Yokogawa TC10-L Operating Manual

TC10
48
48
48
PV
AT
1411
8 mm max.
Optional gasket
65 mm min.
2.56 in min.
45
+0.6
mm
1.78
+0.023
in
45
+0.6
mm
1.78
+0.023
in
65 mm mi
n.
2.56 in min.
RS485
TERMINALS
Pin connector
1.4 mm max. (0.055 in.)
Stripped wire L: 5.5 mm
(0.21 in.)
L
ELECTRICAL CONNECTIONS
Thermo­couple
DI1
OP3
Limiter
OP4 (note)
Output 4: 0-12V DO
Analogue input
mV, V mA
Note: Terminal 4 can be programmed as:
- 0 to 12 V SSR Drive Output (OP4) connecting
the load between terminals 4 and 16;
- 12 Vdc (20 mA) transmitter power supply
connecting the 2 wire transmitter between terminals 4 and 1; for 3 wire transmitter connect terminal 4 to transmitter power supply inputand terminal 1 and2 to transmitter signal output.
Neutral
Line
12VDC (note)
PV
4 to 20 mA
3 wire transmitter
12VDC (note)
PV
Pt100Pt1000
100 to 240 Vac
4 to 20 mA
2 wire transmitter
OP1
Output 1: 4-20 mA
Output
1
2
+
_
TC 10 - L
LIMIT CONTROL TYPE
Engineering Manual
Code: IM 05C01E81-12EN
1.3 MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1. It should be easily accessible;
2. There is minimum vibrations and no impact;
3. There are no corrosive gases;
4. There are no water or other fl uids (i.e. condensation);
5. The ambient temperature is in accordance with the
operative temperature (0 to 50°C);
6. The relative humidity is in accordance with the instrument specifi cations (20 to 90%);
The instrument can be mounted on panel with a maximum thickness of 8 mm.
When the maximum front protection (IP65) is
desired, the optional gasket must be mounted.
This is mandatory for FM approval.
First edition:
Nov. 2019
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750 Japan
www.yokogawa.com/ns
1. OUTLINE DIMENSIONS (mm)
1.1 INSTRUMENT DIMENSIONS
1.2 PANEL CUT-OUT
2. CONNECTION DIAGRAM
2.1 GENERAL NOTES ABOUT WIRING
1. Do not run input wires together with power cables.
2. External components (like zener barriers, etc.) connected
between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents.
3. When a shielded cable is used, it should be connected at one point only.
4. Pay attention to the line resistance; a high line resistance may cause measurement errors.
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 1
2.2 INPUTS
2.2.1 Termocouple Input
External resistance: 100W max., maximum error 25 µV.
Continuity detection current: 250 nA.
Cold junction: automatic compensation between 0 to 55°C.
Cold junction accuracy: 0.04°C/°C after a warm-up of
2
3
Pt1000
mV
V
+
_
+
_
1
2
+
_
4 to 20 mA
Passive
transmitter
4
1
+
_
+
_
1
2
0/4 to 20 mA
Passive
transmitter
_
External
PWS
+
0/4 to 20 mA
Active
transmitter
+
_
+
_
1
2
Digital Input 1
15
16
20 minutes.
Input impedance: > 1 MW.
Burn out: full scale
Calibration: According to EN 60584-1.
Note: For TC wiring use proper compensating cable
preferable shielded.
2.2.2 RTD Pt 100 Input
Input circuit: Current injection (135 µA). Line resistance: Automatic compensation up to 20W/wire
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2.
Note: The resistance of the 3 wires must be the same.
2.2.3 RTD Pt 1000 Input
2.2.5 mA Input
0/4 to 20 mA input wiring for passive transmitter
using the auxiliar
Input impedance: < 53W. Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
0/4 to 20 mA input wiring for passive transmitter
using an external pws
0/4 to 20 mA input wiring for active transmitter
y pws
Line resistance: Not compensated. Pt 1000 input circuit: Current injection (15,5 µA). Pt 1000 calibration: According to EN 60751/A2.
2.2.4 V and mV Input
Input impedance: > 1 MW for mV Input
500 kW for Volt Input.
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 2
2.2.6 Logic Input
Safety notes:
– Do not r
– The instrument needs 150 ms to recognize a contact
status variation;
– Logic inputs are NOT isolated by the measuring input.
A double or reinforced isolation between logic inputs and power line must be assured by the external elements.
