YOKOGAWA SE14 User Manual

Page 1
User's Manual
Model SE14 Magnetic Flow Converter
IM 1E10C1-E
YokogawaElectric Corpo ration
IM 1E10C1-E
7th Edition
Page 2

CONTENTS

Contents
1. INTRODUCTION ..............................................................................................1-1
2. HANDLING PRECAUTIONS .......................................................................... 2-1
2.1 Checking Model and Specifications ............................................................... 2-1
2.2 Accessories ...................................................................................................... 2-1
2.3 Storage Precautions ......................................................................................... 2-1
2.4 Installation Location Precautions.................................................................... 2-1
2.5 Cleaning Precautions....................................................................................... 2-1
3. INSTALLATION................................................................................................3-1
3.1 Installing Magnetic Flow Converter ............................................................... 3-1
3.2 Wiring Precautions .......................................................................................... 3-1
3.2.1 Protective Grounding............................................................................... 3-1
3.2.2 General Precautions ................................................................................. 3-2
3.2.3 Cable T ypes.............................................................................................. 3-2
3.2.4 DC Connections....................................................................................... 3-3
3.2.5 Wiring Ports............................................................................................. 3-3
3.2.6 Connecting to External Instruments ........................................................ 3-4
4. BASIC OPERATING PROCEDURES............................................................ 4-1
4.1 Liquid Crystal Display (LCD) ........................................................................ 4-1
4.2 Types of Display Data .................................................................................... 4-2
4.2.1 The Initial Procedure to Change the Display Mode ................................ 4-3
4.2.2 Flow Rate Display Mode ......................................................................... 4-5
4.2.3 Setting Mode............................................................................................ 4-6
4.2.4 Alarm Display Mode ............................................................................... 4-7
4.2.5 Auto Zero Mode ...................................................................................... 4-8
4.2.6 Indicator Error Mode ............................................................................... 4-8
5. FUNCTION AND DATA SETTINGS ............................................................. 5-1
5.1 Setting Nominal Size ...................................................................................... 5-2
5.2 Setting Flow Span ........................................................................................... 5-3
5.3 Setting Meter Factor ....................................................................................... 5-6
5.4 Power Frequency (For DC version only) ....................................................... 5-7
5.5 Other Functions and Settings .......................................................................... 5-7
5.5.1 Pulse Output............................................................................................. 5-7
5.5.2 Display of Internal Totalization Values.................................................... 5-9
5.5.3 Resetting for Totalization Display ......................................................... 5-10
5.5.4 Damping Time Constant ........................................................................ 5-11
5.5.5 Current Output during Alarm Occurrence ............................................. 5-11
5.5.6 Reversing Flow Direction ...................................................................... 5-11
5.5.7 Limiting Current Output ........................................................................ 5-12
5.5.8 Forward and Reverse Flow Measurement ............................................. 5-13
5.5.9 Automatic Two Range Switching .......................................................... 5-14
5.5.10 Alarm Output at Low Flow Limit (Flow Switch) .................................. 5-15
5.5.11 Totalization Switch Output .................................................................... 5-16
5.5.12 Alarm Output ......................................................................................... 5-17
FD No. IM 1E10C1-E 7th Edition: Jan. 2002 (YK) All Rights Reserved. Copyright © 1998, Yokogawa Electric Corporation
i
IM 1E10C1-E
Page 3
CONTENTS
5.5.13 Data Settings Enable / Inhibit ................................................................ 5-17
5.5.14 Procedure of Selecting Special Application Items................................. 5-18
5.5.15 Rate Limit .............................................................................................. 5-18
6. OPERATION VIA BRAIN TERMINAL (BT200) ......................................... 6-1
6.1 BT200 Connections......................................................................................... 6-1
6.2 BT200 Keypad Layout.................................................................................... 6-2
6.3 BT200 Key Functions ..................................................................................... 6-3
6.4 Displaying Flow Rate Data............................................................................. 6-4
6.5 Setting Parameters........................................................................................... 6-5
6.5.1 Setting Nominal Size ............................................................................... 6-5
6.5.2 Setting Flow Span.................................................................................... 6-7
6.5.3 Setting Meter Factor .............................................................................. 6-10
6.5.4 Power Frequency (For DC version only) ............................................... 6-11
6.6 Other Functions ............................................................................................. 6-11
6.6.1 User-Defined Units ................................................................................ 6-11
6.7 Other Important Points.................................................................................. 6-12
7. OPERATION VIA HART COMMUNICATOR ............................................7-1
7.1 Conditions of Communication Line ............................................................... 7-1
7.1.1 Interconnection between ADMAG SE and HART Communicator ......... 7-1
7.1.2 Communication Line Requirements ........................................................ 7-2
7.2 Basic Operation of the HART Communicator (Model 275) .......................... 7-3
7.2.1 Keys and Functions.................................................................................. 7-3
7.2.2 Display ..................................................................................................... 7-4
7.2.3 Calling Up Menu Addresses .................................................................... 7-4
7.2.4 Entering, Setting and Sending Data......................................................... 7-6
7.3 Parameters ....................................................................................................... 7-8
7.3.1 Parameters Configuration ........................................................................ 7-8
7.3.2 Data Renewing......................................................................................... 7-8
7.3.3 Menu Tree................................................................................................ 7-9
7.3.4 Setting Parameters ................................................................................. 7-12
8. ACTUAL OPERATION .................................................................................... 8-1
8.1 Pre-Operation Zero Adjustment...................................................................... 8-1
8.1.1 Zero Adjustment Using Data Setting Keys .............................................. 8-1
8.1.2 Zero Adjustment Using BT200................................................................ 8-2
8.1.3 Zero Adjustment Using HART Communicator ....................................... 8-3
8.2 Self-diagnostics Functions .............................................................................. 8-4
8.2.1 Output Status during Alarm Occurrence.................................................. 8-4
8.2.2 Self-diagnostics Using HART Communicator ........................................ 8-5
8.2.3 Error Description and Countermeasure ................................................... 8-6
9. MAINTENANCE................................................................................................ 9-1
9.1 Loop Test (Test output) .................................................................................. 9-1
9.1.1 Settings for Test Output Using Data Setting Keys................................... 9-1
9.1.2 Setting for Test Output Using BT200 ...................................................... 9-2
9.1.3 Setting for Test Output Using HART Communicator ............................. 9-3
9.2 Trouble Shooting............................................................................................. 9-5
9.2.1 No Indication ........................................................................................... 9-5
9.2.2 Unstable Zero........................................................................................... 9-6
ii
IM 1E10C1-E
Page 4
CONTENTS
9.2.3 Disagreement of Indication with Actual Flow Rate................................. 9-7
10. OUTLINE.......................................................................................................... 10-1
11. PARAMETER LIST ........................................................................................11-1
11.1 Parameters for ADMAG SE Indicator and BRAIN Terminal ..................... 11-1
11.2 Parameters for HART Communicator .......................................................... 11-7
12. EXPLOSION PROTECTED TYPE INSTRUMENT .................................. 12-1
12.1 CENELEC ATEX(KEMA)........................................................................... 12-1
12.2 FM ................................................................................................................. 12-2
12.2.1 FM Explosionproof (Optional Code /FF1) .............................................. 12-2
12.2.2 FM Nonincendive (Optional Code /FN1)................................................ 12-2
12.3 CSA ............................................................................................................... 12-3
12.4 SAA ............................................................................................................... 12-4
iii
IM 1E10C1-E
Page 5
1. INTRODUCTION

1. INTRODUCTION

This instrument has been already adjusted at the factory before shipment.
To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
Regarding This Manual
• This manual should be passed on to the end user.
• Before use, read this manual thoroughly to compre­hend its contents.
• The contents of this manual may be changed without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this material, including, but not limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual. However, if any errors are found, please inform Yokogawa.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsi­bility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
Safety Precautions
• The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. YOKOGAWA Electric Corpora­tion assumes no liability for the customer’s failure to comply with these requirements. If this instrument is used in a manner not specified in this manual, the protection provided by this instrument may be impaired.
The following safety symbol marks are used in this manual and instrument;
WARNING
A WARNING sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in injury or death of personnel.
CAUTION
A CAUTION sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of part or all of the product.
IMPORTANT
A IMPORTANT sign denotes an attention to avoid leading to damage to instrument or system failure.
NOTE
A NOTE sign denotes a information for essential understanding of the operation and features.
Protective grounding terminal. Function grounding terminal. This terminal
should not be used as a “Protective grounding terminal”.
Alternating current. Direct current.
1-1
IM 1E10C1-E
Page 6
1. INTRODUCTION
Warranty
• The guaranteed term of this instrument is described in the quotation. We repair the damages that occurred during the guaranteed term for free.
• Please contact with our sales office when this instrument is damaged.
• If the instrument has trouble, please inform us model code, serial number, and concrete substances or situations. It is preferable to be attached a outline or data.
• We decide after the examination if free repair is available or not.
• Please consent to the followings for causes of damages that are not available as free repair, even if it occured during the guaranteed term.
A:Unsuitable or insufficient maintenance by the
customer.
B: The handling, using, or storage that ignore the
design and specifications of the instrument.
C: Unsuitable location that ignore the description in
this manual.
D:Remaking or repair by a person except whom we
entrust.
E: Unsuitable removing after delivered. F: A natural disaster (ex. a fire, earthquake, storm and
flood, thunderbolt) and external causes.
For Safety Using
For safety using the instrument, please give attention mentioned below.
WARNING
(1) Installation
• The instrument must be installed by expert engineer or skilled personnel. The procedures described about INSTALLATION are not permitted for operators.
• The Magnetic Flow Tube is a heavy instrument. Please give attention to prevent that persons are injured by carrying or installing. It is prefer­able for carrying the instrument to use a cart and be done by two or more persons.
• In case of high process temperature, care should be taken not to burn yourself because the surface of body and case reach a high temperature.
• When removing the instrument from hazardous processes, avoid contact with the fluid and the interior of the flow tube.
• All installation shall comply with local install­ation requirement and local electrical code.
(2) Wiring
• The instrument must be installed by expert engineer or skilled personnel. The procedures described about WIRING are not permitted for operators.
•Please confirm voltages between the power supply and the instrument before connecting the power cables. And also, please confirm that the cables are not powered before con­necting.
• The protective grounding must be connected to the terminal in order to avoid personal shock
hazard.
(3) Operation
• Wait 10 min. after power is turned off, before opening the covers.
(4) Maintenance
• Please do not carry out except being written to a maintenance descriptions. When these procedures are needed, please contact to nearest YOKOGAWA office.
• Care should be taken to prevent the build up of drift, dust or other material on the display glass and data plate. In case of its maintenance, soft and dry cloth is used.
(5) Explosion Protected Type Instrument
• For explosion proof type instrument, the de­scription in Chapter 12 “EXPLOSION PRO­TECTED TYPE INSTRUMENT” is prior to the other description in this user's manual.
• Only trained persons use this instrument in the industiral location.
• The protective grounding must be connected to a suitable IS grounding system.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous locations.
1-2
IM 1E10C1-E
Page 7
2. HANDLING PRECAUTIONS

2. HANDLING PRECAUTIONS

This instrument has been already tested thoroughly at the factory. When the instrument is delivered, please check externals and make sure that no damage occurred during transportation.
In this chapter, handling precautions are described. Please read this chapter thoroughly at first. And please refer to the relative matter about other ones.
If you have any problems or questions, please make contact with Yokogawa sales office.

2.1 Checking Model and Specifications

The model and specifications are shown on the Data Plate. Please confirm the specifications between the instrument that was delivered and the purchase order (refer to the chapter 10. Outline).
Please let us know Model and Serial No. when making contact with Yokogawa sales office.
MAGNETIC FLOW CONVERTER
MODEL SUFFIX
STYLE SUPPLY
CURRENT OUTPUT PULSE OUTPUT AMB.TEMP. ENCLOSURE TAG NO. NO.
Figure 2.1 Data Plate
VAC~47 to 63Hz 11Wmax.
4 - 20mA (600max.)
30V DC 0.2Amax. –20 to +60 °C IP67
N200
VDC 11Wmax.
Made in Japan

2.2 Accessories

When the instrument is delivered, please make sure that the following accessories are in the package.
• Data sheet (1-sheet)
•Mounting hardware
• Hexagonal wrench 1-piece (for special screw of
converter)
• Unit labels
• Plug 1-piece (only for DC power supply version)

2.3 Storage Precautions

In case the instrument is expected to be stored over a long term, please give attention to the followings;
• The instrument should be stored in its original packing condition.
• The storage location should be selected according to the following conditions:
1) The location where it is not exposed to rain or
water.
2) The location where there is few vibration or
shock.
3) Temperature and humidity should be:
Temperature: –20 to 60˚C (–4 to 140˚F) Humidity: 5 to 80% RH (no condensation) Preferable ambient temperature and humidity are 25˚C(77˚F) and about 65% RH.
2.4 Installation Location
Precautions
Please select the installation location considering the following items to ensure long term stable operation of the flowmeter.
• Ambient Temperature: Please avoid to install the instrument at the location where temperature changes continuously. If the location receives radiant heat from the plant, provide heat insulation or improve ventilation.
•Atmospheric Condition: Please avoid to install the instrument in an corrosive atmosphere. In case of installing in the corrosive atmosphere, please keep ventilating sufficiently and prevent rain from entering the conduit.
•Vibration or shock: Please avoid to install the instrument at the location where there is heavy vibration or shock.

2.5 Cleaning Precautions

Care should be taken to prevent the buildup of dirt, dust or other material on the display glass. Such buildup may interfere with the operation of programming keys.
2-1
IM 1E10C1-E
Page 8
3. INSTALLATION

3. INSTALLATION

WARNING
This instrument must be installed by expert engineer or skilled personnel. The procedures described in this chapter are not permitted for operators.

3.1 Installing Magnetic Flow Converter

A signal cable (AM011) is used between the remote type flow tube and the converter. The maximum signal cable length is 300m (984ft). The converter is mounted on a 2-inch (60.5mm outer dia.) vertical or horizontal pipe. See Figure 3.1.1
Vertical Mounting
2-inch pipe
U-Bolt
Bracket
Nut
CAUTION
Confirm that all connections are corrected before applying power to the instrument. Improper wiring may damage the flow tube or converter.
NOTE
The terminal box cover is locked by special screw. In case of opening the terminal box cover, please use the Hexagonal Wrench attached.
CAUTION
Be sure to lock the cover with the special screw using the Hexagonal Wrench attached after tightening the terminal box cover.
The external signal wirings are connected into the terminal inside the converter. Please connect to each terminal (Please refer to Figure 3.2.1) by taking off a cover backside the converter.
Excitation Cable
Dedicated Cable AM011-4
Converter SE14
Power supply Protective ground 4 to 20 mA DC output Pulse or alarm output
Horizontal pipe Mounting
Nut
Bracket
2-inch pipe
U-Bolt
Figure 3.1.1 Magnetic Flow Converter Installation
F030101.EPS

3.2 Wiring Precautions

This section is described wiring only for converter side. Please see "Wiring" in SE***DJ/EJ Magnetic Flow Tube User's Manual for flow tube side.
A B C
Figure 3.2.1 Wiring
Flow Tube
EX2 EX1
Converter Terminals
SA
A B
SB
C Ex1 Ex2
NOTE : Terminate those shielding wire terminals using tape.
Flow Tube SE***DJ/EJ
(See NOTE below)
(See NOTE below)

3.2.1 Protective Grounding

CAUTION
Please be sure to connect protective grounding of ADMAG SE with cable of 2mm2 or larger cross section in order to avoid the electrical shock to the operators and maintenance engi­neers and prevent the influence of external noise. And further connect the grounding wire to the mark (100 or less).
3-1
A B
C Ex1 Ex2
IM 1E10C1-E
F030201.EPS
Page 9
3. INSTALLATION

3.2.2 General Precautions

Please give attention to the followings in wiring.
CAUTION
• Please pay attention to avoid the cable is bended excessively.
• Please do not connect cables outdoors in case of rain to prevent damages from dew formation and to keep insulation inside the terminal box of the flowmeter.
• The all cable ends are to be provided with round crimp-on terminal.
• The power cables and output signal cables must be routed in separate steel conduit tubes or flexible tubes.(except 4-core 24VDC cable wiring.)
• When waterproof glands or union equipped waterproof glands are used, the glands must be properly tightened to keep the box watertight.
•Please install a external switch or circuit breaker as a means of power off (capacitance; 15A, conform to IEC947-1 and IEC947-3). The preferable location is either near the instrument or other places to easy operation. Further­more, please indicate "power off equipment" on the those external switch or circuit breaker.
• Please be sure to fully tighten the terminal box cover before the power is turned on. After tightening the covers, please be sure to fix it with the special screw using a hexagonal wrench attached.
• Please be sure to turn off the power before opening the terminal box cover.
• In case of DC power supply, a plug is attached. When 4-core cable is used, please put that plug into unused electrical connection port.

