TC10
Temperature Controller
■ General
The TC10 is a compact single loop temperature
controller with easy-to-read 3 dynamic colors led
display. The short depth of the controller helps save
instrument panel space. The TC10 supports easy
configuration with codes for quick start-up.
■ Features
3 Dynamic Colors Led Display
Compact size: 48 x 48 mm (1/16 DIN), depth 48 mm
+ 14 mm (terminals)
Universal Input: (TC, mV, V, mA, Pt100-Pt1000)
3 configurable alarms as absolute, deviation and
band
4 selectable Set Point
Serial Communication (optional): RS-485 Modbus
PID control with single or double action with
overshoot control, ON/OFF, ON/OFF Neutral Zone,
Auto-tuning, Self-tuning
Standby mode of display (selectable)
User calibration for sensor position compensation
■ Functional Specifications
Control Specifications
Control Mode: On/Off heating, On/Off cooling, On/Off
with neutral zone (H/C), PID heating, PID cooling, PID
double action (H/C)
Auto-tuning and Self-tuning algorithms, Overshoot
control
Alarm Functions
Absolute high/low, Absolute inside/outside the band,
Sensor break, Deviation high/low, Deviation inside/
outside the band.
They are combined with Not active at power up,
Latched, Acknowledgeable, and Not active at set point
change for Deviation alarm.
Digital Input Functions
Alarm reset, Alarm acknowledge, Hold of the measured
value, Stand-by mode, Manual mode, Heat with SP1
and Cool with SP2, Sequential set point selection,
SP1/SP2 selection, Binary selection of the set point,
Work in parallel with Up/down key.
Communication Function
Interface type: Isolated (50 V) RS-485
Protocol: Modbus RTU
Baud rate: 1200, 2400, 9600, 19200, 38400 bps
Byte format: 8bit with no parity, one stop bit.
Instrument address: 1 to 254
■ Hardware Specifications
Display Specifications
Main display: 4 digit height 15.5 mm, 3 color red, green
and amber
Secondary display: 4 digit height 7 mm, green color
Display updating time: 500 ms
Universal Input Specifications
TC J -50 to +1000°C -58 to +1832°F
TC K -50 to +1370°C -58 to +2498°F
(*)
TC R -50 to +1760°C -58 to +3200°F
TC T -70 to +400°C -94 to +752°F
Pt1000 -200 to +850°C -328 to +1562°F
Linear 0 to 60 mV
Linear 0 to 20 mA (this selection forces Out 4 = TX)
Linear 4 to 20 mA (this selection forces Out 4 = TX)
Linear 1 to 5 V
Linear 0 to 10 V
Sampling time: 130 ms
Resolution: 30000 counts
Total Accuracy: ±0.5% of F.S. ±1 digit
*: ±1.0% of F.S. ±1 digit
Resistance-temperature detector (RTD) measured
current; Pt100: 150 μA, Pt1000: 15.5 μA
Response time: 2 second or less, 63% (10 - 90%)
(The time required for t r ans mi s sion o utput to reach 63%
of the maximum excursion when PV abruptly changes
from 10% to 90%)
GS 05C01E81-
6th Edition May. 201
All Rights Reserved. Copyright © 2014, Y okogawa Electric Corporation
Output Specifications
OUT 1: Relay SPST - NO 4A/250 Vac or voltage to
drive SSR 13V max. @1mA
Analog output: 0/4 to 20 mA, galvanically
isolated, RL max. 600Ω ±0.2% of F.S. or 0/2 to
10 V, galvanically isolated, RL min.: 500Ω ±
0.3% F.S.
OUT 2: Relay SPST -NO 2A/250 Vac or voltage to drive
SSR 13V max. @1mA, 10.5 min @15mA ±10%
OUT 3: Relay SPST -NO 2A/250 Vac or voltage to drive
SSR 13V max. @1mA, 10.5 min @15mA ±10%
OUT 4: programmable: voltage output to drive SSR 13V
max. @1mA, 10.5 min. @15mA ±10%, 12 VDC
(20 mA) transmitter power supply or 2nd digital
input
Note: Either control output or retransmission output can
be used for analog output.
Regulatory Compliance
CE marking, UL(USA/CANADA)
EMC Directive:
EN 61326-1 Class A, Table 2 (For use in industrial
locations)
EN 55011 Class A, Group 1
(During the test, the instrument continues to operate
at the measurement accuracy within specification.)
LV Directive:
EN 61010-1, EN 61010-2-030
UL 61010-1 CSA 61010-1
Installation category: II
Pollution category: 2
RoHS Directive:
EN 50581
Power Supply Specification and Isolation Voltage
24 VAC/DC (±10% of the nominal value)
100 to 240 VAC (-15 to +10% of the nominal value)
Power consumption: 4.5 VA max. (24 VAC/DC)
6.0 VA max. (100 to 240 VAC)
Isolation Voltage
3000 V AC for 1 minute between primary and
secondary terminals
(Primary terminals = Power
(*)
and relay output
terminals, Secondary terminals = Analog I/O signal
terminals, contact input terminals, and
communication terminals.)
*: Power terminals for 24 V AC/DC models are the
secondary terminals.
Environmental Conditions
Normal Operating Conditions
Operating temperature: 0 to 50°C (32 to 122°F)
Humidity: 20 to 90% RH, not condensing
Temperature Effects
Analog input: It is part of the global accuracy
Reference junction compensation: ±0.1°C/°C or less
Analog output: ±0.05% of F.S./°C or less
Storage temperature
Storage temperature: -20 to +70°C (-4 to +158°F)
Humidity: 20 to 95% RH, not condensing