YOKOGAWA YTA50 User Manual

User’s Manual
6th Edition : Feb. 2007 (YK) All Rights Reserved, Copyright © 1998, Yokogawa Electric Corporation
YTA50 Temperature Transmitter
IM 01C50C01-01E
6th Edition
YOKOGAWA ELECTRIC CORPORATION
Headquarters
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JAPAN
Branch Sales Offices
Nagoya, Osaka, Hiroshima, Fukuoka, Sapporo, Sendai, Ichihara, Toyoda, Kanazawa, Takamatsu, Okayama, and Kitakyusyu.
YOKOGAWA CORPORATION OF AMERICA
Headquarters
2 Dart Road, Newnan, Georgia 30265-1094, U.S.A. Phone : 1-770-253-7000 Fax : 1-770-254-0928
YOKOGAWA EUROPE B. V.
Headquarters
Databankweg 20 Amersfoort 3821 AL, THE NETHERLANDS Phone : 31-33-464-1611 Fax : 31-33-464-1610 Branch Sales Offices / Wien (Austria), Zaventem (Belgium), Ratingen (Germany), Madrid (Spain), Runcorn (United Kingdom), Milano (Italy), Velizy Villacoublay (France), Roodeport (Republic of South Africa), Budapest (Hungary), Stockholm (Sweden)
YOKOGAWA AMERICA DO SUL Ltda.
Head Office
Praca Acapulco, 31 - Santo Amaro. Sao Paulo/SP - BRAZIL Phone : 55-11-5681-2400 Fax : 55-11-5681-4434
YOKOGAWA ELECTRIC ASIA PTE. LTD.
Head Office
5 Bedok South Road, 469270 SINGAPORE Phone : 65-6241-9933 Fax : 65-444-6252
YOKOGAWA ELECTRIC KOREA CO., LTD.
Head Office
14-1, Yangpyongdong-4Ga, Youngdeungpo-Gu, Seoul, 150-866 KOREA Phone : 82-2-2628-6000 Fax : 82-2-2628-6400
YOKOGAWA AUSTRALIA PTY. LTD.
Head Office (Sydney)
Tower A, 112-118 Talavera Road, Macquarie Park, N.S.W.2113, AUSTRALIA Phone : 61-2-8870-1100 Fax : 61-2-8870-1111
YOKOGAWA INDIA LTD.
Head Office
Plot No.96 Electronic City Complex, Hosur Road, Bangalore 560100, INDIA Phone : 91-80-4150-6000 Fax : 91-80-2852-1441
YOKOGAWA CHINA CO., LTD.
K. Wah Centre 29F, 1010 Huai Hai Zhong Rd., Shanghai 200031, CHINA Phone : 86-21-5405-1919 Fax : 86-21-5405-1011
Nov. '06
Ex installation:
For a safe installation of YTA50 in hazardous area the following
must be observed. The module must only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the
serial number.
The sensor circuit is not infallibly galvanically isolated from the
input circuit. However, the galvanic isolation between the circuits is capable of withstanding a test voltage of 500 Vac during 1 minute.
The transmitter must be mounted in an enclosure in order to
provide a degree of ingress protection of at least IP20.
In explosive atmospheres caused by air / dust mixtures:
The transmitter may only be installed in a potentially explosive
atmosphere caused by the presence of combustible dust when mounted in a metal enclosure form B according to DIN 43729 that is providing a degree of ingress protection of at least IP 6X in accordance with EN 60529, that is suitable for the application and is correctly installed.
Cable entries and blanking elements shall be used that are
suitable for the application and correctly installed.
For an ambient temperature ≥60°C, heat resistant cables shall
be used with a rating of at least 20 K above the ambient temperature.
Special Conditions for Safe Use:
If the enclosure in which the transmitter is mounted is made of
aluminium and installed in Zone 0, 1 or Zone 20, 21 or 22 it shall not contain by weight more than 6% in total of magnesium and titanium.
The additional enclosure of the apparatus shall be designed
and/or installed in such a way that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
The YTA50 is a head mount type of temperature transmitter that accepts thermocouple or RTD input and converts it to a 4 to 20 mA DC signal for transmission. The YTA50 conforms to the standard DIN form B head mounting. It is imperative that usres observe the instructions in this manual to ensure the protection and safety of operators.

