
• Enters letters when pressed together with the shift key
Inverse video bar
Menu panel Parameter panel
MENU BATTERY A:VARIABLE B:SET VAR CON.
HOME SET ADJ ESC
Major parameters items A maximum of six items are displayed.
Figure A.1 Key arrangement and screen display of BT200
Message
PARAM Communi A10:PV
100.0 degC A11:mA of RANGE
16.00 mV A12:% of RANGE
50.0 %
DATA DIAG PRNT ESC
Function commands
A-1
Shift keys
Parameters data A maximum of three items are displayed.
F0A01.EPS
IM 01C50T03-01E
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200

A.2 Function of Operation Keys

A.2.1 Entry of Alphanumeric Characters

Numbers, codes, and letters can be entered in combina­tions of the alphanumeric keys and the SHIFT key.
• Entry of numbers, codes, and a space (0 to 9, ., –, )
Enter these items by using the alphanumeric key.
Example
of Entry
-4.3
1 -0.3
• Entry of letters
The letter on the same side of the key as the shift key that is pressed can be entered. Press the SHIFT keys first and then press an alphanumeric key. Press the SHIFT key each time when entering a letter.
Key Operation
F0A02.EPS
Entry of uppercase letters
CODE
CODE
CAPS CLR ESC
Entry of lowercase letters
caps
CLR ESC
F0A05.EPS
• Entry of codes
Codes can be entered by pressing the function key [F1] (CODE). Every time [F1] CODE is pressed, the codes are displayed at the cursor position in the order shown below.
/ . - , + * ) ( ' & % $ # " ! To enter characters after the codes above, move the
cursor using the [>] key before entry.
The letter on the left side of the alphanumeric key is entered.
Example
of Entry
WIC
J.B
Key Operation
The letter on the right side of the alphanumeric key is entered.
F0A03.EPS
F0A04.EPS
• Selection of uppercase/lowercase of letters
Uppercase and lowercase letters can be selected alternately by pressing the function key [F2] (CAPS).
Example
of Entry
l/m
(Lower­case letter)
Key Operation
( l ) ( m )( / )
F0A06.EPS
A-2
IM 01C50T03-01E

A.2.2 Function Keys

The functions of the function keys vary with the commands being displayed on the display screen.
MENU C:SET TAG D:SET SENEOR1 E:SET SENEOR2 F:SET OUTPUT G:FORCED OUT H:SET MODE
HOME SET ADJ ESC
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200
Command
ADJ CAPS/caps CLR COPY DATA DEL DIAG ESC FEED GO HOME LIST NO
OK PARM PON/POFF
PRNT SET SLOT STOP UTIL
Description
Calls up the zero-adjustment menu. Changes the uppercase/lowercase mode. Clears entered data/deletes all data. Prints parameters on the screen. Updates parameter data. Deletes one character. Calls up the self-check screen. Returns to the preceding screen. Paper feed. Starts print out. Calls up the home menu (A: DISPLAY). Prints all parameters of the menus. Setting stop/re-setting. Returns to the previous
screen. Goes to the next screen. Parameter number setting mode. Printer output of data whose setting was
changed Mode on/off. Changes to the prints mode. Calls up the setting menu. (B: SETTING) Returns to the slot selection screen. Stops printing. Transfers to the utility screen.
F0A07.EPS
A-3
IM 01C50T03-01E

