YOKOGAWA YTA User's Manual

User’s Manual
YTA Series Temperature T ransmitter Fieldbus Communication
IM 01C50T02-01E
Yokogawa Electric Corporation
IM 01C50T02-01E
CONTENTS
CONTENTS
1. INTRODUCTION............................................................................................ 1-1
Regarding This Manual............................................................................. 1-1
For Safe Use of Product ........................................................................... 1-2
Warranty.................................................................................................... 1-2
ATEX Documentation ............................................................................... 1-3
2. PART NAMES ............................................................................................... 2-1
3. ABOUT FIELDBUS ....................................................................................... 3-1
3.1 Outline ................................................................................................. 3-1
3.2 Internal Structure of YTA .................................................................... 3-1
3.2.1 System/network Management VFD ............................................. 3-1
3.2.2 Function Block VFD ..................................................................... 3-1
3.3 Logical Structure of Each Block.......................................................... 3-1
3.4 Wiring System Configuration .............................................................. 3-2
4. GETTING STARTED .....................................................................................4-1
4.1 Connection of Devices ........................................................................ 4-1
4.2 Host Setting......................................................................................... 4-2
4.3 Bus Power ON .................................................................................... 4-2
4.4 Integration of DD................................................................................. 4-3
4.5 Reading the Parameters ..................................................................... 4-3
4.6 Continuous Record of Values ............................................................. 4-3
4.7 Generation of Alarm............................................................................ 4-3
5. CONFIGURATION.........................................................................................5-1
5.1 Network Design................................................................................... 5-1
5.2 Network Definition ............................................................................... 5-1
5.3 Definition of Combining Function Blocks ............................................ 5-2
5.4 Setting of Tags and Addresses .......................................................... 5-3
5.5 Communication Setting ....................................................................... 5-4
5.5.1 VCR Setting .................................................................................. 5-4
5.5.2 Function Block Execution Control ................................................ 5-5
5.6 Block Setting ....................................................................................... 5-5
5.6.1 Link Object ................................................................................... 5-5
5.6.2 Trend Object ................................................................................. 5-5
5.6.3 View Object .................................................................................. 5-6
5.6.4 Parameters of Transducer Block ............................................... 5-12
5.6.5 Parameters of AI Function Block ............................................... 5-14
5.6.6 Parameters of DI Function Block ............................................... 5-15
5.6.7 A setting when Sensor input 2 is not connected ....................... 5-15
FD No. IM 01C50T02-01E 7th Edition: Nov. 2007(KP) All Rights Reserved, Copyright © 2000, Yokogawa Electric Corporation
i
IM 01C50T02-01E
CONTENTS
6. IN-PROCESS OPERATION .......................................................................... 6-1
6.1 Mode Transition .................................................................................. 6-1
6.2 Generation of Alarm............................................................................ 6-1
6.2.1 Indication of Alarm ....................................................................... 6-1
6.2.2 Alarms and Events ....................................................................... 6-1
6.3 Simulation Function............................................................................. 6-2
6.4 Operation of Integral Indicator ............................................................ 6-2
7. ERRORS AND WARNINGS .......................................................................... 7-1
7.1 Error and Warning Indications ............................................................ 7-1
7.2 Checking with LCD ............................................................................. 7-1
7.3 Checking with DEVICE_STATUS_1 to _8 of Resource Block........... 7-4
7.4 Precautions on Warnings.................................................................... 7-8
8. HANDLING CAUTION ................................................................................... 8-1
8.1 Installation of Explosionproof Type Transmitters................................ 8-1
8.1.1 CSA Certification .......................................................................... 8-1
8.1.2 CENELEC ATEX Certification...................................................... 8-2
8.1.3 FM Certification ........................................................................... 8-6
8.1.4 SAA Certification ......................................................................... 8-9
8.1.5 IECEx Certification ....................................................................... 8-9
9. GENERAL SPECIFICATIONS ...................................................................... 9-1
9.1 Standard Specifications ...................................................................... 9-1
9.2 Optional Specifications........................................................................ 9-2
APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF THE YTA .. A-1
A1.1 Resource Block ...................................................................................A-1
A1.2 Al Function Block ................................................................................ A-3
A1.3 Dl Function Block ................................................................................A-5
A1.4 Transducer Block ................................................................................ A-6
A1.5 Unit and Code ...................................................................................A-10
APPENDIX 2. Parameters for Basic Settings, and How to Make and Change
the Settings ............................................................................................... A-11
A2.1 Basic Settings and Corresponding Parameters................................A-11
A2.2 Making and Changing Basic Parameter Settings.............................A-12
A2.3 Setting Up the Transducer Block......................................................A-12
A2.4 Setting Up AI Blocks .........................................................................A-15
A2.5 Setting Up DI Blocks.........................................................................A-16
APPENDIX 3. FUNCTION BLOCK DIAGRAM ............................................... A-18
A3.1 AI Block Function Diagram ............................................................... A-18
A3.2 DI Block Function Diagram ...............................................................A-18
ii
IM 01C50T02-01E
CONTENTS
APPENDIX 4. PID BLOCK .............................................................................. A-19
A4.1 Function Diagram..............................................................................A-19
A4.2 Functions of PID Block .....................................................................A-19
A4.3 Parameters of PID Block ..................................................................A-20
A4.4 PID Computation Details...................................................................A-22
A4.4.1 PV-proportional and -derivative Type PID (I-PD)
Control Algorithm ........................................................................ A-22
A4.4.2 PID Control Parameters .............................................................A-22
A4.5 Control Output...................................................................................A-22
A4.5.1 Velocity Type Output Action.......................................................A-22
A4.6 Direction of Control Action ................................................................A-22
A4.7 Control Action Bypass.......................................................................A-22
A4.8 Feed-forward .....................................................................................A-22
A4.9 Block Modes......................................................................................A-23
A4.9.1 Mode Transitions.......................................................................A-23
A4.10Bumpless Transfer ............................................................................ A-23
A4.11Setpoint Limiters ...............................................................................A-24
A4.11.1 When PID Block Is in Auto Mode ............................................ A-24
A4.11.2 When PID Block Is in Cas or RCas Mode...............................A-24
A4.12External-output Tracking ................................................................... A-24
A4.13Measured-value Tracking.................................................................. A-24
A4.14Initialization and Manual Fallback (IMan) .........................................A-25
A4.15Manual Fallback ................................................................................ A-25
A4.16Auto Fallback ....................................................................................A-25
A4.17Mode Shedding upon Computer Failure........................................... A-25
A4.17.1 SHED_OPT .............................................................................. A-25
A4.18Alarms ...............................................................................................A-26
A4.18.1 Block Alarm (BLOCK_ALM) .....................................................A-26
A4.18.2 Process Alarms ........................................................................ A-26
A4.19Example of Block Connections ......................................................... A-26
A4.19.1 View Object for PID Function Block.........................................A-27
APPENDIX 5. LINK MASTER FUNCTIONS ................................................... A-29
A5.1 Link Active Scheduler .......................................................................A-29
A5.2 Link Master........................................................................................A-29
A5.3 Transfer of LAS.................................................................................A-30
A5.4 LM Functions.....................................................................................A-31
A5.5 LM Parameters..................................................................................A-32
A5.5.1 LM Parameter List......................................................................A-32
A5.5.2 Descriptions for LM Parameters ................................................A-34
A5.6 FAQs ................................................................................................. A-36
REVISION RECORD
iii
IM 01C50T02-01E
Blank Page
1. INTRODUCTION

1. INTRODUCTION

This manual contains a description of the YTA320 Temperature Transmitter Fieldbus Communication Type. The Fieldbus communication type is based on the same dual sensor input features as that of the BRAIN or HART communication type and is similar to the BRAIN or HART communication type in terms of basic performance and operation. This manual de­scribes only those topics that are required for operation of the Fieldbus communication type. Refer to the users manual “ YTA series Temperature Transmitter [Hardware]” (IM 01C50B01-01E) for topics common to other communication types.

