Customer Maintenance Parts List ..................................... CMPL 01C50B01-02E
REVISION RECORD
ii
IM 01C50B01-01E
1.PREFACE
1. PREFACE
The YTA temperature transmitter is fully factory-tested
according to the specifications indicated on the order.
In order for the YTA temperature transmitter to be
fully functional and to operate in an efficient manner,
the instruction manual must be carefully read to
become familiar with the functions, operation, and
handling of the YTA.
This Instruction Manual gives instructions on handling,
wiring and maintenance of YTA110, YTA310 and
YTA320 temperature transmitters. Changing the
parameter settings requires a terminal dedicated to the
HART Protocol or the BRAIN Protocol. For details on
how to set the parameters of these transmitters, refer to
the “BRAIN Protocol” IM 0lC50T03-01E or “HART
Protocol” IM 01C50T01-01E.
For FOUNDATION Fieldbus communication type,
please refer to IM 01C50T02-01E in addition to this
manual.
Notes on the Instruction Manual
• This manual should be delivered to the end user.
• The information contained in this manual is subject
to change without prior notice.
• The information contained in this manual, in whole
or part, shall not be transcribed or copied without
notice.
• In no case does this manual guarantee the merchant
ability of the transmitter or its adaptability to a
specific client need.
• Should any doubt or error be found in this manual,
submit inquiries to your local dealer.
•No special specifications are contained in this
manual.
• Changes to specifications, structure, and components
used may not lead to the revision of this manual
unless such changes affect the function and performance of the transmitter.
Notes on Safety and Modifications
• Before handling the YTA, it is absolutely imperative
that users of this equipment read and observe the
safety instructions mentioned in each section of the
manual in order to ensure the protection and safety
of operators, the YTA itself and the system containing the transmitter. We are not liable for any
accidents arising out of handling that does not
adhere to the guidelines established in the safety
instructions.
• No maintenance should be performed on explosionproof type temperature transmitters while the
equipment is energized. If maintenance is required
with the cover open, always first use a gas detector
to check that no explosive gases are present.
• If the user attempts to repair or modify an
explosionproof type transmitter and is unable to
restore it to its original condition, damage to the
explosionproof features result, leading to dangerous
conditions. Contact your authorized Yokogawa
Electric Corporation representative for repairs or
modifications of an explosionproof type transmitter.
For Safety Using
Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about INSTALLATION are not permitted
for operators.
•In case of high process temperature, care should be
taken not to burn yourself because the surface of the
case reaches a high temperature.
• All installation shall comply with local installation
requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
operators.
• Please confirm that voltages between the power
supply and the instrument before connecting the
power cables and that the cables are not powered
before connecting.
(c) Maintenance
• Please do not carry out except being written to a
maintenance descriptions. When these procedures
are needed, please contact nearest YOKOGAWA
office.
•Care should be taken to prevent the build up of drift,
dust or other material on the display glass and
name plate. In case of its maintenance, soft and dry
cloth is used.
1-1
IM 01C50B01-01E
1. PREFACE
Symbols used in this Instruction Manual
The YTA temperature transmitter and this manual use
the following safety related symbols and signals.
WARNING
Contains precautions to protect against the
chance of explosion or electric shock which, if
not observed, could lead to death or serious
injury.
CAUTION
Contains precautions to protect against danger,
which, if not observed, could lead to personal
injury or damage to the instrument.
IMPORTANT
Contains precautions to be observed to protect
against adverse conditions that may lead to
damage to the instrument or a system failure.
NOTE
Contains precautions to be observed with regard
to understanding operation and functions.
Some of the diagrams in this instruction manual are
partially omitted, described in writing, or simplified for
ease of explanation. The screen drawings contained in
the instruction manual may have a display position or
characters (upper/lower case) that differ slightly from
the full-scale screen to an extent that does not hinder
the understanding of functions or monitoring of
operation.
Warranty
• The warranty period of the instrument is written on
the estimate sheet that is included with your purchase. Any trouble arising during the warranty
period shall be repaired free of charge.
• Inquiries with regard to problems with the instrument shall be accepted by the sales outlet or our
local dealer representative.
• Should the instrument be found to be defective,
inform us of the model name and the serial number
of the instrument together with a detailed description
of nonconformance and a progress report. Outline
drawings or related data will also be helpful for
repair.
• Whether or not the defective instrument is repaired
free of charge depends on the result of our inspection.
The following conditions shall not be
eligible for charge-exempt repair.
• Problems caused by improper or insufficient
maintenance on the part of the customer.
• Trouble or damage caused by mishandling, misusage, or storage that exceeds the design or specification requirements.
• Problems caused by improper installation location or
by maintenance conducted in a non-conforming
location.
• Trouble or damage was caused by modification or
repair that was handled by a party or parties other
than our consigned agent.
• Trouble or damage was caused by inappropriate
relocation following delivery.
•Trouble or damage was caused by fire, earthquake,
wind or flood damage, lightning strikes or other acts
of God that are not directly a result of problems with
this instrument.
Trade Mark
• HART is a trademark of the HART Communication
Foundation.
• Registered trademarks or trademarks appearing in
this manual are not designated by a TM or ®
symbol.
• Other company names and product names used in
this manual are the registered trademarks or trademarks of their respective owners.
1-2
IM 01C50B01-01E
2.NOTES ON HANDLING
2. NOTES ON HANDLING
The YTA temperature transmitter is fully factory-
tested upon shipment. When the YTA is delivered,
check the appearance for damage, and also check that
the transmitter mounting parts shown in Figure 2.1 are
included with your shipment. If “No Mounting
Bracket” is indicated, no transmitter mounting bracket
is included.
Nut for U-bolt
Mounting bracket
Spring washer
2.2 Transport
To prevent damage while in transit, leave the transmitter in the original shipping container until it reaches
the installation site.
2.3 Storage
When an extended storage period is expected, observe
the following precautions:
1. If at all possible, store the transmitter in factoryshipped condition, that is, in the original shipping
container.
2. Choose a storage location that satisfies the following requirements.
•A location that is not exposed to rain or water.
•A location subject to a minimum of vibration or
impact.
• The following temperature and humidity range is
recommended. Ordinary temperature and humidity
(25°C, 65%) are preferable.
Temperature: No Integral indicator–40 to 85°C
With Integral indicator –30 to 80°C
Humidity:5 to 100% RH (at 40°C)
Transmitter fastening bolt
U-bolt
F0201.EPS
Figure 2.1 Transmitter mounting parts
2.1 Nameplate
The model name and configuration are indicated on
the nameplate. Verify that the configuration indicated
in the “Model and Suffix Code” in Chapter 7 is in
compliance with the specifications written on the order
sheet.
Specification code
TEMPERATURE
TRANSMITTER
YTA
DC24V
Made in Japan
Style code
Figure 2.2 Name plate
Model name
4~20mA DC
Serial No.
Factory-shipped range and unit
F0202.EPS
3. The performance of the transmitter may be impaired if stored in an area exposed to direct rain and
water. To avoid damage to the transmitter, install it
immediately after removal from shipping container.
Follow wiring instructions in Chapter 5.
2.4 Choosing the Installation
Location
Although the temperature transmitter is designed to
operate in a vigorous environment, to maintain
stability and accuracy, the following is recommended:
(1) Ambient Temperature
It is preferable to not to expose the instrument to
extreme temperatures or temperature fluctuations. If
the instrument is exposed to radiation heat a thermal
protection system and appropriate ventilation is
recommended.
(2) Environmental Requirements
Do not allow the instrument to be installed in a
location that is exposed to corrosive atmospheric
conditions. When using the instrument in a corrosive
environment, ensure the location is well ventilated.
The unit and its wiring should be protected from
exposure to rainwater.
2-1
IM 01C50B01-01E
2. NOTES ON HANDLING
(3) Impact and Vibration
It is recommended that the instrument be installed in a
location that is subject to a minimum amount of impact
and vibration.
2.5 Use of a Transceiver
Although the temperature transmitter is designed to
resist influence from high frequency noise; use of a
transceiver in the vicinity of installation may cause
problems. Installing the transmitter in an area free from
high frequency noise (RFI) is recommended.
2.6 Insulation Resistance Test
and Withstand Voltage Test
CAUTION
(1) Overvoltage of the test voltage that is so
small that it does not cause an dielectric
breakdown may in fact deteriorate insulation
and lower the safety performance; to prevent
this it is recommended that the amount of
testing be kept to a minimum.
(2) The voltage for the insulation resistance test
must be 500 VAC or lower, and the voltage
for the withstand voltage test must be 500
VAC or lower. Failure to heed these guidelines may cause faulty operation.
(3) Where a built-in arrester is provided (suffix
code: /A), the voltage for the insulation
resistance test must be 100 VDC or lower,
and the voltage for the withstand voltage test
must be 100 VAC or lower. Failure to heed
these guidelines may cause faulty operation.
Follow the steps below to perform the test, the wiring
of the transmission line must be removed before
initiating testing.
2.6.1 Insulation resistance test procedure
Testing between the output terminal and
input terminal
1. Lay transition wiring between the + terminal, the -
terminal, and the check terminal of the terminal box.
2. Lay wiring across terminals 1, 2, 3, and 4 of the
terminal box.
3. Connect the insulation resistance meter (with the
power turned OFF) between the transition wiring of
Steps 1 and 2 above. The polarity of the input
terminals must be positive and that of the output
terminals must be negative.
4. Turn the power of the insulation resistance meter
ON and measure the insulation resistance. The
duration of the applied voltage must be the period
during which 100M⍀ or more is confirmed (or
20M⍀ if the unit is equipped with a built-in
arrester).
5. Upon completion of the test, remove the insulation
resistance meter, connect a 100K⍀ resistor between
the transition wiring, and allow the electricity to
discharge. Do not touch the terminal with your bare
hands while the electricity is discharging for more
than 1 second.
Testing between the output terminal and
grounding terminal
1. Lay transition wiring between the + terminal, the terminal, and the check terminal of the terminal box,
then connect an insulation resistance meter (with the
power turned OFF) between the transition wiring
and the grounding terminal. The polarity of the
transition wiring must be positive and that of the
grounding terminal must be negative.
2. Turn the power of the insulation resistance meter
ON and measure the insulation resistance. The
duration of the applied voltage must be the period
during which 100M⍀ or more is confirmed (or
20M⍀ if the unit is equipped with a built-in
arrester).
3. Upon completion of the test, remove the insulation
resistance meter, connect a 100K⍀ resistor between
the transition wiring and the grounding terminal, and
allow the electricity to discharge. Do not touch the
terminal with your bare hands while the electricity is
discharging for more than 1 second.
Testing between the input terminal and
grounding terminal
1. Lay transition wiring between terminals 1, 2, 3, 4
and 5 of the terminal box, and connect the insulation
resistor (with the power turned OFF) between the
transition wiring and the grounding terminal. The
polarity of the transition wiring must be positive and
that of the grounding terminal must be negative.
2. Turn the power of the insulation resistance meter
ON and measure the insulation resistance. The
duration of the applied voltage must be the period
during which 100M⍀ or more is confirmed (or
20M⍀ if the unit is equipped with a built-in
arrester).
3. Upon completion of the test, remove the insulation
resistance meter, connect a 100K⍀ resistor between
the transition wiring and the grounding terminal, and
allow the electricity to discharge. Do not touch the
terminal with your bare hands while the electricity is
discharging for more than 1 second.
2-2
IM 01C50B01-01E
2. NOTES ON HANDLING
2.6.2 Withstand voltage test procedure
Testing between the output terminal and the
input terminal
1. Lay transition wiring between the + terminal, the –
terminal, and the check terminal of the terminal box.
2. Lay transition wiring between terminals 1, 2, 3, 4
and 5 of the terminal box.
3. Connect the withstand voltage tester (with the power
turned OFF) between the transition wiring shown in
Steps 1 and 2 above.
4. After setting the current limit value of the withstand
voltage tester to 10mA, turn the power ON, and
carefully increase the impressed voltage from 0V to
the specified value.
5. The voltage at the specified value must remain for a
duration of one minute.
6. Upon completion of the test, carefully reduce the
voltage so that no voltage surge occurs.