3.2.3 Cable Types

IMPORTANT
If the cable is longer than required, cut off any extra length, rather coiling it up, and terminate the conductors as shown in Figure 3.2.3. Avoid using intermediate terminal boards to extend the cable length, or this will interrupt the shielding.
Unit : mm (inch)
ACB
SA
(WHITE)
On the converter side
Figure 3.2.3 Treatment of Dedicated Signal Cable
25 (0.98)
(BLACK)
150
8 (0.3) Max.
(5.9)
20 (0.8)
SB
50 (1.97)
(RED)
L (SPECIFIED LENGTH)
70 (2.76)
80 (3.15)
AM011*A
ACB
90 (3.5)
(WHITE)
8 (0.3) Max.
150
(5.9)
ø10.5 (0.4)
(BLACK)
On the flow
tube side
F030203.EPS
CAUTION
Since A, B, SA, SB, and C all operate at differ­ent electrical potentials, securely insulate them from each other so they do not touch. The shields must not be allowed to touch each other or to touch the case. Cover each shield with vinyl tube or wrap in vinyl tape.
55 (2.2)
90 (3.5)
(RED)
(1) Dedicated Signal Cable(AM011)
The flow signal is transmitted via this dedicated cable. The cable is constructed with double shielding over the two conductors, and used heat-resistant vinyl as the outer jacket material.
Finished diameter: 10.5 mm (0.413 in.) Maximum length: 30 m (98 ft) Maximum temperature: 80°C (176°F)
Conductors
Shields
Tape
Outer jacket
Shield
Insulation
Insulation
Figure 3.2.2 Dedicated Signal Cable AM011
10.5mm
(0.413in.)
F030202.EPS
NOTE
Conductors A and B carry the signal from the electrodes, and C is at the potentials of the liquid it self (signal common) . Shields SA and SB are kept at the same potentials as the individual electrodes (these are actively driven shields). This is done to reduce the effect of the distrib­uted capacitance of the cable at long cable length. Note that, since the signals from the individual electrodes are impedance converted inside the converter, errors will result if they come in contact with any other component. Great care must be taken in the cable end treatment.
3-2
IM 1E10C1-E
Page 10
3. INSTALLATION
(2) Power, Excitation, or Output Cable Power Cable
• Crimp-on Terminal
• Green/Yellow covered conductors shall be used only for connection to PROTECTIVE CONDUCTOR TERMINALS.
• Conform to IEC277 or IEC245 or equivalent national authorization.
Excitation or Output Cable
• Please use Polyvinyl chloride insulated and sheathed control cables (JIS C3401) or Polyvinyl chloride insulated and sheathed portable power cables (JIS C3312) or equivalents.
Outer Diameter
•6.5 to 12mm in diameter (10.5 to 11.5 mm for waterproof gland / ECG, /ECU)
Nominal Cross Section
• Single wire; 0.5 to 2.5mm2 , Stranded wire; 0.5 to
2
2.5mm
EX1
EX2
60
(2.4)
85
(3.3)
Unit: mm (inch)
EX1
EX2
1000
(3300)
900
(2970)
800
(2640)
700
(2310)
Allowed
600
cable
(1980)
length
500
m(ft)
(1650)
400
(1320)
300
(990)
200
(660)
100
(330)
0
Cable cross section area : 1.25mm
Supply Voltage and Cable Length
20
22
24
Usable range E(V)
2
26
28
Cable cross section area : 2mm
F030205.EPS
Figure 3.2.5 Supplied Power and Cable Length
(2)Setting Power Supply Frequency
IMPORTANT
In case of DC power supply, the frequency of the power supply has to be adjusted. Please adjust for the local power frequency. The power supply frequency is set in parameter B12 (or Power freq for HART). Refer to 5.4, 6.5.4, or
7.3.4 for data setting procedure.
2
On the converter side On the flow tube side
F030204.EPS
Figure 3.2.4 End Treatment of Excitation Cable

3.2.4 DC Connections

(1)Connecting Power Supply
IMPORTANT
In case of 24VDC power supply, AC power supplies or reversed polarities cannot be con­nected. It will cause the fuse to burn out.
IMPORTANT
In case of 24VDC power supply, the specifica­tion for the supply voltage is 24VDC (-15 to +20%), but the input voltage of the converter drops due to cable resistance so it should be used within the following range.

3.2.5 Wiring Ports

Please select the most suitable standard of wiring procedure for the wiring ports by customer’s own.
(1)Using the Waterproof Gland
IMPORTANT
To prevent water or condensate from entering the converter housing, waterproof glands are recommended. Do not over-tighten the glands or damage to the cables may result. Tightness of the gland can be checked by confirming that the cable is held firmly in place.
Gasket
Gasket
Washer
Tightening gland
Water-proof gland(/ECG)
Figure 3.2.6 Waterproof Gland
(2)Conduit Wiring
In case of conduit wiring, please use the waterproof gland to prevent water flowing through the conduit pipe into the wiring connection.
Washer
Tightening gland
G1/2
Water-proof gland with union joint(/ECU)
F030206.EPS
3-3
IM 1E10C1-E
Page 11
3. INSTALLATION
Please slope the conduit pipe down, and install a drain valve at the low end of the vertical pipe.
Please open the drain valve regularly.
Drain valve
F030207.EPS
Figure 3.2.7 Conduit Wiring
3.2.6 Connecting to External Instru-
ments
CAUTION
All the devices to be connected to current output and pulse output must be conformed to CSA1010, CSA950, or IEC950.
(1)Analog Signal Output(4 to 20mADC)
ADMAG SE
ADMAG SE
PULSE OUT
PULSE OUT
PLS/ALM+
+
PLS/ALM–
PLS/ALM+
+
PLS/ALM–
Protective diode
Mechanical counter
30 V DC, 0.2A. max*
*In case of FM Nonincendive type, 0.135A max.
Load
Universal counter or
Electronic counter
F030209.EPS
Figure 3.2.9 Pulse Output Connection
(3)Alarm or Status Output
IMPORTANT
This is a transistor contact(insulated type) so attention must be paid to voltage and polarity when making connections. This output can not switch an AC load. To do this, another relay (see the figure below) is required.
* The alarm output works from "close"(Normal) to
"open"(Alarm).
ADMAG SE
PLS/ALM+
Protective diode
Load
PLS/ALM–
+
ADMAG SE
CUR+
CUR–
+
RECEIVER
Load Resistance max. 600
F030208.EPS
Figure 3.2.8 Connection for Analog Singal Output
(2)Pulse Output
IMPORTANT
Please give attention to voltage and polarity in wiring, because it is transister contact (insula­tion type.)
• In case of the filtering constant of Electric Counter is more than the pulse width, it makes signal decreases and can not be calculated correctly.
• In case of input impedance of electric counter is large inductive noise from power supply bring bad influence to measurement. To calculate correctly, it is recommended to use shield cable or to make input impedance small enough within the limits of pulse output of flowmeter.
This connection cannot be made.
ADMAG SE
PLS/ALM+
PLS/ALM–
External
Power supply
30 V DC, 0.2A. max*
*In case of FM Nonincendive type, 0.135A max.
Figure 3.2.10 Contact Output Connection
Magnetic
valve
AC power supply
F030210.EPS
3-4
IM 1E10C1-E
Page 12

4. BASIC OPERATING PROCEDURES

4. BASIC OPERATING PROCEDURES
All data settings can be performed with the three keys on the front panel (SET,SHIFT, and INC), or using a handheld Brain Terminal (BT) or using a HART communicator. The following sections describe basic data components and how to use the three panel keys. (Please refer to Chapter 6 for the operation via Brain Terminal and Chapter 7 for the operation via HART communicator.)

4.1 Liquid Crystal Display (LCD)

ADMAG SE display panel (if equipped) shows the components as follows.
4:Decimal Point
1:Data Display
3:Unit Display
µMmNkgalbbl scftm3 /d /s /h /m
SET
SHIFT
%
INC
2:Infrared Switches (if equipped)
Figure 4.1 Components of Display
1: Data Display: Displays flow rate data, setting data and type of alarm generated. 2: Infrared Switches: These keys are used to change the display and type of setting data. 3: Unit Display: Displays flow rate units. In order to display other units, the
required unit label should be selected from the provided data sheets.
4: Decimal Point: Displays decimal point.
• Structure of the Display
* The Display consists of six figure and five dots for the decimal point between them. * Two types of data can be entered : direct entry of numerals and entry of desired data
items using codes. Please refer to Chapter 11. Parameter List for information on how to change settings.
NOTE
The infrared switches operates as “ON” status by detecting the infrared ray reflection from a finger put over the switches through the glass plate of the cover. Switches are just below the printed letters SET, SHIFT, or INC on the faceplate and are circled with a white line. When you “touch” the swiches, please note the follwing.
The switches may operate even when you don’t touch the glass plate if your finger comes near just above the glass plate. so please touch the switches sliding in your finger from the lower part of the glass plate. Also be sure not to touch more than one switch at one time by covering your other fingers over the faceplate.
4-1
IM 1E10C1-E
Page 13

4.2 Types of Display Data

The Display Data is divided into 5 types as follows.
4. BASIC OPERATING PROCEDURES
Please refer to section 4.2.2
Flow Rate Display Mode
This mode indicates the instantaneous flow rate and totalization data. Display settings can be set in the Setting Mode and parameter No.“d01” (DISP SELECT) by using infrared switches, Brain Terminal, or HART communicator.
Setting Mode
This mode makes certain about contents of parameter and rewrite data.This mode is called up from Flow Rate Display Mode by touching the SET key for 3 sec. and inputting a password.
Alarm Display Mode
When an alarm occurs in the Flow Rate Display Mode, this mode indicates the alarm code number and normal data alternately.
Please refer to section 4.2.4
Pass-Word Input Mode
Please refer to section 4.2.3
Number Changing Mode
Data Changing Mode
Data confirmation Mode
Auto Zero Mode
This mode is indicated during automatic zero setting.
Indicator Error Mode
This mode is shown in case the keys keep staying “ON” by stains or obstacles on front glass of the case.The error is canceled by cleaning them.
4-2
Please refer to section 4.2.5
Please refer to section 4.2.6
IM 1E10C1-E
Page 14

4.2.1 The Initial Procedure to Change the Display Mode

•The procedure of changing the display from the Flow Rate Display Mode into the Setting Mode by using infrared switches on the converter is described as follows.
(1) Procedure in General
4. BASIC OPERATING PROCEDURES
The Flow Rate
Display Mode
SET key
(for 3 sec.)
The Pass-word
Input Mode
Password Input
(It is always “4321”.)
(2) Procedure in Detail
Switch Operation Display Description
(After power on)
SET SHIFT INC
(for 3 sec.)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
(example)
To go to the Setting Mode, it is needed to go to the Password Input Mode first. Please touch the SET key for 3 sec., and the display goes into the Password Input Mode.
By touching the SET key again, the display goes into the Number Input Mode. Please input the Password as follows, by touching the SHIFT and INC keys.
By touching the INC key for some moment, change “0” into “4”.
By touching the SHIFT key, the cursor moves to the next digit.
The Setting
Mode
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
NOTE
By touching the INC key for some moment again, change “0” into “3”.
By continuing this for the rest of two digits, please change the whole digits into “4321”.
By touching the SET key, whole Display is blinking. And by touching the SET key again, setting the password is completed.
(Setting is now completed)
By touching the SET key again, the display goes to the number changing mode.
In the Password Input Mode, if keys were not operated for more than 20 sec., or if correct password were not set, the display goes back into the Flow Rate Display Mode automatically.
4-3
IM 1E10C1-E
Page 15
4. BASIC OPERATING PROCEDURES
• The procedure of returning from the Setting Mode to the Flow Rate Display Mode by using infrared switch on the converter is described as follows.
Switch Operation Display Description
The number changing mode of the Setting Mode.
SET SHIFT INC
(SHIFT key first)
(1) Functions of
Number
Changing Mode
SET SHIFT INC
(2) Functions of
Number
Changing Mode
(example)
After all settings have been completed, touch the SET key simultaneously while touching the SHIFT key. Then the display goes back to the Flow Rate Display Mode.
• Additional information on the functions of the keys is described here.
SHIFT
key
When the SHIFT key is touched in the Number Changing Mode, it shows as follows.
<< The Cursor Position moves alternately by touching the SHIFT key.
Cursor Position
Cursor Position
key
INC
The INC key in the Number Changing Mode has each working at each cursor position. a) In case the Cursor Position is at upper figure
SET SHIFT INC
The parameter number changes the followings by touching the INC key.
b) In case the Cursor Position is at lower figure
The parameter number changes from small number to big one by touching the INC key. For example; 02, 03,
...
, 37, 02, 03,
...
(in case of parameters with “b”)
4-4
IM 1E10C1-E
Page 16