Regarding This Manual

•This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and fitness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales office.
• The specifications covered by this manual are limited to those for the standard type under the specified model number break-down and do not cover custom-made instrument.
• Please note that changes in the specifications, construction, or component parts of the instrument may not immediately be reflected in this manual at the time of change, provided that postponement of revisions will not cause difficulty to the user from a functional or performance standpoint.
• The following safety symbol marks are used in this Manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
1-1
IM 01C50T02-01E
1. INTRODUCTION

For Safe Use of Product

For the protection and safety of the operator and the instrument or the system including the instrument, please be sure to follow the instructions on safety described in this manual when handling this instru­ment. In case the instrument is handled in contradiction to these instructions, Yokogawa does not guarantee safety. Please give your attention to the followings.
(a) Installation
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
• In case of high process temperature, care should be taken not to burn yourself because the surface of the case reaches a high temperature.
• All installation shall comply with local installation requirement and local electrical code.
(b) Wiring
• The instrument must be installed by an expert engineer or a skilled personnel. The procedures described about WIRING are not permitted for operators.
• Please confirm that voltages between the power supply and the instrument before connecting the power cables and that the cables are not powered before connecting.
(c) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact nearest YOKOGAWA office.
•Care should be taken to prevent the build up of drift, dust or other material on the display glass and name plate. In case of its maintenance, soft and dry cloth is used.

Warranty

•The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurred during the warranty period shall basically be repaired free of charge.
• In case of problems, the customer should contact the Yokogawa representative from which the instrument was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specification and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• Responsible party for repair cost for the problems shall be determined by Yokogawa based on our investigation.
• The Purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by the purchaser.
- Failure or damage due to improper handling, use or storage which is out of design conditions.
- Use of the product in question in a location not conforming to the standards specified by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modification or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as fires, earth­quakes, storms/floods, thunder/lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
(d) Modification
• Yokogawa will not be liable for malfunctions or damage resulting from any modification made to this instrument by the customer.
1-2
IM 01C50T02-01E
1. INTRODUCTION

ATEX Documentation

This procedure is only applicable to the countries in European Union.
GB
All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative.
DK
Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk. Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler.
I
Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante.
E
Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano.
NL
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä. Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos produtos Ex da ATEX estão disponíveis em Inglês, Alemão e Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa.
F
Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die Betriebsanleitungen für Ex-Produkte in Ihrer Landessprache benötigen, setzen Sie sich bitte mit Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant.
Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger.
GR
       ATEX Ex   ,   .        Ex           Yokogawa   .
1-3
IM 01C50T02-01E
1. INTRODUCTION
SK
CZ
LT
PL
SLO
H
LV
EST
BG
RO
M
1-4
IM 01C50T02-01E
2. PART NAMES
Refer to the individual instruction manuals for detailed descriptions of the parts. This section describes the topics applicable to the Fieldbus communication type.
(1) In the Fieldbus communication type, the
amplifier(CPU) assembly consists of two boards, as shown in Figure 2.1.
(2) In other communication types, there's the pin
switch which is used for selecting the direction of hardware burnout at the position of 'SW1' on the amplifier assembly, while Fieldbus communication type does not have this pin.
(3) The Fieldbus communication type has a simulation
function. A SIMULATE-ENABLE switch is mounted at 'SW1' on the amplifier. Refer to Section 6.3, “Simulation Function” for details of the simulation function.

2. PART NAMES

Simulation
setting switch
Amplifier Assembly
Figure 2.1 Diagram of the Amplifier Assembly
F0201.EPS
2-1
IM 01C50T02-01E
3. ABOUT FIELDBUS

3. ABOUT FIELDBUS

3.1 Outline

Fieldbus is a bi-directional digital communication protocol for field devices, which offers an advancement in implementation technologies for process control systems and is widely employed by numerous field devices.
YTA Series Fieldbus communication type employs the specification standardized by The Fieldbus Foundation, and provides interoperability between Yokogawa devices and those produced by other manufacturers. Fieldbus comes with software consisting of four AI function blocks and four DI function blocks, providing the means to implement a flexible instrumentation system.
For information on other features, engineering, design, construction work, startup and maintenance of Fieldbus, refer to “Fieldbus Technical Information” (TI 38K3A01-01E).

3.2 Internal Structure of YTA

The YTA contains two virtual field devices (VFD) that share the following functions.
• Outputs temperature signal.
•Carries out scaling, damping and square root extraction.
(4)DI function block
•Limit switch for temperature.
•Accepts the discrete signal from Transducer block and Outputs the discrete signal to show if the temperature exceeds the preset limit.
(5)PID function block
• Performs the PID control computation based on the deviation of the measured value from the setpoint.
3.3 Logical Structure of Each
Block
YTA Fieldbus
System/network management VFD
PD Tag
Node address
Link Master (option)
Communication
parameters
VCR
Function block
execution schedule

3.2.1 System/network Management VFD

• Sets node addresses and Phisical Device tags (PD Tag) necessary for communication.
• Controls the execution of function blocks.
•Manages operation parameters and communication resources (Virtual Communication Relationship: VCR).

3.2.2 Function Block VFD

(1)Resource block (RS)
• Manages the status of YTA hardware.
•Automatically informs the host of any detected faults or other problems.
(2)Transducer block (TR)
• Accepts temperature input from sensors and trans­fers to AI function block.
• Operates limit swtich calculation and transfers to DI function block.
(3)AI function block
• Conditions raw data from the Transducer block.
Function block VFD
PID function
block (option)
DI function
Transducer
Sensor
input
Sensor
block
Block tag
Parameters
Temperature
Resource block
Block tag
Parameters
Figure 3.1 Logical Structure of Each Block
block
AI function
block
Block tag
Parameters
OUT
Setting of various parameters, node addresses, and PD Tags shown in Figure 3.1 is required before starting operation.
Output
F0301.EPS
3-1
IM 01C50T02-01E

3.4 Wiring System Configuration

The number of devices that can be connected to a single bus and the cable length vary depending on system design. When constructing systems, both the basic and overall design must be carefully considered to allow device performance to be fully exhibited.
3. ABOUT FIELDBUS
3-2
IM 01C50T02-01E
4. GETTING STARTED

4. GETTING STARTED

Fieldbus is fully dependent upon digital communica­tion protocol and differs in operation from conven­tional 4 to 20 mA transmission and the BRAIN or HART communication protocol. It is recommended that novice users use field devices in accordance with the procedures described in this section. The proce­dures assume that field devices will be set up on a bench or an instrument shop.