Logic inputs driven by dry contact
Maximum contact resistance: 100W. Contact rating: DI1 = 10 V, 6 mA;
un logic input wiring together with power cables;
2.3 OUTPUTS
Safety notes:
– To avoid electrical shocks, connect power line at last. – For supply connections use No. 16 AWG or larger wires
rated for at last 75°C. – Use copper conductors only. – SSR outputs are not isolated. A reinforced isolation must
be assured by the external solid state relays. – For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire. – Do not short-circuit the terminals of the SSR output.
WARNING! Before connecting the output actuators,
we recommend to confi gure the parameters to
suit your application (e.g.: input type, Control
mA
+
-
7
8
V
+
-
7
8
C
NO
13
14
C
NO
11
12
SSR
+
-
4
Out4
4
16
D +
D -
D +
D -
D +
D -
D +
D -
RS-485
5
6
Power Supply
9
10
Neutral
Line
strategy, alarms, etc.).
2.3.1 Output 1 (OP1)
Function: retransmission
Output type: isolated output
Current Analog Output
2.4 SERIAL INTERFACE
mA output:
0/4... 20 mA, galvanically isolated, RL max. 600W.
Voltage Analog Output
V output: 0/2... 10 V
, galvanically isolated
2.3.2 Output 2 (OP2)
Function: limiter output
Relay Output
Contact rating: • 2 A /250 V cosϕ = 1;
• 1 A /250 V cosϕ = 0.4.
Operation: 1 x 105.
2.3.3 Output 3 (OP3)
Relay Output
Contact rating: • 2 A /250 V cosϕ = 1;
• 1 A /250 V cosϕ = 0.4.
Operation: 1 x 105.
, RL min.: 500W.
Interface type: Isolated (50 V) RS-485; Voltage levels: According to EIA standard; Protocol type: Modbus RTU; Byte format: 8 bit with no parity; Stop bit: 1 (one); Baud rate:
Address: Programmable between 1 to 254.
Notes: 1. RS-485 interface allows to connect up to 30
2. The cable length must not exceed 1.5 km at
Programmable between 1200 to 38400 baud;
devices with one remote master unit.
9600 baud.
2.5 POWER SUPPLY
Supply Voltage: 100 to 240 VAC (-15 to +10%).
Notes: 1. Before connecting the instrument to the power
line, make sure that line voltage is equal to the voltage shown on the identifi cation label;
2. The polarity of the power supply has no importance;
3. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
2.3.4 Output 4 (OP4)
SSR Output
Logic level 0: Vout < 0.5 VDC;
Logic level 1: 12 V ±20%, 20 mA max..
Note: Overload protected.
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 3
3. TECHNICAL CHARACTERISTICS
4. MODEL AND SUFFIX CODES
3.1 TECHNICAL SPECIFICATION
Case:
Front protection: IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
Terminal block:
0.25 to 2.5 mm2 (AWG22 to AWG14) with connection diagram, tightening torque 0.5 Nm;
Dimensions: 48 x 48, depth 73 mm, (1.89 x 1.89 x 2.87 in.)
Panel cutout: 45[-0, +0.6] x 45[-0, +0.6] mm
(1.78[- 0.000, +0.023] x 1.78[- 0.000, +0.023] in.)
Weight: 180 g max..
Power supply: 100 to 240 VAC (-15 to +10% of the
nominal value);
Power consumption: 6.0 VA max. (100 to 240 VAC);
Insulation voltage: 2300 V rms according to EN 61010-1;
Display updating time: 500 ms;
Sampling time: 130 ms;
Resolution: 30000 counts;
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Plastic, self-extinguishing degree: V-0 according to UL 94;
16 screw terminals for cables of
Model Code
TC10 -L
Fixed code -L Always "-L" Power supply H 100 to 240 VAC Fixed code C Always "C"
Retransmission
Limit control output R limit control relay output
Alarm output 1 - 2
Fixed code D
Serial communication
Fixed code F Always “F” Option Code /GK Panel gasket for IP65
Suffix codes Description
oCo o oDo
N None A PV retrans. output 4 to 20 mA
F Temperature Controller
N None
R
S RS485 Modbus N None
Alarm output:2 Points (OT3 relay + OT4 SSR drive)
Always "D"
Electromagnetic compatibility and safety requirements
Compliance: directive EMC 2004/108/CE (EN 61326-1), directive LV 2006/95/CE (EN 61010-1), UL 61010-1 CSA 61010-1;
Note: During the test, the instrument continues to operate at
the measurement accuracy within specifi cation.