Testing between the output terminal and the
grounding terminal
1. Lay the transition wiring between the + terminal, the
- terminal and the check terminal of the terminal
box, and connect the withstand voltage tester (with
the power turned OFF) between the transition wiring
and the grounding terminal. Connect the grounding
side of the withstand voltage tester to the grounding
terminal.
2. After setting the current limit value of the withstand
voltage tester to 10mA, turn the power ON, and
gradually increase the impressed voltage from 0V to
the specified value. .
3. The voltage at the specified value must remain for a
duration of one minute.
4. Upon completion of the test, carefully reduce the
voltage so that no voltage surge occurs.
Testing between the input terminal and the
grounding terminal
1. Lay the transition wiring across terminals 1, 2, 3, 4,
and 5 of the terminal box and connect the withstand
voltage tester (with the power turned OFF) between
the transition wiring and the grounding terminal.
Connect the grounding side of the withstand voltage
tester to the grounding terminal.
2. After setting the current limit value of the withstand
voltage tester to 10mA, turn the power ON, and
gradually increase the impressed voltage from 0V to
the specified value.
3. The voltage at the specified value must remain for a
duration of one minute.
4. Upon completion of the test, carefully reduce the
voltage so that no voltage surge occurs.
2.7 Installation of Explosion
Protected T ype Transmitters
In this section, further requirements and differences
and for explosionproof type instrument are described.
For explosionproof type instrument, the description in
this chapter is prior to other description in this users
manual.
CAUTION
To preserve the safety of explosionproof equipment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair
activities. Please read the following sections very
carefully.
2.7.1 CSA Certification
Model YTA110/CU1, YTA310/CU1 and YTA320/CU1
temperature transmitters can be selected the type of
protection (CSA Intrinsically Safe, Non-incendive, or
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
a) CSA Intrinsically Safe Type/Non-incendive
Type
Caution for CSA Intrinsically safe type. (Following
contents refers “DOC No. ICS008-A13 P.1-1 and P.12”)
Note 1. Model YTA110/CU1, YTA310/CU1 and
YTA320/CU1 temperature transmitters
are applicable for use in hazardous
locations:
• Intrinsically Safe for Class I, II, III, Division 1,
Groups A, B, C, D, E, F & G.
• Non-incendive for Class I, II, Division 2, Groups A,
B, C, D, E, F & G, Class III, Division 1.
• Encl. “Type 4X”
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
2-3
IM 01C50B01-01E
2. NOTES ON HANDLING
Note 2. Entity Parameters (Electrical/Non-
incendive field wiring parameters)
• [Supply Circuit]
Vmax = 30 V, Imax = 165 mA, Pmax = 0.9 W
Ci = 18 nF, Li = 730 µH
• [Sensor Circuit]
Voc = 9 V, Isc = 40 mA, Po = 90 mW,
Ca = 1 µF, La = 10 mH
Note 3. Installation
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• For the sensor circuitry, the above parameters for
sensor circuit must be taken into account.
• Dust-tight conduit seal must be used when installed in
class II and III environments.
• In any used safety barrier, output current must be
limited by a resistor 'R' such that Isc=Voc/R.
• The safety barrier must be CSA certified, and the
input voltage of the barrier must be less than
250Vrms/Vdc.
• For non-incendive type, general purpose equipment
must be CSA certified and the equipment which have
non-incendive field wiring parameters.
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
[Intrinsically Safe]
Hazardous
Location
YTA Series
Temperature
Transmitter
1
2
3
Sensor
4
5
Hazardous
Location
+
Supply
–
[Non-incendive]
Nonhazardous
Location
Safety Barrier
+
+
–
–
Nonhazardous
Location
General
Purpose
Equipment
+
–
b) CSA Explosionproof Type
Caution for CSA Explosionproof type
Note 1. Model YTA110/CU1, YTA310/CU1 and
YTA320/CU1 temperature transmitters
are applicable for use in hazardous
locations:
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II, Groups E, F and G,
Class III.
• Encl “Type 4X”
• Temperature Class:T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as
shown in the figure.
WARNING: A SEAL SHALL BE INSTALLED
WITHIN 50 cm OF THE ENCLOSURE. UN SCELLEMENT DOIT
ÊTRE INSTALLÉ À MOINS DE
50 cm DU BOÎTIER.
• When installed in Division 2, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED”.
Note 3. Operation
• Keep strictly the “WARNING” on the label
attached on the transmitter.
WARNING: OPEN CIRCUIT BEFORE RE-
MOVING COVER. OUVRIR LE
CIRCUIT AVANT D´ENLEVER LE
COUVERCLE.
• Take care not to generate mechanical spark when
access to the instrument and peripheral devices in
hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Canadian Standards Explosionproof
Certification.
YTA Series
Temperature
Transmitter
1
2
3
4
Sensor
5
Supply
+
–
Not Use
Safety Barrier
General
Purpose
Equipment
+
–
F0204.EPS
2-4
IM 01C50B01-01E
2. NOTES ON HANDLING
HAZARDOUS LOCATIONS DIVISION 1
50 cm Max.
Sensor
Sealing Fitting
Certified/Listed Temper ature Sensor
Explosionproof Class I, Groups C and D
Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.
Sensor
Certified/Listed Temper ature Sensor
Explosionproof Class I, Groups C and D
Dustignitionproof Class II, Groups E, F and G, Class III
Wiring method shall be suitable for the specified hazardous locations.
YTA Series
HAZARDOUS LOCATIONS DIVISION 2
YTA Series
50 cm Max.
Conduit
Conduit
Sealing Fitting
Sealing Fitting
NON-HAZARDOUS
LOCATIONS
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
NON-HAZARDOUS
LOCATIONS
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
F0203.EPS
2.7.2 CENELEC ATEX (KEMA) Certification
Model YTA110/KU2, YTA310/KU2 and YTA320/
KU2 temperature transmitters can be selected the type
of protection (CENELEC ATEX(KEMA) Intrinsically
Safe or CENELEC ATEX(KEMA) Flameproof or
CENELEC ATEX Type of Protection “n”) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
(1) Technical Data
a) CENELEC ATEX (KEMA) Intrinsically Safe
Type
Caution for CENELEC ATEX (KEMA) Intrinsically
safe type
Note 1. Model YTA110/KU2, YTA310/KU2 and
YTA320/KU2 temperature transmitters for
potentially explosive atmospheres:
• No. KEMA 02ATEX1026X
•Type of Protection and Marking code: II 1G EEx ia
IIC T5, T4
• Temperature Class: T5, T4
• Ambient Temperature: –40 to 70°C for T4, –40 to
50°C for T5
• Enclosure: IP67
Note 2. Electrical Data
•In type of explosion protection intrinsic safety II 1G
EEx ia IIC only for connection to a certified
intrinsically safe circuit with following maximum
values:
• [Supply circuit]
Ui = 30 VIi = 165 mA
Pi = 900 mW
Effective internal capacitance, Ci = 20 nF
Effective internal inductance, Li = 660 µH
• [Sensor circuit]
Uo = 8.6 VIo = 30 mA
Po = 70 mW
Max. allowed external capacitance, Co = 3 µF
Max. allowed external inductance, Lo = 20 mH
Note 3. Installation
•All wiring shall comply with local installation
requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
KEMA Intrinsically safe Certification.
2-5
IM 01C50B01-01E
2. NOTES ON HANDLING
s
Note 5. Special condition for safe use
• Because the enclosure of the Temperature
Transmitter is made of aluminium, if it is mounted
in an area where the use of category 1G apparatus is
required, it must be installed such, that, even in the
event of rare incidents, ignition source due to impact
and friction sparks are excluded.
[Installation Diagram]
Hazardous
Location
Transmitter
1
2
3
4
Sensor
5
*1: In any safety barriers used the output current must be limited by
a resistor “R” such that Imaxout-Uz/R.
+
Supply
–
Nonhazardou
Location
Safety Barrier
+
–
*1
F0208.EPS
b) CENELEC ATEX (KEMA) Flameproof Type
Caution for CENELEC ATEX (KEMA) Flameproof
Type
Note 1. Model YTA110/KU2, YTA310/KU2 and
YTA320/KU2 temperature transmitters for
potentially explosive atmospheres:
• No. KEMA 02ATEX2155
• Type of Protection and Marking Code: II 2G EEx d
IIC T5, T6
• Temperature Class: T5, T6
• Ambient Temperature: –40 to 80°C for T5, –40 to
75°C for T6
• Enclosure: IP67
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
•All wiring shall comply with local installation
requirement.
•The cable entry devices shall be of a certified
flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep strictly the “WARNING” on the label on the
transmitter.
WARNING: AFTER DE-ENERGIZING, DELAY
5 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP. ⭌
70⬚C, USE THE HEATRESISTING CABLES OF HIGHER THAN
90⬚C.
• Take care not to generate mechanical spark when
access to the instrument and peripheral devices in
hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
KEMA Flameproof Certification.
c) CENELEC ATEX Type of Protection “n”
WARNING
When using a power supply not having a nonincendive circuit, please pay attention not to
ignite in the surrounding flammable atmosphere.
In such a case, we recommend using wiring
metal conduit in order to prevent the ignition.
Caution for CENELEC ATEX Type of Protection “n”
Note 1. Model YTA110/KU2, YTA310/KU2 and
YTA320/KU2 temperature transmitters for
potentially explosive atmospheres:
• Type of Protection and Marking Code: II 3G EEx
nL IIC T5, T4
• Temperature Class: T5, T4
• Ambient Temperature: –40 to 50°C for T5, –40 to
70°C for T4
• Enclosure: IP67
Note 2. Electrical Data
[Supply circuit]
Ui = 30 V
Effective internal capacitance, Ci = 20 nF
Effective internal inductance, Li = 660 µH
[Sensor circuit]
Uo= 8.6 V Io = 30 mA Po = 70 mW
Max. allowed external capacitance, Co = 3 µF
Max. allowed external capacitance, Lo = 20 mH
Note 3. Installation
•All wiring shall comply with local installation
requirements. (refer to the installation diagram)
2-6
IM 01C50B01-01E
2. NOTES ON HANDLING
s
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Type of Protection “n” Certification.
[Installation Diagram]
Hazardous
Location
Nonhazardou
Location
(Zone 2 only)
Temperature
Transmitter
+
Power Supply
+
Suppry
–
–
F0212.EPS
Ratings of the Power Supply are as follows:
Maximum Voltage: 30 V
(2) Electrical Connection
The type of electrical connection is stamped near
the electrical connection port according to the
following marking.
(5) Maintenance and Repair
WARNING
The instrument modification or parts replacement
by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.
(6) Name Plate
Name plate for type n protection
TEMPERATURE
TRANSMITTER
YTA
10.5⫺30 (42) V DC
TOKYO 180-8750 JAPAN
:Refer to USER’S MANUAL.
4⫺20 mA DC
0344
II
1G
No. KEMA 02ATEX1026 X
EEx ia IIC T5
Tamb -40 TO 50⬚C
EEx ia IIC T4
Tamb -40 TO 70⬚C
ENCLOSURE: IP67
SUPPLY INPUT
Ui=30V, Ii=165mA, Pi=900mV
Ci=20nF, Li=660H
SENSOR OUTPUT
Uo=8.6V, Io=30mA, Po=70mW
Co=3F, Lo=20mH
2GIIII 3G
No. KEMA 02ATEX2155
EEx d IIC T6
Tamb -40 TO 75⬚C
EEx d IIC T5
Tamb -40 TO 80⬚C
ENCLOSURE: IP67
WARNING
AFTER DE-ENERGIZING, DELAY
5 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP.⭌70⬚C,
USE THE HEAT-RESISTING
CABLES⭌90⬚C.
Cross out unnecessary marking other than the selected type
of protection. When II 3G is selected, cross out 0344.
MODEL: Specified model code.
SUFFIX: Specified suffix code.
STYLE: Style code.
SUPPLY: Supply voltage.
NO.: Serial number and year of production*1.
OUTPUT: Output signal.
FACTORY CAL: Specified calibration range.
TOKYO 180-8750 JAPAN:
The manufacturer name and the
address*2.
Location of the marking
F0200.EPS
(3) Installation
WARNING
All wiring shall comply with local installation
requirement and local electrical code.
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in hazardous locations.
*1: (a) The production year for the serial number
starting with other than “S.”