4.2.2 Flow Rate Display Mode

• Flow Rate Display Mode indicates flow rates and totalization data. ADMAG SE can indicate 12 types as follows.
INDICATOR
DISPLAY ITEM CONTENTS BT200 SETTING
Flow Rate (%)
Flow Rate Actual Flow Rate
Instantaneous flow rate is displayed within a range of -8 (or -108%) to 108% for the span.
The actual meter rate of instataneous flow rate is displayed. (See NOTE) The decimal place is the same as for the span setting. However, since a decimal point set at the least significant bit cannot be displayed.
Parameter
No.
d01
d01
Code
No.
D01: DISP SELECT
00
D01: DISP SELECT
01
4. BASIC OPERATING PROCEDURES
HART
Communicator
RATE(%)
RATE
Disp Select PV % rnge
Disp Select PV
Actual Flow Rate Totalization Values
Reverse Flow Rate Totalization Values
Differential Between the Forward and Reverse Flow Totalization Values
Alternate Display of Flow Rate (%) and Forward Flow Rate Totalization Values
Alternate Display of Actual Flow Rate and Forward Flow Rate Totalization Values
Alternate Display of Actual Flow Rate and Forward Flow Rate(%)
Alternate Display of Flow Rate (%) and Reverse Flow Totalization Values
Alternate Display of Forward Flow Rate and Reverse Flow Totalization Values
Alternate Display of Flow Rate (%) and Differential Flow Totalization Values
Alternate Display of Forward Flow Rate and Differential Flow Totalization Values
Display actual flow rate totalization value
Display reverse flow rate totalization value
Differential totalization between forward totalization and reverse totalization is displayed.
Display alternately between display of “RATE(%)” and “FOR. TTL” every 4 second interval.
Display alternately between display of “RATE” and “FOR. TTL”.
Display alternately between display of “RATE” and “RATE(%)” every 4 second interval.
Display alternately between display of “RATE(%)” and “REV. TTL” every 4 second interval.
Display alternately between display of “RATE” and “REV. TTL” every 4 second interval.
Actual flow rate (%) and differential between forward and reverse totalization values are indicated alternately every 4 sec.
Actual flow rate and forward and reverse totalization values are indicated alternately every 4 sec.
d01
d01
d01
d01
d01
d01
d01
d01
d01
d01
D01: DISP SELECT
02
D01: DISP SELECT
03
D01: DISP SELECT
04
D01: DISP SELECT
05
D01: DISP SELECT
06
D01: DISP SELECT
07
D01: DISP SELECT
08
D01: DISP SELECT
09
D01: DISP SELECT
10
D01: DISP SELECT
11
FOR. TOT AL
REV. TOTAL
DIF. T OTAL
RATE %/FOR TTL
RATE/FOR TTL
RATE/RATE %
RATE %/REV. TTL
RATE/REV . TTL
RATE %/DIF. TTL
RATE/DIF. TTL
Disp Select Totl
Disp Select Rev. totl
Disp Select Diff. totl
Disp Select PV % rnge/Totl
Disp Select PV/Totl
Disp Select PV % rnge/PV
Disp Select PV % rnge/Rev. totl
Disp Select PV/Rev. totl
Disp Select PV % rnge/Diff. totl
Disp Select PV/Diff. totl
NOTE
• The display can set the units by setting parameter No.“b04” and “b05”.
• When special display of flow rate is specified in parameter “D10 flow user unit”, this special display has higher priority in displaying than actual flow rate.
•Those 12 types function can be selected and set by changing into the Setting Mode. (Please refer to 4.2.3 Setting Mode.)
• Those 12 types function can be selected by using infrared switches, Brain Terminal, or HART communicator. (For using BT, please refer to Chapter 6. OPERATION VIA BRAIN TERMINAL(BT 200). For using HART communicator, Chapter 7. OPERA­TION VIA HART Communicator.)
4-5
IM 1E10C1-E
Page 17

4.2.3 Setting Mode

The Setting Mode confirms contents of parameter and rewrite data.
Number
Changing Mode
Cursor position is blinking.
4. BASIC OPERATING PROCEDURES
• Detailed procedures of data setting are explained in “ Chapter 5. Function and Data Settings”.
• Procedure of data setting
* When the display is in the Setting Mode just after power
ON, it always starts from “b02”.
* After that, it starts from the former selected number.
SET SHIFT INC SET SHIFT INC
*Keys for number changing SHIFT: for changing positions (to the right) INC: for changing alphabets or numerals
SET SHIFT INC
Data Changing
Mode
*By touching the SET key the display goes to the Data Changing Mode.
* Two types of data can be entered : direct entry of numerals and entry of desired data
items using codes. Please refer to “Chapter 11. Parameter List” for information on how to change settings.
SET SHIFT INC SET SHIFT INC
* Keys for data changing SHIFT: for changing positions (to the right) INC: for changing numerals or the position of decimal point
*Data types are as follows.
Direct entry of numerals Entry of selected number
5-figure data = A decimal point is sure to show somewhere, The last figure (6th figure)
is always SPACE. 6-figure data(totalized value) = A decimal point doesn't show anywhere and no SPACE. Selection type data = It is always 2-figure(other figures are always SPACE).
SET SHIFT INC
Data Confirmation Mode
SET SHIFT INC
SET SHIFT INC
Whole display is blingking.
Data is completed.
The marks are always shown at the highest figure.
It changes: “+” and “–” (“+” is shown as “ ”.)
*When it is the Data Changing Mode and touch SET key, it
changes into the Check Up Mode, whole of the display begins to blink.
* During the display is blinking, touch the SET key, then the
data is completed.
* Then touch the SET key again and the display goes back to
the Number Changing Mode.
* During the display is blinking and touch other keys except
the SET key, the data setting is canceled and the display goes back to the Number Changing Mode.
4-6
IM 1E10C1-E
Page 18

4.2.4 Alarm Display Mode

• When an alarm occurs, a content of the alarm is shown as an alarm code number. However, this mode is available during the Flow Rate Display Mode. In this mode, alarm number and flow rate are shown alternately.
For example;
• When alarm No. 6 is raised.
• When alarm No.6 and No.8 are raised at the same time.
4. BASIC OPERATING PROCEDURES
<< Flow Rate is indicated for 4 sec.
%
<< Alarm No. is indicated for 2 sec.
<< Flow Rate is indicated for 4 sec.
%
NOTE
<< Alarm No.6 is indicated for 2 sec.
<< Flow Rate is indicated for 4 sec.
%
<< Alarm No.8 is indicated for 2 sec.
For further description of the alarm functions, please refer to “Chapter 8.2 Self­diagnostics Functions”.
4-7
IM 1E10C1-E
Page 19

4.2.5 Auto Zero Mode

•Three ways of the auto zero adjustment can be done by using the infrared switches on the converter, BT Terminal, or HART communicator. Please refer to “8.1 Pre-Operation Zero Adjustment” in detail.
• The display can be changed into the Auto Zero Mode from any mode.
• The Auto Zero Mode is shown as follows (for 20sec.).
• When the Auto Zero Mode is finished, the display goes back into the Flow Rate Display Mode automatically.

4.2.6 Indicator Error Mode

In the event the glass is stained or objects are placed near or on the glass, the switches can be activated due to the infrared deflection. This will cause the "Password Input Mode" to be displayed frequently and make the normal display mode unavailable. The following comments relate to this possible occurrence.
*When the front glass of case is stained, please wipe out the glass by soft and dry
cloth.
*In case that each key keeps touching for more 120 sec. and it is continued, the
Password Input Mode is not available to enter.
*In case all keys are “OFF” for more 3 sec. , this mode is cancelled. *This condition (the above-mentioned) is not an alarm, but the followings are shown
on LCD to indicate this condition. (4 to 20 mA Output , Status Output , Flow Rate Indication Value and Self-check Function work normally.)
*When these errors are raised, the display indicates alternately as follows.
4. BASIC OPERATING PROCEDURES
IMPORTANT
<< Flow Rate is indicated for 4 sec.
%
<< Warning is indicated for 2 sec.
In case of the front cover is loosened, "dSPErr" may occur, so please make sure the cover is always fastened tightly.
4-8
IM 1E10C1-E
Page 20

5. FUNCTION AND DATA SETTINGS

5. FUNCTION AND DATA SETTINGS
A Magnetic flowmeter calculates volume flow rate from a minute voltage that corre­sponds to the flow velocity of a fluid an outputs as a 4 to 20mA signal.
The three parameters must be set to obtain a correct signal.
NOTE
NOTE
Nominal size, flow span and meter factor must be set.
This chapter explaines how to set flow span, other functions and data settings. Please set data correctly.
you cannot set the leftmost digit of display to numeric value
greater than "4". If the leftmost digit of the span must be "4" or more, set the numeric value beginning from the digit second from the left on the display (the fourth digit).
If the leftmost digit of the display is set to "3", the digits to its right can be set to "0" only, regardless of the decimal point position.
Basic Key Operations
How to change the display into the setting mode? How to move the cursor on the display during parameter setting? How to change the display into the data changing mode? How to move the cursor in the data changing mode? How to change the data? Finally, How to input the set data?
Key OperationItem
SET SHIFT SET SHIFT INC SET (Twice)
5-1
IM 1E10C1-E
Page 21
5. FUNCTION AND DATA SETTINGS

5.1 Setting Nominal Size

Switch Operation Display Description
(See 4.2.1 The initial procedure to change the display)
SET SHIFT INC
Change the display into the setting mode through the password input mode. (Please refer to Chapter 4 “BASIC OPERATION PROCEDURES.”)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
By touching the SHIFT and INC key, select the parameter No. “b06”.
Defalt is set as 00 (Size Unit is mm). Below is an example to set it “01” .(Size Unit is inch)
By touching the SET key, change the display into the data changing mode.
By touching the INC key, select code “01” for inch.
By touching the SET key, whole Display is blinking. And by touching the SET key again, the data is completed.
(Setting is now completed)
By touching the SET key again, the display goes back to the number changing mode.
By touching the SHIFT and INC key, select the parameter No. “b07”.
Code
00 01
Size Unit
mm inch
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
Below is an example to change to “2.0”.
(Setting is now completed)
By touching the SET key, change the display into the data changing mode.
By touching the SHIFT key, the cursor moves to the next digit. By touching the INC key, change “1” into “0”.
By touching the SHIFT key, the cursor moves to the next digit.
By touching the INC key, change “0” into “2”.
By touching the SET key twice, the setting is completed.
By touching the SET key again, the display goes back to the number changing mode.
5-2
IM 1E10C1-E
Page 22

5.2 Setting Flow Span

(1) Determing the Flow Span
The flow rate span is the instantaneous flow rate value at which the output current is to be 20mA. Please determine the span under considering the followings.
Please set the maximum flow rate at the most variable flow rate line. If the flow rate of the fluid exceeds the flow rate span value, the flow rate that exceeds this value (20mA or more) is not output and the flowmeter will not display the correct flow rate. (108% or more can't be output)
In a line where the flow rate is comparatively stable, set a value that is 1.5 to 2.0 times larger than the normal flow rate.
Please set a value that will correspond to a flow velocity of 0.3 to 10m/s. Please comfirm the flow velocity by sizing data or parameter No. “b13”. (Parameter No. “b13” indicates corresponding flow velocity to set span)
The basic input value for display is flow span value. It is recommended that the accuracy of the first digit is in a 0.05 to 0.1% in case inputting the flow rate span value. For example, 30m3/h should be set as 30.00m3/h.
In a span setting, the maximum value that can set is “30000” except any relation with decimal position.
5. FUNCTION AND DATA SETTINGS
5-3
IM 1E10C1-E
Page 23
5. FUNCTION AND DATA SETTINGS
(2) Span Settings by Infrared Switches on the Converter (Example: Flow Span 30.0m3/h)
Span Value Setting
Switch Operation Display Description
(See 4.2.1 The initial procedure to change the display)
SET SHIFT INC
Change the display into the setting mode through the password input mode. (Please refer to Chapter 4 “BASIC OPERATION PROCEDURES.”)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
By touching the SHIFT and INC key, select the parameter No. “b03”.
Defalt is set as 1.0000. Below is an example to change it into 0030.0.
By touching the SET key, change the display into the data changing mode.
By touching the INC key, change “1” into “0”.
By touching the SHIFT key, the cursor moves to the decimal point. The decimal point on the cursor can be moved by touching the INC key.
And by touching the SHIFT key, blinking part moves to the right.
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
(Setting is now completed)
By touching the INC key, change “0” into “3”.
By touching the SET key, whole Display is blinking. And by touching the SET key again, the data is completed.
By touching the SET key again, the display goes back to the number changing mode.
5-4
IM 1E10C1-E
Page 24
5. FUNCTION AND DATA SETTINGS
Setting Volume Measurement (m3) and Time Unit (/h)
Switch Operation Display Description
(Select m3)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
Defalt : 12
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
Change the display into the number changing mode through the setting mode.
By touching the SHIFT and INC key, please select the parameter No.“b04”.
And by touching the SET key, change into the data changing mode.
By touching the INC key, set the “01” (equivalent as m
3
)
By touching the SET key, whole display is blinking. And touching the SET key again, the data is completed.
Code
00 01 02 03 04 05 06 07 08 09 10 11 12 13
Volume Unit
3
km
(103X
m3)
3
m
L(liter)
3
cm
(10-2X
m)
M gal
k gal
gal
m gal
k bbl
bbl
m bbl
u bbl
m
ft.
3
SET SHIFT INC
(Select /h)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
Defalt : 03
And by touching the SET key, the data is completed and the display goes back into the number changing mode.
By touching the SHIFT and INC key, select the parameter No. “b05”.
By touching the SET key, change the display into the data changing mode.
By touching the INC key, set the
Time Unit
01” (equivalent as /h)
By touching the SET key, whole display is blinking.
Code
00 01 02 03
/d /h
/m
/s
And touoching the SET key again, the data is completed.
* If keys that except SET key are touched during display is
blinking, input data is not completed and back to former data.
SET SHIFT INC
(Setting is now completed)
By touching the SET key again, the display goes back to the number changing mode.
5-5
IM 1E10C1-E
Page 25
5. FUNCTION AND DATA SETTINGS

5.3 Setting Meter Factor

The meter factor is engraved on the data plate of the combined flow tube.
Switch Operation Display Description
(See 4.2.1 The initial procedure to change the display)
SET SHIFT INC
Change the display into the setting mode through the password input mode. (Please refer to Chapter 4 “BASIC OPERATION PROCEDURES.”)
SET SHIFT INC
SET SHIFT INC
SET SHIFT INCSET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
SET SHIFT INC
By touching the SHIFT and INC key, select the parameter No. “b08”.
Defalt is set as 1.0000. Below is an example to set it “1.1200”.
By touching the SET key, change the display into the data changing mode.
By touching the SHIFT key twice, the cursor moves to the next digit.
By touching the INC key, change “0” into “1”.
By touching the SHIFT key, the cursor moves to the next digit.
By touching the INC key, change “0” into “2”.
SET SHIFT INC
SET SHIFT INC
(Setting is now completed)
By touching the SET key twice, the setting is completed.
By touching the SET key again, the display goes back to the number changing mode.
5-6
IM 1E10C1-E
Page 26
5. FUNCTION AND DATA SETTINGS

5.4 Power Frequency (For DC version only)

IMPORTANT
the frequency differs. The meter is set to 50.00Hz at the factory.
Display Description
Set the value in areas where the frequency differs in “b12”.
Default: 50.00Hz