A.3 Calling of Menu Address

APPENDIX A. OPERATION OF BRAIN TERMINAL BT200
STARTUP SCREEN
INITIAL DATA SCREEN
MENU SCREEN
±±WELCOME±±
BRAIN TERMINAL ID: BT200
check connection push ENTER key
UTIL FEED
PARAM 01:MODEL YTA320 02:TAG NO. YOKOGAWA 03:SELF CHECK GOOD
(HOME MENU SCREEN)
MENU A:VARIABLE B:SET VAR CON.
HOME SET ADJ ESC
OK
UTILITY
1.ID
2.SECURITY CODE
3.LANGUAGE SELECT
4.LCD CONTRAST
5.PRINTER ADJUST
The utility screen contains the following items.
1. BT200 ID settings
2. Security code settings
3. Switching language of messages
ESC
(Japanese or English)
4. LCD contrast setting
(UTIL)
(ESC)
(SET)
5. Setting print temperature (BT200-P00 only)
FUNC
1.MENU
2.UPLOAD TO BT200
3.DOWNLOAD TO INST
4.PRINT ALL DATA
HOME SET ADJ ESC
(ADJ)
(SET MENU SCREEN) (ADJ MENU SCREEN)
MENU C:SET TAG D:SET SENSOR1 E:SET SENSOR2 F:SET OUTPUT G:FORCED OUT H:SET MODE
HOME SET ADJ ESC
MENU J:CAL SENSOR1 K:CAL SENSOR2 L:CAL OUTPUT M:SET METER O:MEMO P:RECORDS
HOME SET ADJ ESC
PARA­METER SCREEN
SETUP SCREEN
PARAM A60:SELF CHECK GOOD
PARAM A20:SV
26.5 deg C DATA DIAG PRNT ESC
PARAM A10:PV
125.06 degC A11:mA of RANGE
16.51 mV A12:% of RANGE
50.25 % DATA DIAG PRNT ESC
SET C10:TAG NO. YOKOGAWA YOKOGAWA
CODE CAPS CLR ESC
PARAM C10:TAG NO. YOKOGAWA C60:SELF CHECK GOOD
DATA DIAG PRNT ESC
See, “BT200 Instruction Manual” for details concerning uploading and downloading parameters, and making printouts (BT200-P00).
Calling up menu address using the operating keys
PARAM J30:SNS1 SERIAL
PARAM J05:SNSR1 CLR USER CAL ACT
DATA DIAG PRNT ESCDATA DIAG PRNT ESC
J07:IN TRIM MODE V.R./ZERO&GAIN J10:SNSR1 ZERO
1.125 mV J20:SNSR1 GAIN
1.125 mV DATA DIAG PRNT ESC
F0A08.EPS
A-4
IM 01C50T03-01E
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200

A.3.1 Data Display with BT200

The following procedure is used to display data on the BT200 screen.
Display Description
Press the key to turn
<When power is off>
[STARTUP SCREEN]
––WELCOME–– BRAIN TERMINAL ID: BT200
check connection push ENTER key
UTIL FEED
[INITIAL DATA SCREEN]
PARAM 01:MODEL YTA320 02:TAG NO. YOKOGAWA 03:SELF CHECK GOOD
[HOME MENU SCREEN]
MENU A:VARIABLE B:SET VAL CON.
HOME SET ADJ ESC
on the BT200. “Please wait...” is displayed for several seconds and [Start display] is displayed.
Connect YTA and BT200 using a communication cable and press the key.
Displays the model name, the tag number, and diagnostics information. Press the (OK) key after confirmation. (The text specified upon order
OK
is set for TAG.)
While the highlight bar is at A: VARIABLE, press the key to enter the parameter display.