4.1 Connection of Devices

The following instruments are required for use with Fieldbus devices:
• Power supply:
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
• Terminator:
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
•Field devices:
Connect Fieldbus communication type YTA320. Two or more YTA320 devices or other devices can be connected.
• Host:
Used for accessing field devices. A dedicated host (such as DCS) is used for an instrumentation line while dedicated communication tools are used for experimental purposes. For operation of the host, refer to the instruction manual for each host. No details of the host are explained in the rest of this material.
processing depends on the type of device being deployed. For YTA, use an M4 screw terminal claw. Some hosts require a connector.
Refer to Yokogawa when making arrangements to purchase the recommended equipment.
Connect the devices as shown in Figure 4.1. Connect the terminators at both ends of the trunk, with a minimum length of the spur laid for connection.
The polarity of signal and power must be maintained.
Fieldbus power supply
Terminator
Figure 4.1 Cabling
YTA320
HOST
Terminator
F0401.EPS
NOTE
No CHECK terminal is used for Fieldbus com­munication YTA. Do not connect the field indica­tor and check meter. Use the instrument with the short-bar being installed between (-) terminal and the CHECK terminal.
Before using a Fieldbus configuration tool other than the existing host, confirm it does not affect the loop functionality in which all devices are already installed in operation. Disconnect the relevant control loop from the bus if necessary.
•Cable:
Used for connecting devices. Refer to “Fieldbus Technical Information” (TI 38K3A01-01E) for details of instrumentation cabling. If the total length of the cable is in a range of 2 to 3 meters for laboratory or other experimental use, the following simplified cable (a twisted pair wire with a cross section of 0.9 mm2 or more and cycle period of within 5 cm (2 inches) may be used. Termination
IMPORTANT
Connecting a Fieldbus configuration tool to a loop with its existing host may cause communi­cation data scrambles resulting in a functional disorder or a system failure.
4-1
IM 01C50T02-01E
4. GETTING STARTED

4.2 Host Setting

To activate Fieldbus, the following settings are required for the host.
IMPORTANT
Do not turn off the power immediately after setting. When the parameters are saved to EEPROM, the redundant processing is executed for the improvement of reliability. If the power is turned off within 60 seconds after setting is made, the modified parameters are not saved and the settings may return to the original values.
Table 4.1 Operation Parameters
Symbol Parameter Description and Settings
V (ST) Slot-Time V (MID)
Minimum-Inter-PDU­Delay
V (MRD)
Maximum-Response­Delay
V (FUN) First-Unpolled-Node
V (NUN) Number-of-
consecutive­Unpolled-Node
0x00
Set 4 or greater value. Set 4 or greater value.
Set so that V (MRD) V (ST) is 12 or greater
Indicate the address next to the address range used by the host. Set 0x15 or greater.
Unused address range. YTA address is factory-set to 0xF3. Set this address to be within the range of the BASIC device in Figure
4.2.
T0401.EPS
Not used

4.3 Bus Power ON

Turn on the power of the host and the bus. Where the YTA is equipped with an LCD indicator, first all segments are lit, then the display begins to operate. If the indicator is not lit, check the polarity of the power supply.
Using the host device display function, check that the YTA is in operation on the bus.
The device information, including PD tag, Node address, and Device ID, is described on the sheet attached to YTA. The duplicates of device information are provided on this sheet.
Device ID : 5945430005XXXXXXXX PD Tag : TT1001 Device Revision : 2 Node Address : 0xf3 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or http://www.yokogawa.co.jp/Sensor/fieldbus/download.htm (Japanese)
Device ID : 5945430005XXXXXXXX PD Tag : TT1001 Device Revision : 2 Node Address : 0xf3 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or http://www.yokogawa.co.jp/Sensor/fieldbus/download.htm (Japanese)
DEVICE INFORMATION
DEVICE INFORMATION
0x10
Bridge device
0x14
LM device
V(FUN)
Unused V(NUN)
V(FUN)V(NUN)
YTA(0xF3)
0xF7 0xF8
BASIC device
Default address
0xFB 0xFC
Portable device address
0xFF
Note 1: LM device: with bus control function (Link Master function) Note 2: BASIC device: without bus control function
F0402.EPS
Figure 4.2 Available Address Range
Figure 4.3 Device Information Sheet Attached to YTA
If no YTA is detected, check the available address range and the polarity of the power supply. If the node address and PD tag are not specified when ordering, default value is factory set. If two or more YTAs are connected at a time with default value, one YTA will keep the address upon shipment while the other will have a default address as they have the same initial addres. Separately connect each YTA and set a different address for each.
4-2
IM 01C50T02-01E
F0403.EPS
4. GETTING STARTED

4.4 Integration of DD

If the host supports DD (Device Description), the DD of the YTA needs to be installed. Check if host has the following directory under its default DD directory.
594543\0005
(594543 is the manufacturer number of Yokogawa Electric Corporation, and 0005 is the YTA device number, respectively.)
If this directory is not found, DD of YTA has not been included. Create the above directory and copy the DD file (0m0n.ffo,0m0n.sym) (m, n is a numeral) into the directory. If you do not have the DD or capabilities files, you can download them from our web site. Visit the following web site.
http://www.yokogawa.com/fld Once the DD is installed in the directory, the name and
attribute of all parameters of the YTA are displayed. Off-line configuration is possible by using capabilities
files.
NOTE
Ensure to use the suitable file for the device. YTA has three types, one with the standard function blocks, one with /LC1(additional PID and LAS function) and one with /LC2(additional 2 PIDs and LAS function). If the different type capabilities file is used, some errors may occur at downloading to the device.

4.6 Continuous Record of Values

If the host has a function of continuously recording the indications, use this function to list the indications (values). Depending on the host being used, it may be necessary to set the schedule of Publish (the function that transmits the indication on a periodic basis).

4.7 Generation of Alarm

If the host is allowed to receive alarms, generation of an alarm can be attempted from YTA. In this case, set the reception of alarms on the host side. YTA’s VCR-6 is factory-set for this purpose. For practical purposes, all alarms are placed in a disabled status; for this reason, it is recommended that you first use one of these alarms on a trial basis. Set the value of link object-3 (index 30002) as “0, 298, 0, 6, 0”. Refer to section 5.6.1 Link Object for details.
Since the LO_PRI parameter (index 4029) of the AI1 block is set to “0”, try setting this value to “3”. Select the Write function from the host in operation, specify an index or variable name, and write “3” to it.
The LO_LIM parameter (index 4030) of the AI1 block determines the limit at which the lower bound alarm for the process value is given. In usual cases, a very small value is set to this limit. Set the value which is apparantely higher than expected measured value to the limit. For example, in case masuering room tempera­ture of 28C, SET '50(C)' to the limit. Since the measured temperature is lower than the limit, lower bound alarm is raised. Check that the alarm can be received at the host. When the alarm is confirmed, transmission of the alarm is suspended.

4.5 Reading the Parameters

To read YTA parameters, select the AI1 block of the YTA from the host screen and read the OUT param­eter. The current temperature which is assign to AI1 block is displayed. Sensor 1 input is assigned to AI1 block upon shipment. Check that actual of MODE_BLOCK of the function block and resource block is set to Auto, and increase the temperature measured by Sensor1 and read the parameter again. A new designated value should be displayed.
The above-mentioned items are a description of the simple procedure to be carried out until YTA is connected to Fieldbus. In order to take full advantage of the performance and functionality of the device, it is recommended that it be read together with Chapter 5, which describes how to use the YTA.
4-3
IM 01C50T02-01E
5. CONFIGURATION

5. CONFIGURATION

This chapter contains information on how to adapt the function and performance of the YTA to suit specific applications. Because two or more devices are con­nected to Fieldbus, settings including the requirements of all devices need to be determined. Practically, the following steps must be taken.
(1)Network design
Determines the devices to be connected to Fieldbus and checks the capacity of the power supply.
(2)Network definition
Determines the tag and node addresses for all devices.
(3)Definition of combining function blocks
Determines the method for combination between each function block.
(4)Setting tags and addresses
Sets the PD Tag and node addresses one by one for each device.
(5)Communication setting
Sets the link between communication parameters and function blocks.
(6)Block setting
Sets the parameters for function blocks.
The following section describes each step of the procedure in the order given. Using a dedicated configuration tool allows the procedure to be signifi­cantly simplified. This section describes the procedure to be assigned for a host which has relatively simple functions. Refer to Appendix 5 when the YTA is used as Link Master.
• Terminator
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
•Field devices
Connect the field devices necessary for instrumenta­tion. YTA has passed the interoperability test conducted by The Fieldbus Foundation. In order to properly start Fieldbus, it is recommended that the devices used satisfy the requirements of the above test.
• Host
Used for accessing field devices. A minimum of one device with bus control function is needed.
• Cable
Used for connecting devices. Refer to “Fieldbus Technical Information” for details of instrumenta­tion cabling. Provide a cable sufficiently long to connect all devices. For field branch cabling, use terminal boards or a connection box as required.
First, check the capacity of the power supply. The power supply capacity must be greater than the sum of the maximum current consumed by all devices to be connected to Fieldbus. The maximum current con­sumed (power supply voltage 9 V to 32 V) for YTA is
16.6 mA. The cable must have the spur in a minimum length with terminators installed at both ends of the trunk.

