YOKOGAWA YTA110/KU2, YTA310/KU2, YTA320/KU2 User Manual

User’s Manual
Oct. 1, 2008
Yokogawa Electric Corporation
YTA Series Temperature Transmitters (Hardware)
IM 01C50B01-01E (12th)
Manual Change No. 08-013
Page and Item
Page 2-6, 7-6
ATEX Documentation
Contents of Correction
Change Marking Code for CENELEC ATEX Type of Protection “n”.
IM 01C50B01-01E
2-5
2. NOTES ON HANDLING
Sensor
Sensor
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
NON-HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS DIVISION 1
50 cm Max.
Sealing Fitting
Conduit
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
NON-HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS DIVISION 2
Sealing Fitting
Sealing Fitting
50 cm Max.
Certified/Listed Temper ature Sensor Explosionproof Class I, Groups C and D Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.
YTA Series
YTA Series
Conduit
F0203.EPS
Certified/Listed Temper ature Sensor Explosionproof Class I, Groups C and D Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.
2.7.2 CENELEC ATEX (KEMA) Certification
Model YTA110/KU2, YTA310/KU2 and YTA320/ KU2 temperature transmitters can be selected the type of protection (CENELEC ATEX(KEMA) Intrinsically Safe or CENELEC ATEX(KEMA) Flameproof or CENELEC ATEX Type of Protection “n”) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
(1) Technical Data a) CENELEC ATEX (KEMA) Intrinsically Safe
Type
Caution for CENELEC ATEX (KEMA) Intrinsically safe type
Note 1. Model YTA110/KU2, YTA310/KU2 and
YTA320/KU2 temperature transmitters for potentially explosive atmospheres:
• No. KEMA 02ATEX1026X
• Applicable Standard: EN 50014, EN 50020, EN 50284
• Type of Protection and Marking code: II 1G EEx ia IIC T5, T4
• Temperature Class: T5, T4
• Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
• Enclosure: IP67
Note 2. Electrical Data
• In type of explosion protection intrinsic safety II 1G EEx ia IIC only for connection to a certified intrinsically safe circuit with following maximum values:
• [Supply circuit]
Ui = 30 V Ii = 165 mA Pi = 900 mW Effective internal capacitance, Ci = 20 nF Effective internal inductance, Li = 660 µH
• [Sensor circuit]
Uo = 8.6 V Io = 30 mA Po = 70 mW Max. allowed external capacitance, Co = 3 µF Max. allowed external inductance, Lo = 20 mH
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Intrinsically safe Certification.