A.3.2 Data Setting with BT200

The following procedure is used to change YTA data settings.
Example: Changing C10 TAG to “FIC-la.”
Display Description
Press the key to turn on
<When power is off>
[STARTUP SCREEN]
––WELCOME–– BRAIN TERMINAL ID: BT200
check connection push ENTER key
UTIL FEED
[INITIAL DATA SCREEN]
PARAM 01:MODEL YTA320 02:TAG NO. YOKOGAWA 03:SELF CHECK GOOD
[HOME MENU SCREEN]
MENU A:VARIABLE B:SET VAL CON.
the BT200. “Please wait...” is displayed for several seconds and [Start display] is displayed.
Connect YTA and BT200 using a communication cable and press the key.
Displays the model name, the tag number, and diagnostics information. Press the (OK) key after confirmation. (The text specified upon order
OK
is set for TAG.)
Press the (SET) key to display SET menu panel.
[PARAMETER SCREEN]
PARAM A10:PV
125.06 degC A11:mA of RANGE
16.51 mV A12:% of RANGE
50.25 % DATA DIAG PRNT ESC
PARAM A10:PV
125.06 degC
A11:mA of RANGE
16.51 mV
A12:% of RANGE
50.25 % DATA DIAG PRNT ESC
• A maximum 3 items of data is displayed on one screen.
• Communication is executed at 5-second intervals. (Data is updated in a 5-second cycle.)
• Use
for page forward and item
selection.
Execution of function keys
F1 : Updates the current data.
Pressing this key forces communication with the connected equipment and the data of the equipment is read and displayed.
F2 : Displays the self-
diagnosis screen.
F3 : Displays the parameter
print screen.
F4 : Returns to the previous
screen (the menu screen)
F0A09.EPS
HOME SET ADJ
ESC
[SET MENU SCREEN]
MENU C.SET TAG D.SET SENSOR1 E.SET SENSOR2 E.SET OUTPUT F.FORCED OUT H:SET MODE
HOME SET ADJ
ESC
[PARAMETER SCREEN]
MENU C10:TAG YOKOGAWA C60:SELF CHECK GOOD
DATA DIAG PRNT
ESC
Select C: SETTING and press the key.
Select C10: TAG NO. and press the key.
F0A10.EPS
A-5
IM 01C50T03-01E
[SETUP SCREEN]
SET C10:TAG YOKOGAWA YOKOGAWA
CODE CAPS CLR
ESC
[SETUP SCREEN]
SET C10:TAG YOKOGAWA FIC-1a _
CODE caps CLE ESC
[CONFIRMATION SCREEN]
SET C10:TAG YOKOGAWA FIC-1a
PRINTER OFF F2:PRINTER ON
FEED POFF NO
[SETTING COMPLETED SCREEN]
SET C10:TAG FIC-1a
FEED NO OK
[PARAMETER SCREEN]
PARAM C10:TAG FIC-1a C60:SELF CHECK GOOD
Set the new TAG NO. (FIC-1A)
FOKOGAWA FIKOGAWA FICOGAWA FIC-GAWA FIC-1AWA
(caps)
FIC-1aWA FIC-1a
When you have made an entry mistake, return the cursor using the key, then reenter.
Set TAG NO. and press the key.
This is the panel for confirming set data. The set data items flash. When all items have been confirmed, press the again. (To go back to the setting panel, press the (NO) key.
(OK)
The YTA TAG NO. was overwritten. Press the (OK) key to return to the parameter panel. Press the (NO) key to return to the setting parameter.
APPENDIX A. OPERATION OF BRAIN TERMINAL BT200
DATA DIAG PRNT ESC
F0A11.EPS
A-6
IM 01C50T03-01E

