Yokogawa VJCE-01A User Manual

User’s Manual
Model VJCE-01A VJ Mounting Base for Communication
IM 77J01C51-11E

CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

If this symbol is indicated on the product, the operator should refer to the explanation given in the user's manual in order to avoid injury or death to either themselves or other personnel, and/or damage to the instrument. The manual describes the special care the operator should exercise to avoid shock or other dangers that may result in injury or loss of life.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
NOTE
Draws attention to information that is essential for understanding the operations and/or features of the products.
Network Solutions Business Divisiion
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan Phone: +81-422-52-7179 Facsimile: +81-422-52-6793
IM 77J01C51-11E
1st Edition July 2004

INTRODUCTION

The VJCE-01A has been manufactured under strict quality control and thoroughly tested at the factory before ship­ment. When you receive it, visually inspect it for damage.

(1) Model and Suffix Codes Check

Check that the model and suffix codes for VJ mounting base and VJ series signal conditioner are as ordered.
Model and Suffix Code Input Output-1 Output-2
VJCE-01A Screw terminal Screw terminal
List of Mountable Models
Signal Conditioners
with Communication Function
Model and Suffix Code
VJH7
-02-❐❐P0
VJA7
-02-❐❐P0
VJU7
-02-❐❐P0
VJS7
-02-❐❐P0
VJP8
-02-❐❐P0
VJQ8
-02-❐❐P0
VJQ7
-02-❐❐P0
VJX7
-02-❐❐P0
VJET
-01-1 0 0 0
Signal Conditioners
of Single Output Type
Model and Suffix Code
VJC1
-01 N-❐❐N0
VJH1
-01-❐❐N0
VJH7
-01-❐❐N0
VJHF
-01-❐❐N0
VJHR
-01-❐❐N0
VJA1
-01-❐❐N0
VJA4
-01-❐❐N0
VJA5
-01-❐❐N0
VJA7
-01-❐❐N0
VJT6
-01-❐❐N
VJR6
-01-❐❐N
VJU7
-01-❐❐N0
VJS2
-01-❐❐N
VJS7
-01-❐❐N0
VJP1
-01-❐❐N0
VJP4
-01-❐❐N0
VJP8
-01-❐❐N0
VJQ8
-01-❐❐N0
VJQ2
-01-❐❐N0
VJQ0
-01-❐❐N0
VJQ7
-01-❐❐N0
VJF1
-01-❐❐N0
VJB1
-01-❐❐N
VJG1
-01-❐❐N0
VJB3
-01-❐❐N0
VJD1
-01-❐❐N0
VJX7
-01-❐❐N0
VJXS
-01-❐❐N0
Loop Powered Isolator Isolator Isolator (Multi-function) Isolator (Super Speed Response Type) Isolator (Reverse Output Type) Distributor Distributor (Non-isolated) Distributor (with Square Root Extractor) Distributor (Multi-function) Thermocouple Converter RTD Converter Universal Temperature Converter Potentiometer Converter Potentiometer Converter (Multi-function) Pulse Repeater Pulse Rate Converter Pulse Rate Converter (Multi-function) Pulse to Analog Converter (Multi-function) Pulse to Analog Converter (Free Range Type) Analog to Pulse Converter Analog to Pulse Converter (Multi-function) Pneumatic to Electrical Converter CT Converter (RMS) PT Converter (RMS) AC Converter (RMS) Tachometer Converter Universal Computing Unit (Multi-function) Universal Computing Unit Ethernet/RS-485 Converter
Product Name
RS-485 Communication terminal
2
IMPORTANT
Do not mount any signal conditioners other than the above. It may result in a communication failure or a malfunction. Be sure to confirm the model and suffix codes of each signal conditioner when mounting it.
The ❐” in Model and suffix codes differs depending on the models of signal conditioner. Refer to the general specifications for respective signal conditioners.
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00
3