Installation category: II;
Pollution category: 2;
Temperature drift: It is part of the global accuracy;
Operating temperature: 0 to 50°C (32 to 122°F);
Storage temperature: -20 to +70°C (-4 to +158°F);
Humidity: 20 to 95% RH, not condensing.
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 4
5. CONFIGURATION PROCEDURE
SP
HYS
PV
(A) (B) (C) (A) (B)(D)
EXCEEDED
LAMP
OUT
LAMP
lit
off
OUTPUT
RELAY
confirmation
(accepted)
confirmation
(not accepted)
lit
off
Energized
De-energized
OFF
OFFOFF
Lit
OFF
Lit
OFF
ON
OFF
Lit
OFF
Power
ON
OFF
SP
HYS
PV
(A) (B) (D)(C)
EXCEEDED
LAMP
OUT
LAMP
lit
off
OUTPUT
RELAY
confirmation
(accepted)
lit
off
Energized
De-energized
OFF
OFF
OFF
Lit
ON
OFF
Lit
OFF
Power
ON
OFF
OFF
ON
OFF
5.1 INTRODUCTION
When the instrument is powered, it starts immediately to work according to the parameters values loaded in its memory.
The instrument behaviour and its performance are governed by the value of the stored parameters.
At the fi rst start up the instrument will use a “default” param­eter set (factory parameter set); this set is a generic one (e.g. a TC J input is programmed).
WARNING! Before connecting the output actuators, we
recommend to confi gure the parameters to suit your application (e.g.: input type, Control strategy, alarms, etc.).
To change these parameters you need to enter the “Confi gu­ration mode”.
5.2 INSTRUMENT BEHAVIOUR AT POWER ON
At power ON the instrument can operate in two different mode according to the value assigned to [34] r.md param­eter [34] r.md equal to 0
(Limit output is de-energized at power on in any cases.)
The output relay is always de-energized (opened) at power­on,even if PV does not exceed SP(A). The output (OUT) display lamp is lit. If thePV does not exceed SP, after the confi rming operation, output relay will be energized (closed) and the output (OUT) display lamp turns off .
5.3 HOW TO ENTER THE “CONFIGURATION MODES”
The confi guration procedure allows to take advantage of all instrument features.
The instrument have one complete parameter set.
We call this set “confi guration parameter set” (or “confi guration parameters”).
The access to the confi guration parameters is password.
5.3.1 Complete confi guration procedure
The confi guration parameters are collected in various groups. Every group defi nes all parameters related with a specifi c function (e.g.: control, alarms, output functions).
1. Push the button for more than 3 seconds. The upper
display will show PASS while the lower display will show 0.
2. Using and buttons set the programmed password.
Notes: 1. The factory default password for confi guration
parameters is equal to 30.
3. Push the button
If the password is correct the display will show the acronym
protected by a
[34] r.md equal to 1(Limit output is de-energized at power on in any cases.)The state of output relay is energized (closed) and the output (OUT) display lamp turns off if the PV does not exceed SP at power-on.
of the fi rst parameter group preceded by the symbol:
In other words the upper display will show:
]inp
]
.
(group of the Input parameters).
The instrument is in confi guration mode.
5.4 HOW TO EXIT THE “CONFIGURATION MODE”
Push button for more than 3 seconds, the instrument will come back to the “standard display”.
5.5 KEYBOARD FUNCTIONS DURING PARAMETER CHANGING
A short press allows to exit from the current parameter
group and select a new parameter group.
A long press allows you to close the confi guration
parameter procedure (the instrument will come back to the “standard display”).
When the upper display is showing a group and the
lower display is blank, this key allows to enter in the selected group.
When the upper display is showing a parameter and
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 5
the lower display is showing its value, this key allows to store the selected value for the current parameter and access the next parameter within the same group.
Allows to increase the value of the selected parameter. Allows to decrease the value of the selected parameter.
+ These two keys allow to return to the previous
group. Proceed as follows:
Push the button and maintaining the pressure,
then push the button; release both the buttons.
Note: The group selection is cyclic as well as the selection
of the parameters in a group.