5.2 Network Definition

5.1 Network Design

Select the devices to be connected to the Fieldbus network. The following instruments are necessary for operation of Fieldbus.
• Power supply
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
Before connection of devices with Fieldbus, define the Fieldbus network. Allocate PD Tag and node addresses to all devices (excluding such passive devices as terminators).
The PD Tag is the same as the conventional one used for the device. Up to 32 alphanumeric characters may be used for definition. Use a hyphen as a delimiter as required.
The node address is used to specify devices for communication purposes. Because data is too long for a PD Tag, the host uses the node address in place of the PD Tag for communication. A range of 16 to 247
5-1
IM 01C50T02-01E
5. CONFIGURATION
(or hexadecimal 10 to F7) can be set. The device (LM device) with bus control function (Link Master function) is allocated from a smaller address number (16) side, and other devices (BASIC device) without bus control function allocated from a larger address number (247) side respectively. Place YTA in the range of the BASIC device. When the YTA is used as Link Master, place YTA in the range of LM device. Set the range of addresses to be used to the LM device. Set the following parameters.
Table 5.1 Parameters for Setting Address Range
Symbol
V (FUN) First-Unpolled-Node
V (NUN) Number-of-
Parameters Description
Indicates the address next to the address range used for the host or other LM device.
Unused address range consecutive­Unpolled-Node
T0501.EPS
The devices within the address range written as “Unused” in Figure 5.1 cannot be used on a Fieldbus. For other address ranges, the range is periodically checked to identify when a new device is mounted. Care must be taken not to allow the address range to become wider, which can lead to exhaustive consump­tion of Fieldbus communication performance.
0x00
Not used
0x10
Bridge device
0x14
V(FUN)
V(FUN)V(NUN)
0xF7 0xF8
0xFB
0xFC
0xFF
Figure 5.1 Available Range of Node Addresses
LM device
Unused V(NUN)
BASIC device
Default address
Portable device address
F0501.EPS
To ensure stable operation of Fieldbus, determine the operation parameters and set them to the LM devices. While the parameters in Table 5.2 are to be set, the worst-case value of all the devices to be connected to the same Fieldbus must be used. Refer to the specifica­tion of each device for details. Table 5.2 lists YTA specification values.
Table 5.2 Operation Parameter Values of the YTA to be
Set to LM Devices
Symbol Parameters Description and Settings
V (ST) Slot-Time
V (MID) Minimum-Inter-PDU-
Delay
V (MRD) Maximum-Reply-Delay
Indicates the time necessary for immediate reply of thje device. Unit of time is in octets (256 µs). Set maximum specification for all devices. For YTA, set a value of 4 or greater.
Minimum value of communication data intervals. Unit of time is in octets (256 µs). Set the maximum specification for all devices. For YTA, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slot­time; set the value so that V (MRD) V (ST) is the maximum value of the specification for all devices. For YTA, the setting must be a value of 12 or greater.

5.3 Definition of Combining Function Blocks

The input/output parameters for function blocks are combined. For the YTA, four AI blocks output parameter (OUT), four DI blocks output parameter (OUT_D) and PID block are subject to combination. They are combined with the input of the control block as necessary. Practically, setting is written to the YTA link object with reference to “Block setting” in Section
5.6 for details. It is also possible to read values from
the host at proper intervals instead of connecting the YTA block output to other blocks.
The combined blocks need to be executed synchro­nously with other blocks on the communications schedule. In this case, change the YTA schedule according to the following table. Enclosed values in the table are factory-settings.
Table 5.3 Execution Schedule of the YTA Function Blocks
Setting (Enclosed is
factory-setting)
Cycle (MACROCYCLE) period of control or measurement. Unit is 1/32 ms. (16000 = 0.5 s)
AI1 block startup time. Elapsed time from the start of MACROCYCLE specified in 1/32 ms. (0 = 0 s)
AI2 block startup time. Elapsed time from the start of MACROCYCLE specified in 1/32 ms. (4000 = 125ms)
Not used.
IM 01C50T02-01E
5-2
Index Parameters
269
MACROCYCLE_
(SM)
DURATION
276
FB_START_ENTRY.1
(SM)
277
FB_START_ENTRY.2
(SM)
278
FB_START_ENTRY.3
to
to FB_START_ENTRY.10
285
(SM)
T0502.EPS
T0503.EPS
5. CONFIGURATION
A maximum of 50 ms is taken for execution of each AI block. A maximum of 30 ms is taken for execution of each DI block, and 100ms for each PID block. For scheduling of communications for combination with the next function block, the execution is so arranged as to start after a lapse of longer than 100 ms. In no case should function blocks of the YTA be executed at the same time (execution time is overlapped).
Figure 5.3 shows an example of schedule based on the loop shown in Figure 5.2.
TIC100
YTA
#1
TT100
YTA
#2
TT 200
Figure 5.2 Example of Loop Connecting Function Block of
Two YTA with Other Instruments
TC200
TV200
F0502.EPS

5.4 Setting of Tags and Addresses

This section describes the steps in the procedure to set PD Tags and node addresses in the YTA. There are three states of Fieldbus devices as shown in Figure 5.4, and if the state is other than the lowest SM_OPERATIONAL state, no function block is executed. YTA must be transferred to this state when an YTA tag or address is changed.
UNINITIALIZED
(No tag nor address is set)
Tag clear Tag setting
INITIALIZED
(Only tag is set)
Address clear
SM_OPERATIONAL
(Tag and address are retained, and
the function block can be executed.)
Figure 5.4 Status Transition by Setting PD Tag and Node
Address
Address setting
F0504.EPS
Macrocycle (Control Period)
TT100
OUT
Function
Block
Schedule
Commu-
nication
Schedule
Figure 5.3 Function Block Schedule and Communication
Schedule
IN
TIC100
BKCAL_IN
TT200
OUT
CAS_IN
TC200
IN
BKCAL_IN
Unscheduled
Communication
BKCAL_OUT
TV200
BKCAL_OUT
Scheduled Communication
F0503.EPS
When the control period (macrocycle) is set to more than 4 seconds, set the following interval to be more than 1% of the control period.
- Interval between “end of block execution” and “start of sending CD from LAS”
- Interval between “end of block execution” and “start of the next block execution”
YTA has a PD Tag (TT1001) and node address (243, or hexadecimal 0xF3) that are set upon shipment from the factory unless otherwise specified. To change only the node address, clear the address once and then set a new node address. To set the PD Tag, first clear the node address and clear the PD Tag, then set the PD Tag and node address again.
Devices whose node address was cleared will await the default address (randomly chosen from a range of 248 to 251, or from hexadecimal F8 to FB). At the same time, it is necessary to specify the device ID in order to correctly specify the device. The device ID of the YTA is 5945430005xxxxxxxx. (The xxxxxxxx at the end of the above device ID is a total of 8 alphanumeric characters.)
5-3
IM 01C50T02-01E
5. CONFIGURATION

5.5 Communication Setting

To set the communication function, it is necessary to change the database residing in SM-VFD.