(2) Related User's Manual

This manual dose not explain the details (handling, maintenance and the like) for signal conditioners mounted on VJCE-01A. The lineup and User’s Manual numbers of JUXTA VJ series signal conditioners are shown below.
Model VJCE-01A VJA1 VJA4 VJA5 VJA7 VJB1 VJB3 VJC1 VJD1 VJF1 VJG1 VJH1 VJH7 VJHF VJHR VJP1 VJP4 VJP8 VJQ0 VJQ2 VJQ7 VJQ8 VJR6 VJS2 VJS7 VJT6 VJU7 VJX7 VJXS VJET VJ77
VJ Mounting Base for Communication: This manual Distributor Distributor (Non-isolated) Distributor (with Square Root Extractor) Distributor CT Converter (RMS) AC Converter (RMS) Loop Powered Isolator Tachometer Converter Pneumaic to Electrical Converter PT Converter (RMS) Isolator Isolator (Multi-function) Isolator (Super Speed Response Type) Isolator (Reverse Output Type) Pulse Repeater Pluse Rate Converter Pluse Rate Converter (Multi-function) Analog to Pulse Converter Pulse to Analog Converter (Free Range Type) Analog to Pulse Converter Pulse to Analog Converter (Multi-function) RTD Converter Potentiometer Converter Potentiometer Converter (Multi-function) Thermocouple Converter Universal Temperature Converter Universal Computing Unit (Multi-function) Universal Computing Unit Ethernet/RS-485 Converter Parameter Setting Tool VJ Series Communication Function
Product Name [Document title]
User's Manual No.
IM 77J01C51-11E IM 77J01A01-01E IM 77J01A04-01E IM 77J01A05-01E IM 77J01A07-01E IM VJB1-01E IM VJB3-01E IM VJC1-01E IM VJD1-01E IM VJF1-01E IM VJG1-01E IM 77J01H01-01E IM 77J01H07-01E IM VJHF-01E IM 77J01H12-01E IM VJP1-01E IM VJP4-01E IM 77J01P08-01E IM VJQ0-01E IM VJQ2-01E IM 77J01Q17-01E IM 77J01Q08-01E IM 77J01R06-01E IM VJS2-01E IM 77J01S07-01E IM 77J01T06-01E IM 77J01U07-01E IM 77J01X07-01E IM VJXS-01E IM 77J01E11-01E IM 77J01J77-01E IM 77J01J11-01E

1. PRODUCT OVERVIEW

The VJCE-01A is a horizontally installed, side-by-side multiple mounting base that complies with the standard rack­mounting dimensions specified by the JIS/EIA standards. A maximum of 16 signal conditioners of JUXTA VJ series can be mounted on VJCE.
Different signal conditioners of VJ series can be mixed and housed in the same mounting base.
The VJET Ethernet/RS-485 converter can be mounted.
Multi-drop connection is used for output-2.
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00

2. EXTERNAL DIMENSIONS

482.6 465 446
Input terminals
for slots 1 to 8
Input terminals
for slots 9 to 16
4
Unit : mm
121
46.8
25.8
RS-485 communication terminals
37.757.1
50 24.5
130
Output-1 terminals for slots 1 to 8
Output-1 terminals for slots 9 to 16
Power supply terminals
30.5

3. INSTALLATION OF VJCE-01A

The VJCE-01A can be installed horizontally on 19 inches rack complies with JIS/EIA standards, or horizontally on the wall. Under the conditions mentioned in Article 3.2, a maximum of 5 mounting bases can be installed on one side of the cabinet.

3.1 Environmental Conditions

3.1.1 Ambient temperature and humidity
Ambient temperature and humidity during operation of the instruments would be as follows: Temperature: 0 to 50°C, Humidity: 5 to 90% RH
3.1.2 Vibration condition
Vibration of installation place would be less than 2m/s
3.1.3 Air purification degree
Air dirty is desirous to be less than 0.2mg/m
3
. Also, corrosive gas such as hydrogen sulfide, sulfurous acid gas, chlo-
rine and conductive dust such as iron and carbon are desirous to be as little as possible.
(Note) Permissible limit of hydrogen sulfide (H
29 (1979) CLASS S1*. JEIDA: Japan Electronic Industrial Development Association JEIDA-29 (1979) CLASS S1 H
S: 0.01ppm or less, SO2: 0.05ppm or less
2
(Ambient temperature: 25°C ± 5°C, ambient humidity: 40 to 80%RH)
2
at 10 to 150Hz
S) and sulfurous acid gas (SO2) would be as standard of JEIDA-
2
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00