The third figure from the last shows the last one
figure of the year of production. For example, the
production year of the product engraved in “NO.”
column on the name plate as follows is 2001.
12A819857 132
The year 2001
(b) The production year for the serial number
starting with “S.”
The third and fourth figures from the left show the
last two figures of the year of production. For
example, the production year of the product
engraved in “NO.” column on the name plate as
follows is 2001.
S201D0229335
The year 2001
*2: “180-8750” is a zip code which represents the
following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
2-7
IM 01C50B01-01E
2. NOTES ON HANDLING
s
2.7.3 CENELEC (KEMA) Certification
Model YTA110/KU1, YTA310/KU1 and YTA320/
KU1 temperature transmitters can be selected the type
of protection (CENELEC (KEMA) Intrinsically Safe or
CENELEC (KEMA) Flameproof or IEC(KEMA) Type
of Protection “n”) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
a) CENELEC (KEMA) Intrinsically Safe Type
Caution for CENELEC (KEMA) Intrinsically safe type
Note 1. Model YTA110/KU1, YTA310/KU1 and
YTA320/KU1 temperature transmitters for
potentially explosive atmospheres:
• Type of Protection and Marking code: EEx ia IIC
• Temperature Class: T4, T5
• Ambient Temperature: –40 to 70°C for T4, –40 to
50°C for T5
Note 2. Electrical Data
• In type of explosion protection intrinsic safety EEx
ia IIC only for connection to a certified intrinsically
safe circuit with following maximum values:
• [Supply circuit]
Ui = 30 VIi = 165 mA
Pi = 0.9 W
Effective internal capacitance, Ci = 20 nF
Effective internal inductance, Li = 660 µH
•All wiring shall comply with local installation
requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
KEMA Intrinsically safe Certification.
[Installation Diagram]
Hazardous
Location
Transmitter
1
2
3
4
Sensor
5
*1: In any safety barriers used the output current must be limited by
a resistor “R” such that Imaxout-Uz/R.
+
Supply
–
Nonhazardou
Location
Safety Barrier
+
–
*1
F0208.EPS
b) CENELEC (KEMA) Flameproof Type
Caution for CENELEC (KEMA) Flameproof Type
Note 1. Model YTA110/KU1, YTA310/KU1 and
YTA320/KU1 temperature transmitters for
potentially explosive atmospheres:
• Type of Protection and Marking Code: EEx d IIC T6
Temperature Class: T6
• Ambient Temperature: –40 to 75°C
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
Output signal: 4 to 20 mA
Note 3. Installation
•All wiring shall comply with local installation
requirement.
•The cable entry devices shall be of a certified
flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep strictly the “WARNING” on the label on the
transmitter.
WARNING: WAIT 5 MIN. AFTER POWER-
DISCONNECTION, BEFORE
OPENING THE ENCLOSURE.
WHEN THE AMBIENT TEMP. ⭌
70⬚C, USE THE HEATRESISTING CABLES OF HIGHER
THAN90⬚C
• Take care not to generate mechanical spark when
access to the instrument and peripheral devices in
hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
KEMA Flameproof Certification.
2-8
IM 01C50B01-01E
2. NOTES ON HANDLING
s
c) IEC (KEMA) Type of Protection “n”
Caution for IEC (KEMA) Type of Protection “n”
Note 1. Model YTA110/KU1, YTA310/KU1 and
YTA320/KU1 ditemperature transmitters
for potentially explosive atmospheres:
• Type of Protection and Marking Code: Ex nC IIC
T5, T4
• Temperature Class: T5, T4
• Ambient Temperature: –40 to 50°C for T5, –40 to
70°C for T4
• Enclosure: IP67
Note 2. Electrical Data
Ui = 30 VIi = 150 mA
(terminals + and –)
Note 3. Installation
•All wiring shall comply with local installation
requirements. (refer to the installation diagram)
Note 4. Operation
• Keep strictly the “WARNING” on the label on the
transmitter.
WARNING: WAIT 5 MIN. AFTER POWER-
DISCONNECTION, BEFORE
OPENING THE ENCLOSURE.
WHEN THE AMBIENT TEMP. ⭌
70⬚C, USE THE HEATRESISTING CABLES OF HIGHER
THAN90⬚C
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
KEMA Type of Protection “n” Certification.
[Installation Diagram]
Hazardous
Location
(Zone 2 only)
Temperature
Transmitter
+
Suppry
–
Ratings of the Power Supply are as follows:
Maximum Voltage: 30 V
Maximum Current: 150 mA
Nonhazardou
Location
Power Supply
+
–
F0212.EPS
2.7.4 FM Certification
a) FM Intrinsically Safe Type
Caution for FM Intrinsically safe type.
Note 1. Model YTA /FU1 temperature transmitter
is applicable for use in hazardous
locations
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D.
Class II, Division 1, Groups E, F & G and Class III,
Division 1 Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
Note 2. Entity Parameters of the temperature
transmitter:
• Supply Circuit (+ and -) •Sensor Circuit ( 1 to 5 )
Vmax : 30 VVoc/Vt : 9 V
Imax : 165 mAIsc/It : 40 mA
Pmax : 0.9 WCa : 1 µF
Ci : 18 nFLa : 10 mH
Li : 730 µH
• For the sensor input circuitry, these entity parameters
must be taken into account when installed.
• Installation Requirements between temperature
transmitter and safety barrier:
Voc Vmax, Isc Imax, Ca Ci + Ccable, La
Li + Lcable
Voc , Isc, Ca and La are parameters of the safety
barrier.
Note 3. Installation
• The safety barrier must be FM approved.
• Input voltage of the safety barrier must be less than
250 Vrms/Vdc.
•Installation should be in accordance with ANSI/ISA
RP12.6 “Installation of Intrinsically Safe Systems
for Hazardous (Classified) Locations” and the
National Electric Code (ANSI/NFPA 70).
• Intrinsically safe sensor must be FMRC Approved or
be simple apparatus (a device which will neither
generate nor store more than 1.2 V, 0.1 A, 25 mW
or 20 µJ, ex. switches, thermocouples, LED’s or
RTD’s).
• Dust-tight conduit seal must be used when installed
in a Class II and III environments.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.
2-9
IM 01C50B01-01E
2. NOTES ON HANDLING
[Intrinsically Safe]
Hazardous
Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F and G
Intrinsically
Safe Sensor
or Simple
Apparatus
Temperature
Transmitter
1
2
3
4
Sensor
5
Supply
+
–
C
Nonhazardous
Location
General
Purpose
Equipment
+–
Safety Barrier
+
+
–
–
F0210.EPS
b) FM Non-incendive Type
Caution for FM Non-incendive type.
Note 1. Model YTA /FU1 temperature transmitter
is applicable for use in hazardous
locations
• Non-incendive for Class I, Division 2, Groups A, B,
C & D.
Class II, Division 2, Groups E, F & G and Class III,
Division 1 Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
Note 2. Non-incendive field wiring Parameters of
the temperature transmitter:
• Supply Circuit (+ and -) •Sensor Circuit ( 1 to 5 )
Vmax : 30 V Voc/Vt : 9 V
Imax : 165 mA Isc/It : 40 mA
Pmax : 0.9 W Ca : 1 µF
Ci : 18 nF La : 10 mH
Li : 730 µH
• For the sensor input circuitry, these non-incendive
parameters must be taken into account when
installed.
• Installation Requirements between temperature
transmitter and general purpose equipment:
Voc Vmax, Isc Imax, Ca Ci + Ccable, La
Li + Lcable
Voc , Isc, Ca and La are non-incendive field wiring
parameters of general purpose equipment.
Note 3. Installation
• The general purpose equipment must be FM approved which have non-incendive field wiring
parameters.
•Installation should be in accordance with ANSI/ISA
RP12.6 “Installation of Intrinsically Safe Systems
for Hazardous (Classified) Locations” and the
National Electric Code (ANSI/NFPA 70).
• non-incendive sensor must be FMRC Approved or
be simple apparatus (a device which will neither
generate nor store more than 1.2 V, 0.1 A, 25 mW
or 20 µJ, ex. switches, thermocouples, LED’s or
RTD’s).
• Dust-tight conduit seal must be used when installed
in a Class II and III environments.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.
[Nonincendive]
Hazardous
Location
Class I, II, Division 2,
Groups A, B, C, D, E, F and G
Class III, Division 1.
Non-incendive
Sensor
or Simple
Apparatus
Temperature
Transmitter
1
2
3
4
Sensor
5
+
Supply
–
C
Nonhazardous
Location
General
Purpose
Equipment
+
–
c) FM Explosionproof Type
Caution for FM Explosionproof type
Note 1. Model YTA /FU1 and YTA /FF1 tempera-
ture transmitters are applicable for use in
hazardous locations:
• Explosionproof for Class I, Division 1, Groups A, B,
C, and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical Codes.
• “FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED”.
2-10
IM 01C50B01-01E
F0211.EPS
2. NOTES ON HANDLING
Note 3. Operation
• Keep strictly the “WARNING” on the nameplate
attached on the transmitter.
WARNING: OPEN CIRCUIT BEFORE RE-
MOVING COVER. “FACTORY
SEALED, CONDUIT SEAL NOT
REQUIRED”. INSTALL IN ACCORDANCE WITH THE INSTRUCTION
MANUAL IM 1C50B1.
• Take care not to generate mechanical spark when
access to the instrument and peripheral devices in
hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Explosionproof Approval.
2.7.5 JIS Certification
a) JIS Flameproof Type
The model YTA /JF3 temperature transmitter, which
has obtained certification according to technical criteria
for explosion-protected construction of electric machinery and equipment (Standards Notification No.556
from the Japanese Ministry of Labor) conforming to
IEC standards, is designed for hazardous areas where
explosive gases and/or inflammable vapors may be
present. (This allows installation in Division 1 and 2
areas)
To preserve the safety of flameproof equipment
requires great care during mounting, wiring, and
piping. Safety requirements also place restrictions on
maintenance and repair activities. Users absolutely
must read “Installation and Operating Precautions for
JIS Flameproof Equipment” at the end of this manual.
WARNING
The terminal cover should not be opened at
least for three minutes after the power is turned
off.
The terminal section of the flameproof YTA
series is made of resin-filled, explosion-protected
construction. The technical standards for this
flameproof construction require that the possibility of explosion resulting from a prospective
short-circuit current*2 of up to 4000 A be prevented even for cases when external power
supply circuits are short-circuited accidentally.
Install a fuse or a circuit breaker having a
breaking capacity of at least 4000 A in the
higher-order power line connected to the YTA
series. The breaking capacity refers to the upper
limit of current that can be cut off. Normally, a
fuse or a circuit breaker having a breaking
capacity of greater than 5000 A is used in power
supply circuits. Confirm that this is true with your
factory. No extra measures need be taken after
the confirmation.
Note that the rated current of the YTA series in
terms of explosion protection is 4 to 20 mA;
keep the input current of the YTA series within
the appropriate range.
*2: Refers to a current that flows when a fuse in a circuit is
substituted with a connecting metal piece having virtually no
impedance and the circuit is then shorted. For AC circuits, this
current is represented by a root-mean-square value (JIS C6575).
2.7.6 SAA Certification
Model YTA110/SU1, YTA310/SU1 and YTA320/SU1
temperature transmitters can be selected the type of
protection (SAA Intrinsically Safe, Type of Protection
“n” or Flameproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, cross out
unnecessary marking on the label other
than the selected type of protection when
the transmitter is installed.
a) SAA Intrinsically Safe/Type N Type
Caution for SAA Intrinsically safe/Type n type
Note 1. Model YTA110/SU1, YTA310/SU1 and
YTA320/SU1 temperature transmitters for
potentially explosive atmospheres:
• Type of Protection and Marking code:
Ex ia IIC T4 (Tamb=70°C) IP66/67 Zone 0
Ex n IIC T4 (Tamb=70°C) IP66/67 Zone 2
• Ambient Temperature: –40 to 70°C
Note 2. Entity Parameter
• In type of explosion protection only for connection
to a certified intrinsically safe/type n circuit with
following maximum values:
[Input parameters (terminals +&-/C)]
Maximum Input Voltage(Ui) = 30 V
Maximum Input Current(Ii) = 165 mA
Maximum Input Power(Pi) = 0.9 W
Maximum Internal Capacitance(Ci) = 30.2 nF
Maximum Internal Inductance(Li) = 738 µH
2-11
IM 01C50B01-01E
2. NOTES ON HANDLING
NOTE
[Output parameters (terminals 1 to 5)]
Maximum Output Voltage(Uo) = 8.6 V
Maximum Output Current(Io) = 30 mA
Maximum Output Power(Po) = 62 mW
Maximum External Capacitance = 1 µF
Maximum External Inductance = 20 mH
Maximum External Connected L/R = 0.5mH/⍀
Note 3. Installation
•All wiring shall comply with Australian Standards.