5.5.1 VCR Setting

Set VCR (Virtual Communication Relationship), which specifies the called party for communication and resources. YTA has 30 VCRs whose application can be changed, except for the first VCR, which is used for management.
YTA has VCRs of four types: Server(QUB) VCR
A Server responds to requests from a host. This communication needs data exchange. This type of communication is called QUB (Queued User­triggered Bidirectional) VCR.
Source (QUU) VCR
A Source multicasts alarms or trends to other devices. This type of communication is called QUU (Queued User-triggered Unidirectional) VCR.
Publisher (BNU) VCR
A Publisher multicasts AI block and DI block output to another function block(s). This type of communi­cation is called BNU (Buffered Network-triggered Unidirectional) VCR.
Subscriber (BNU) VCR
A Subscriber receives output of another function block(s) by PID block.
A Server VCR is capable to respond to requests from a Client (QUB) VCR after the Client initiates connection to the Server successfully. A Source VCR transmits data without established connection. A Sink (QUU) VCR on another device can receive it if the Sink is configured so. A Publisher VCR transmits data when LAS requests so. An explicit connection is established from Subscriber (BNU) VCR(s) so that a Subscriber knows the format of published data.
Each VCR has the parameters listed in Table 5.4. Parameters must be changed together for each VCR because modification for each parameter may cause inconsistent operation.
Table 5.4 VCR Static Entry
Sub-
index
1 FasArTypeAndRole
2 FasDllLocalAddr
3 FasDllConfigured
4 FasDllSDAP
5 FasDllMaxConfirm
6 FasDllMaxConfirm
7 FasDllMaxDlsduSize
8 FasDllResidual
9 FasDllTimelinessClass
10 FasDllPublisherTime
11 FasDllPublisher
Parameter Description
RemoteAddr
DelayOnConnect
DelayOnData
ActivitySupported
WindowSize
SynchronizaingDlcep
Indicates the type and role of communication (VCR). The following 4 types are used for YTA. 0x32: Server (Responds to
requests from host.)
0x44: Source (Transmits
alarm or trend.)
0x66: Publisher (Sends AI
block output to other blocks.)
0x76: Subscriber (Receives
output of other blocks by PID block.)
Sets the local address to specify VCR in YTA. A range of 20 to F7 in hexadecimal.
Sets the node address of the called party for communication and the address (DLSAP or DLCEP) used to specify VCR in that address. For DLSAP or DLCEP, a range of 20 to F7 in hexadecimal is used. Addresses in Subindex 2 and 3 need to be set to the same contents of the VCR as the called party (local and remote are reversed).
Specifies the quality of communication. Usually, one of the following types is set. 0x2B: Server 0x01: Source (Alert) 0x03: Source (Trend) 0x91: Publisher/Subscriber
To establish connection for communication, a maximum wait time for the called party's response is set in ms. Typical value is 60 seconds (60000).
For request of data, a maximum wait time for the called party's response is set in ms. Typical value is 60 seconds (60000).
Specifies maximum DL Service Data unit Size (DLSDU). Set 256 for Server and Trend VCR, and 64 for other VCRs.
Specifies whether connection is monitored. Set TRUE (0xff) for Server. This parameter is not used for other communication.
Not used for YTA. Not used for YTA.
Not used for YTA.
T0504-1.EPS
5-4
IM 01C50T02-01E
5. CONFIGURATION
Sub-
index
12 FasDllSubsriberTime
13 FasDllSubscriber
14 FmsVfdId
15 FmsMaxOutstanding
16 FmsMaxOutstanding
17 FmsFeatures
Parameter
WindowSize
SynchronizationDlcep
ServiceCalling
ServiceCalled
Supported
Description
Not used for YTA.
Not used for YTA.
Sets VFD for YTA to be used.
0x1: System/network
management VFD
0x1234: Function block
VFD
Set 0 to Server. It is not used for other applications.
Set 1 to Server. It is not used for other applications.
Indicates the type of services in the application layer. In the YTA, it is automatically set according to specific applications.
T0504-2.EPS
30 VCRs are factory-set as shown in the table below.
Table 5.5 VCR List
Index
(SM)
293 For system management (Fixed)1 294 Server (LocalAddr = 0xF3)2 295 Server (LocalAddr = 0xF4)3 296 Server (LocalAddr = 0xF7)4 297 Trend Source (LocalAddr = 0x07,
298 6
299 322
VCR
Number
5
Remote Address=0x111) Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
7 to 30
to
Not used.
Factory Setting
T0505.EPS

5.5.2 Function Block Execution Control

According to the instructions given in Section 5.3, set the execution cycle of the function blocks and schedule of execution.
Parameters must be changed together for each VCR because the modifications made to each parameter may cause inconsistent operation.
Table 5.6 Link Object Parameters
Sub-
index
1 LocalIndex
2 VcrNumber
3 RemoteIndex 4 ServiceOperation
5StaleCountLimit
Parameters Description
Sets the index of function block parameters to be combined; set “0” for Trend and Alert.
Sets the index of VCR to be combined. If set to “0”, this link object is not used.
Not used in YTA.Set to “0”. Set one of the following.
Set only one each for link object for Alert or Trend. 0: Undefined 2: Publisher 3: Subscriber 6: Alert 7: Trend
Set the maximum number of consecutive stale input values which may be received before the input status is set to BAD. To avoid the unnecessary mode transition caused when the data is not correctly received by subscriber, set this parameter to “2” or more.
T0506.EPS
26 Link objects are not factory-set.

5.6.2 Trend Object

It is possible to set the parameter so that the function block automatically transmits Trend. YTA has ten Trend objects, six of which are used for Trend in analog mode parameters and four is used for Trend in discrete mode parameter. A single Trend object specifies the trend of one parameter.
Each Trend object has the parameters listed in Table
5.8. The first four parameters are the items to be set.

5.6 Block Setting

Set the parameter for function block VFD.

5.6.1 Link Object

Link object combines the data voluntarily sent by the function block with VCR. YTA has 26 link objects. A single link object specifies one combination. Each link object has the parameters listed in Table 5.6.
5-5
IM 01C50T02-01E
5. CONFIGURATION
Table 5.8 Parameters for Trend Objects
Sub-
index
1 Block Index
2 Parameter Relative
3 Sample Type
4 Sample Interval
5 Last Update
6 to 21 List of Status
21 to 37 List of Samples
Parameters
Index
Description
Sets the leading index of the function block that takes a trend.
Sets the index of parameters taking a trend by a value relative to the beginning of the function block.
Specifies how trends are taken. Choose one of the following 2 types:
1: Sampled upon
execution of a function block.
2: The average value is
sampled.
Specifies sampling intervals in units of 1/32 ms. Set the integer multiple of the function block execution cycle.
The last sampling time. Status part of a sampled
parameter. Data part of a sampled
parameter.
T0508.EPS
Five trend objects are factory-set as shown Table 5.9.