3.2 Condition of Installation

NOTE
(1) Secure space for top and bottom to avoid
heating.
Apart more than 100 mm from the floor
board.
Apart more than 100 mm from panel top
and make air exhaust hole or set cooling
fan at panel upper.
If wall stands at back in case of rack
mounting, apart more than 60mm from the
wall for ventilation.
(2) Take enough space for front and side faces
so as not to interfere wiring, piping and maintenance area.
(3) In case storing in cabinet, air cooling is
compulsorily required to prevent from raise of
temperature. (4) Do not install it on the heating materials. (5) In case of installing the VJCE-01A one above
another to up and down direction, take
installation space as shown in the figure on
the right. (78 mm for rack mounting, 128 mm
for wall mounting)
19 inches Rack Mounting Wall Mounting
Cooling fan or exhaust hole Cooling fan or
100 or more
78 or more
60 or more
100 or more
128 or more
5
Unit : mm
exhaust hole

3.3 Installation

3.3.1 Installation of VJCE-01A
Use four (4) M5 screws for installation.
3.3.2 Installation of signal conditioners
Connect the pin on the back of the signal conditioner to the VJCE-01A connector as shown in the figure on the right. Then tighten the fixing screw on the front of the signal conditioner.
NOTE
Insert and pull out the signal conditioner vertically to VJCE. Inserting and pulling it out slantwise may make the pin bent and cause a failure such as a bad contact.
IMPORTANT
Only one VJET can be mounted in slot 16 of VJCE­01A. Do not mount it in other slots.
VJET
VJCE
Signal Conditioner
Fixing screw
Blank Plate (Option) Parts Number : T9093TT
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00

4. EXTERNAL WIRING

4.1 Field Side Wiring and Wiring of Power Supply and Ground

Flexible twisted cable and durable round crimp-on terminals of good contact are recommended to use.
6
D1
D2
Cross sectional
area
0.75 mm
A
L
0.9 mm2
1.25 mm
2.0 mm
2
2 2
Screw
M3.5 3.7 or more 6.9 or less About 19 3.2 or more
D1
Hole dia.
(mm)
A
Terminal out dia.
(mm)
L
Terminal length
(mm)
øD2
Insulation coating
(mm)
4.1.1 Signal cable
Nominal cross-sectional area of conductor: 0.75 to 2 mm Example of suitable cable: Vinyl code (VSF) twisted cable (JIS C3306)
2
4.1.2 Power cable
Nominal cross-sectional area of conductor: 1.25 to 2 mm Example of suitable cable: 600V vinyl code (IV) twisted cable (JIS C3307)
Vinyl insulated cable (KIV) (JIS C3316)
2
4.1.3 Ground cable
Nominal cross-sectional area of conductor: 2 mm Example of suitable cable: 600 V vinyl code (IV) twisted cable (JIS C3307)
Vinyl insulated cable (KIV) (JIS C3316)
2

4.2 Field Side Input/Output Terminals, Piping and System Side Wiring

Assignment of Input/Output Terminals on and after page 7 shows relation between VJCE-01A field side input/output terminals and signal conditioner input /output signal at the terminals. Field side input/output terminals are M3.5 screws. Connect input air pressure signal of VJF1 to connecting hole of front face of signal conditioner directly. Connect power and ground cables to power terminals of VJCE-01A. Power would internally be distributed to respec­tive signal conditioners.
WARNING
It is recommended that CT protector (CTG-5) be attached to the current input terminals connected to the secondary side of the CT when mouning VJB1 (CT transmitter) on VJCE-01A. Since a high potential develops over the secondary side, the CT may burn and break if you unplug the VJB1 from the VJCE­01A while the VJB1 is turned on and it has no CT protector.
IMPORTANT
Ensure the followings before turning on the power. Use of signal conditioners of VJ series ignoring the specifications may cause overheating or damage to VJCE-01A and signal conditioners.
· Power supply voltage and input signal value applied to VJCE-01A and signal conditioners should meet the required specifications.
· The external wiring to the terminals is as specifications.
Do not operate the product in the presece of flammable or explosive gases or vapors. To do so is highly dangerous.
Many semi-conductor integrated circuit parts are used for signal conditioners. Take care of static electricity trouble at the maintenance or change of setting for the signal conditioners.
The grounding resistance must be 100 Ω (JIS Class D grounding). The length and thickness of the grounding cable should be as short and thick as possible. Directly connect the lead from the ground terminal of the product to the ground. Do not carry out daisy-chained inter-ground terminal wiring.
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00
7
5.