APPENDIX B. THE SENSOR MATCHING FUNCTION

APPENDIX B. THE SENSOR MATCHING
FUNCTION

B.1 Specifications

Function: The sensor-specific constants can be pro­grammed into the transmitter.
Applicable model: YTA310 /CM1, YTA320 /CM1 RTD sensor: Pt100, Pt200, Pt500
Significant temperature measurement accuracy im­provement can be attained using a temperature sensor that is matched to a temperature transmitter. This matching process entails teaching the temperature transmitter the relationship between resistance and temperature for a specific RTD sensor. This relation­ship, approximated by the Callendar-Van Dusen equation, is described as:
Rt = R0 {1 + ( 1 + 0.01 ) t -  / 104 t2 -  / 10 ( t - 100 ) t3 }
where:Rt = Resistance (ohms) at Temperature t (C)
R0 = Sensor - Specific Constant (Resistance at t = 0 C)
B = Sensor - Specific Constant C = Sensor - Specific Constant (0 at t > 0 C)
These two equations are equivalent. A model YTA can cope with either case above-mentioned.
IMPORTANT
There is the following limitations for R0, , , , A, B, and C with the YTA.
•IT is necessary to enter the value, which is normalized by the exponential part specified for each parameter. See Table B.1.
It is necessary to enter the value, which is rounded off to three or two decimal places
8
specified for each parameter. See Table B.1.
When a three decimal place data is entered, it may be automatically changed to the four decimal place data that is equivalent to the input data.
Example: +3.809 E-3 +3.8089 E-3
= Sensor - Specific Constant = Sensor - Specific Constant = Sensor - Specific Constant (0 at t > 0 C)
The exact values for R0 , , , and are specific to each RTD sensor, and are obtained by testing each individual sensor at various temperatures. These constants are known as Callendar-Van Dusen con­stants.
Generally the constants R0, A, B, and C are also being used as the characteristic coefficients of the sensor instead of R0, , , and . These are derived from the IEC Standard Curve and the relationship is described as:
Rt = R0 [ 1 + At + Bt2 + C ( t - 100 ) t3 ] where:Rt = Resistance (ohms) at Temperature t (C)
R0 = Sensor - Specific Constant (Resistance at t = 0 C)
A = Sensor - Specific Constant
Table B.1
Number of
Item
decimal
places
R0 A B C
2 3 3 3 3 3 3
exponential
part
non E-3 (10 E-7 (10-7) E-12 (10 E-3 (10-3) E0 (10 E-1 (10-1)
-3
-12
0
Input
Example
+ 100.05
)
+ 3.908 E-3
- 5.802 E-7
)
- 0 E-12 + 3.850 E-3
)
+ 1.507 E0 + 0 E-1
Factory
Initial
+100 +3.9083 E-3
-5.7749 E-7
-4.183 E-12 +3.8505 E-3 +1.4998 E0 +1.0862 E-1
T0B01.EPS
B-1
IM 01C50T03-01E
APPENDIX B. THE SENSOR MATCHING FUNCTION
B.2 Operations (The Sensor
Matching Function)
IMPORTANT
This function is effective only in three kinds of sensors, Pt100, Pt200, and Pt500. Input relations between the sensor type and the value of R0 properly. When Pt100 is specified as an input type, the value close to 100 must be set to R0. When Pt500 is specified as input type, the value close to 500 must be set to R0. When the sensor type was changed, the Sensor Matching Parameters must be set up again or the Sensor Matching function must be set to “DISABLE”.
Example: To set Pt200, 3wire sensor as “Sensor 1”
input.
And to input R0, , , and values, as
sensor-specific constants.
F0B01.EPS
3-11.Input beta values and press [ENTER] twice. 3-12.Press [OK].
4. Enable the Sensor Matching function: 4-1. Select D50: SNSR1 MATCH and press
[ENTER]. 4-2. Select “ENABLE” and press [ENTER] twice. 4-3. Press [OK].
When “DISABLE” is selected in the step 4-2, tempera­ture is calculated by using the default value of R0, , , and .
If using the A, B, and C parameters, replace D55, D56 and D57 with D52, D53 and D54 in step 3-4 through 3-10.
If using two sensors with a Model YTA320, replace Dnn with Enn (nn is same number) and repeat the procedures for the second sensor.
1. Set the sensor type: 1-1. Select D10: SENSOR1 TYPE and press
[ENTER].
1-2. Select “Pt200 (IEC751)” and press
[ENTER] twice.
1-3. Press [OK].
2. Set the number of wires: 2-1. To set the number of wire connections, select
D20: SENSOR1 WIRE and press [ENTER]. 2-2. Select “3WIRE” and press [ENTER] twice. 2-3. Press [OK].
3. Set the sensor-specific constants: 3-1. Select D51: SNSR1 R0 and press [ENTER].
3-2. Input R0 values and press [ENTER] twice. 3-3. Press [OK]. 3-4. Select D55: SNSR1 ALPHA and press
[ENTER]. 3-5. Input alpha values and press [ENTER] twice. 3-6. Press [OK]. 3-7. Select D56: SNSR1 DELTA and press
[ENTER]. 3-8. Input delta values and press [ENTER] twice. 3-9. Press [OK]. 3-10.Select D57: SNSR1 BETA and press
[ENTER].
B-2
IM 01C50T03-01E

APPENDIX C. SAFETY INSTRUMENTED SYSTEMS INSTALLATION

APPENDIX C. SAFETY INSTRUMENTED
SYSTEMS INSTALLATION
WARNING
The contents of this appendix are cited from exida.com safety manual on the YTA series pressure transmitters specifically observed for the safety transmitter purpose. When using the YTA for Safety Instrumented Systems (SIS) application, the instructions and procedures in this section must be strictly followed in order to preserve the transmitter for that safety level.