5.5 Other Functions and Settings

5.5.1 Pulse Output

PLS/ALM+, PLS/ALM–terminals are for common use with pulse, alarm and other status
In case of DC power supply version, setting power frequency is required in areas where
NOTE
(1) Pulse Output Overview
output functions. Therefore, in case this function is used, other functions are not available to use.
• By setting a pulse weight, a scaled pulse is transmitted to external counters or measuring instruments.
Pulse Output Overview
Output Specifications Connecting
Terminals
Pulse Width Output Rate
* Please refer to “3.2.6 Output Connection to External Instruments” for information how to connect external
instruments.
(2) Procedures for Setting Pulse Output
Example setting: 10 liter output per pulse in a flow rate span of  m3/h
ContentItem
Transistor contact output (contact capacity is 30V DC, 200mA) PLS/ALM+, PLS/ALM–
When using these for pulse output, alarm output or status output are not
available as the terminals are used commonly. Selection: DUTY50%, 0.5, 1, 20, 33, 50, 100ms Min. 0.0001p/s, Max. 1000p/s
Display Description
Pulse output can be set in parameter No. “b10” and selected “00” (Pulse output).
Default: 00
ContentCode
00
Pulse output
01
Alarm output
02
Forward / reverse flow measurement
03
Automatic two range switching
04
Alarm output at low flow limit
05
Totalization switch
5-7
IM 1E10C1-E
Page 27
5. FUNCTION AND DATA SETTINGS
■■
Display Description
After setting the number changing mode, the unit of pulse weight is set in parameter No. “F01”.
Default : 06
Volume unit in that for the flow rate span ×10
00
Volume unit in that for the flow rate span ×10
01
Volume unit in that for the flow rate span ×10
02
Volume unit in that for the flow rate span ×1
03
Volume unit in that for the flow rate span ×10
04
Volume unit in that for the flow rate span ×10
05
Number of pulses output per second at 100%
06
output
Volume UnitCode
-9
-6
-3
3 6
When pulses are to be output per some liter with the flow rate span of
m3/h, select “02” since L = 10-3 × m
Set the pulse weight “10” in parameter No. “F02”.
Default : 0
Set the low cut range nearby 0% in parameter No. “F03”.
Default: (3%)
Setting Range: 0 to 100% (of span)
The pulse width can be set in parameter No. “F04”.
Pulse WidthCode
Default: 00
00
50%DUTY (Max. 1000p/s Min. 0.0001p/s)
01
0.5ms (Max. 1000p/s Min. 0.0001p/s)
02
1ms (Max. 500p/s Min. 0.0001p/s)
03
20ms (Max. 25p/s Min. 0.0001p/s)
04
33ms (Max. 15p/s Min. 0.0001p/s)
05
50ms (Max. 10p/s Min. 0.0001p/s)
06
100ms (Max. 5p/s Min. 0.0001p/s)
Normally, these are all required settings. The following settings are made depending on the applications that are used.
3
(Flow rate value after damping)
Default: 01
Default: 00
5-8
The pulse output calculation can be set in parameter No. “n01” by selecting flow rate or flow rate value after damping.
In case the pulse output transistor should be OFF ACTIVE, please change the parameter No. in “n02” to “01”.
IM 1E10C1-E
Page 28

5.5.2 Display of Internal Totalization Values

■■
• By setting a weight per a pulse, flow rate totalized value is shown on the display of the converter.
(1) Setting Totalization Pulse Weight
Example: To output 10 liter per pulse in flow rate span of  m3/h.
Display Description
5. FUNCTION AND DATA SETTINGS
Set the pulse weight unit in parameter No. “E01”.
Defalt : 06
Default : 3%
(Damped flow rate value)
Default : 01
Volume unit in that for the flow rate span ×10
00
Volume unit in that for the flow rate span ×10
01
Volume unit in that for the flow rate span ×10
02
Volume unit in that for the flow rate span ×1
03
Volume unit in that for the flow rate span ×10
04
Volume unit in that for the flow rate span ×10
05
Number of pulses output per second at 100%
06
output
When pulses are to be output per some liter with the flow
Volume UnitCode
rate span of
m3/h, select “02” since L = 10-3 × m
-9
-6
-3
3 6
3
Set the pulse weight “10(l)” in parameter No. “E02”.
Set the low cut range nearby 0% in parameter No. “E03”. Setting Range: 0 to 100% (of span)
The flow rate totalized value calculation can be set in parameter No. “n01” by selecting “NO DAMPING” or “DAMPING”.
5-9
IM 1E10C1-E
Page 29

5.5.3 Resetting for Totalization Display

(1) Presetting for Forward Totalization Display
• E04, E05 are used for reset or preset the totalization values of the display.
Display Description
Default: 00 (disabled)
Default: 0
5. FUNCTION AND DATA SETTINGS
The totalization value presetting enable can be selected at parameter No. “E04”.
ContentCode
00
Totalization preset inhibit
01
Totalization preset enable
The totalization value presetting enable is selected at parameter number “E05”. The initial value is “0”, if it is no setting, the function is zero setting.
SET SHIFT INC
(Twice)
(2) Zero-resetting for Reverse Toralization Display
Display Description
Default: 00 (disabled)
SET SHIFT INC
(Twice)
During the A30 :TOTAL (totalization value of flow rate) is shown, the totalization value display is becoming the value that is set at parameter number “E05”, by touching SET key twice.
The totalization value presetting enable can be selected at parameter No. “E04”.
00 01
During the A31 :REV.TOTAL (totalization value of reverse flow rate) is shown, the totalization value display is becoming zero, by touching SET key twice.
ContentCode
Totalization preset inhibit Totalization preset enable
5-10
IM 1E10C1-E
Page 30

5.5.4 Damping Time Constant

• The time constant can be changed by setting the parameter No. “b02” to suppress a fluctuation or change a response time.
• The time constant influences to flow rate, pulse output and internal totalization. However, in case “00” is selected in parameter No. “n01”, the pulse output and internal totalization are not influenced by it.
Display Description
Default: 3(sec).

5.5.5 Current Output during Alarm Occurrence

• The current output and display values during alarming can be selected in advance.
Display Description
Default: 03
5. FUNCTION AND DATA SETTINGS
The time constant can be set in parameter No. “02”. Setting Range: 0.5 to 200.0 sec.
The current output value during alarming can be set in parameter No. “b11”.
Code
00 01 02 03
Content
2.4mA or less
4.0mA HOLD
21.6mA or more

5.5.6 Reversing Flow Direction

•The flow direction is set to “FORWARD” at the factory. This function enables to set flow direction from “FORWARD” to “REVERSE”.
Display Description
The flow derection can be set in parameter No. “b14”.
Default: 00
Code
00 01
Content
Forward direction Reverse direction to flow arrow
5-11
IM 1E10C1-E
Page 31

5.5.7 Limiting Current Output

(1) 4 to 20mA Low Cut Output (Current output nearby 0% range)
• This function makes it possible to reduce fluctuations in the 0% region to reduce it to 0%.
Display Description
5.6mA(10%)
5. FUNCTION AND DATA SETTINGS
Output
(2) 4 to 20mA Low Limit
(3) 4 to 20mA High Limit
Default : 00
4mA
Setting range: 0 to 10% Default:0(%)
0.5%0.5%
Set value
Hysteresis:1% fixed
• This function limits the low end of the analog output.
• The default value is set at –20%, and –10% as reverse flow limit. Please set in case other setting is required.
• 2.4mA or less output in alarming is also limited.
Display Description
Default : -20(%)
Setting Range: –20 to 100%
Default: –20%
5.6mA(10%)
Output
4mA
• This function limits the high end of the analog output.
• The default value is set at 120%, and please set in case other setting is required.
• 21.6mA or more output in alarming is also limited.
Display Description
Output
18.4mA (90%)
Default : 120(%)
4mA
Setting Range: 0 to 120%
Default: 120%
5-12
IM 1E10C1-E
Page 32

5.5.8 Forward and Reverse Flow Measurement

• This function enables to measure forward and reverse flow rate without change the detector direction.
•By setting reverse range, in case fluids flow to reverse direction the flowmeter measures it as reverse direction range automatically. In this time, a status signal that shows changing into the reverse direction is output.
• To set the internal totalizing function for forward direction can also show it for reverse direction by parameter settings.
• PLS/ALM+, PLS/ALM– are used for output connection.
PLS/ALM+, PLS/ALM– terminals are for common use with pulse, alarm and other
NOTE
status output functions. Therefore, in case this function is used, other functions are not available to use.
Display Description
Default: 00
5. FUNCTION AND DATA SETTINGS
F and R flow rate measurement can be selected as “02” in parameter No. “b10”.
Code
00
Pulse output
01
Alarm output
02
Forward / reverse flow measurement
03
Automatic two range switching
04
Alarm output at low flow limit
05
Totalization switch
Content
Default: 2%
Reverse direction span can be set in parameter No. “b30”. Flow rate unit is the same as forward direction span.
Futher reverse range span should be set in the same number of places of decimals as forward range span. Example: forward flow rate : 1.000 then reverce flow rate should be 4.000.
Hysteresis width at switching direction can be set in parameter No. “b31”. It is the rate (%) of the smaller span, either forward or reverse span. “b31”.
0%
Flow Rate
Hysteresis
Status output Forward flow measurement: OFF Reverse flow measurement: ON
5-13
When using reversed status (ON/OFF) is required, it can be set in “N02 Output Mode”
IM 1E10C1-E
Page 33

5.5.9 Automatic Two Range Switching

•When an input exceeds 100% of the first range, the range is automatically transferred to the second range and the status output changes state.
• PLS/ALM+, PLS/ALM–terminals are used for output connection.
PLS/ALM+, PLS/ALM–terminals are for common use with pulse, alarm and other status
NOTE
output functions. Therefore, in case this function is used, other functions are not available to use.
Display Description
Default : 00
5. FUNCTION AND DATA SETTINGS
Automotic two range transfer can be selected “03” in parameter No. “b10”.
Code
Pulse output
00
Alarm output
01
Forward / reverse flow measurement
02
Automatic two range switching
03
Alarm output at low flow limit
04
Totalization switch
05
Content
Default : 1.0000
Default: 10%
Forward second range can be set by calling up parameter No. “b33”. Setting restrictions: First range 2nd range.
Further second range span should be set in the same number of places of decimals as first range span in parameter No. “b03”. Example: First range : 1.000 then second range should be
4.000
Hysteresis width at switching range can be set in parameter No. “b34”. It is the rate (%) of first range span.
Output
100%
0 %
1st range: OFF 2nd range: ON
Status Output ON
Hysteresis (%)
Status Output
2nd range1st range
Flow Rate
5-14
When using reversed status (ON/OFF) is required, it can be set in “N02 Output Mode”.
IM 1E10C1-E
Page 34

5.5.10 Alarm Output at Low Flow Limit (Flow Switch)

• In case flow rate decrease under set level, an status signal is output.
PLS/ALM+, PLS/ALM– terminals are for common use with pulse, alarm and other
NOTE
status output functions. Therefore, in case this function is used, other functions are not available to use.
Display Description
Alarm output at low flow limits can be selected “04” in parameter No. “b10”.
Defalt : 00
Defalt : -10(%)
Code
00 01 02 03 04 05
The Low Limit value can be set in parameter No. “b36” as parcentage for 4 to 20 mA.
5. FUNCTION AND DATA SETTINGS
Content
Pulse output Alarm output Forward / reverse flow measurement Automatic two range switching Alarm output at low flow limit Totalozation switch
Default : 5(%)
Hysteresis width is set in parameter No. “b37”.
Output
low flow limits value.
Hysteresis
Status Output
On
When using reversed status (ON/OFF) is required, it can be set in “N02 Output Mode”.
5-15
IM 1E10C1-E
Page 35

5.5.11 Totalization Switch Output

• In case the Internal Totalization Value increase over set level, an alarm signal is output.
PLS/ALM+, PLS/ALM– terminals are for common use with pulse, alarm and other
NOTE
status output functions. Therefore, in case this function is used, other functions are not available to use.
Display Description
Default : 00
5. FUNCTION AND DATA SETTINGS
Totalization switch can be selected as “05” in parameter No. “b10”.
Code
00
Pulse output
01
Alarm output
02
Forward / reverse flow measurement
03
Automatic two range switching
04
Alarm output at low flow limit
05
Totalization switch
Content
Default : 0
Switch level can be selected by calling up parameter No. “E06”.
Totalization
999999
Setting value 10000
Status Output
ON
When using reversed status (ON/OFF) is required, it can be set in “N02 Output Mode”.
Input
5-16
IM 1E10C1-E
Page 36

5.5.12 Alarm Output

• This function is for status output from PLS/ALM+, PLS/ALM– terminals, when an
PLS/ALM+, PLS/ALM–terminals are for common use with pulse, alarm and other
NOTE
status output functions. Therefore, in case this function is used, other functions are not available to use.
• All of the alarms are able to output except empty pipe detection function that can be
• The status goes from close to open (OFF) during alarming.
alarm occurs.
selected in parameter No. “n07” as out of selection.
Display Description
The alarm output can be selected “01” in parameter No. “b10” and P+, P– terminals are only for alarm output.
Default: 00
Code
00
Pulse output
01
Alarm output
02
Forward / reverse flow measurement
03
Automatic two range switching
04
Alarm output at low flow limit
05
Totalization switch
5. FUNCTION AND DATA SETTINGS
Content
* Item “n” can be called up in setting “55” in parameter No. “L02”.

5.5.13 Data Settings Enable / Inhibit

• This function can inhibit to change all data except parameter No. “ L01”. However, auto zero adjustment function can work, if it has been set in parameter No. “C01”. And the preset totalization value function also can work, if it has been set in param­eter No. “E04”.
Displayed Description
Default: 01
Default: 01
The empty pipe output selection can be set in parameter No. “n07”.
Code
00 01
The data settings inhibit item can be set “00” in parameter No. “L01”.
Code
00 01
Content
ALARM NO ALARM
Content
INHIBIT ENABLE
5-17
IM 1E10C1-E
Page 37

5.5.14 Procedure of Selecting Special Application Items

• Only the special application (“n” items) shipped being unpublished. In case the “n” items should be used, it can be set “55” in parameter No. “L02”.
Displayed Description
The “n” items can be set “55” in parameter No. “L02”.
5. FUNCTION AND DATA SETTINGS

5.5.15 Rate Limit

Default: 00
Code
00 55
Content
Accessible up to L parameters. Accessible up to n parameters.
• This function is used to remove noise that cannot be removed by increasing the damping time constant.
•In case unexpected noise from step signal or slurry is entered, a basis is set to recognize that signal is flow rate or noise. The recoginition depends on rate limit value (upper and lower limit) and dead time (sampling time).
• Determination of rate limit value and dead time.
Rate limit value:
Determine the level to reduce output fluctuation. For example, reducing 2% or more fluctuation by setting as 2% to reduce.
2% 2%
Dead time T0:
Please determine the dead time depending on ouput fluctuation width. In case of noise of which is longer than the dead time, please set the dead time longer.
T
0
T
0
Signal processing procedures:
The function sets a certain upper and lower limit (rate limit value) for first order delay response values of flow rate data obtained in a previous sampling. If currently sampled flow rate data exceeds or goes below the limit is regarded as current flow rate value. Signals whose protruding portions show the same trends during a certain number of sampling times (dead time) are identified as flow rate signals.
5-18
IM 1E10C1-E
Page 38
Example 1: Step Input
5. FUNCTION AND DATA SETTINGS
10%
1%
Dead time: 3 sec. (Sampling 80 ms × 18 times)
1
Step Signal
Flow rate value after rate limiting
9
Shows 1% response cause of excessive signal beyond the rate limit. However, actual output is under damping that described by a solid line. Shows the flow rate signal (1%) of just after damping calculation ( 1 ) and rate limit
2
value. This signal is recognized as a flow rate signal since it does not return to within the
3
rate limit value within the dead time. The output signal follows the damping curve and tracks the step signal.
4
Example 2: Slurry Noise
Slurry Noise
Flow rate value after rate limiting
+1%
Input: 0 to 10% Damping time constant: 3 sec. Dead time: 3 sec. Rate limit value: 1%
63.2%
Flow rate value after damping
18
Input: 0 to 10% Damping time constant: 1 sec. Dead time : 1 sec. Rate limit value: 1%
–1%
The left figure shows that the slurry noise is not a flow rate signal.
Flow rate value after rate limiting and damping.
Dead time: 1 sec.
Displayed Description
The rate limit value can be set in parameter No. “n03”. Setting Range: 0 to 10%
Default: 5(%)
The dead time can be set in parameter No. “n04”. Setting Range: 0 to 15 sec.
Default: 0(%)
(Rate limit function halt at 0)
5-19
IM 1E10C1-E
Page 39
6. OPERATION VIA BRAIN TERMINAL

6. OPERATION VIA BRAIN TERMINAL (BT200)

Products come equipped with a BRAIN communication function communicate with dedicated BRAIN terminals (BT200) or computer system. In the BRAIN Series commu­nications system, modulated signal is superimposed onto the 4 to 20 mA DC analog signal for data transmission. Since the modulated wave is an AC signal superimposed on the analog signal will cause no error in the DC component of the analog signal. In this way, monitoring can be performed via communications while the ADMAG SE is online.
This section describes the operation procedures using BRAIN terminal. For details on the functions of the ADMAG SE, see Chapter 5, “Function and Data Settings.” And also, see the “BT200 Instruction Manual” (IM 1C0A11-01E) for more detailed information.