5.6.3 View Object

This is the object to form groups of parameters in a block. One of advantage brought by forming groups of parameters is the reduction of load for data transaction. YTA has four View Objects for each Resource block, Transducer block and each function block, and each View Object has the parameters listed in Table 5.11 to
5.13.
Table 5.10 Purpose of Each View Object
Description
VIEW_1
VIEW_2
VIEW_3 VIEW_4
Set of dynamic parameters required by operator for plant operation. (PV, SV, OUT, Mode etc.)
Set of static parameters which need to be shown to plant operator at once. (Range etc.)
Set of all the dynamic parameters. Set of static parameters for configuration or
maintenance.
T0510.EPS
Table 5.9 Trend Object are Factory-Set
Index Parameters Factory Settings
32000
to
32005 32006 TREND_DIS.1
to
32010
TREND_FLT.1
to
TREND_FLT.6
to
TREND_DIS.4
Not used.
Not used.
T0509.EPS
5-6
IM 01C50T02-01E
Table 5.11 View Object for Resource Block
Relative
index
Parameter
VIEW1VIEW2VIEW
1 ST_REV 2 2TAG_DESC 3 STRATEGY 4ALERT_KEY 5 MODE_BLK 4 6 BLOCK_ERR 2 7 RS_STATE
11
8 TEST_RW
9 DD_RESOURCE 10 MANUFAC_ID 11 DEV_TYPE 12 DEV_REV 13 DD_REV 14 GRANT_DENY 15 HARD_TYPES 16 RESTART 17 FEATURES 18 FEATURE_SEL 19 CYCLE_TYPE 20 CYCLE_SEL 21 MIN_CYCLE_T 22 MEMORY_SIZE 23 NV_CYCLE_T 24 FREE_SPACE
425 FREE_TIME 26 SHED_RCAS 27 SHED_ROUT
128 FAULT_STATE 29 SET_FSTATE 30 CLR_FSTATE 31 MAX_NOTIFY 32 LIM_NOTIFY 33 CONFIRM_TIME 34 WRITE_LOCK 35 UPDATE_EVT 36 BLOCK_ALM 37 ALARM_SUM
8 38 ACK_OPTION 39 WRITE_PRI 40 WRITE_ALM 41 ITK_VER 42 SOFT_REV 43 SOFT_DESC 44 SIM_ENABLE_MSG
VIEW
3
22
4 2
2
2
2
4 4
4 4 4
1
1 4 1
8
5. CONFIGURATION
Relative
4
2
index
45 DEVICE_STATUS_1
Parameter
46 DEVICE_STATUS_2 2 1
47 DEVICE_STATUS_3
48 DEVICE_STATUS_4
49 DEVICE_STATUS_5
50 DEVICE_STATUS_6
51 DEVICE_STATUS_7
52 DEVICE_STATUS_8
Total in byte
4
VIEW1VIEW2VIEW
3
4 4 4 4 4 4 4 4
22 30 54 31
VIEW
4
T0511.EPS
2 1 1
2
2
2
4 2
1
2 1
2
5-7
IM 01C50T02-01E
Table 5.12 View Object for Transducer Block
Relative
index
Parameter
1 ST_REV 2 2TAG_DESC 3 STRATEGY 4ALERT_KEY 5 MODE_BLK 4 6 BLOCK_ERR 2 7UPDATE_EVT 8 BLOCK_ALM 9 TRANSDUCER_DIRECTORY
12 COLLECTION_DIRECTORY 13 PRIMARY_VALUE_TYPE_1
15 PRIMARY_VALUE_RANGE_1 16 CAL_POINT_HI_1 17 CAL_POINT_LO_1 18 CAL_MIN_SPAN_1 19 CAL_UNIT_1 20 SENSOR_TYPE_1 21 SENSOR_RANGE_1 22 SENSOR_SN_1 23 SENSOR_CAL_METHOD_1 24 SENSOR_CAL_LOC_1 25 SENSOR_CAL_DATE_1 26 SENSOR_CAL_WHO_1 27 SENSOR_CONNECTION_1 28 PRIMARY_VALUE_TYPE_2 29 30 31 32 33 34 35 36 37 38 39 40 41 42
PRIMARY_VALUE_2 PRIMARY_VALUE_RANGE_2 CAL_POINT_HI_2 CAL_POINT_LO_2 CAL_MIN_SPAN_2 CAL_UNIT_2 SENSOR_TYPE_2 SENSOR_RANGE_2 SENSOR_SN_2 SENSOR_CAL_METHOD_2 SENSOR_CAL_LOC_2 SENSOR_CAL_DATE_2 SENSOR_CAL_WHO_2 SENSOR_CONNECTION_2
43 SECONDARY_VALUE 5 44 45
SECONDARY_VALUE_UNIT 2 MODULE_SN 32
VIEW
1
210 TRANSDUCER_TYPE 111 XD_ERROR
514 PRIMARY_VALUE_1
5
VIEW
2
2
2
2
4 4
2
4 4
VIEW
3
2
4 2
2 1
5
5
VIEW
4
(1st)
2
2 1
2
5. CONFIGURATION
VIEW
VIEW
VIEW
4
(2nd)
4
(3rd)
4
(4th)
VIEW
4
(5th)
2222
11
4 2 2
11 32
1
32
6
32
2
11
4 2 2
11 32
32
32
2
T0512-1.EPS
1
6
5-8
IM 01C50T02-01E
Relative
index
Parameter
46 ALARM_SUM 47 PRIMARY_VALUE_FTIME_1 48 CAL_STATE_1 49 CJC_SELECT_1 50 CONSTANT_CJC_TEMP_1 51 WIRING_RESISTANCE_1 52 SENSOR_MATCH_R0_1 53 SENSOR_MATCH_A_1 54 SENSOR_MATCH_B_1