C.1 Scope and Purpose

This section provides an overview of the user responsi­bilities for installation and operation of the YTA in order to maintain the designed safety level for Safety Instrumented Systems (SIS) applications. Items that will be addressed are proof testing, repair and replace­ment of the transmitter, reliability data, lifetime, environmental and application limits, and parameter settings.
C.2 Using the YTA for an SIS
Application

C.2.1 Safety Accuracy

The YTA has a specified safety accuracy of 2%. This means that the internal component failures are listed in the device failure rate if they will cause an error of 2% or greater.

C.2.2 Diagnostic Response Time

The YTA will report an internal failure within 8 seconds of the fault occurrence.

C.2.3 Setup

During installation the transmitter must be setup with engineering units parameters. This is typically done with a handheld terminal. These parameters must be verified during the installation to insure that the correct parameters are in the transmitter. Engineering range parameters can be verified by reading these parameters from the optional local display or by checking actual calibration of the transmitter.
The calibration of the transmitter must be performed after parameters are set.

C.2.4 Required Parameter Settings

The following parameters need to be set in order to maintain the designed safety integrity.
Table C.2.4 Required Parameter Settings
Item
Burnout direction switch
Write protection switch
To specify if the output should go 21.6 mA or higher or 3.6 mA or lower upon detection of an internal failure.
The write function should be disabled.
Description
TA0101.EPS

C.2.5 Proof Testing

The objective of proof testing is to detect failures within the transmitter that are not detected by the diagnostics of the transmitter. Of main concern are undetected failures that prevent the safety instrumented function from performing its intended function. See table C.2.5 for proof testing method.
The frequency of the proof tests (or the proof test interval) is to be determined in the reliability calcula­tions for the safety instrumented functions for which the YTA is applied. The actual proof tests must be performed more frequently or as frequently as specified in the calculation in order to maintain required safety integrity of the safety instrumented function.
The following tests need to be specifically executed when a proof test is performed. The results of the proof test need to be documented and this documentation should be part of a plant safety management system. Failures that are detected should be reported to Yokogawa.
The personnel performing the proof test of the trans­mitter should be trained in SIS operations including bypass procedures, YTA temperature transmitter maintenance, and company management of change procedures.
C-1
IM 01C50T03-01E
Table C.2.5 Proof Testing
Testing method Tools required Expected outcome Remarks
Analog Output Loop Test:
1. Bypass the safety PLC or take other appropriate action to avoid a false trip.
2. Send a HART or BRAIN command to the transmitter to go to the high alarm current output and verify that the analog current reaches that value.
3. Send a HART or BRAIN command to the transmitter to go to the low alarm current output and verify that the analog current reaches that value.
4. Use the HART or BRAIN communicator to view detailed device status to ensure no alarms or warnings are present in the transmitter.
5. Perform reasonability check on the sensor value(s) versus an independent estimate (i.e. from direct monitoring of BPCS value) to show current reading is good.
6. Restore the loop to full operation.
7. Remove the bypass from the safety PLC or otherwise restore normal operation.
Analog Output Loop Test and Temperature Spot Check:
1. Bypass the safety PLC or take other appropriate action to avoid a false trip.
2. Perform Analog Output Loop Test.
3. Verify the measurement for two temperature points.
4. Perform reasonability check of the housing temperature.
5. Restore the loop to full operation.
6. Remove the bypass from the safety PLC or otherwise restore normal operation.
APPENDIX C. SAFETY INSTRUMENTED SYSTEMS INSTALLATION
• Handheld terminal Proof Test Coverage =61%
• Handheld terminal Proof Test Coverage =96%
The output needs to be monitored to assure that the transmitter communicates the correct signal.
The output needs to be monitored to assure that the transmitter communicates the correct signal.
TA0102.EPS

C.2.6 Repair and Replacement

If repair is to be performed with the process online, the YTA will need to be bypassed during the repair. The user should setup appropriate bypass procedures.
In the unlikely event that the YTA has a failure, the failures that are detected should be reported to Yokogawa.
When replacing the YTA, the procedure in the installa­tion manual should be followed.
The personnel performing the repair or replacement of the YTA should have a sufficient skill level.

C.2.7 Startup Time

The YTA generates a valid signal within 5 seconds of power-on startup.