6.1 BT200 Connections

(1) Connecting BT200 to 4 to 20 mA DC Transfer Line
The communication signal of the ADMAG SE with BRAIN communication function is superimposed onto the 4 to 20 mA DC analog signal to be transferred.
4 to 20mA DC signal
transfer line
ADMAG SE
Intermediate
terminals
CUR+
CUR–
Figure 6.1 Interconnection Diagram
Control room
Receiver
Terminal board
Receiver resistance,
250 to 600
BT200BT200 BT200
6-1
IM 1E10C1-E
Page 40

6.2 BT200 Keypad Layout

Figure 6.2 shows the key pad layout of BT200.
Power
ON/OFF key
6. OPERATION VIA BRAIN TERMINAL
LCD
8 lines with 21 characters each
Function keys
Executes the commands displayed at the bottom of the screen.
Arrow keys
• Selects an item.
• Moves the cursor.
• Page feeding.
ENTER key
• Goes to the selected item.
• Sets the entry data to the object communication instrument.
• Executes the BT200 functions.
Entry cursor (Inverse video)
Menu panel Parameter panel
MENU BATTERY A: DISPLAY B: SET C: ADJUST D: DISP SEL E: TOTAL SET F: PULSE SET
HOME SET ADJ ESC
Major parameters items
A maximum of six items are displayed.
Message
PARAM A10:FLOW RATE(%)
0.6% A20:FLOW RATE
0.06 m3/h A30:TOTAL 0
DATA DIAG PRNT ESC
Function commands
Alphanumeric keys
• Enters a number.
• Enters letters when pressed together with the shift key.
SHIFT keys
Parameter data
A maximum of three items are displayed.
Figure 6.2 Key Layout and Functions
6-2
IM 1E10C1-E
Page 41

6.3 BT200 Key Functions

(1) Entry of Alphanumeric Characters
Numbers, codes and letters can be entered in combinations of the alphanumeric keys and the SHIFT key.
Entry of numbers, codes and a space (0 to 9, ., -, ) Entering of them is possible by using the alphanumeric keys.
Example of Entry Key Operation
6. OPERATION VIA BRAIN TERMINAL
[
–4.3
1 –0.3
XW
NM
1
HG
4
ZY
SPACE
VU
.
XW
Entry of letters
Press an alphanumeric key while one of the SHIFT keys is pressed and the letter on the same side of the key as the SHIFT key that is pressed can be entered. Press the SHIFT key each time when entering a letter.
Example of Entry Key Operation
WIC
J. B
SHIFT
5
The letter on the left side of the alphanumeric key is entered.
XW
SHIFTSHIFT
JI
SHIFT
VU
.
3 0
5
SHIFT
RQ
BA
VU RQ
.
3
TS
7
SHIFT
The letter on the right side of the alphanumeric key is entered.
JI
SHIFT
BA
DC
8
7
Selection of capital/small letters
Capital and small letters can be selected alternately by pressing the function key [F2] (CAPS).
Entry of capital letters
CODE CAPS CLR ESC
F2
F1 F3 F4 F1 F2 F3 F4
Entry of small letters
CODE caps CLR ESC
Entry of codes
Codes can be entered by pressing the function key [F1] (CODE). Every time [F1] CODE is pressed, the codes are displayed at the cursor position in the order shown below.
/ . - , + * ) ( ' & % $ ” ! To enter characters after the above codes, move the cursor using the [>] key before entry.
Example of Entry Key Operation
l/m
F2 F1
SHIFT
LW
6
>
SHIFT
( m )( / )( l )(Small letter)
XW
1
6-3
IM 1E10C1-E
Page 42
(2) Function Keys
6. OPERATION VIA BRAIN TERMINAL
The functions of the function keys vary with the commands being displayed on the display panel.
MENU A: DISPLAY B: SET C: ADJUST D: DISP SEL E: TOTAL SET F: PULSE SET
HOME SET ADJ ESC
F2F1 F3 F4
Function keys
*The command is available only for BT200-P00.

6.4 Displaying Flow Rate Data

Flow rate data can be displayed on the BT200 panel according to the following proce­dure.
Command
ADJ
CAPS/caps
CLR
CODE
COPY*
DAT A
DEL
DIAG
ESC FEED* HOME
LIST*
NO OK
PARM
PON/POFF*
PRNT*
SET
SLOT
GO* STOP*
UTIL
Calls up the zero-adjustment menu.
Description
Changes the capital/small letter mode. Clears entered data/deletes all data. See the above “Entry of code.” Prints parameters on the panel. Updates parameter data. Deletes one character. Calls up the self-check panel. Returns to the previous panel. Paper feed. Calls up the home menu (A:DISPLAY). Prints all parameters of the menus. Setting stop/re-setting. Returns to the previous panel. Goes to the next panel. Parameter number setting mode. Printer output of data whose setting was changed Mode on/off. Changes to the print mode. Calls up the setting menu. (B:SETTING) Returns to the slot selection panel. Starts print out. Stops printing. Calls up the utility panel.
Display Description
ON/OFF
--WELCOME-­BRAIN TERMINAL ID:BT200
Check cable connection and press the ENT key.
UTIL FEED
ENTER
PARAMETER 01:MODEL SE14-A00 02:TAG NO.
03:SELF CHECK GOOD
or
F4
Inverse video bar
MENU A:DISPLAY B:SET C:ADJUST D:DISP SEL E:TOTAL SET F:PULSE SET
HOME SET ADJ ESC
ENTER
PARAM A10:FLOW RATE(%)
0.6 % A20:FLOW RATE
0.06 m3/h A30:TOTAL 0
DATA PRNTDIAG ESC
Turn the power on and the panel as shown on the left appears after “Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel as shown on the left to be displayed.
The tag number specified upon ordering has been entered.
OK
Pressing the F4 key [OK] or the ENTER key causes the menu panel
ENTER
as shown on the left to be displayed. Select “A:DISPLAY” on the menu screen with the inverse video bar
and press the ENTER key to make the flow data panel appear.
A maximum of three data items can be displayed on one panel.
Data are updated at an interval of 5 seconds.
The arrow keys, [], [], [<] or [>], are used for page feeding or
item selection.
6-4
IM 1E10C1-E
Page 43

6.5 Setting Parameters

The three parameters must be set to obtain a correct signal.
NOTE

6.5.1 Setting Nominal Size

Nominal size, flow span and meter factor must be set.
Example: Nominal Size 2.00 inch
Display Description
6. OPERATION VIA BRAIN TERMINAL
ON/OFF
--WELCOME-­BRAIN TERMINAL ID:BT200
CHECK CABLE CONNECTION AND PRESS THE ENT KEY.
UTIL FEED
ENTER
PARAM 01:MODEL SE14-A00 02:TAG NO.
03:SELF CHECK GOOD
or
ENTER
MENU A:DISPLAY B:SET C:ADJUST D:DISP SEL E:TOTAL SET F:PULSE SET
HOME SET ADJ ESC
ENTER
PARAM B01:TAG NO
B02:DAMPING
3.0 s B03:FLOW SPAN
1.00 m/s DATA DIAG ESC
Turn the power on and the panel as shown on the left appears after “Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel to be displayed.
OK
Pressing the F4 key or ENTER key causes the menu panel to be
F4
displayed.
Use the arrow key to select “B:SET” with the arrow key and press the ENTER key.
Then, the parameter panel is displayed.
PARAM B04:FLOW UNIT m B05:TIME UNIT /S B06:SIZE UNIT mm
DIAG
DATA
SET B06:SIZE UNIT mm < mm > < inch >
ENTER
Select “B06:SIZE UNIT” by feeding the page with the arrow key and press ENTER key to call up the following data setup panel.
ESC
Press ENTER key on the parameter panel to display the data setup panel as shown on the left. (If the security panel appears, enter the security code.*)
ESC
Select “inch” using the arrow keys. Default:mm
* For entry of the security code, see IM1C0A11-01E.
6-5
IM 1E10C1-E
Page 44
Display Description
SET B06:SIZE UNIT mm < mm > < inch >
ENTER
SET B03:SIZE UNIT inch
ESC
Press ENTER key twice at an interval of a few seconds.
×2
The display as shown on the left appears.
6. OPERATION VIA BRAIN TERMINAL
NO OK
PARAM B04: FLOW UNIT m B05: TIME UNIT /S B06: SIZE UNIT inch
DATA DIAG ESC
PARAM B05: TIME UNIT /S B06: SIZE UNIT inch B07: NOMINAL SIZE
10.00 inch
DIAGDATA ESC
ENTER
SET B07:NOMINAL SIZE
10.00 inch
002.00
ESC
“2.00”
ENTER
SET B07:NOMINAL SIZE
2.00 inch
If the data is correct, press F4 key [OK].
F4
The parameter panel is displayed again.
Select “B07:NOMINAL SIZE” by feeding the page with the arrow key.
Press ENTER key to display the data setup panel.
Enter “2.00” using the alphanumeric keys and press ENTER key twice at an interval of a few seconds.
×2
Default:10.00(for inch) 100.00(for mm) (If the security panel appears, enter the security code.*)
NO OK
If the data is correct, press the F4 key [OK].
F4
PARAM B05: TIME UNIT /S B06: SIZE UNIT inch B07: NOMINAL SIZE
2.00 inch DIAGDATA ESC
The parameter panel appears again. The setting is completed.
* For entry of the security code, see IM1C0A11-01E.
6-6
IM 1E10C1-E
Page 45

6.5.2 Setting Flow Span

Example: Flow span 30.0 m3/h
6. OPERATION VIA BRAIN TERMINAL
Display Description
ON/OFF
--WELCOME-­BRAIN TERMINAL ID:BT200
CHECK CABLE CONNECTION AND PRESS THE ENT KEY.
UTIL FEED
ENTER
PARAM 01:MODEL SE14-A00 02:TAG NO.
03:SELF CHECK GOOD
or
ENTER
MENU A:DISPLAY B:SET C:ADJUST D:DISP SEL E:TOTAL SET F:PULSE SET
HOME SET ADJ ESC
ENTER
PARAM B01:TAG NO
B02:DAMPING
3.0 s B03:FLOW SPAN
1.00 m/s DATA DIAG ESC
ENTER
SET B03:FLOW SPAN
1.0000 m/s
0
Turn the power on and the panel as shown on the left appears after “Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel to be displayed.
OK
Pressing the F4 key or ENTER key causes the menu panel to be
F4
displayed.
Use the arrow key to select “B:SET” with the arrow key and press the ENTER key.
Then, the parameter panel is displayed.
Select “B03:FLOW SPAN” using the arrow key and press ENTER key to call up the following data setup panel.
Press ENTER key on the parameter panel to display the data setup panel as shown on the left. (If the security panel appears, enter the security code.*)
DEL CLR ESC
Enter “30.0” using the alphanumeric keys. Default:1.0000(m/s)
“30.0”
(This “B03: FLOW SPAN” is for entering the value, not units.)
* For entry of the security code, see IM1C0A11-01E.
6-7
IM 1E10C1-E
Page 46
Display Description
SET B03:FLOW SPAN
1.00 m/s
30.0
DEL CLR ESC
ENTER
SET B03:FLOW SPAN
30.0 m/s
6. OPERATION VIA BRAIN TERMINAL
Press ENTER key twice at an interval of a few seconds.
×2
The display as shown on the left appears.
NO OK
PARAM B01: TAG NO
B02: DAMPING
3.0 S
B03: FLOW SPAN
30.0 m/s
DATA DIAG ESC
PARAM B02: DAMPING
3.0 S
B03: FLOW SPAN
30.0 m/s
B04: FLOW UNIT m
DIAGDATA ESC
ENTER
SET B04:FLOW UNIT m < km3 > < m3 > < l > < cm3 >
ESC
ENTER
SET B04:FLOW UNIT m3
If the data is correct, press F4 key [OK].
F4
The parameter panel is displayed again.
Select “B04:FLOW UNIT” by feeding the page with the arrow key.
Press ENTER key to display the data setup panel.
3
3
3
: 10
Xm
*km
3
cm : (10-2Xm)
Select “m interval of a few seconds. Default:m
×2
(If the security panel appears, enter the security code.*)
3
3
” with the arrow key and press ENTER key twice at an
NO OK
If the data is correct, press the F4 key [OK].
F4
* For entry of the security code, see IM1C0A11-01E.
6-8
IM 1E10C1-E
Page 47
6. OPERATION VIA BRAIN TERMINAL
Display Description
PARAM B02: DAMPING
3.0 S
B03: FLOW SPAN
30.0 m3/s
B04: FLOW UNIT m3
DATA DIAG ESC
PARAM B03: FLOW SPAN
30.0 m3/s
B04: FLOW UNIT m3 B05: TIME UNIT /s
DIAGDATA
SET B05:TIME UNIT /s < /s > < /d > < /h > < /m >
SET B05:TIME UNIT /h
ESC
ENTER
ESC
ENTER
The parameter panel appears again.
Select “B05:TIME UNIT” by feeding the page with the arrow key.
Press the ENTER key to call up the data setup panel.
Select “/h” with the arrow key and press ENTER key twice at an interval of a few seconds. Default:s
×2
NO OK
PARAM B03:FLOW SPAN
30.0 m3/h
B04:FLOW UNIT m3 B05:TIME UNIT /h
HOME SET ADJ ESC
If the data is correct, press the F4 key [OK].
F4
The parameter panel appears again. The setting is completed.
6-9
IM 1E10C1-E
Page 48

6.5.3 Setting Meter Factor

The meter factor is engraved on the data plate of the combined flow tube.
Example: set “1.1200” as meter factor.
6. OPERATION VIA BRAIN TERMINAL
Display Description
ON/OFF
--WELCOME--
BRAIN TERMINAL ID:BT200
CHECK CABLE CONNECTION AND PRESS THE ENT KEY.
UTIL FEED
ENTER
PARAM 01:MODEL SE14-A00 02:TAG NO.
03:SELF CHECK GOOD
or
ENTER
MENU A:DISPLAY B:SET C:ADJUST D:DISP SEL E:TOTAL SET F:PULSE SET
HOME SET ADJ ESC
ENTER
PARAM B01:TAG NO
B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s
DATA DIAG ESC
Turn the power on and the panel as shown on the left appears after “Please wait...” is displayed for a few seconds.
Pressing the ENTER key causes the initial data panel to be displayed.
OK
Pressing the F4 key or ENTER key causes the menu panel to be
F4
displayed.
Use the arrow key to select “B:SET” with the arrow key and press the ENTER key.
Then, the parameter panel is displayed.
PARAM B06:SIZE UNIT inch B07:NOMINAL SIZE
2.00 inch
B08:MF
1.0000
DATA
DIAG
ESC
Select “B08:MF” by feeding the page with the arrow key and press ENTER key to call up the following data setup panel.
Press ENTER key on the parameter panel to display the data setup panel as shown on the left. (If the security panel appears, enter the security code.*)
ESC
Select “1.1200” using the alphanumeric keys. Default:1.0000
SET B08:MF
1.0000
0
ENTER
CLRDEL
“1.1200”
* For entry of the security code, see IM1C0A11-01E.
6-10
IM 1E10C1-E
Page 49
Display Description
SET B08: MF
1.0000
1.1200
6. OPERATION VIA BRAIN TERMINAL
DEL
SET B08: MF
1.1200
PARAM B06: SIZE UNIT inch B07: NOMINAL SIZE
2.00 inch
B08: MF
1.1200
DATA DIAG ESC
CLR
ENTER
NO OK
ESC
Press ENTER key twice at an interval of a few seconds.
×2
The display as shown on the left appears.
If the data is correct, press F4 key [OK].
F4
The parameter panel is displayed again. The setting is completed.