• The input and output cables are to be installed either
as seperate cables or as seperate screened circuits.
• Certified IP66/67 glands or plugs must be used on
the enclosure cable entries.
Note 4. Maintenance and Repair
•The instrument modification or parts replacement by other
than authorized representative of Yokogawa Electric
Corporation is prohibited and will void SAA Certification.
[Installation Diagram for intrinsically safe type]
Hazardous Location
(Zone 0)
Transmitter
1
2
3
Sensor
4
5
Hazardous Location
(Zone 2)
Transmitter
*1: In any safety barriers used the output current must be limited by
a resistor “R” such that Imaxout-Uz/R.
+
Supply
–
[ Installation Diagram for Type n ]
+
+
SuppryPower Supply
–
–
Nonhazardous Location
Safety Barrier
+
–
Nonhazardous Location
+
+
–
–
*1
F2013.EPS
b) SAA Flameproof Type
Caution for SAA Flameproof Type
Note 1. Model YTA110/SU1, YTA310/SU1 and
YTA320/SU1 temperature transmitters for
potentially explosive atmospheres:
• Type of Protection and Marking Code:
Ex d IIC T6(Tamb 75°C) IP66/67 Zone 1
• Ambient Temperature: –40 to 75°C
Note 2.Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
•All wiring shall comply with Australian Standards.
•The cable entry devices shall be of a certified
flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep strictly the “WARNING” on the label on the
transmitter.
WARNING: WAIT 5 MIN. AFTER POWER-
DISCONNECTION, BEFORE
OPENING THE ENCLOSURE.
WHEN THE AMBIENT TEMP.
⭌ 70⬚C, USE THE HEATRESISTING CABLES OF HIGHER THAN
90⬚C
• Take care not to generate mechanical spark when
access to the instrument and peripheral devices in
hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void SAA
Certification.
2.8 EMC Conformity Standards
EN61326, AS/NZS 2064
YOKOGAWA recommends customer to apply
the Metal Conduit Wiring or to use the twisted
pair Shield Cable for signal wiring to conform the
requirement of EMC Regulation, when customer
installs the YTA Series Transmitters to the plant.
2-12
IM 01C50B01-01E
3. PART NAMES AND FUNCTIONS
3.PART NAMES AND FUNCTIONS
3.1 Part Names
Burn out output direction
setting pin upon hardware failure
Name plate
Stud bolt
CPU assembly
Terminal cover
LCD assembly
(with indicator)
Grounding
Amp. cover
Lock screw
Wiring connector
(input signal side)
terminal
Tag plate
Grounding
terminal
Wiring connector
(output signal side)
Figure 3.1Part Names
Built-in indicator display
Output signal terminal
3-1
Input signal terminal
F0301.EPS
F0301.EPS
IM 01C50B01-01E
3. PART NAMES AND FUNCTIONS
3.2 Setting the Hardware Error
Burnout Change-over Switch
The temperature transmitter is equipped with a hardware error burnout function used to set the output
direction upon hardware error, and a sensor burnout
function that sets the direction of the output in the
event of burnout of the temperature sensor. When
factory-shipped under normal conditions, the output of
both hardware error burnout and sensor burnout are set
to HIGH, but if suffix code /C1 is specified, the
hardware error burnout is set to LOW (-5%) output,
and sensor burnout is set to LOW (-2.5%) output,
respectively. The setting of the direction of output from
burnout can be changed.
To change the direction of output arising from burnout,
switch the setting pin on the CPU assembly (see Figure
3.1 and Table 3.1). To change the direction of output
arising out of sensor burnout, a dedicated hand-held
terminal is required to rewrite the parameters within
the transmitter. For details, refer to the separate
instruction manual, IM 01C50T01-01E “HART
Protocol” or IM 01C50T03-01E “BRAIN Protocol”.
Table 3.1Output Direction Setting Pins for Hardware
Error Burnout
Pin
position
H
L
H
L
burnout
direction
HIGH
LOW
Hardware error
burnout
output
110% or more
(21.6 mA DC)
-5% or less
(3.2 mA DC)
RemarkHardware error
Set to HIGH upon
shipment from the
factory
Set to LOW when
suffix code /C1
is provided
T0301.EPS
3.3 Built-in Indicator Display
(1)Output bar chart display
The output value is displayed in a bar chart. Resolution
of the bar chart is to the extent of 32 divisions (each
increment is about 3.125%). If the output exceeds 0%
or 100%,䉲 is lit. The bar chart can be toggled ON/
OFF using the bar chart display parameter.
(2) Communication protocol display
The indicator is on in accordance with each communication protocol.
(3)Operation mode display
Lit when each operation mode is activated.
M.D.:Lit when the multidrop mode of HART commu-
nication specification is activated.
B.M.: Lit during burst mode transfer of HART commu-
nication specification.
F.O.: Lit when manual mode is active.
W.P.: Lit when write protect status is active.
(4)Input display
Indicates the type of input in accordance with the value
shown in the column in Item (5).
Sns1: Meant to show the process variable allocated to
Sensor 1.
Sns2: Meant to show the process variable allocated to
Sensor 2. (Can be displayed only with the
YTA320.) .
Term: Meant to show the temperature of the terminal
box of the temperature transmitter.
Avg: Meant to show the average of the process
variable allocated to Sensor1 and Sensor2. (Can
be displayed only with the YTA320.).
Function
Communication protocol display
Output bar chart display
Operation mode
display
Input display
Process variable display
Unit display
Display of sensor type and
number of wire connections
Figure 3.2Built-in Indicator Display Function
F0302.EPS
Dif: Meant to show the difference of the process
variable allocated to Sensor1 and Sensor2. (Can
be displayed only with the YTA320.)
(5)Process variable display
Displays the process variable or output value. The
value is displayed down to the second decimal position
if the integer part is less than three digits, or down to
the first decimal position if the integer part is 4 digits.
If the value is negative, the minus (⫺) sign is lit. For
process variables, the indicators for each item specified
in the column of input display in Item (4) and the unit
column in Item (6) are lit. For output value, % or mA
in the unit column in Item (6) is lit. When burnout of
the temperature sensor is identified, or the temperature
transmitter is found abnormal, an error code flashes.
For a list of error codes, refer to “Error code table” in
Section 6.4.
3-2
IM 01C50B01-01E
3. PART NAMES AND FUNCTIONS
(6)Unit display
The unit specified as the unit of process in the process
variable display column in Item (5) is lit. The output
display is fixed to mA or %.
(7)Display of sensor type and number of wire
connections
Displays process variable/output items, the number of
sensor wiring connections and the multidrop address in
dot matrix (only applies to HART communication). In
the event of hardware error, “FAIL” is displayed.
Process variable:To display the process variable
value in the process variable
display in Item (5), display the type
of applicable process variable
(“PV”, “SV”, “TV”).
Output display:To display the output value in the
process variable display in Item
(5), display “OUT”. During the
output of sensor burnout, “Abn”
and “OUT” are alternately dis
played.
Upon shipment from the factory, the indicator is set as
follows.
Table 3.2Setting of Indicator upon Shipment from the
Factory
Display location
Output bar chart display
Input display
Process variable display
Unit display
Display of sensor type and
number of wire connections
Output bar chart display is on.
Sns1 is lit.
PV value and output value
(mA) are alternately displayed.
The unit specified upon
shipped from factory and mA
are lit.
“PV” and “OUT” are displayed
alternately.
Contents
T0302.EPS
WIRE:Displays the number of wiring
connections. There are two wiring
connections for thermocouple
input, while there are two to four
connections for thermometer
resistor; these are displayed
alternately with the sensor type.
The display can be hidden by
setting an applicable parameter.
Note that the DIF and AVG display
does not allow the sensor type to
be displayed.
TYPE:Displays the type of sensor. Note
that the DIF and AVG display does
not allow the sensor type to be
displayed. If the sensor is customordered, “Z1” and “Z2” are
displayed.
Multidrop address: If the multidrop address is 1
through 15 in HART communication, the output display brings up
these addresses instead of display
ing “OUT”.
3-3
IM 01C50B01-01E
4.INSTALLATION
4. INSTALLATION
IMPORTANT
• When performing on-site pipe fitting work that
involves welding, use care to prevent outflow
of the welding current into the transmitter.
• Do not use the transmitter as a foothold for
installation.
• For details of choosing the installation location, refer
to the guidelines outlined in Section 2.4, “Choosing
the installation location”.
• The mounting bracket shown in Figure 4.1 is used
for the transmitter and is installed on 50A (2B) pipe.
It can be installed either on a horizontal pipe and a
vertical pipe or on a wall.
• To install the mounting bracket on the transmitter,
torque the transmitter lock screw (1) to about 20 to
30N⭈m.
Horizontal Pipe Mounting
U-bolt nut
Mounting bracket
Spring washer
Transmitter lock scraps
2B pipe
(60.5dia.)
U-bolt
Vertical Pipe Mounting
Wall Mounting
Note: Wall mounting bolts are user-
supplied.
Figure 4.1Mounting the Transmitter
4-1
F0401.EPS
IM 01C50B01-01E
5.WIRING
F0501.EPS
<Hazardous location><Nonhazardous location>
+
Output signal
–
Distributor
(power supply unit)
Receiver
Input signal
(thermocouple,
RTD, mV, etc.)
F0502.EPS
<Hazardous location><Nonhazardous location>
+
Output signal
–
Distributor
(power supply unit)
Receiver
Safety
barrier
Input signal
(thermocouple,
RTD, mV, etc.)
5.1 Notes on Wiring
IMPORTANT
• Apply a waterproofing sealant to the
threads of the connection port. (It is recommended that you use non-hardening sealant
made of silicon resin for waterproofing.)
• Lay wiring as far away as possible from
electrical noise sources such as large transformers, motors and power supplies.
• Remove the wiring connection dust-caps
before wiring.
• To prevent electrical noise, the signal cable
and the power cable must not be housed in
the same conduit.
• The terminal box cover is locked by an Allen
head bolt (a shrouding bolt) on CENELEC,
SAA and JIS flameproof type transmitters.
When the shrouding bolt is driven clockwise
by an Allen wrench, it is going in and cover
lock is released, and then the cove can be
opened by hands. See Subsection 6.3
“Disassembly and Reassembly” for details.
5.2 Loop Construction
The YTA is a two-wire temperature transmitter that
uses the output power supply wiring and signal wiring
alternately.
5. WIRING
Figure 5.1Loop Construction (for General-use Type and
Figure 5.2Loop Construction (for Intrinsically Safe
resistance
Flameproof Type)
Type)
600
External
load
250
R
(⍀)
R=
E–10.5
0.0236
Communication
applicable range
BRAIN and HART
The transmission loop requires DC power. Connect the
transmitter with the distributor as shown in Figure 5.1
or Figure 5.2.
For the transmission loop, the load resistance of the
distributor or other instrument to be installed in the
loop and the lead wire must be within the range shown
in Figure 5.3.
For details of communication requirements, refer to the
additional reference materials, IM 01C50T03-01E “YTA
Series BRAIN Communication”, and IM 01C50T01-01E
“YTA Series HART Communication”.
10.5 16.424.742
Power supply voltage E (V DC)
Figure 5.3Relation between Power Supply Voltage and
Note: For intrinsic safe explosion-proof type units, the internal
5-1
Load Resistance
resistance of the safety barrier is also included in the load
resistance.
IM 01C50B01-01E
F0503.EPS
5. WIRING
5.3 Cable Selection
5.3.1 Input signal Cable Selection
A dedicated cable is used for connection between the
temperature sensor and the temperature transmitter.