5.6 FACTORY RESET - DEFAULT PARAMETERS LOADING PROCEDURE
Sometime, e.g. when you re-confi gure an instrument previously used for other works or from other people or when you have made too many errors during confi guration and you decided to re-confi gure the instrument, it is possible to restore the factory confi guration.
This action allows to put the instrument in a defi ned condition (the same it was at the fi rst power ON).
The default data are those typical values loaded in the instrument prior to ship it from factory.
To load the factory default parameter set, proceed as follows:
1. Press the
display will show PASS while the lower display shows 0;
2. Using
3. Push
4. The instrument will turn OFF all LEDs for a few seconds,
then the upper display will show dFLt (default) and then all LEDs are turned ON for 2 seconds. At this point the instrument restarts as for a new power ON.
The procedure is complete.
Note: The complete list of the default parameters is available
in Appendix A.
button for more than 5 seconds. The upper
and buttons set the value -481;
button;
5.7 CONFIGURING ALL THE PARAMETERS
In the following pages we will describe all the parameters of the instrument. However, the instrument will only show the parameters applicable to its hardware options in accordance with the specifi c instrument confi guration (i.e. setting AL1t [Alarm 1 type] to nonE [not used], all parameters related to alarm 1 will be skipped).
]inP Group - Main and auxiliary input confi guration
[1] SEnS - Input type
Available: Always. Range: • When the code of the input type is equal to c
(see paragraph “How to order”).
J TC J (-50... +1000°C/-58... +1832°F); crAL TC K (-50... +1370°C/-58... +2498°F); S TC S (-50... 1760°C/-58... +3200°F); r TC R (-50... +1760°C/-58... +3200°F); t TC T (-70... +400°C/-94... +752°F); n TC N (-50...1300°C/-58...2372°F); Pt1 RTD Pt 100 (-200... 850°C/-328... 1562°F); Pt10 RTD Pt 1000 (-200... 850°C/-328... 1562°F);
0.60 0... 60 mV linear;
12.60 12... 60 mV linear;
0.20 0... 20 mA linear;
4.20 4... 20 mA linear;
0.5 0... 5 V linear;
1.5 1... 5 V linear;
0.10 0... 10 V linear;
2.10 2... 10 V linear.
Notes: 1. When a TC input is selected and a decimal fi gure
is programmed (see the next parameter) the max. displayed value becomes 999.9°C or 999.9°F.
2. Every change of the SEnS parameter will produces a change of the related parameter and in particular:
• [7] bS (PV bias) will be forced to zero
• [11] Ao1L and [12] Ao1H (when the analog retransmission is present) will be forced to the Ex.Range limits.
• [13] AL1 and [30] AL2 will be forced to :
– for an absolute maximum alarm, them will be
forced to the maximum input span
– for an absolute minimum alarm, them will be
forced to the minimum input span
– for all other alarm, them will be forced to zero
• [14] HAL1 and [31] HAL2 will be forced equal to the 0.5% of the input span
• [28] AL2L extended limit low
• [29] AL2H extended limit high
• [35] HYS will be forced equal to 0.05 % of the input span
• [37] SPLL and [38] SPHL
• [39] SP
• the CAL group will be reset [51]A.L.P, [52] A.L.O, [53] A.H.P, [54] A.H.O
[2] dP - Decimal point position
Available: Alw Range: 0 to 3 when [1] SenS = Linear input;
0 or 1 when [1] SenS different from linear input.
Note: Every change of the dP parameter setting will produce
a change of the parameters related with it (e.g.: set points, proportional band, etc.).
ays.
[3] SSc - Initial scale read-out for linear inputs
Available: When a linear input is selected b Range: -1999 to 9999.
Notes: 1. SSc allows the scaling of the analog input to set
the minimum displayed/measured value. The instrument will show a measured value up to 5% less than SSc value and then it will show an underrange error.
2. It is possible to set a initial scale read-out higher than the full scale read-out in order to obtain a reverse read-out scaling.
E.g.:
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).
y [1] SenS.
[4] FSc - Full scale read-out for linear input
Available: When a linear input is selected by [1] SenS. Range: -1999 to 9999.
Notes: 1. Fsc allows the scaling of the analog input to set
the maximum displayed/measured value. The instrument will show a measured value up to 5% higher than [4] FSc value and then it will show
Yokogawa Electric Corporation - TC10-L - ENGINEERING MANUAL - PAG. 6
Loading...
+ 14 hidden pages