6.5.4 Power Frequency (For DC version only)

IMPORTANT
In case of DC power supply version, setting power frequency is required.
Display Description
PARAM B10: OUTPUT FUNC PULSE OUT B11: 4-20 ALM OUT
21.6mA OR MORE
B12: POWER FREQ
50.00Hz
DATA DIAG ESC
Set the value in areas where the frequency differs in “B12:POWER FREQ”.
Default: 50.00Hz

6.6 Other Functions

Please set other needed parameters. For detail on the functions, see Chapter 5, “Func­tions and Settings” except “User-Defined Units” function. For “User-Defined Units” function, see 6.6.1 below.

6.6.1 User-Defined Units

This function displays the instantaneous flow rate indicated in “A20 FLOW RATE” in user-defined units.
(1) User-Defined Unit for Instantaneous Flow Rate
Example 1:Displaying the flow rate of a fluid (its specific gravity is 2) in weight (kg)
in a flow rate span of 10 m3/h. When the flow rate is 100%, 20,000 kg/h is displayed.
6-11
IM 1E10C1-E
Page 50
6. OPERATION VIA BRAIN TERMINAL
Display Description
PARAM D02:FL USER SEL PROVIDED D03:FL USER SPAN
20000.0
D10:FL USER UNIT kg/h
DATA DIAG ESC
PARAM A10:FLOW RATE(%)
100.0 %
A20:FLOW RATE
20000.0 kg/h
A30:TOTAL
0
DIAGDATA
PRNT
(2) User-Defined Unit for Totalization Value
User-defined unit can be added to the totalization display in “A30 TOTAL
Display Description
PARAM E04:TOTAL SET INHIBIT E05:TL SET VALUE 0 E10:TL USER UNIT kg
DATA DIAG ESC
Select “PROVIDED” in “D02:FL USER SEL.” Default:NOT PROVIDED
In “D03:FL USER SPAN” set the value of 100% flow rate to be displayed in “A20:FLOW RATE” The user-defined unit is set in “D10:FL USER UNIT” Default:100.0
Set the user-defined unit in “D10:FL USER UNIT
The instantaneous flow rate in user-defined unit can be displayed in “A20:FLOW RATE
ESC
Set the user-defined unit in “E10:TL USER UNIT
PARAM A10:FLOW RATE(%)
100.0 %
A20:FLOW RATE
20000.0 kg/h
A30:TOTAL
40000kg
DIAGDATA
The totalization value in user-defined unit can be displayed in “A30:TOTAL
ESC

6.7 Other Important Points

(1) The automatic power-off function turns the BT200 off automatically with no key
access for about 5 minutes or more. However, this function does not operate when the BT200 is displaying “A10:FLOW RATE (%)” or “A20:FLOW RATE”
(2) When “A10:FLOW RATE (%)” or “A20:FLOW RATE” is displayed, the data are
updated every 5 seconds.
(3) UPLOAD/DOWNLOAD functions which can copy the setting date between
ADMAG SE and BT200 are provided. (For details, see the “BT200 Instruction Manual IM 1C0A11-01E.”) Parameters that can be copied are as follows:
B02 DAMPING, B03 FLOW SPAN, B04 FLOW UNIT, B05 TIME UNIT, B06 SIZE UNIT, B07 NOMINAL SIZE, B10 OUTPUT FUNC, B11 4-20 ALM OUT, D01 DISP SELECT, D02 FL USER SEL, D03 FL USER SPAN, D10 FL USER UNIT, E01 TOTAL UNIT, E02 TOTAL SCALE, E03 TOTAL LOWCUT, E04 TOTAL SET, E05 TL SET VALUE, E10 TL USER UNIT, F01 PULSE UNIT, F02 PULSE SCALE, F03 PULSE LOWCUT, F04 PULSE WIDTH, G01 4-20 LOW CUT, G02 4-20 LOW LMT, G03 4-20 H LMT
6-12
IM 1E10C1-E
Page 51

7. OPERATION VIA HART COMMUNICATOR

7. OPERATION VIA HART COMMUNI­CATOR
Matching of communicator DD and instrument DD
CAUTION
Before using model 275 HART communicator, check that the DD(Device Description) installed in the communicator matches to that of instruments to set up. To check the DD in the instrument or the HART communicator, follow the steps below. If the correct DD is not installed in the communicator, you must upgrade the DD at the HART official programming sites. For communication tools other than Model 275 HART communica­tor, contact vendors of each for upgrade information.
[Example]
1. Checking the DD in the instrument
1) Connect the communicator to the instrument to set up.
ADMAG SE Review Fld dev rev 2
2) Call “Device setup” and press [→].
3) Call “Review” and press [].
4) By pressing [NEXT] or [PREV], find “Fld dev rev” to show the DD of the instrument.
2. Checking the DD in Model 275 HART communicator.
1) Turn on the communicator alone.
HELP PREV NEXT EXIT
“The instrument DD is Version 2”
[Example]
HART Communicator Fld dev rev 1 Dev v1 , DD v2 2 Dev v2 , DD v1
2) Call “Utility” from main menu and press [→].
3) Call “Simulation” and press [→].
4) Select “YOKOGAWA” from manufacturers list by pressing [] and press [] .
“The communicator DD supports Version 1 and 2.”
5) Select the model name of the instrument (i.e. ADMAG SE) by pressing [] and press [] to show the DD of the communicator.
Version 1 and 2

7.1 Conditions of Communication Line

7.1.1 Interconnection between ADMAG SE and HART Communicator

The HART Communicator can interface with the ADMAG SE from the control room, the ADMAG SE site, or any other wiring termination point in the loop, provided there is a minimum load resistance of 230between the connection and the receiving instru­ment. To communicate, it must be connected in parallel with the ADMAG SE, the connections are non-polarized. Figure 7.1.1 illustrates the wiring connections for direct interface at the ADMAG SE site. The HART Communicator can be used for remote access from any terminal strip as well.
Control room
ADMAG SE
4 to 20 mA DC signal line
CUR+
+
CUR-
Communicator
Model 275
HART
Relaying
terminals
HART
Communicator
Model 275
Figure 7.1.1 Interconnection Diagram
Terminal board
Receiving instrument load resistance:
HART
Communicator
Model 275
230 to 600
7-1
IM 1E10C1-E
Page 52

7.1.2 Communication Line Requirements

Specifications for Communication Line:
Load resistance: 230 to 600Ω (including cable resistance)
When multidrop mode, see Figure 7.1.2. Minimum cable size: 24 AWG, (0.51 mm diameter) Cable type: Single pair shielded or multiple pair with overall shield Maximum twisted-pair length: 6,500 ft (2,000 m) Maximum multiple twisted-pair length: 3,200 ft (1,000 m) Use the following formula to determine cable length for a specific application;
7. OPERATION VIA HART COMMUNICATOR
(R×C)
6
(Cf+10,000)
C
65×10
L =
where: L = length in feet or meters
R = resistance in ohms, current sense resistance C = cable capacitance in pF/ft or pF/m Cf = 50,000 pF
Load
Resistance
()
800
600
400
200
0
12 345678910 11 12 13 14 15
* Maximum Load Voltage: 600Ω × 25 mA = 15 V
230
571
500
444
400
363
333
Q’ty of connected field devices
307
Figure 7.1.2 Load Resistance and Quantity of Devices in Multidrop Mode
285
266
NOTE
The above graph shows the load resistance in case that each current output of all connected transmitters is 4 mA.
7-2
IM 1E10C1-E
Page 53
7. OPERATION VIA HART COMMUNICATOR

7.2 Basic Operation of the HART Communicator (Model 275)

7.2.1 Keys and Functions

Communication Cable
LCD (Liquid crystal display)
(21 characters×8 lines)
Function keys
Functions of the keys are indicated on the display.
Power ON/OFF
Shift keys
Use to enter alphabetic characters.
Move the inverse video bar (cursor) on the display for selecting the desired item.
Hot key
Call up Hot Key Menu as follows:
1. Span
2. Enable Write
3. New Password
1. Change the display contents.
2. Move the position where a number or character is to be entered.
Example
Pressing calls up the display corresponding to the item pointed with the cursor.
Pressing returns to the previous display. (See 7.2.3 Calling up Menu
Alphanumeric keys
1.Enter numbers and characters.
2.Select the desired menu item with the corresponding number. (See 7.2.4 Entering, Setting and Sending Data)
Example
Pressing single key enters the number. Pressing the key with shift key enters the alphabetic character.
(Press) (ENTER)
To enter “7”,
To enter “C”,
ABC
7
ABC
7
‘7’
‘C’
Figure 7.2.1 HART Communicator
7-3
IM 1E10C1-E
Page 54

7.2.2 Display

7. OPERATION VIA HART COMMUNICATOR
The HART Communicator automatically searches for ADMAG SE on the 4 to 20 mA loop when it is turned on. When the HART Communicator is connected to the ADMAG SE, it displays “Online” menu as shown below. (If ADMAG SE is not found, the communicator displays the message “No Device
Found. Press OK....” Press the OK ‘F4’ function key and the main menu appears. Please
retry after confirming the connection with the ADMAG SE.)
Manufacturer’s Field Device Type Code
<2>
<3>
<4>
<5>
Tag (8 Characters) <1>
appears when the voltage
level of the battery is low
The arrow mark corresponding to the pressed key appears.
Inverse video bar
Function keys
Figure 7.2.2 Display
<1> appears and flashes during communication between the HART Communicator
and the ADMAG SE. At Burst mode*, appears. <2> The current display menu title appears. <3> Each item in menu of <2> appears.
<4> and/or appear when the items are scrolled out of the display. <5> On any given menu, the label appearing above a function key indicates the function
of that key for the current menu. Note: Refer to “7.3.4 Setting Parameters (7) Burst Mode”.

7.2.3 Calling Up Menu Addresses

7.3.3 Menu Tree shows the configuration of Online Menu which is needed for the operation with HART Communicator. The desired item can be displayed with ease by understanding the menu configuration.
When the HART Commnicator is connected to the ADMAG SE, “Online” menu will be displayed after the power is turned on (See figure 7.2.2). Call up the desired item as follows:
7-4
IM 1E10C1-E
Page 55
Key operation
7. OPERATION VIA HART COMMUNICATOR
There are two choices to select the desired menu item.
1. Use the or key to select the desired item, and then press the key.
2. Press the number key displayed for the desired item.
Device setup PV PV AO Span
Display Operation
ADMAG SE : FI-100
1
Online 1 Device setup 2 PV 3 PV AO 4 Span
DEL SET ESC ENTER
• To return to the previous display, press the
key, EXIT (F4), ESC (F3) or
ABORT (F3).
Example: Call up the “Tag” to change the tag number.
Check where “Tag” is located in the menu configuration. Then, call up “Tag” on the display according to the menu configuration.
process variables Diag/Service Basic setup Detailed setup Review
STU
or
1
: Line size PV Damp Tag
ADMAG SE : FI-100 Tag FI-100 FI-100
Descriptor :
Display appears when the HART Communicator is turned
1
HELP DEL ESC ENTER
on. Select “Device setup”.
ADMAG SE : FI-100
2
Device setup 1 Process variables 2 Diag/Service 3 Basic setup 4 Detailed setup 5 Review
DEL SAVE HOME ENTER
ADMAG SE : FI-100
3
Basic setup 1 PV Unit 2 Span 3 Nominal size 4 PV Damp 5 Tag
HELP SAVE HOME ENTER
ADMAG SE : FI-100
4
Tag FI-100 FI-100
HELP DEL ESC ENTER
or
YZ /
3
or
MNO
5
×2
Select “Basic setup”.
Select “Tag”.
×4
The display for Tag setting appears. (The default value of “Tag” is blank.)
7-5
IM 1E10C1-E
Page 56

7.2.4 Entering, Setting and Sending Data

The data which are input with the keys are set in the HART Communicator by pressing ENTER (F4). Then, by pressing SEND (F2), the data are sent to the ADMAG SE. Note that the data are not set in the ADMAG SE if SEND (F2) is not pressed. All the data set with the HART Communicator is held in memory unless power is turned off, so every data can be sent to the ADMAG SE at one lot.
Operation
Entering data on the “Tag” setting display. On alphabetic characters, only capital letters can be used for setting Tag No. with HART Communicator.
Example: Set “FIC-1A”.
Call up “Tag” setting display.
1. Device setup 3. Basic setup 5. Tag
ADMAG SE :
1
Tag
7. OPERATION VIA HART COMMUNICATOR
5. Tag
HELP DEL ESC ENTER
On the setting display shown above, enter the data as follows:
Character to
Operation Display
be entered
DEF
8
I
C
: +
-
1
*
STU
1
A
GHI
9
ABC
7
ABC
7
FF
F I
F I C
F I C -
F I C - 1
F I C - 1 A
7-6
IM 1E10C1-E
Page 57
Display Operation
ADMAG SE :
1
Tag FIC-1A
HELP DEL ESC ENTER
F4
(ENTER)
7. OPERATION VIA HART COMMUNICATOR
Press ENTER (F4) to set the data in the HART Communicator after entering the data.
ADMAG SE :
2
Basic setup 1 PV Unit 2 Span 3 Line size 4 PV Damp 5 Tag FIC-1A
HELP SEND HOME ENTER
ADMAG SE : FIC-1A
3
Basic setup 1 PV Unit 2 Span 3 Line size 4 PV Damp 5 Tag FIC-1A
HELP SAVE HOME ENTER
NOTE
F2
Press SEND (F2) to send the data to the ADMAG SE. * is flashing during communication.
(SEND)
SEND SAVE
label changed to label, and the transmission
is completed. Press HOME (F3), and return “Online Menu”.
Parameter setting on the indicator of ADMAG SE is prohibited during HART Com­munication.
7-7
IM 1E10C1-E
Page 58

7.3 Parameters

7.3.1 Parameters Configuration

Parameters of HART Communicator is constructed hierarchically. The menu tree for Online menu is shown in 7.3.3 Menu Tree.
See “Chapter 11. Parameter List” about the usage of each parameter. Note the differ­ences between parameters on ADMAG SE display and those on HART Communicator.
The Online menu summary is shown below.
Table 7.1.3 Online Menu Summary
No. Display Item Contents
1
Device setup 2 3 4