C.2.8 Firmware Update

In case firmware updates are required, they will be performed at factory. The replacement responsibilities are then in place. The user will not be required to perform any firmware updates.
C-2
IM 01C50T03-01E
APPENDIX C. SAFETY INSTRUMENTED SYSTEMS INSTALLATION

C.2.9 Reliability Data

A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is available from Yokogawa with all failure rates and failure modes.
The YTA is certified up to SIL2 for use in a simplex (1oo1) configuration, depending on the PFDavg respectively PFH calculation of the entire Safety Instrumented Function.
The development process of the YTA is certified up to SIL3, allowing redundant use of the transmitter up to this Safety Integrity Level, depending the PFDavg respectively PFH calculation of the entire Safety Instrumented Function.
When using the transmitter in a redundant configura­tion, the use of a common cause factor (-factor) of 5% is suggested. If the owner-operator of the plant would institute common cause failure training and more detailed maintenance procedures for avoiding common cause failure, a beta factor of 2% would be applicable.

C.2.10Lifetime Limits

The expected lifetime of the YTA is 50 years. The reliability data listed in the FMEDA report is only valid for this period. The failure rates of the YTA may increase sometime after this period. Reliability calculations based on the data listed in the FMEDA report for YTA lifetimes beyond 50 years may yield results that are too optimistic, i.e. the calculated Safety Integrity Level will not be achieved.

C.2.11Environmental Limits

The environmental limits of the YTA are specified in the user’s manual IM 01C50B01-01E.

C.2.12Application Limits

The application limits of the YTA are specified in the user’s manual IM 01C50B01-01E. If the transmitter is used outside of the application limits, the reliability data listed in C.2.9 becomes invalid.
SIS Safety Instrumented System –
Implementation of one or more Safety Instrumented Functions. A SIS is composed of any combination of sensor(s), logic
solver(s), and final element(s). SLC Safety Lifecycle Safety Freedom from unacceptable risk
of harm Functional Safety The ability of a system to carry
out the actions necessary to
achieve or to maintain a defined
safe state for the equipment /
machinery / plant / apparatus
under control of the system Basic Safety The equipment must be designed
and manufactured such that it
protects against risk of damage to
persons by electrical shock and
other hazards and against resulting
fire and explosion. The protection
must be effective under all
conditions of the nominal
operation and under single fault
condition Verification The demonstration for each phase
of the life-cycle that the (output)
deliverables of the phase meet the
objectives and requirements
specified by the inputs to the
phase. The verification is usually
executed by analysis and / or
testing Validation The demonstration that the safety-
related system(s) or the
combination of safety-related
system(s) and external risk
reduction facilities meet, in all
respects, the Safety Requirements
Specification. The validation is
usually executed by testing.

C.3 Terms and Definitions

FMEDA Failure Mode Effect and
Diagnostic Analysis SIF Safety Instrumented Function SIL Safety Integrity Level
Safety Assessment The investigation to arrive at a
judgment - based on evidence - of the safety achieved by safety­related systems
Further definitions of terms used for safety techniques and measures and the description of safety related systems are given in IEC 61508-4.
C-3
IM 01C50T03-01E

Revision Record

• Manual No. : IM 01C50T03-01E
• Title : YTA series Temperature Transmitter (BRAIN Protocol)
Edition Date Page Revised item
1st Sep. 1998
2nd Jan. 1999 Error correction
3rd June 1999 Add Appendix B The Sensor Matching Function
Contents B-1 to B-3
New Publication
Add Appendix B The Sensor Matching Function
4th
5th Sep. 2006 Remove style code
July 2000
Cover Contents 3-3 3-16 4-3 5-2, 5-3
Cover Contents 1-1 to 1-3 3-2, 3-3, 5-3, A-4 3-11 3-12 4-2, 5-1 C-1 to C-3
Add style No. Add 3.2.16 Add parameters H01 & H02 Add "3.2.16 CJC Selection" Change T ab le data (T0403E) Change of parameter table
Add Appendix C Change Introduction and add ATEX documentation
Add a parameter Add Hardware Write Protect Function
Change Sensor Trim procedure Add an error item New Publication
Written by Product Marketing Dept.
Transmitters Center Industrial Automation Systems Business Div. Yokogawa Electric Corporation
Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180, JAPAN
Loading...