When a thermocouple is used as the temperature
sensor, a compensation wire must be used that it
appropriate for the type of thermocouple (refer to
compensating cables for JIS C 1610/IEC584-3 thermocouples). When a resistance temperature sensor (RTD)
is used as the temperature sensor, 2-core/3-core/4-core
cable must be used (refer to resistance thermometer
sensor JIS C 1604/IEC751). The terminal of the
dedicated cable is a 4 mm screw.
5.3.2 Output Signal Cable Selection
• With regard to the type of wire to be used for
wiring, use twisted wires or cables with performance equivalent of 600V vinyl insulated cable
(JIS C3307).
• For wiring in areas susceptible to electrical noise,
use shielded wires.
• For wiring in high or low temperature areas, use
wires or cables suitable for such temperatures.
• For use in an atmosphere where harmful gases or
liquids, oil, or solvents are present, use wires or
cables made of materials resistant to those substances.
• It is recommended that a self-sealing terminal with
insulation sleeve (4-mm screw) be used for lead
wire ends.
CAUTION
When wiring, pay attention not to damage the
cable and cores. All the cores of the cable must
have the sufficient insulation around them.
STEP 1
(1)
a. Cable connection to thermometer resistor(RTD),
3-wire
STEP 2
(2)
b. Power supply cable connection
Figure 5.4Terminal Connection Pro cedure
F0504.EPS
WARNING
If the YTA is JIS flameproof and the ambient
temperature is 50°C or more, use an external
cable having a maximum allowable heat resistance of at least 70°C in consideration of the
instrument’s generation of heat or the cable’s
self-heating.
5.4 Cable and Terminal Connections
5.4.1 Input Terminal Connections
NOTE
It is recommended that the terminals be connected in the order of input terminal (1) and
output terminal (2).
䊏 The temperature sensor is to be connected
as shown in Figures 5.6 and 5.7.
Figure 5.5Terminal diagram
5-2
IM 01C50B01-01E
F0505.EPS
5. WIRING
Sensor1(YTA110, YTA310)
1
(+)
2
3
(–)
4
5
Thermocouple and
DC voltage
(A)
1
(B)
2
(B)
3
4
5
RTD and resistance
(3-wire)
RTD and resistance
1
2
3
4
5
1
2
3
4
5
(A)
(B)
(2-wire)
(A)
(A)
(B)
(B)
RTD
(4-wire)
F0506.EPS
Figure 5.6YTA110 and YTA310 Input Terminal Wire
Connection Diagram
1 input (YTA320)
1
(+)
2
3
(–)
4
5
Thermocouple and
DC voltage
(A)
1
(B)
2
(B)
3
4
5
RTD and resistance
(3-wire)
(A)
1
2
(B)
3
4
5
RTD and resistance
(2-wire)
(A)
1
(A)
2
(B)
3
(B)
4
5
RTD
(4-wire)
5.4.2 Output Terminal Connection
(1) Connection of output signal/power supply
cable
Connect the output signal cable (shared with the
power supply cable) to the – terminal and the +
terminal. For details, refer to Figure 5.2, “Loop
construction”.
(2) Connection of wiring for field indicator
Connect the lead wire for the field indicator with
the – terminal and the C terminal.
Note: Use a field indicator with an internal resistance of 10W or less.
Field indicator
Power
supply
+
Figure 5.8Connection to Field Indicator
(3) Connection of check meter
Connect the check meter with the – terminal and
the C terminal.
The current signal of output signal 4 to 20 mA DC
is output from the – terminal and the C terminal.
Note: Use a check meter with internal resistance of 10⍀ or less.
Check meter
––+
F0508.EPS
2 input (YTA320)
(+)
1
2
(–)
3
4
(+)
5
Thermocouple and
DC voltage
(+)
1
(–)
2
3
4
5
(B)
(B)
(A)
Thermocouple +
RTD and resistance
(A1)
1
(B1)
2
(B1)
3
(B2)
4
(B2)
5
(A2)
RTD and resistance
(3-wire)
(A1)
1
(B1)
2
3
(B2)
4
(A2)
5
RTD and resistance
(2-wire)
(3-wire)
Figure 5.7YTA320 Input Terminal Wire Connection
Diagram
Figure 5.9Check Meter Connection
+
–
Power
supply
F0509.EPS
5-3
IM 01C50B01-01E
5. WIRING
5.5 Wiring Cautions
(1) General-use Type and Intrinsically Safe
Type
Use metal conduit wiring or a waterproof gland
(metal wiring conduit JIS F 8801) for cable wiring.
•Apply nonhardening sealant to the threads of the
wiring tap and a flexible fitting for secure waterproofing. Figure 5.10 shows an example of wiring
on the output side. This example also applies to the
wiring on the input side.
Flexible fitting
Wiring conduit
Apply a nonhardening
sealant to the threads for
waterproofing.
Figure 5.10 Example of Wiring Using a Wiring Conduit
(2) JIS Flameproof Type
Wire cables through a flameproof packing adapter,
or using a flameproof metal conduit.
Tee
Drain plug
F0510.EPS
Table 5.1Flameproof Packing and Appropriate Cable
Wiring Port
Thread
Diameter
G1/2
Outer Diameters
Appropriate
Cable Outer
Diameter (mm)
8 -10
10.1-12
Identifying
Mark
16168-10
10-12
Part
Number
G9601AM
T0501.EPS
Follow the procedure below to install the flameproof
packing adapter.
1. Screw the flameproof packing adapter into the
terminal box until the O-ring touches the terminal
box wiring port (at least 6 full turns), and tighten the
lock nut.
2. Insert the cable through the union cover, the union
coupling, the gland the clamp nut, the clamp ring,
one washer, the rubber packing, and the packing
box, in that order.
3. Insert the end of the cable into the terminal box.
4. Tighten the union cover to grip the cable. When
tightening the union cover, tighten approximately
one turn past the point where the cable will no
longer move up and down. Proper tightening is
important. If it is too tight, a circuit break in the
cable may occur; if not tight enough, the flameproof
effectiveness will be compromised.
䊏 Wiring cable through flameproof packing
adapter for only JIS flameproof type (see
Figure 5.11)
• Use only flameproof packing adapters approved by
Yokogawa.
• Apply a nonhardening sealant to the terminal box
connection port and to the threads on the flameproof packing adapter for waterproofing.
Flexible fitting
Wiring conduit
Apply a nonhardening
sealant to the threads for
waterproofing.
Figure 5.11 Typical Cable Wiring Using Flameproof
Packing Adapter
Tee
Drain plug
F0510.EPS
•Measure the cable outer diameter in two directions
to within 0.1mm.
• Calculate the average of the two diameters, and use
packing with an internal diameter nearest to this
value from among the three provided (see
Table5.1).
CAUTION
Tighten the union cover approximately one turn
after the point where you can no longer shift the
cable up and down by hand. Take great care in
this step, since proper tightening is very important.
5. Fasten the cable with tightening the clamp nut.
6. Tighten the lock nut on the union cover.
7. Connect the cable wires to each terminal.
Lock nut
Cable
Union cover
Union coupling
Clamp nut
Clamp ring
Grand
Washer
Rubber packing
Packing box
Lock nut
Adapter body
O-ring
CAUTION
Be sure to apply nonhardening sealant to
the threads for water
proofing.
Figure 5.12 Flameproof Gland Packing Adapter
lnstallation
F0512.EPS
5-4
IM 01C50B01-01E
5. WIRING
NOTE
䊏 Flameproof metal conduit wiring
•A seal fitting must be installed near the terminal
box connection port for a sealed construction.
• Apply a nonhardening sealant to the threads of the
terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.
Flameproof flexible
metal conduit
Gas sealing
device
Apply a nonhardening
sealant to the threads of
these fittings for
waterproofing
Seal fitting
After wiring, impregnate the fitting
with a compound to seal tubing.
Figure 5.13 Typical Wiring Using Flameproof Metal
Conduit
Non-hazardous
area
Hazardous
area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
F0513.EPS
5.6 Grounding
Grounding should satisfy JIS Class D requirements
(with ground resistance of 100⍀ or less). Grounding
work is required for withstand voltage explosionproof
type units and intrinsic safe explosionproof type
transmitters.
For a transmitter with built-in arrester, grounding
should satisfy JIS Class C requirements (with
ground resistance of 10⍀ or less).
Grounding terminals are located both inside and
outside the terminal board.
Use 600V vinyl insulation wires for the grounding
conductor.
Grounding
terminal
Grounding
terminal
Figure 5.14 Grounding Terminal
F0511.EPS
5-5
IM 01C50B01-01E
6.MAINTENANCE
6. MAINTENANCE
6.1 General
Each component of this instrument is configured in
units to make maintenance easier.
This chapter contains disassembly and assembly
procedures associated with calibration, adjustment and
part replacement required for maintenance of the
affected instrument.
IMPORTANT
1. Maintenance of this instrument should be
performed in a service shop where the necessary tools are provided.
2. Handling the CPU assembly
Some of the parts contained in the CPU
assembly are susceptible to static electricity
damage. Before performing maintenance, use
a ground wrist band or other antistatic mea
sures, and avoid touching the electronic
components and circuits with bare hands.
When removed from the instrument, keep the
CPU assembly in an antistatic bag.
Table 6.1Calibration Equipment List
NameRecommendedRemark
Power supply
Load resistance
Voltmeter
Universal
calibrator
Variable resistor
a. Wiring of power supply and output
SDBT, SDBS
type distributor
2792 type standard
resistor
(250⍀ ±0.005%)
Model 1271 digital
multimeter
(accuracy: ±0.002%)
Model 9100 type
279301 type 6-dial
variable resistor
(accuracy: ±0.005%)
+ Output signal
–
Load
resistance
4 to 20mA DC
(Output voltage:
26.5±1.5V, drop by
internal 250⍀
resistance included)
For 4 to 20mA DC
For 4 to 20mA DC
signal
For calibration of
DC voltage and
thermocouple
For calibration of
thermometer resistor
(RTD) input
T0601.EPS
6.2 Calibration
This instrument is fully factory-tested and is guaranteed for the intended accuracy, eliminating the need for
calibration. When calibration needs to be varified, the
following equipment and calibration procedure is
recommended.
6.2.1 Selection of Equipment for Calibration
Table 6.1 lists the equipment required for calibration.
The calibration equipment traceable to a verifying
agency standard should be used.
6.2.2 Calibration Procedure
To conduct calibration required to evaluate the uncertainty while using the instrument, follow the steps
below:
1. In accordance with the example wiring shown in
Figure 6.1, connect each equipment and initiate
warm up. Lay wiring on the input side according to
the sensor to be used.
Voltmeter
b. Example of wiring for thermocouple
or DC voltage input
(when 1 input type is used)
1
2
3
4
5
c. Example of wiring for thermometer
resistor 4-core type
(when 1 input type is used)
1
2
3
4
5
Figure 6.1Example of Wiring for Calibration Equipment
(+)
(–)
DC voltage generator
(A)
(A)
(B)
(B)
Variable resistor
F0601.EPS
2. For DC voltage input
With a voltage generator, deliver input signals
corresponding to 0, 25, 75, or 100% of the input
span to the temperature transmitter. Measure the
resulting input signal with the voltmeter (digital
multimeter) and check the output value relative to
the input value.
6-1
IM 01C50B01-01E
6. MAINTENANCE
3. For thermocouple input
Since this instrument is equipped with a reference
junction compensating function, use a reference
junction compensating function in universal
calibrator in order to compensate for this function
upon calibration. According to the reference
milivolt table for thermocouple, obtain milivolt
corresponding to 0, 25, 50, 75, or 100% of the
span, and use that power as the input value, then
deliver it from the universal calibrator to the
temperature transmitter. Measure the resulting
output signal with the voltage meter (digital
multimeter) and check the output value relative to
the input value.
4. Thermometer resistor (RTD)
Using a thermometer resistor as input, calibration of
the temperature transmitter is carried out via a 4core wire connection.
As defined the reference resistor value table of the
thermometer resistor (RTD), obtain resistance
values corresponding to 0, 25, 50, 75 or 100% of
the span, and use the obtained resistance as the
input value, then deliver it to the temperature
transmitter by means of a variable resistor. Measure
the resulting output signal with the voltmeter
(digital multimeter) and check the output value
relative to the input value.