7.3.2 Data Renewing

PV
PV AO
SPAN
7. OPERATION VIA HART COMMUNICATOR
Set parameters for ADMAG SE. Display process value in engineering unit. Display analog output in mA. Display set span in engineering unit.
NOTE
There are two methods to load the data of ADMAG SE from/to HART Communicator, periodic data renewing and discretionary data renewing.
(1) Periodic Data Renewing
The follwing data are renewed in 0.5 to 2 seconds cycle.
PV, PV AO, PV % rnge, Totl, Reverse total, Diff. total, Power freq, Velocity check
(2) Discretionary Data Renewing
The following data can be loaded from/to ADMAG SE. Up load can be done with SAVE (F2) on any online menu, and down load can be done on Saved Configuration menu in Offline menu. (Refer to HART Communicator Manual.)
Descriptor, Message, Date, Tag, Span, Line size, Size unit, PV Damp, Base vol unit, Base time unit, Disp select, Fl user sel, Fl user span, Total unit, Total scale, Total low cut, Tl set value, Total set, Analog low cut, Analog low lmt, Analog hi lmt, Analog alarm out, Output function, Pulse unit, Pulse scale, Pulse low cut, Pulse width.
The changed data with HART Communicator is sent to ADMAG SE by pressing SEND (F2) of HART Communicator.
7-8
IM 1E10C1-E
Page 59

7.3.3 Menu Tree

7. OPERATION VIA HART COMMUNICATOR
Online Menu
1 Device setup 2 PV [r]
3 PV AO [r] 4 Span [r]
1 Process
variables
2 Diag/Service
3 Basic setup
1 PV [r] 2 Totl [w]
1 Test device
2 Loop test [sel]
3 Status out [sel]
1 PV Unit [sel]
2 Span [w] 3 Line size [w] 4 PV Damp [w] 5 Tag [w] 6 Descriptor [w] 7 Message [w] 8 Date [w]
1 Sensor
1 Status [r]
1 Test/Status
2 Auto zero [exe] 3 Zero tuning [sel] 4 Output trim
4mA, 20mA, Other, End
Normal, Closed(on), Open(off)
gal/min L/min Cum/h m/s ft/s Spcl
1 PV [r] 2 Flow units
2 Self test [exe]
Inhibits, Enable
1 D/A trim 2 Scaled D/A trim
1 Base vol unit [sel]
Status group 1 Status group 2 Status group 3
k Cum, Cum, L, Cucm, M gal, k gal, gal, m gal, k bbl, bbl, m bbl, u bbl, m, ft
4 Detailed
setup
2 Input
to be continued to next page
3 Velocity check [r]
4 Sensor config
1 PV% rnge [r] 2 Span [w] 3 PV Damp [w]
4 Signal
processing
2 Base time unit
[sel]
1 Size unit [sel] 2 Line size [w]
3 MF [w] 4 Auto zero [exe] 5 Flow dir [sel]
1 Rate limit [w] 2 Dead time [w]
3 Power synch [sel] 4 Power freq [w]
d, h, min, s
mm, in
Forward, Reverse
Yes, No
[r] : read [w] : write [sel] : select [exe] : execute
7-9
IM 1E10C1-E
Page 60
7. OPERATION VIA HART COMMUNICATOR
Online Menu
1 Device setup 2 PV [r]
3 PV AO [r] 4 Span [r]
4 Detailed
setup
3 Totalizer
4 Outputs
1 Totl [w] 2 Total unit [sel] 3 Total scale [w]
4 Total low cut [w] 5 TI set value [w]
6 Total set [sel] 7 Total switch [w]
8 Reverse total [w] 9 Diff. total [r]
1 Analog set
2 Analog output
n UNIT/P, u UNIT/P, m UNIT/P, UNIT/P, k UNIT/P, M UNIT/P, PULSE/s
Inhibit, Enable
1 Analog low cut [w] 2 Analog low lmt [w] 3 Analog hi lmt [w]
1 PV AO [r] 2 PV AO Alrm typ [r]
3 Loop test [sel] 4 Output trim
5 Analog alarm out
[sel]
4mA, 20mA, Other, End 1 D/A trim
2 Scaled D/A trim
2.4mA or less
4.0mA Hold
21.6mA or more
to be continued to next page
3 HART output
4 Function set
5 Pulse output
1 Poll addr [w] 2Num req preams [r]
3 Burst mode [sel]
4 Burst option [sel]
1 Output function [sel] 2Reverse span [w]
3Bi direction hys [w] 4 Forward span2 [w] 5Auto range hys [w] 6 Low alarm [w] 7 Low alarm hys [w]
1 Pulse unit [sel] 2 Pulse scale [w]
3 Pulse low cut [w] 4 Pulse width [sel]
Off On
PV % range/current Process vars/crnt
Pulse out Alarm out Bi direction Auto 2 ranges Low alarm Total switch
n UNIT/P, u UNIT/P, m UNIT/P, UNIT/P, k UNIT/P, M UNIT/P, PULSE/s
50% Duty,
0.5 ms, 1 ms, 20 ms, 33 ms, 50 ms, 100 ms
[r] : read [w] : write [sel] : select [exe] : execute
7-10
IM 1E10C1-E
Page 61
Online Menu
1 Device setup 2 PV [r]
3 PV AO [r] 4 Span [r]
4 Detailed
setup
4 Outputs
6 Disp output
7. OPERATION VIA HART COMMUNICATOR
PV % rnge PV
1 Disp select [sel]
Totl Rev.totl Diff.totl PV % rnge/Totl PV/Totl PV % rnge/PV PV % rnge/Rev.totl PV/Rev.totl PV %rnge/Diff.totl PV/Diff.totl
5 Reivew
5 Device info
1 Review 1 2 Review 2 3 Review 3
7 Appl set
1 Manufacturer [r] 2 Tag [w] 3 Descriptor [w] 4 Message [w] 5 Date [w] 6 Dev id [r] 7Write protect [r]
8 Revision #’s
2 FI user sel [sel]
3 FI user span [w]
1 Total/pulse [sel] 2 Output mode [sel]
3 Empty pipe [sel]
1 Universal rev [r] 2 Fld dev rev [r] 3 Software rev [r]
Not provided Provided
No damp, Damp
On active Off active
Alarm, No alarm
Hot key Span [w]
Wrt protect menu
Write protect [r] Enable wrt 10min [w] New password [w] Software seal [r]
7-11
[r] : read [w] : write [sel] : select [exe] : execute
IM 1E10C1-E
Page 62
7. OPERATION VIA HART COMMUNICATOR