ASSIGNMENT OF INPUT/OUTPUT TERMINALS AND POWER SUPPLY TERMINALS

Only the signal conditioners of single-output type and the signal conditioners of dual-output type with output-2 for communication (RS-485) can be mounted. Be sure to check not only the model but also suffix codes of the signal conditioner to be mounted. (Refer to List of Mountable Models on page 2.)

5.1 Assignment of Input/Output Terminals

Mountable Signal Conditioners
VJH1, VJH7, VJHF, VJHR VJQ0, VJQ7 VJXS, VJX7
VJC1 (*1)
VJT6 VJU7 (TC or mV input)
VJR6 VJU7 (RTD input)
VJS2, VJS7
When using internal power
VJA1 VJA5 VJA7
VJA4 (*1)
VJB1
supply
When using external power supply (When used as an iso­lator)
N.C. in the table denotes unassigned terminals.
Input T erminal
1347
⫹⫺
(*2)
Channel-1
⫹⫺
⫹⫺
RJC
ABB
100%
CENTER
PS+ N.C.
N.C. ⫹⫺
Channel-1
+
A
N.C.
N.C.
0%
N.C.
N.C.
Output-1 T erminal
⫹⫺
Channel-1
⫹⫺
⫹⫺
⫹⫺
⫹⫺
⫹⫺
⫹⫺
Channel-1
⫹⫺
⫹⫺
Input Terminals
SLOT*
9
31
N.C.
4
* in the figure above denotes a slot number. Slots are numbered from 1 to 16, beginning with the left­most slot, when viewed from the VJCE-01A front.
Output-1 Teminals
7*9
Assignment of RS-485 communication terminals (Output-2 terminals)
1 2 3
Terminal Number Signal Symbol
1 2 3
* The terminal for output-2 is multidrop-connected to the
output-2 of all slots.
RS-485 B (⫹) RS-485 A (⫺) RS-485 COM
V
VJG1
L
A/V
VJB3
V
VJD1
VJP1 VJP4 VJP8 VJQ2 VJQ8
VJF1
VJET (*3)
*1: Only 1-channel type of VJC1 and VJA4 can be mounted. *2: When receiving current input (current pulse), external shunt resistor (receiving resistor) is required. *3: Only one VJET can be mounted in slot 16 of VJCE-01A. Do not mount it in other slots.
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00
Non-voltage contact / Voltage contact Internally powered current pulse
(two-wire system) Internally powered voltage pulse
(three-wire system)
N.C. ⫹⫺ PS+ ⫹⫺
PS+ ⫹⫺
N.C. N.C. N.C.
Input through one-touch fitting 6 of the VJF1.
N.C. N.C. N.C.
N.C.
N
N.C.
N.C.
⫹⫺
⫹⫺
⫹⫺
⫹⫺
(*2)
⫹⫺
N.C. N.C.

5.2 Assignment of Power Supply Terminals

Terminal Number Signal Symbol
1
1
2 3
2 3
SUPPLY L(⫹) SUPPLY N(⫺) GND
CAUTION
Ensure that the power supply voltage for VJCE-01A matches that for the signal conditioner to be mounted on VJCE-01A. Supply of different power supply voltage may damage VJCE-01A and signal conditioners.

6. CALIBRATION

Refer to the Users Manual of respective signal conditioners for how to calibrate and the equipment required for cali­bration.

6.1 Items to Check before Power on

Supply power rating is 12 to 36 V DC or 85 to 246 V AC / DC.
Wiring of signal cables
Installation, ambient temperature, humidity, dust and vibration
Please power on after checking the above items. The VJCE-01A would be in operational status upon power on. However, 10 to 15 minutes are required to satisfy its specifications and performance
8
All Rights Reserved. Copyright © 1999, Y okogawa M&C Corporation IM 77J01C51-11E 1st Edition July 23,2004-00