5. In Steps 2 through 4, if the output signal deviates
from the given range of accuracy when a given
input signal is delivered, adjust the output using the
handheld terminal. For details of how to adjust the
output, refer to the additional references, “BRAIN
Protocol” IM 01C50T03-01E or “HART Protocol”
IM 01C50T01-01E and the instruction manual for
each terminal.
Precautions for CENELEC and JIS Flameproof Type Transmitters
• For a withstand flameproof type transmitter, as
a rule, move the transmitter to a non-hazardous
location, then proceed with maintenance and
restore the instrument to the original condition.
• For a withstand CENELEC and JIS flameproof
type transmitter, turn the lock bolt (hexagon
socket bolt) clockwise with a wrench for hexagon head, unlock and remove the cover. When
installing the cover, it is the must to turn the
lock bolt counterclockwise and lock the cover
(locked to a torque of 0.7 Nm).
• For a withstand flameproof type transmitter, in
no case should the user be allowed to modify
the transmitter. Therefore, no user is allowed to
add a built-in indicator, or use the transmitter
with the indicator removed. Contact us for any
modification.
Terminal cover
6.3 Disassembly and Assembly
This section details the procedure for part replacement
or disassembly and assembly of each component
depending on the maintenance process.
Before starting disassembly and assembly work, turn
off the power, and use a tool suited to the associated
work.
Table 6.2 lists the tools required for disassembly and
assembly of the instrument.
CPU assembly
LCD board
(with indicator)
Amp. Cover
Lock bolt
Stud bolt
Mounting screw
Figure 6.3Mounting and Removal of Built-in Indicator
and CPU Assembly
6-2
IM 01C50B01-01E
F0602.EPS
6. MAINTENANCE
NOTE
6.3.1 Replacement of Built-in Indicator
䊏 Removal of built-in indicator
1. Remove the cover.
2. Loosen two mounting screws while using your hand
to support the built-in indicator.
3. Remove the LCD assembly from the CPU assembly. At this time, straighten and pull the LCD
assembly forward so that the connector connecting
the CPU assembly and the LCD assembly is not
damaged.
䊏 Mounting the built-in indicator
Integral Indicator can be installed in the following
three directions.
6.3.2 Replacement of CPU Assembly
䊏 Removal of CPU assembly
1. Remove the cover.
2. Use a Phillips screwdriver to loosen the two screws.
3. For a CPU assembly with a built-in indicator,
remove it as described in Section 6.3.1. Next loosen
the two stud bolts.
4. Pull the CPU assembly directly toward you.
5. Remove the cable (with a brown connector attached
at the head).
Use care not to apply excessive force to the
CPU assembly during removal.
䊏 Mounting the CPU assembly
1. Connect the cable with the CPU assembly.
2. Align the pin on the base board with the connector
(black) of the CPU assembly, and insert the CPU
assembly straight into the board.
F0603.EPS
Figure 6.4Installation Direction of Indicator
1. Place the LCD assembly in desired direction over
the CPU assembly.
2. Align the mounting hole of the LCD assembly with
the stud bolt hole, and carefully insert the indicator
into the connector in a straight manner so that the
connector is not damaged.
3. Tighten the two mounting screws that secure the
indicator.
4. Install the cover.
IMPORTANT
Use care not to pinch the cable under the cover,
and fully insert the cable into the case.
3. Loosen the two screws. If the unit includes a builtin indicator, install it as described in Section 6.3.1.
4. Mount the cover.
6-3
IM 01C50B01-01E
6. MAINTENANCE
6.4 Troubleshooting
When the measured value is found abnormal, follow
the troubleshooting flowchart below. If the complex
nature of the trouble means that the cause cannot be
identified using the following flowchart, refer the
matter to our service personnel.
6.4.1 Basic Troubleshooting Flow
When the process measurement is found to be abnormal, it is necessary to determine whether the input
temperature is out of range, the sensor has failed or
being damaged, or the unit has been improperly wired.
If it is suspected that the measurement system is the
source of the problem, use the flowchart to identify the
affected area and determine how to proceed.
In these troubleshooting steps, the self diagnostic
function provides helpful solutions to the problem,
refer to the instructions in Section 6.5 for details.
:Part supported
by self-diagnosis
Measured value
is found faulty
YES
Inspect the process
YES
Error in process
variable?
NO
Faulty
area in measurement
system
Receiver error
Error in measurement
system
6.4.2 Example of Troubleshooting Flow
The following phenomena indicate that this
instrument may be out of operation.
[Example]
• No output signal is delivered.
• Process variable changes but the output
signal remains unchanged.
• The assessed value of the process variable
and the output are not coincident.
• If a built-in indicator is attached, check the
display of the error code.
• Connect a hand-held terminal and check
self-diagnosis.
Was a faulty
area found with self-
diagnosis?
NO
Is the polarity
of the power supply
correct?
YES
Are the power
supply voltage and load
resistance correct?
YES
Refer to the error message list and
check for recovery measures.
Check the polarity between the
power supply and terminal box and
correct it.
Refer to Section 5.2 and set
the specified voltage and load
resistance.
YES
NO
NO
Inspect receiver
Environmental condition
Environmental condition:
check, study, correction
Operating requirements:
check, study, correction
Figure 6.5Basic Flow and Self-diagnosis
NO
Check the transmitter
Operating requirements
Transmitter
F0604.EPS
Is the sensor
correctly connected?
YES
Is there a
disconnection in the loop?
Do the loop numbers
correspond to the
counterpart?
YES
Refer to our service personnel for details.
Figure 6.6Example of Troubleshooting Flow
Check the sensor connection and
correct it.
Check for disconnection or faulty
wiring and take corrective
measures.
6-4
NO
NO
F0605.EPS
IM 01C50B01-01E
Table 6.3Problems, Causes and Countermeasures
Observed ProblemsPossible CauseCountermeasure
Output fluctuates
greatly.
Transmitter outputs
fixed current.
Span is too narrow.
Input adjustment by user was
not corrctly done.
Output adjustment by user
was not correctly done.
The transmitter is in manual
(test output) mode.
Check the range, and change the
settings to make the span larger.
Clear the user adjustment (Sensor
trim) value or set it to off.
Clear the user adjustment (output
trim) value or set it to off.
Release manual mode. (Make the
transmitter return to Automatic
F10:LRV
F20:URV
J05:SNSR1 CLR
K05:SNSR2 CLR
L05:OUT CLR
G10:OUTPUT MODE
Mode)
Clear the user adjustment (Sensor
trim) value or set it to off.
Clear the user adjustment (output
trim) value or set it to off.
Set the correct value to URV and
LRV.
Set the transmitter to normal
output mode.
Release write protect.
Set Sensor1 as PV and Sensor2
as SV.
• Check the type and wire
settings for Sensor1 and
J05:SNSR1 CLR
K05:SNSR2 CLR
L05:OUT CLR
F10:LRV
F20:URV
H10:REVERSE OUT
H40:WRITE PROTCT
B10:PV is
B20:SV is
D10:SENSOR1 TYPE
E10:SENSOR2 TYPE
Output is reversed.
(See note 1)
Parameters cannot
be changed.
Sensor backup
function doesn’t work
correctly.
Input adjustment by user was
not corrctly done.
Output adjustment by user
was not correctly done.
LRV is greater than URV.
The transmitter is set to
reversed output mode.
The transmitter is in write
protect status.
Settings of Process Variables
are not correct.
Configuration of Sensor1 and
Sensor2 is not correct.
Sensor2.
• Check the connection of
Sensor1 and Sensor2.
Check the Sensor Burnout setting.
Change the Sensor Backup
function to “enable.”
Set correct value.
If output fluctuation is great, set a
greater value for PV damping
F40:BURN OUT
H20:SNSR BACKUP
B12:PV DAMPING
B13:DMP POINT
Output damping
doesn’t work.
Sensor Burnout is set to “off.”
Sensor backup mode is not
enabled.
Damping time constant is set
to “0 second.”
Setting for “PV damping point”
is too small.
point than current setting. (Initial
setting is “2%” of output)
Note 1: If the reversed output is desired and necessary setting was done by user, it is not considered as a problem.
6. MAINTENANCE
Related Parameter
(HART protocol)(BRAIN protocol)
PV LRV (4)
PV URV (5)
Snsr1 Trim Act (123312)
Snsr2 Trim Act (123322)
D/A Clr to Default
(12343)
Loop test (122)
Snsr1 Trim Act (123312)
Snsr2 Trim Act (123322)
D/A Clr to Default
(12343)
PV LRV (4)
PV URV (5)
Chng wrt Protect
(Hot key)
PV is (11211)
SV is (11212)
Snsr1 config (134)
Snsr2 config (135)
Sensor barnout (14315)
Snsr backup (14141)
PV damp (1322)
PV damp point (1323)
T0603.EPS
6-5
IM 01C50B01-01E
6.5 Integral Indicator and Error
Display
For temperature transmitters equipped with an integral
indicator, errors in the temperature sensor or the
transmitter cause an integral indicator to call up the
applicable error code. Table 6.4 lists the error codes
and the associated corrective actions.
Table 6.4List of Error Codes
6. MAINTENANCE
IndicatorBT200 displayCause
N/AGood
Er-01Output Too Low
Er-02Output Too High
Er-03Sensor1 Failure
Er-04Sensor2 Failure
(YTA320 only)
Er-05S1 Signal Error
Er-06S2 Signal Error
(YTA320 only)
Er-07Amb Temp Low
Er-08Amb Temp High
Er-09Sns Backup Start
(YTA320 only)
Er-10Illegal PV MAP
Er-11Term Sns Failure
Er-12EEPROM Failure
Er-13CPU Failure
Er-14AD Conv Failure
Input value is lower than the
PV low range value.
Input value is higher than the
PV upper range value.
Sensor1 fails or disconnects
from the terminal block.
Sensor2 fails or disconnects
from the terminal block.
Sensor1 input value greatly
exceeds the sensor
measurement range. Sensor
type setting or connection
polarity may be incorrect.
Sensor2 input value greatly
exceeds sensor
measurement range. Sensor
type setting or connection
polarity may be incorrect.
The ambient temperature
exceeds the lower ambient
temp limit and the specified
accuracy cannot be
achieved.
The ambient temperature
exceeds the upper ambient
temp limit and the specified
accuracy cannot be
achieved.
Sensor backup mode is in
effect.
There is a problem with the
PV mapping settings.
Terminal block temperature
sensor failed.
EEPROM failed.
Output side hardware failure.
Input circuit hardware failure.
Output operation upon error
Output goes to minimum
value(–2.0%).
Output goes to maximum
value(105%).
If sensor1 is set as PV, the
burnout value is output.
When sensor backup mode
is set in YTA320, sensor2
input is used as output.
If sensor2 is set as PV, or
sensor backup mode is in
effect, sensor burnout value
is output.
Output goes to minimum
value(–2.0%) or maximum
value(105%).
Output goes to minimum
value(–2.0%) or maximum
value(105%).
Continues to operate and
output.
Continues to operate and
output.
Sensor2 input is used as
output. If sensor2 also fails,
the transmitter operate with
burnout settings.
Output status immediately
before error is retained
(HOLD).
Operation and output
continues.
The output goes to the
value set by the hardware
failure mode jumper.
The output goes to the
value set by the hardware
failure mode jumper.
The output goes to the
value set by the hardware
failure mode jumper.
6-6
Action
Check the LRV setting and
adjust.
Check the URV setting and
adjust.
•Check sensor for damage.
•Check terminal connection.
• If sensor backup mode is set,
refer to “Er-09”.
•Check sensor for damage.
•Check terminal connection.
• If sensor backup mode is set,
repair wiring or replace
damaged sensors.
•Check sensor connections.
•Check the sensor type
selected.
•Check sensor connections.
•Check sensor type selected
.
Use a heater to raise the
ambient temperature, or reset to
a higher level.
Take enough distance from the
source of heat, or reset to a
lower level.
Restore the status of sensor1 to
normal and Enable sensor1
return parameters, or turn the
power ON again.
Check the setting for PV
mapping and correct the setting.
Contact our service personnel.
Contact our service personnel.
Contact our service personnel.
Contact our service personnel.
T0604.EPS
IM 01C50B01-01E
7. STANDARD SPECIFICATIONS
7.STANDARD SPECIFICATIONS
7.1 Standard Specifications
For the specifications of Fieldbus communication type
marked with (䉫), refer to IM 01C50T02-01E.