55 SENSOR_MATCH_C_1 56 SENSOR_MATCH_ALPHA_1 57 SENSOR_MATCH_DELTA_1 58 SENSOR_MATCH_BETA_1
59 PRIMARY_VALUE_FTIME_2 60 61 62 63 64 65 66 67 68 69 70
CAL_STATE_2 CJC_SELECT_2 CONSTANT_CJC_TEMP_2 WIRING_RESISTANCE_2 SENSOR_MATCH_R0_2 SENSOR_MATCH_A_2 SENSOR_MATCH_B_2
SENSOR_MATCH_C_2 SENSOR_MATCH_ALPHA_2 SENSOR_MATCH_DELTA_2
SENSOR_MATCH_BETA_2 71 SECONDARY_VALUE_FTIME 72 DIFFERENTIAL_VALUE 73 DIFFERENTIAL_UNIT 74 75
76 77 78 79 80 81 82 83 84 85 86 87 88
89 90
DIFFERENTIAL_VALUE_FTIME AVERAGE_VALUE AVERAGE_UNIT AVERAGE_VALUE_FTIME BACKUP_VALUE BACKUP_UNIT BACKUP_RETURN_SENSOR1 SENSOR_BURNOUT_DETECT LIMSW_1_VALUE_D LIMSW_1_TARGET LIMSW_1_SETPOINT LIMSW_1_ACT_DIRECTION LIMSW_1_HYSTERESIS LIMSW_1_UNIT
LIMSW_2_VALUE_D LIMSW_2_TARGET
LIMSW_2_SETPOINT
VIEW
1
VIEW
2
VIEW
3
VIEW
4
(1st)
8
4
4
1
5
5
2
4
5
5
2
4
55
2
22
1
4
1 4 2
22
1
4
VIEW
4
(2nd)
1 1 4 4
VIEW
4
(3rd)
5. CONFIGURATION
VIEW
VIEW
4
(4th)
4
(5th)
1 1 4 4
T0512-2.EPS
5-9
IM 01C50T02-01E
Relative
index
91 92 93 94 95 96 97 98 99
100 101 102 103 104
105
LIMSW_2_ACT_DIRECTION LIMSW_2_HYSTERESIS LIMSW_2_UNIT
LIMSW_3_VALUE_D
LIMSW_3_TARGET
LIMSW_3_SETPOINT
LIMSW_3_ACT_DIRECTION
LIMSW_3_HYSTERESIS
LIMSW_3_UNIT
Parameter
LIMSW_4_VALUE_D LIMSW_4_TARGET LIMSW_4_SETPOINT LIMSW_4_ACT_DIRECTION LIMSW_4_HYSTERESIS
LIMSW_4_UNIT 106 DISPLAY_AI_OUT 107 DISPLAY_ERROR 108 DISPLAY_WARNING 109 DISPLAY_ADDR 110 DISPLAY_CYCLE 111 WARNING_ENABLE_1 112 WARNING_ENABLE_2 113 WARNING_ENABLE_3 114 WARNING_ENABLE_4 115 MODEL 116 YTA_OPTION
VIEW
1
VIEW
2
VIEW
3
VIEW
4
(1st)
1 4 2
22
1
4
1 4 2
22
1
4
1 4 2
1 1
1 1
1 4
4 4 4
2
VIEW
4
(2nd)
VIEW
4
(3rd)
5. CONFIGURATION
VIEW
VIEW
4
(4th)
4
(5th)
Total in byte
44 60 57 99
76 73 76 73
T0512-3.EPS
5-10
IM 01C50T02-01E
5. CONFIGURATION
Table 5.13 View Object for AI Function Block
Relative
index
Parameter
1 ST_REV 2
VIEW1VIEW
2
2 2 TAG_DESC 3 STRATEGY 4 ALERT_KEY 5 MODE_BLK 4 6 BLOCK_ERR 2 7PV
55 8 OUT 5 9 SIMULATE
10 XD_SCALE 11 OUT_SCALE 12 GRANT_DENY
11 11
2 13 IO_OPTS 14 STATUS_OPTS 15 CHANNEL 16 L_TYPE 17 LOW_CUT 18 PV_FTIME
519 FIELD_VAL 20 UPDATE_EVT 21 BLOCK_ALM
822 ALARM_SUM 23 ACK_OPTION 24 ALARM_HYS 25 HI_HI_PRI 26 HI_HI_LIM 27 HI_PRI 28 HI_LIM 29 LO_PRI 30 LO_LIM 31 LO_LO_PRI 32 LO_LO_LIM 33 HI_HI_ALM 34 HI_ALM 35 LO_ALM 36 LO_LO_ALM
Total in byte
31 26 31 46
VIEW
3
2
4 2
5
5
8
VIEW
4
2
2 1
2 2 2 1 4 4
2 4 1 4 1 4 1 4 1 4
T0513.EPS
Table 5.14 View Object for DI Function Block
Relative
index
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Parameter
ST_REV TAG_DESC STRATEGY ALERT_KEY MODE_BLK BLOCK_ERR PV_D OUT_D SIMULATE_D XD_STATE OUT_STATE GRANT_DENY IO_OPTS STATUS_OPTS CHANNEL PV_FTIME FIELD_VAL_D UPDATE_EVT BLOCK_ALM ALARM_SUM ACK_OPTION DISC_PRI DISC_LIM DISC_ALM
Total in byte
VIEW
1
2
4 2 2 2
2
8
22
VIEW
Table 5.15 Indexes of View for Each Block
Resource block Transducer block
AI Function block
DI Function block
PID Function block
1 2 3 4 1 2 3 4 1 2
VIEW_1
40100 40200 40400
40410 40420 40430 40600 40610 40620 40630 40800 40810
VIEW_2
40101 40201 40401
40411 40421 40431 40601 40611 40621 40631 40801 40811
VIEW_3
40102 40202 40402
40412 40422 40432 40602 40612 40622 40632 40802 40812
VIEW
VIEW
2
2
4
3
2
2
2
1 4 2 2 2
2 2 2
2
2
2
4 2
8
2
1
1
22
19
T0514.EPS
8
VIEW_4
40103 40203
- 40207 40403 40413 40423 40433 40603 40613 40623 40633 40803 40813
T0515EPS
5-11
IM 01C50T02-01E
5. CONFIGURATION