1. MODEL AND SUFFIX CODES

Model
Suffix code Descriptions
..................
YTA50
Output Signal
-A
.............
Optional Specifications
Te mperature Transmitter (Head Mount Type)
4 to 20 mA DC
CENELEC ATEX intrinsically
/KS2
safe approval
EEx ia llC T1-6 Amb. Temperature T1-4: -40 to 85°C T5-6: -40 to 60°C
CENELEC ATEX/FM intrinsically
/DS2
safe approval combination
CENELEC: EEx ia llC T1-6 FM: IS Class I, Div.1, Groups A, B, C & D
T01E.EPS

2. WARRANTY

The warranty period of the instrument is as of condition shown when purchasing. Any trouble arising during the warranty period shall be replaced at free of charge. The following problems or troubles shall not be eligible of charge-exempt repair.
• Caused by improper usage or storage of the customer which exceeds the specification requirements.
• Caused by mishandling or modification.
• Caused by fire, earthquake or other acts of God that are not directly a result of problems of the instrument.

3. HANDLING PRECAUTIONS

(1) Read this manual thorughly and carefully before handling
the instruments. Observe the instructions.
(2) Store the product in location that meets the following
requirements.
• No exposure to rain or water
• No major mechanical vibration or shock
• Humidity and Temperature limitations
• Ordinary conditions(25°C, 65%) is preferable. Otherwise, as of specified in “Standard Specifications.”
(3) Avoid corrosive atmosphere for storage and installation. (4) For safe installation of the transmitter in hazardous area,
the following must be observed. The module must only be installed by qualified personnels who are familiar with the national and international laws, directives, and standards that apply to this area.
(5) Yokogawa will not be liable for malfunctions or damage
resulting from any modification made to this instrument by the customer.

4. STANDARD SPECIFICATIONS

Accuracy
See table in the right.
Cold Junction Compensation Accuracy(For T/C only)
±1°C(±1.8°F)
Ambient Temperature Effects (per 10°C Change)
See table in the right
Type
T/C
B E J K N R S T L U W3 W5 Pt100
RTD
Ni100 DC Voltage [mV] Resistance []
Standard
IEC584
DIN43710
ASTM E988-90
IEC751
DIN43760
Input
ranges °C
400 to 1820
-100 to 1000
-100 to 1200
-180 to 1372
-180 to 1300
-50 to 1760
-50 to 1760
-200 to 400
-100 to 900
-200 to 600 0 to 2300 0 to 2300
-200 to 850
-60 to 250
-10 to 800 mV 0 to 5000
Minimum
span °C
200
50 50
50 100 200 200
50
50
75 200 200
25
25
5 mV
30
Accuracy *
±0.1% or ±2.0°C
±0.1% or ±1.0°C
±0.1% or ±2.0°C
±0.1% or ±1.0°C
±0.1% or ±2.0°C
±0.1% or ±0.2°C
±0.1% or ±0.01mV ±0.1% or ±0.1
1
±0.1% or ±2.0°C
±0.1% or ±0.5°C
±0.1% or ±2.0°C
±0.1% or ±0.5°C
±0.1% or ±2.0°C
±0.1% or ±0.1°C
±0.1% or ±10V ±0.1% or ±0.1
Temperature
effect *
*1 : The value whichever is greater. value in % indicates the
% of span.
Power Supply Effects
±0.005% of FS per Volt
RFI Effects
Tested per EN 61326, field intensity up to 10 V/m.
EMC Conformity
EN 61326
Maximum Zero Offset
±50% of the maximum temperature
1
T02E.EPS
Input Signal Source Resistance (for T/C input)
10 M, or 3 k at power-off
Input Lead Wire Resistance (for RTD input)
5 per wire or lower
Burnout
High (21.6 mA or more) or Low (3.6 mA or less)
Output
Two wire 4 to 20 mA DC
Response Time
1 to 60 sec (as specified upon shipment)
Ambient Temperature Limits (Option code may affect limit.)
–40 to 85°C (–40 to 185°F)
Ambient Humidity Limits
5 to 90% RH at 40°C (104°F)
Supply Voltage
7 to 35 V DC 7 to 30 V DC for Intrinsically safe type
Load Resistance (Limitation)
0 to (E–7)/0.023 [], where E is power supply voltage. Ex. 739 max. @ 24 V DC
Isolation
Input/output isolated to 1500 V AC.
Mounting
DIN form B head mounting
Terminals
M3 screws
Weight
50 g(0.11 lb)