Input signal:
Input points:YTA110; 1, YTA310; 1,
YTA320; 2
Thermocouple:J, K, E, T, R, S, B, N
(T/C)(JIS/IEC584), L, U
2/3/4-wire
DC voltage:mV
Resistance:Resistor 2/3-wire
Input resistance:
1M or higher (3k or higher with power ON)
Input signal source resistance:
1k or lower (at thermocouple, DC voltage
input)
Input lead wire resistance:
10/1-core or less (with thermometer resistor,
resistance input)
Output signal(䉫):
4 to 20 mA DC 2-core
Communication line conditions(䉫):
Power supply voltage; 16.4 to 42 VDC
Load resistance; 250 to 600 (including cable
resistance)
For relation between power supply voltage and
load resistance, refer to Figure 5.3.
Maximum line length; 2 km when CEV cable is
used.
Load resistance; 0.22 µF or less
Load inductance; 3.3 mH or less
Spacing to power line;
Output signal line; 15 cm or longer (avoid
parallel wiring)
Input signal line; 100 cm or longer (avoid
parallel wiring)
Input impedance of receiver connected to
receiver resistance; 10 k or higher (at 2.4 kHz)
Accuracy(䉫):
YTA110;
A/C conversion accuracy + D/A conversion
accuracy (Refer to Table 7.1) or ±0.1%,
whichever is greater. For thermocouple input,
above plus reference junction compensation
accuracy.
YTA310, YTA320;
A/C conversion accuracy + D/A conversion
accuracy (Refer to Table 7.1) For thermocouple
input, above plus reference junction compensa
tion accuracy.
Measuring range:
Refer to Table 7.1.
Power supply voltage(䉫):
For general use type;
10.5 to 42 VDC
With lightning protection (Optional code A);
10.5 to 32 VDC
For intrinsically safe, Type n, non-incendive or
non-sparking type;
10.5 to 32 VDC
Reference junction compensation accuracy:
±0.5°C (±0.9°F)
Ambient temperature:
–40 to 85°C (–40 to 185°F) . . . general type
–30 to 80°C (–1 to 176°F) . . . . with Integral
indicator
Ambient temperature effect per 10°C change(䉫) :
YTA110;
± 0.1% or ± (Temperature Coefficient/span),
whichever is greater (refer to Table 7.2)
YTA310, YTA320;
A/D conversion temperature factor + D/A
conversion temperature factor (refer to Table
7.3)
7-1
IM 01C50B01-01E
Ambient humidity:
5 to 100%RH at 40°C (104°F)
Effect of supply voltage fluctuation:
±0.005%/V
Insulation:
Input/output insulated at 500 V AC
Mounting:
Mounted on 2B pipes and wall
Waterproofing:
JIS0920, water-resistant type (equivalent of
NEMA TYPE4X)
Electrical connection:
Refer to “Model and Specification Codes”.
Case and cover:
Aluminum alloy casting
Painting:
Polyurethane resin baked finish
Deep sea moss green (equivalent of Munsell
0.6GY3.1/2.0)
7. STANDARD SPECIFICATIONS
Integral indicator (option):
LCD digital indicator (5-digit display)
Output bar graph; 0 to 100% display
Damping constant:
1 to 99 seconds (integer range that can be set)
Sensor burnout (Output Signal Code D&E) :
High (110%, 21.6 mA DC) or Low (–2.5%, 3.6
mA DC)
Weight:
1.2 kg; without built-in indicator (without mounting bracket)
1.4 kg; with Integral indicator (without mounting
bracket)
EMC compliant standard: ,
EN61326, AS/NZS 2064
7-2
IM 01C50B01-01E
7. STANDARD SPECIFICATIONS
Table 7.1Input Type, Measurement Range and Accuracy
Sensor T ype
T/C
RTD
mV
ohm
Reference
Standard
B100 to 1820212 to 3308
E
J
K
IEC584
N
R
S
T
W3
ASTM
E988
W5
L
DIN43710
U
Pt100
Pt200IEC751-200 to 850-328 to 1562
Pt500-200 to 850-328 to 1562
JPt100
JIS C1604
SAMA
Cu-70 to 150-94 to 302
RC21-4
Ni120-70 to 320-94 to 608-70 to 320-94 to 608 ± 0.11 ± 0.19
Measurement Range
CF
-200 to 1000-328 to 1832
-200 to 1200-328 to 2192
-200 to 1372-328 to 2502
-200 to 1300-328 to 2372
-50 to 1768-58 to 3214
-50 to 1768-58 to 3214
-200 to 400-328 to 752
0to230032 to 4172
0to230032 to 4172
-200 to 900-328 to 1652
-200 to 600-328 to 1112
-200 to 850-328 to 1562-200 to 850-328 to 1562 ± 0.14 ± 0.25
-200 to 500-328 to 932-200 to 500-328 to 932 ± 0.16 ± 0.29
-10 to 100
0to2000
[mV]
[Ω]20 [Ω]
Minimum Span
(Recommended)
25 C
(45 F)
10 C
(18 F)
3 [mV]
Input range
CF
100 to 300212 to 572 ±3.0 ± 5.4
300 to 400572 to 752 ±1.0 ± 1.8
400 to 1820752 to 3308 ± 0.75 ± 1.35
100 to 600212 to 1112 ± 0.60 ± 1.08
600 to 17681112 to 3214 ± 0.40 ± 0.72
-200 to-50-328 to-58 ± 0.25 ± 0.45
-50 to 400-58 to 752 ± 0.14 ± 0.25
0to 40032 to 752 ± 0.80 ± 1.44
400 to 1400752 to 2552 ± 0.50 ± 0.90
1400 to 20002552 to 3632 ± 0.60 ± 1.08
2000 to 23003632 to 4172 ± 0.90 ± 1.62
0to 40032 to 752 ± 0.70 ± 1.26
400 to 1400752 to 2552 ± 0.50 ± 0.90
1400 to 20002552 to 3632 ± 0.70 ± 1.26
2000 to 23003632 to 4172 ± 0.90 ± 1.62
-200 to-50-328 to-58 ± 0.30 ± 0.54
-50 to 900-58 to 1652 ± 0.20 ± 0.36
-200 to-50-328 to-58 ± 0.50 ± 0.90
-50 to 600-58 to 1112 ± 0.25 ± 0.45
-200 to 850-328 to 1562 ± 0.30 ± 0.54
-200 to 850-328 to 1562 ± 0.20 ± 0.36
-70 to-40-94 to-40 ± 1.35 ± 2.43
-40 to 150-40 to 302 ±1.0 ± 1.8
Accuracy
A/D Accuracy
CF
± 12 [µV]
± 0.35 [Ω]
D/A
Accuracy
± 0.02%
of span
T0701.EPS
7-3
IM 01C50B01-01E
7. STANDARD SPECIFICATIONS
Table 7.2YTA110 Effect of Ambient Temperature
Sensor T ype
Thermocouples E, J, K, N, T, L, U
Thermocouples R, S, W3, W5
100C Reading < 300C
T/C B
300C Reading
RTD
mV
ohm
Temperature Coefficient
0.08C + 0.02% of abs.reading
0.25C + 0.02% of abs.reading
1C + 0.02% of abs.reading
0.5C + 0.02% of abs.reading
0.08C + 0.02% of abs.reading
0.002 mV + 0.02% of abs.reading
0.1 + 0.02% of abs.reading
T07021.EPS
Table 7.3YTA310, YTA320 Effect of Ambient Temperature
Sensor T ype
B
E
J
K
N
R
T/C
S
T
W3
W5
L
U
Pt100
Pt200
Pt500
RTD
JPt100
Cu
Ni120
mV
ohm
C
100 to
300 to
1000 to
-200 to
-200 to
0to
-200 to
0to
-200 to
0to
-50 to
200 to
-50 to
200 to
-200 to
0to
0to
1400 to
0to
1400 to
-200 to
0to
-200 to
0to
-200 to
-200 to
-200 to
-200 to
-70 to 150
-70 to
Input Range
212 to
300
0
572 to
1832 to
-328 to
-328 to
1000
1820
1000
1200
-328 to
0
1372
-328 to
0
1300
-58 to
200
200
0
392 to
-58 to
392 to
-328 to
1768
1768
400
1400
2552 to
2300
1400
2552 to
2300
-328 to
0
900
-328 to
0
600
-328 to
850
-328 to
850
-328 to
850
-328 to
500
-94 to
320
F
32 to
32 to
32 to
32 to
32 to
32 to
32 to
32 to
± (
572
± (
1832
± (
3308
± (
1832
± (
32
± (
2192
± (
32
± (
2502
± (
32
± (
2372
± (
392
± (
3214
± (
392
± (
3214
± (
32
± (
752
± (
2552
± (
4172
± (
2552
4172
± (
± (
32
± (
1652
± (
32
± (
1112
± (
1562
± (
1562
± (
1562
± (
932
± ( 0.320C0.120 % of reading)-94 to302
± (
608
± (0.001mV0.0043 % of abs.reading)
± (
A/D CoefficientD/A Coeffieicient
0.530C0.080 % of reading)
0.350C0.021 % of reading )
C)
0.140
0.035C0.042 % of abs.reading)
0.039C0.020 % of abs.reading)
C0.0029 % of reading)
0.039
0.046C0.020 % of abs.reading)
C0.0054 % of reading)
0.046
0.054C0.010 % of abs.reading)
C0.0036 % of reading)
0.054
0.210C0.032 % of abs.reading)
C)
0.150
0.210C0.032 % of abs.reading)
C)
0.150
0.046C0.036 % of abs.reading)
C)
0.046
± {0.0088% of span0.007% of (readingLRV)}
0.100C0.0040 % of reading)
C0.020 % of reading)
-0.130
0.100C0.0040 % of reading)
C0.020 % of reading)
-0.120
0.039C0.020 % of abs.reading)
C0.0029 % of reading)
0.039
0.046C0.036 % of abs.reading)
C)
0.046
0.047C0.009 % of reading)
0.065C0.012 % of reading)
0.047C0.009 % of reading)
0.047C0.009 % of reading)
0.016C0.007 % of reading)
0.0400.0088 % of reading)
Note: Temperature Effect = A/D coeffieicnt + D/A coefficient (The data in the table is the coeffcient per 10C change.)
Example 1; Pt100, 0 to 200C calibration range, 50C reading
Tag No.
Input sensor type
Lower bound of calibration range
Upper bound of calibration range
Unit of calibration range
Damping constant
Sensor burnout
Output when transmitter fails
*1: When option code C1 is specified, Low takes effect (–2.5%, 3.6mADC).
*2: When option code C1 is specified, Low takes effect (–5%, 3.2mADC or less).
Left blank if not specified in order
“Pt100, 3-wire” if not specified in order
“0” if not specified in order
“100” if not specified in order
“°C” if not specified in order
2 seconds
High side (110%, 21.6 mA DC)
High side (110%, 21.6 mA DC)
*1
*2
T0705.EPS
7.2 Model and Suffix Codes
ModelBasic Specification CodesDescription
YTA110
YTA310
YTA320
Output
signal
—
Electrical
connection
Built-in indicator
Mounting bracket
Additional specifications
*1: Applicable for YTA320 only.
*2: Use bolts for wall mounting.
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
–D . . . . . . . . . . . . . . . . . . . .
–E . . . . . . . . . . . . . . . . . . . .
–F . . . . . . . . . . . . . . . . . . . .
A . . . . . . . . . . . . . . . . . Always A
0 . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . .
3 . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . .
D . . . . . . . . . . . .
N . . . . . . . . . . . .
B . . . . . . . . . SUS304 2B pipe mounting
N . . . . . . . . .
/Additional specifications
Temperature transmitter (1 input type)
High precision temperature transmitter (1 input type)
High precision temperature transmitter (2 input type)
4 to 20mA DC output, BRAIN communication type
4 to 20mA DC output, HART communication type
FOUNDATION Fieldbus communication type
Electrical connection : G1/2 female
Applicable cable : O.D. 8.5 to 11 mm
C)
IP66/67, Ex n IIC T4(Tamb=70
C)
IP66/67
C
C)
, IP66/67
5
*1 : Applicable for Electrical Connection Code 2 and 4.