5.6.4 Parameters of Transducer Block

The transducer block makes settings for the tempera­ture transmitter-specific functions of the YTA320, such as the temperature input and display settings. See Appendix 1 for a list of all parameters of the YTA320; this section describes only the settings for important parameters.
Note that you can choose “˚C” or “Kelvin” as the unit of temperature. “˚F” or “˚R” can also be selected for a model with the option code /D2.
Mode Setting Parameter
MODE_BLK
Supports O/S and Auto modes. In the O/S mode, the transducer block does not function, as implied by the mode name “Out of Service.”
Parameters Related to Sensor Input
The number “2” enclosed in parentheses appearing in the following parameter names and descriptions indicates that the preceding number “1” should be read as “2” for the cases of sensor 2, respectively.
SENSOR_TYPE_1 (2)
Shows and stipulates the type of sensor connected to sensor input 1 (or 2). The following sensors can be connected.
· Thermocouple: Types B, E, J, K, N, R, S, and T (IEC584), types L and U (DIN43710), and Types W3 and W5 (ASTM E-988)
· 2-/3-/4-wire RTD: Pt100, Pt200, Pt500 (IEC751) JPt100 (JIS), Ni120, Cu (SAMARC21-4)
· 2-/3-/4-wire resistance input
·2-wire DC mV input
IMPORTANT
Whenever 4-wire input is specified for Sensor 1, set ‘Non Connection’ for Sensor 2. 4-wire input cannot be used as Sensor 2.
PRIMARY_VALUE_1 (2)
Shows the value and status of the input from sensor 1 (or 2). The unit set in PRIMARY_VALUE_RANGE_1 (or ..._2) applies to the unit of the value. The damping time constant is set in PRIMARY_VALUE_FTIME_1 (or ..._2).
NOTE
If an input exceeds the range shown­in PRIMARY_VALUE_RANGE_1(2), the value up to 120% of the range will be output for up er limit side, and -20% of the range will be out ut for lower limit side. In thie case, the accuracy of the input exceeding the range shall not be guaranteed.
SECONDARY_VALU
Shows the value and status of the terminal board temperature. The unit of temperature is set in SECONDARY_VALUE_UNIT, and the damping time constant in SECONDARY_VALUE_FTIME.
DIFFERENTIAL_VALUE
Shows the value and status of the difference between 2 inputs [sensor 1 input value minus sensor 2 input value] when 2 sensors are connected. The unit of temperature is set in DIFFERENTIAL_UNIT, and the damping time constant in DIFFERENTIAL_VALUE_FTIME. When there is no connection to sensor 2 input, the status of DIFFERENTIAL_VALUE is Bad and the value is undefined.
AVERAGE_VALUE
Shows the value and status of the average of 2 inputs when 2 sensors are connected. The unit of temperature is set in AVERAGE_UNIT, and the damping time constant in AVERAGE_VALUE_FTIME. When there is no connection to sensor 2 input, the status of AVERAGE_VALUE is Bad and the value is undefined.
SENSOR_CONNECTION_1 (2)
Shows and stipulates the number of wires connected to sensor input 1 (or 2). This setting only valid for RTD and resistance input.
5-12
BACKUP_VALUE
When 2 sensors are connected, this parameter normally shows the value input from sensor 1, and in case of burnout of sensor 1 (when the backup action becomes active), shows the value input from sensor 2. The unit and damping time constant follow the respective settings for the input currently selected.
IM 01C50T02-01E
5. CONFIGURATION
If you want to switch back to select sensor 1 input while the backup action is active after the sensor 1 input recovers, set 1 (Enable) in BACKUP_RETURN_SENSOR1. Because this data is not retained, set 1(Enable) in the parameter every switch back. When there is no connection to sensor 2 input, the status of BACKUP_VALUE is Bad and the value is undefined.
Parameters Related to Limit Switches
Parameters whose names begin with “LIMSW” store the settings for limit switch signals output to DI function blocks. The transducer block has 4 limit switches numbered from 1 to 4, and these param­eters determine the specifications of the respective switches. In the following parameter names and descriptions, read the number “1” as “2,” “3,” or “4” according to the intended limit switch number.
LIMSW_1_VALUE_D
Stores the value and status of limit switch 1.
LIMSW_1_TARGET
Stipulates the value that should be compared with the threshold. PRIMARY_VALUE_1, PRIMARY_VALUE_2, SECONDARY_VALUE, DIFFERENTIAL_VALUE, AVERAGE_VALUE, or BACKUP_VALUE can be chosen.
LIMSW_1_SETPOINT
Stipulates the threshold of switching on limit switch
1.
LIMSW_1_ACT_DIRECTION
Stipulates whether limit switch 1 should work as a high limit switch or low limit switch.
LIMSW_1_HYSTERESIS
Stipulates the hysteresis of limit switch 1.
DISPLAY_ERROR
Select whether to display the error code on the LCD. Selecting 1 (INHIBIT) will hide the error code from the LCD even when an error occurs.
DISPLAY_WARNING
Select whether to display the warning code on the LCD. Even if this parameter is set to ‘SHOW’, error code for warning will not be shown when the functions themselves are disabled by parameters WARNING_ENABLE_#.
DISPLAY_ADDRESS
Select whether to display the device address on the LCD.
DISPLAY_CYCLE
Sets the display refresh cycle.
Parameters Related to Warnings
Faults found as a result of self-diagnostics of the YTA320 are categorized into errors and warnings. Warnings can be hidden from the LCD as necessary by changing the values of the parameters below. Refer section 7.4 for the notes on using Warning function.
WARNING_ENABLE_1, (2, 3, 4)
Switches on and off the generation of warnings.
Parameters Related to Input Calibrations
The number “2” enclosed in parentheses appearing in the following parameter names and descriptions indicates that the preceding number “1” should be read as “2” for the cases of sensor 2, respectively.
CAL_STATE_1 (2)
Shows if user adjustment function for Sensor1(2) input is invalid(User Cal off) or valid(User cal on). Setting ‘2(Calibration Exec)’ will allow users to adjust the input.
Parameters Related to Display
For a model with the Integral indicator, the display information can be selected by parameters that have names beginning with “DISPLAY.” For the details of contents to be displayed, refer to section 6.4.
DISPLAY_AI_OUT
Specify an AI block number or numbers to select the AI blocks whose output values should be displayed on the LCD. If two or more AI blocks are selected, the respective values are displayed in turn cyclically.
IMPORTANT
If you changing the sensor type once after making user adjustment function valid, re-do user adjustment or set ‘0(User Cal off)’ to CAL_STATE_1 (2) to make the function off.
5-13
IM 01C50T02-01E
5. CONFIGURATION
CAL_POINT_HI_1 (2), CAL_POINT_LO_1 (2)
These parameters store the calibrated upper and lower range limit values for sensor input 1 (or 2). To perform a calibration, apply a voltage (for a thermocouple or voltage input) or a resistance (for a RTD or resistance input) between the corresponding input terminals, and write the applied level to these parameters. The values written must meet the following conditions:
CAL_POINT_HI_1 > CAL_POINT_LO_1
CAL_POINT_HI_2 > CAL_POINT_LO_2 The table below shows the recommended input levels for calibrations.
Table 5.16 Recommended Input Levels for Calibration
0 mV 0 mV
40 40
0 mV
40
Input
High Level
(CAL_POINT_
HI_1/2)
25 mV 75 mV
330
1600
75 mV
1600
Input Type
Thermocouple
RTD
DC mV Resistance
Sensor Type
Type B, R, S, or T Type E, J, K, N, W3, W5, L, U Pt100, JPt100, Ni120, Cu Pt200, Pt500 mV Ohm
Low Level
(CAL_POINT_
LO_1/2)
T0516.EPS
Table 5.17 Input Selected by CHANNEL Setting
CHANNEL
Setting
1 Sensor 1 input (PRIMARY_VALUE_1) 2 Sensor 2 input (PRIMARY_VALUE_2) 3Terminal board temperature
(SECONDARY_VALUE)
4Temperature difference between sensors 1 and 2
(DIFFERENTIAL_VALUE)
5Average temperature of sensors 1 and 2
(AVERAGE_VALUE)
6 Backup temperature (BACKUP_VALUE)
Input Selected
XD_SCALE
Stipulates the range of the input from the transducer. The customer-specified range (or the default range if the range was not specified when ordering) is set before the YTA320 is shipped from the factory. If the unit of the input temperature value is set as mV or ohm in the transducer block and the unit of XD_SCALE is set as a unit of temperature (e.g., °C), or vice versa, the status becomes Uncertain or Bad. It is recommended to set the same unit for the transducer block and AO blocks.
L_TYPE
Stipulates the calculation in the AI block. Setting L_TYPE to:
T0517.EPS

5.6.5 Parameters of AI Function Block

Parameters of function blocks can be read and written from a host computer. See Appendix 1 for a list of all parameters of the YTA320. For a model incorporating the PID function block and link master feature, see Appendixes 4 and 5. This section describes only the settings for important parameters of each AI block.
MODE_BLK
Supports O/S, Auto, and Manual modes. The AI block does not function in the O/S mode, does not update the measured value in the Manual mode, and updates the measured value in the Auto mode. Normally, set the mode to Auto. Before the YTA320 is shipped from the factory, AI1 and AI2 are set to Auto mode, and AI3 and AI4 to O/S.
NOTE
The CHANNEL of unused blocks are recom­mended to set to ‘3’ (SECONDARY_VALUE).
CHANNEL
Selects the input to the AI block from the trans­ducer. The table below shows the input value depending on the setting of CHANNEL. Set CHANNEL according to the value you want to input to the AI block.
5-14
· “Direct” puts the value that is input to CHAN­NEL, in OUT as is.
· “Indirect” performs scaling of the input value based on XD_SCALE and OUT_SCALE and puts the scaled value in OUT.
· “IndirectSQRT” performs scaling of the input value based on XD_SCALE, extracts the square root of the scaled value, performs scaling of the square root, and then puts the scaled value in OUT.
PV_FTIME
Stipulates the time constant (in seconds) of the first­order lag filter inside the AI block.
OUT_SCALE
Stipulates the range of OUT (by setting the upper and lower range limits). The unit can also be set freely. OUT_SCALE is set to 0 to 100% before the YTA320 is shipped from the factory. Change the setting as necessary.
Alarm Priorities: HI_HI_PRI, HI_PRI, LO_PRI, and LO_LO_PRI
These parameters determine the respective priority levels of the four types of process alarms: HI_HI_ALM, HI_ALM, LO_ALM, and LO_LO_ALM. Only the alarms whose priority level is set to 3 or higher will be transmitted upon occurrence.
IM 01C50T02-01E
Loading...
+ 67 hidden pages