*2 : Applicable for Electrical Connection Code 2.
*3 : If cable wiring is to be used to a JIS flameproof type transmitter, do not fail to add the YOKOGAWA-assured flameproof packing
adapter.
*4 : Not applicable for Output Signal Code F.
*5 : Applicable for Electrical connection code 2, 3 and 4.
Intrinsically safe for Class I, Division 1, Groups A, B, C and D; Class II, Division 1, Groups
E, F and G; Class III, Division 1:
Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups E,
F and G; Class III, Division 1:
Canadian Standards
Association (CSA)
Enclosure Type 4X Temperature Class : T4, Ambient Temperature : -40 to 60C,
Explosionproof Class I, Div.1, Groups B, C and D, Class II, Groups E, F and G, Class III. For
Class I, Div.2 Locations “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED”
Enclosure Type 4X Temperature Class : T4 Ambient Temperature : -40 to 60C
Electrical Connection : 1/2 NPT female*
*1 : Not applicable for Output Signal Code F.
*2 : Applicable for Electrical Connection Code 2 and 4.
7.4 Dimensions
Electrical
Connection
(Output signal)
111(4.37)
Electrical Connection
Descriptions
With Indicator
(Input signal)
Code
1
CU1
2
2
T0707.EPS
Unit: mm (Approx. inch)
65.4(2.57)
1
*
46(1.81)65(2.56)
18.5
(0.73)
Terminal Cover
Communication
Terminals (BT200 etc.)
Connection hook
CHECK METER
Connection hook
2
*
56(2.21)
102
(4.02)
164
(6.46)
Shrouding Bolt
(For Explosionproof approval)
40
(1.58)
2-inch pipe, ø60.5(ø2.38)
*1: When Integral Indicator is specified.
Terminal Configuration
Power Supply and output terminal
External Indicator (ammeter) terminal
Ground terminal
*2: When using an external indicator or check meter,
the internal resistance must be 10Ω or less.
M101.5 12-deep female
for mounting bracket
The hook is not available for Fieldbus communication type(output signal code F).
25
(0.99)
70(2.76)
90(3.55)
ø93
(3.66)
Ground T erminal
Tag Plate
Mounting Bracket
2
*
F0701.EPS
7-7
IM 01C50B01-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
INSTALLATION AND OPERATING PRECAUTIONS FOR
JIS FLAMEPROOF EQUIPMENT
Apparatus Certified Under Technical Criteria
(IEC-compatible Standards)
1.General
The following describes precautions on electrical apparatus
of flameproof construction (hereinafter referred to as
flameproof apparatus) in explosion-protected apparatus.
Following the Labour Safety and Health Laws of Japan,
flameproof apparatus is subjected to type tests to meet either
the technical criteria for explosionproof electrical machinery
and equipment (standards notification no. 556 from the
Japanese Ministry of Labour) (hereinafter referred to as
technical criteria), in conformity with the IEC Standards, or
the “Recommended Practice for Explosion-Protected
Electrical Installations in General Industries,” published in
1979. These certified apparatus can be used in hazardous
locations where explosive or inflammable gases or vapours
may be present.
Certified apparatus includes a certification label and an
equipment nameplate with the specifications necessary for
explosion requirements as well as precautions on explosion
protection. Please confirm these precautionary items and use
them to meet specification requirements.
For electrical wiring and maintenance servicing, please refer
to “Internal Wiring Rules” in the Electrical Installation
Technical Standards as well as “USER’S GUIDELINES for
Electrical Installations for Explosive Gas Atmospheres in
General Industry,” published in 1994.
construction is of completely enclosed type and its enclosure
shall endure explosive pressures in cases where explosive
gases or vapours entering the enclosure cause explosion. In
addition, the enclosure construction shall be such that flame
caused by explosion does not ignite gases or vapours outside
the enclosure.
In this manual, the word "flameproof" is applied to the
flameproof equipment combined with the types of protection
"e", "o", "i", and "d" as well as flameproof equipment.
3.Terminology
(1) Enclosure
An outer shell of an electrical apparatus, which encloses live
parts and thus is needed to configure explosion-protected
construction.
(2) Shroud
A component part which is so designed that the fastening of
joint surfaces cannot be loosened unless a special tool is
used.
(3) Enclosure internal volume
This is indicated by:— the total internal volume of the
flameproof enclosure minus the volume of the internal
components essential to equipment functions.
To meet flameproof requirements, equipment that can be
termed “flameproof” must:
(1) Be certified by a Japanese public authority in accordance
with the Labour Safety and Health Laws of Japan and
have a certification label in an appropriate location on its
case, and
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and
precautionary information furnished.
2.Electrical Apparatus of Flameproof Type of ExplosionProtected Construction
Electrical apparatus which is of flameproof construction is
subjected to a type test and certified by the Japanese Ministry
of Labour aiming at preventing explosion caused by electrical
apparatus in a factory or any location where inflammable
gases or vapours may be present. The flameproof
(4) Path length of joint surface
On a joint surface, the length of the shortest path through
which flame flows from the inside to outside of the
flameproof enclosure. This definition cannot be applied to
threaded joints.
(5) Gaps between joint surfaces
The physical distance between two mating surfaces, or
differences in diameters if the mating surfaces are cylindrical.
Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are
determined by such factors as the enclosure’s internal
volume, joint and mating surface construction, and the
explosion classification of the specified gases and vapours.
1
EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
4.Installation of Flameproof
Apparatus
(1) Installation Area
Flameproof apparatus may be installed, in accordance with
applicable gases, in a hazardous area in Zone 1 or 2, where
the specified gases are present. Those apparatus shall not be
installed in a hazardous area in Zone 0.
Note: Hazardous areas are classified in zones based upon the
frequency of the appearance and the duration of an explosive
gas atmosphere as follows:
Zone 0: An area in which an explosive gas atmosphere is
present continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is
likely to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not
likely to occur in normal operation and if it does
occur it will exist for a short period only.
(2) Environmental Conditions
The standard environmental condition for the installation of
flameproof apparatus is limited to an ambient temperature
range from –20°C to +40°C (for products certified under
Technical Criteria). However, some field-mounted
instruments may be certified at an ambient temperature up to
+60°C as indicated on the instrument nameplates. If the
flameproof apparatus are exposed to direct sunshine or
radiant heat from plant facilities, appropriate thermal
protection measures shall be taken.
5.External Wiring for Flameproof
Apparatus
Flameproof apparatus require cable wiring or flameproof
metal conduits for their electrical connections. For cable
wiring, cable glands (cable entry devices for flameproof type)
to wiring connections shall be attached. For metal conduits,
attach sealing fittings as close to wiring connections as
possible and completely seal the apparatus. All non-live
metal parts such as the enclosure shall be securely grounded.
For details, see the “USER’S GUIDELINES for Electrical
Installations for Explosive Gas Atmospheres in General
Industry,” published in 1994.
(1) Cable Wiring
• For cable wiring, cable glands (cable entry devices for
flameproof type) specified or supplied with the apparatus
shall be directly attached to the wiring connections to
complete sealing of the apparatus.
• Screws that connect cable glands to the apparatus are
those for G-type parallel pipe threads (JIS B 0202) with
no sealing property. To protect the apparatus from
corrosive gases or moisture, apply nonhardening sealant
such as liquid gaskets to those threads for waterproofing.
• Specific cables shall be used as recommended by the
“USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry,”
published in 1994.
• In necessary, appropriate protective pipes (conduit or
flexible pipes), ducts or trays shall be used for
preventing the cable run (outside the cable glands) from
damage.
• To prevent explosive atmosphere from being propagated
form Zone 1 or 2 hazardous location to any different
location or non-hazardous location through the protective
pipe or duct, apply sealing of the protective pipes in the
vicinity of individual boundaries, or fill the ducts with
sand appropriately.
• When branch connections of cables, or cable connections
with insulated cables inside the conduit pipes are made,
a flameproof or increased-safety connection box shall be
used. In this case, flameproof or increased-safety cable
glands meeting the type of connection box must be used
for cable connections to the box.
(2) Flameproof Metal Conduit Wiring
• For the flameproof metal conduit wiring or insulated
wires shall be used as recommended by the USER’S
GUIDELINES for Electrical Installations for Explosive
Gas Atmospheres in General Industry, published in
1994.
• For conduit pipes, heavy-gauge steel conduits
conforming to JIS C 8305 Standard shall be used.
• Flameproof sealing fittings shall be used in the vicinity
of the wiring connections, and those fittings shall be
filled with sealing compounds to complete sealing of the
apparatus. In addition, to prevent explosive gases,
moisture, or flame caused by explosion form being
propagated through the conduit, always provide sealing
fittings to complete sealing of the conduit in the
following locations:
(a) In the boundaries between the hazardous and non-
hazardous locations.
(b) In the boundaries where there is a different
classification of hazardous location.
• For the connections of the apparatus with a conduit pipe
or its associated accessories, G-type parallel pipe threads
(JIS B 0202) shall be used to provide a minimum of
five-thread engagement to complete tightness. In
addition, since these parallel threads do not have sealing
property, nonhardening sealant such as liquid gaskets
shall thus be applied to those threads for ensuring
waterproofness.
• If metal conduits need flexibility, use flameproof flexible
fittings.
2
EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR JIS FLAMEPROOF EQUIPMENT
6.Maintenance of Flameproof
Apparatus
To maintain the flameproof apparatus, do the following. (For
details, see Chapter 10 “MAINTENANCE OF EXPLOSIONPROTECTED ELECTRICAL INSTALLATION” in the
USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry.)
(1) Maintenance servicing with the power on.
Flameproof apparatus shall not be maintenance-serviced with
its power turned on. However, in cases where maintenance
servicing is to be conducted with the power turned on, with
the equipment cover removed, always use a gas detector to
check that there is no explosive gas in that location. If it
cannot be checked whether an explosive gas is present or not,
maintenance servicing shall be limited to the following two
items:
(a) Visual inspection
Visually inspect the flameproof apparatus, metal
conduits, and cables for damage or corrosion, and other
mechanical and structural defects.
(b) Zero and span adjustments
These adjustments should be made only to the extent
that they can be conducted from the outside without
opening the equipment cover. In doing this, great care
must be taken not to cause mechanical sparks with tools.
(2) Repair
If the flameproof apparatus requires repair, turn off the power
and transport it to a safety (non-hazardous) location. Observe
the following points before attempting to repair the
apparatus.
(a) Make only such electrical and mechanical repairs as will
restore the apparatus to its original condition. For the
flameproof apparatus, the gaps and path lengths of joints
and mating surfaces, and mechanical strength of
enclosures are critical factors in explosion protection.
Exercise great care not to damage the joints or shock the
enclosure.
(b) If any damage occurs in threads, joints or mating
surfaces, inspection windows, connections between the
transmitter and terminal box, shrouds or clamps, or
external wiring connections which are essential in
flameproofness, contact Yokogawa Electric Corporation.
requirements for flameproof apparatus (however, bear in
mind that the apparatus must always be restored to its
original condition). If you attempt to repair the
flameproof apparatus, company-specified components
shall be used.
(d) Before starting to service the apparatus, be sure to check
all parts necessary for retaining the requirements for
flameproof apparatus. For this, check that all screws,
bolts, nuts, and threaded connections have properly been
tightened.
(3) Prohibition of specification changes and
modifications
Do not attempt to change specifications or make
modifications involving addition of or changes in external
wiring connections.
7.Selection of Cable Entry
Devices for Flameproof Type
IMPORTANT
The cable glands (cable entry devices for flameproof
type) conforming to IEC Standards are certified in
combination with the flameproof apparatus. So,
Yokogawa-specified cable entry devices for flameproof
type shall be used to meet this demand.
References:
(1) Type Certificate Guide for Explosion-Protected
Construction Electrical Machinery and Equipment
(relating to Technical Standards Conforming to International Standards), issued by the Technical Institution of
Industrial Safety, Japan
(2) USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry (1994),
issued by the Japanese Ministry of Labour, the Research
Institute of Industrial Safet
CAUTION
Do not attempt to re-process threaded connections or
refinish joints or mating surfaces.
(c) Unless otherwise specified, the electrical circuitry and
internal mechanisms may be repaired by component
replacement, as this will not directly affect the