7.3.4 Setting Parameters

The three parameters must be set to obtain a correct signal.
NOTE
(1) Nominal Size
Call up “Size unit” setting display.
1. Device setup 4. Detailed setup 1. Sensor 4. Sensor config 1. Size unit
ADMAG SE :
1
Size unit mm mm in
Nominal size, flow span and meter factor must be set.
The nominal size is engraved on the data plate of the combined flow tube.
Example: Set “2 inch”.
1. Size unit
2. Line size
Select “in” (inch).
DEL DEL ESC ENTER
ADMAG SE :
2
Size unit mm mm in
DEL DEL ESC ENTER
ADMAG SE :
3
Sensor config 1 Size unit in 2 Line size 3 MF 4 Auto zero 5 Flow dir
HELP SEND HOME ENTER
Call up “Line size” setting display.
4. Sensor config 3. Line size
ADMAG SE :
1
Line size
10.00 in
10.00
DEL DEL ESC ENTER
F4
(ENTER)
F2
(SEND)
‘2’
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
Enter “2” with alphanumeric keys.
ADMAG SE :
2
Line Size
10.00 2
DEL DEL ESC ENTER
ADMAG SE :
3
Sensor config 1 Size unit in 2 Line size 3 MF 4 Auto zero 5 Flow dir
HELP SEND HOME ENTER
F4
(ENTER)
F2
(SEND)
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE. By pressing HOME (F3), the display returns to “Online Menu.”
7-12
IM 1E10C1-E
Page 63
7. OPERATION VIA HART COMMUNICATOR
(2) Span
Example: Set “20.0 Cum /h”.
1. Base vol unit
2. Base time unit
1. Span
Call up “Base vol unit” setting display.
1. Device setup 4. Detailed setup 1. Sensor 2. Flow units 1. Base vol unit
ADMAG SE :
1
Flow unit m m bbl u bbl m ft
DEL DEL ESC ENTER
ADMAG SE :
2
Flow unit m Cum L Cucm M gal
DEL DEL ESC ENTER
F4
(ENTER)
Select “Cum” (m3).
×11
Press ENTER (F4).
ADMAG SE :
3
Flow units 1 Base vol unit Cum 2 Base time unit s
(SEND)
HELP SEND HOME ENTER
Call up “Base time unit” setting display.
2. Flow units 2. Base time unit
ADMAG SE :
1
Base time unit s d h min s
DEL DEL ESC ENTER
ADMAG SE :
2
Base time unit s d h min s
DEL DEL ESC ENTER
ADMAG SE :
3
Flow units 1 Base vol unit Cum 2 Base time unit h
(ENTER)
(SEND)
F2
F4
F2
Press SEND (F2) to set data to the ADMAG SE.
Select “h”.
×2
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
HELP SEND HOME ENTER
7-13
IM 1E10C1-E
Page 64
Call up “Span” setting display.
Hot key 1. Span
ADMAG SE :
1
Flow units 1 Flow unit Cum 2 Time unit h
DEL SAVE HOME ENTER
ADMAG SE :
2
Hot key 1 Span 1 Cum/h 2 Enable write 3 New password
DEL SAVE ESC ENTER
ADMAG SE :
3
Span 1 Cum/h 1
HELP DEL ESC ENTER
7. OPERATION VIA HART COMMUNICATOR
Press Hot key.
Select “Span”.
Enter “20.0” with alphanumeric keys.
‘20.0’
ADMAG SE :
4
Span 1 Cum/h
20.0
DEL DEL ESC ENTER
ADMAG SE :
5
Hot key 1 Span 20.0Cum/h 2 Enable write 3 New password
DEL SEND ESC ENTER
NOTE
F4
(ENTER)
F2
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE. Return to the presious display by pressing or .
(SEND)
When the span is set in engineering units using the ADMAG SE front panel key switches, consideration should be given to the least significant digit which is to be displayed for all ranges on the rate indicator of the ADMAG SE (parameter A20 FLOW RATE). For example, if the flow rate value is to be displayed to three decimal places, set the span as “20.000” as opposed to “20.”
7-14
IM 1E10C1-E
Page 65
(3) Flow Units
(4) Meter Factor
7. OPERATION VIA HART COMMUNICATOR
For actual flow unit setting, the following parameters are provided. <1> “PV Unit”
This parameter can be set only with HART Communicator. The selectable units are shown below.
gal/min, Cum/h, L/min, m/s, ft/s
<2> Combination of “Base vol unit” and “Base time unit”
These parameters can be set with both ADMAG SE and HART Communicator. The selectable units are shown below.
“Base vol unit”: k Cum, Cum, L, Cucm, M gal, k gal, gal, m gal, k bbl, bbl,
m bbl, u bbl, m*, ft* * “m” and “ft” can be combined only with /s.
“Base time unit”: /d, /h, /min, /s If the unit undefined in “PV Unit” is set in these parameters, the display of “PV Unit” indicates “Spcl.”
The meter factor is engraved on the data plate of the combined flow tube.
Example: Set “1.2345” as meter factor.
3. MF
Call up “MF” setting display.
1. Device setup 4. Detailed setup 1. Sensor 4. Sensor config 3. MF
ADMAG SE :
1
MF
1.0000
1.0000
DEL DEL ESC ENTER
ADMAG SE :
2
MF
1.0000
1.2345
DEL DEL ESC ENTER
ADMAG SE :
3
Sensor config 1 Size unit in 2 Line size 3 MF 1.2345 4 Auto zero 5 Flow dir
HELP SEND HOME ENTER
‘1.2345’
F4
(ENTER)
F2
(SEND)
Enter “1.2345” with alphanumeric keys.
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
7-15
IM 1E10C1-E
Page 66
7. OPERATION VIA HART COMMUNICATOR
(5) Power Frequency (For DC version only)
In case of DC power supply version, setting power frequency is required in area where
IMPORTANT
the frequency differs. The meter is set to 50.00Hz at the factory.
Example: Set “60.00”.
4. Power freq
Call up “Power freq” setting display.
1. Device setup 4. Detailed setup 2. Input 4. Signal procesing 4. Power freq
ADMAG SE :
1
Power freq
50.00
50.00
DEL DEL ESC ENTER
‘60.00’
Enter “60.00” with alphanumeric keys.
ADMAG SE :
2
Power freq
50.00
60.00
DEL DEL ESC ENTER
ADMAG SE :
3
Signal processing 1 Rate limit 2 Dead time 3 Power synch 4 Power freq 60.00
HELP SEND HOME ENTER
F4
(ENTER)
F2
(SEND)
Press ENTER (F4).
Press SEND (F2) to set data to the ADMAG SE.
7-16
IM 1E10C1-E
Page 67
(6) Trim Analog Output
Fine output adjustment is carried out with “D/A trim” or “Scaled D/A trim”.
D/A TrimD/A trim” is to be carried out if the calibration digital ammeter does not read 4.000 mA and 20.000 mA exactly with the output signal of 0% and 100%.
Scaled D/A TrimScaled D/A trim” is to be carried out if the output is adjusted using a voltmeter or other types of meters with 0% to 100% scale.
Example 1: For the adjustment using an ammeter (±1uA is measurable.)
Call up “Output trim” display.
1. Device setup 2. Diag/Service 1. Test device 4. Output trim
ADMAG SE :
1
Output trim 1 D/A trim 2 Scaled D/A trim
HELP SAVE HOME ENTER
Select “D/A trim”.
7. OPERATION VIA HART COMMUNICATOR
ADMAG SE :
2
WARN-Loop should be removed from automatic control
DEL DEL ABORT OK
ADMAG SE :
3
Connect reference meter
HELP SEND ABORT OK
ADMAG SE :
4
Setting fld dev output to 4mA
DEL DEL ABORT OK
ADMAG SE :
5
Enter meter value
4.0000
HELP DEL ABORT ENTER
F4
(OK)
F4
(OK)
F4
(OK)
‘4.115’
F4
(ENTER)
Press OK (F4).
Connect the ammeter (±1µA is measurable.), and press OK (F4).
Press OK (F4), and the ADMAG SE outputs the output signal of 0%.
Ammeter reading: 4.115
Enter the read value “4.115” of the ammeter, and press ENTER (F4). (The output of the ADMAG SE changes.)
7-17
IM 1E10C1-E
Page 68
ADMAG SE :
6
Fld dev output 4.000 mA equal to reference meter? 1 Yes 2 No
HELP SAVE ABORT OK
F4
(ENTER)
7. OPERATION VIA HART COMMUNICATOR
Ammeter reading: 4.000
Because the reading on the ammeter is 4.000 mA, select “Yes” and press ENTER (F4). If the reading is not 4.000 mA, select “No”. Repeat step until the ammeter reads 4.000 mA.
5
ADMAG SE :
7
Setting fld dev output of 20mA
DEL DEL ABORT OK
ADMAG SE :
8
Enter meter value
20.000
HELP DEL ABORT ENTER
ADMAG SE :
9
Fld dev output 20.000 mA equal to reference meter? 1 Yes 2 No
DEL DEL ABORT ENTER
ADMAG SE :
10
NOTE-Loop may be returned to automatic control
HELP DEL ABORT OK
F4
(OK)
‘19.050’
F4
(ENTER)
F4
(ENTER)
F4
(OK)
Press OK (F4), and the ADMAG SE outputs the output signal of 100%.
Ammeter reading: 19.050
Carry out the same procedures as those described under .
5
Ammeter reading: 20.000
Returning fld dev to original output” appears.
Press OK (F4).
ADMAG SE :
1
Trim analog output 1 D/A trim 2 Scaled D/A trim
HELP SAVE HOME ENTER
ADMAG SE :
2
WARN-Loop should be removed from automatic control
DEL DEL ABORT OK
Example 2: For the adjustment using a voltmeter
VWX
2
F4
(OK)
Select the “Scaled D/A trim”.
Press OK (F4).
7-18
IM 1E10C1-E
Page 69
ADMAG SE :
3
Trim will be scaled from 4.000 to 20.000 1 Proceed 2 Change
HELP SAVE ABORT ENTER
VWX
2
7. OPERATION VIA HART COMMUNICATOR
Select “Change”, and press ENTER (F4). The same operations as for “D/A trim” are required when selecting “Proceed”.
ADMAG SE :
4
Set scale- Lo output value
4.000000
4.000000
HELP DEL ABORT ENTER
ADMAG SE :
5
Set scale- Hi output value
20.000000
20.000000
HELP DEL ABORT ENTER
ADMAG SE :
6
Trim will be scaled from 1.000 to 5.000 1 Proceed 2 Change
DEL DEL ABORT ENTER
ADMAG SE :
7
Connect reference meter
HELP DEL ABORT OK
‘1’
F4
(ENTER)
‘5’
F4
(ENTER)
F4
(ENTER)
F4
(OK)
Enter the read value on the meter when the signal is 4 mA. In this case, enter the value of the voltage across a 250 resistor (1 V), and press ENTER (F4).
Enter the read value on the meter when the signal is 20 mA. Then, enter “5” (5 V), and press ENTER (F4).
Select “Proceed” and press ENTER (F4).
Connect the voltmeter, and press OK (F4).
ADMAG SE :
8
Setting fld dev output to 4mA
HELP SAVE ABORT OK
ADMAG SE :
9
Enter meter value
1.000000
1.000000
DEL DEL ABORT ENTER
ADMAG SE :
10
Scaled output: 1.000 equal readout device? 1 Yes 2 No
DEL DEL ABORT ENTER
F4
(OK)
‘1.01’
F4
(ENTER)
F4
(ENTER)
Press OK (F4). The output signal of 0% is output.
Voltmeter reading: 1.010
Enter the reading of the voltmeter (1.010), and press ENTER (F4). (The output of the ADMAG SE changes.)
Voltmeter reading: 1.000
Because the reading on the voltmeter is 1.000, select “Yes” and press ENTER (F4). If the reading is not 1.000, select “No”. Repeat step until the voltmeter reads 1.000 V.
9
7-19
IM 1E10C1-E
Page 70
ADMAG SE :
11
Settting fld dev output to 20mA
HELP SAVE ABORT OK
F4
(OK)
7. OPERATION VIA HART COMMUNICATOR
Press OK (F4). The output signal of 100% is output.
ADMAG SE :
12
Enter meter value
5.000000
5.000000
HELP DEL ABORT ENTER
ADMAG SE :
13
Scaled output: 5.210 equal readout device? 1 Yes 2 No
HELP DEL ABORT ENTER
ADMAG SE :
14
NOTE-Loop may be returned to automatic control
DEL DEL ABORT OK
IMPORTANT
‘5.21’
F4
Voltmeter reading: 5.210
Enter the reading of the voltmeter (5.210), and press ENTER
(ENTER)
F4
(ENTER)
(F4).
Voltmeter reading: 5.000
Select “Yes” and press ENTER (F4). “Returning fld dev to original output” appears.
F4
(OK)
Press OK (F4).
D/A trim should be executed only at single range mode. If D/A trim is executed at Bi direction mode, it is feared that the current output becomes 108%.
7-20
IM 1E10C1-E
Page 71
7. OPERATION VIA HART COMMUNICATOR
(7) Burst Mode
The ADMAG SE continuously sends the data stored in it when the burst mode is set “On”. Either one of instantaneous flow rate, output in %, totalization values and current output can be selected and sent. The data is sent intermittently as a digital signal when the ADMAG SE is set in the burst mode.
Setting of Burst Mode
Call up “Burst option” display.
1. Device setup 4. Detailed setup 4. Outputs 3. HART output 4. Burst option
ADMAG SE : Burst option ******** PV % range/current Process vars/crnt
HELP DEL ESC ENTER
Call up “Burst mode” display.
3. HART output 3. Burst mode
ADMAG SE :
1
Burst mode Off Off On
DEL DEL ESC ENTER
ADMAG SE :
2
HART output 1 Poll addr 0 2 Num req preams 5 3 Burst mode On 4 Burst option PV
HELP SEND HOME ENTER
Releasing from Burst Mode
Call up “Burst mode” display, and set “Off”.
F4
(ENTER)
F2
(SEND)
F4
(ENTER)
F2
(SEND)
Set the data to be sent.
• Instantaneous flow rate (PV)
• Output in % and current output (% range/current)
• Instantaneous flow rate, totalization value* and current output (Process vars/crnt) * “Totl”, “Reverse total” or “Diff. total”
Set “ON” and press ENTER (F4).
Press SEND (F2).
7-21
IM 1E10C1-E
Page 72
7. OPERATION VIA HART COMMUNICATOR
(8) Multidrop Mode
Field devices in multidrop mode refer to the connection of several field devices on a communication single line. Up to 15 field devices can be connected when set in the multidrop mode. To activate multidrop communication, the field device address must be changed to a number from 1 to 15. This change deactivates the 4 to 20 mA output and turns it 4 mA. Refer to Fig. 7.1.2 for the load resistance.
Setting of Multidrop Mode
Call up “Poll addr” display.
1. Device setup 4. Detailed setup 4. Outputs 3. HART output 1. Poll addr
ADMAG SE : Poll addr 0 0
HELP DEL ESC ENTER
‘1’
F4
(ENTER)
F2
(SEND)
Set the polling address (a number from 1 to 15) and press ENTER (F4). Then, press SEND (F2) to send the data.
Call up “Auto Poll” display.
HART output Online Menu Main Menu 4. Utility 1. Configure Communication
ADMAG SE :
1
HART output 1 Poll addr 1 2 Num req preams 5 3 Burst mode On 4 Burst option PV
HELP SAVE HOME ENTER
ADMAG SE :
2
Online 1 Device setup 2 PV 20Cum/h 3 PV AO 20mA 4 Span 20Cum/h
HELP SAVE HOME ENTER
HART Communicator
3
1 Offline 2 Online 3 Frequency Device 4 Utility
HELP SEND HOME ENTER
HART Communicator
4
Utility 1 Configure Communic 2 system Information 3 Listen for PC 4 Storage Location 5 Simulation
HELP SEND HOME ENTER
F3
(HOME)
JLK
4
1. Polling
Return to “Online Menu” with HOME (F3).
Return to “Main Menu” with a “previous” key.
Select “Utility”.
Select “Configure Communication”.
HART Communicator
5
Configure Communicat 1 Polling 2 Contrast 3 Off Time 4 Ignore diagnostics
HELP SEND HOME ENTER
Select “Polling”.
7-22
IM 1E10C1-E
Page 73
HART Communicator
6
Polling Never Poll Never Poll Ask Before Polling Always Poll Digital Poll
HELP SAVE ESC ENTER
NOTE
HART Communicator
1
Online 1 1: FIC-1A 2 2: FIC-2A 3 3: PIC-1A
DEL DEL ESC ENTER
ADMAG SE:FIC-1A:
2
Online 1 Device setup 2 PV 3 PV AO 4 Span
HELP SAVE HOME ENTER
HART Communicator
3
1 Offline 2 Online 3 Frequency Device 4 Utility
7. OPERATION VIA HART COMMUNICATOR
Select “Digital Poll” and press ENTER (F4).
×3
F4
(ENTER)
1. If “Never Poll” is set in “Polling” when the address is set, “Online Menu” cannot be called up and displayed. Be sure to set “Digital Poll” in “Polling” after setting the polling address.
2. When the same polling address is set for two or more field devices in multidrop mode, communication with these field devices is disabled.
Example: Communication when set in the multidrop mode.
(1) The HART Communicator searches for the field device is set in the
multidrop mode when the HART Communicator is turned on. When the HART Communicator is connected to the field device, the tag will be displayed (display ).
1
(2) Select desired field device. After that, normal communication with the
selected field device is possible. However, the communication speed is slow in this case (display ).
(3) To communicate with another field device, call up display , and select
2
3
Online”.
(4) Display will appear. Repeat the above operation.
1
HELP SAVE HOME ENTER
Releasing from Multidrop Mode
First, call up the “Poll addr” display, and set the address to 0. Second, call up the “Polling” display, and set “Never Poll”.
If the above releasing method is carried out in the reverse order, “Online Menu” can
NOTE
not be called up.
7-23
IM 1E10C1-E
Page 74
(9) Write Protection
Write protection function is used to prevent unauthorized data being written into the device, ADMAG SE. This function becomes active by entering a password in “New password”. Write protection status is released for 10 minutes by entering the password in “Enable wrt 10min”.
When the write protection function is active, data setting changes in all parameters of
NOTE
the ADMAG SE are inhibited and cannot be changed using either the HART Commu­nicator or the ADMAG SE front panel key switches.
Setting Password
Example: Set the password to “1 2 3 4
Call up “Wrt protect menu” in Hot key menu.
Hot key 2. Wrt protect menu2. Wrt protect menu
ADMAG SE :
1
Hot key 1 Span 1 m/s 2 Wrt protect menu
VWX
2
7. OPERATION VIA HART COMMUNICATOR
3. New password Select “Wrt protect menu”.
HELP SAVE HOME ENTER
ADMAG SE :
2
Wrt protect menu 1 Write protect No 2 Enable wrt 10min 3 New password 4 Software seal Keep
HELP SAVE
ADMAG SE :
3
Enter new password to change state of write protect
HELP DEL ABORT ENTER
ADMAG SE :
4
Re-enter new password within 30 seconds: 1234 1234
HELP DEL ABORT ENTER
ADMAG SE :
5
Change to New password
ABORT ENTER
YZ /
3
Select “New password”.
Set “1 2 3 4” and press ENTER (F4).
STU1VWX2YZ /3JKL
F4
(ENTER)
STU1VWX2YZ /3JKL
F4
(ENTER)
Set “1 2 3 4” again and press ENTER (F4).
Write protect” status changes from “No” to “Yes”.
4
4
DEL DEL
ADMAG SE :
6
It changed the state of protection related password
HELP DEL OK
ABORT OK
ABORT
F4
(OK)
Press OK (F4).
7-24
IM 1E10C1-E
Page 75
Changing Password
Example: Change the password from “1 2 3 4” to “6 7 8 9 A”.
Call up “Wrt protect menu” in Hot key menu.
Hot key 2. Wrt protect menu 2. Enable wrt 10min
ADMAG SE :
1
Enter current password to enable to write for 10 minutes:
HELP DEL ABORT ENTER
ADMAG SE :
2
Release the write protection for 10 minutes.
DEL DEL ABORT OK
ADMAG SE :
3
If you wish to release completely, you have to change password to all of spaces.
HELP DEL ABORT OK
2. Wrt protect menu
“1 2 3 4”
(ENTER)
F4
F4
(OK)
F4
(OK)
Enter the password and press ENTER (F4).
Press OK (F4). Write protect status is released for 10 minutes.
Press OK (F4).
7. OPERATION VIA HART COMMUNICATOR
ADMAG SE :
4
Wrt protect menu 1 Write protect No 2 Enable wrt 10min 3 New Password 4 Software seal Keep
HELP SAVE ABORT OK
ADMAG SE :
5
Enter new password to change state of write protect
HELP DEL ABORT ENTER
ADMAG SE :
6
Re-enter new Password write 30 seconds: 6789A 6789A
HELP DEL ABORT ENTER
ADMAG SE :
7
Change to New password
HELP DEL
ABORT OK
YZ/
3
“6 7 8 9 A”
F4
(ENTER)
“6 7 8 9 A”
F4
(ENTER)
Select “New password”.
Set “6 7 8 9 A” and press ENTER (F4).
Set “6 7 8 9 A” again and press ENTER (F4).
ADMAG SE :
8
It changed the state of protection related password.
HELP DEL OK
ABORT
F4
(OK)
Press OK (F4).
7-25
IM 1E10C1-E
Page 76
NOTE
7. OPERATION VIA HART COMMUNICATOR
1. “Enable wrt 10min” releases write protection status for 10 minutes. While write protection status is released, it is possible to enter a new password in the “New password”. It will not be possible when 10 minutes have elapsed.
2. To release write protection status completely, enter 8 spaces in the “New pass­word”. This causes “Write protect” status to change from “Yes” to “No”.
3. If both ADMAG SE and HART Communicator power off and on again within 10 minutes after releasing of write protection status, the enabled write protection status becomes unavailable.
4. “L01:TUNING” which is the write protection for ADMAG SE front panel key switches, can be set “00:INHIBIT” or “01:ENABLE” only when “Write Protect” on HART Communicator shows “No”.
* “Joker password" and “Software Seal”
When you forget the password that has been registered, it is possible to release the mode for 10 minutes by using a joker password. Enter YOKOGAWA to release “Write protect” status for 10 minutes. If this joker password is used, the status shown in the parameter “Software seal” is changed from “Keep” to “Break”. Press Hot key and select “2. Wrt Protect menu”. Current status is shown in “4. Software seal”. This status will be returned from “Break” to “Keep” by registering a new password.
(10) Other Functions and Operation
Please set the other needed parameters with the same way. The following document is useful for your operation.
Product Manual for the HART Communicator: MAN 4250
7-26
IM 1E10C1-E
Page 77

8. ACTUAL OPERATION

After you have installed the flow tube into the process piping, wired the input / output terminals, set up the required parameters and performed the pre-operation zero adjust­ment, the magnetic flowmeter should output an accurate flow signal from its terminals as soon as the measured fluid begins to flow. This section describes procedures of zero adjustment and alarms countermeasure.

8.1 Pre-Operation Zero Adjustment

This section describes three procedures for performing zero adjustment. Using the data setting keys on the converter front panel, using a BT200 or using a Hart Communicator. Zero adjustment is made to set the instrument output to 0% (4mA) when the flow rate is
0.
1. Zero adjustment should be done only when the fluid is filled in the flow tube and the
IMPORTANT
fluid velocity is completely zero by closing the valve.
2. Zero adjustment should be done prior to the other operation. For 20 seconds during the zero adjustment, any setting cannot be accepted.
8. ACTUAL OPERATON

8.1.1 Zero Adjustment Using Data Setting Keys

Display Description
Call up “C01” (ZERO TUNING) on the setting mode and touch SET key to make the data display.
SET
SET
SET
SET
Code
00
INHIBIT
01
ENABLE
×2
Call up “C02” (MAGFLOW ZERO) and touch SET key.
Touch SET key twice.
×2
-ZEro-” is displayed for about 20 seconds.
Content
Set “01” and touch SET key twice.
It changes into the Flow Rate Display Mode after the zero adjustment is completed.
8-1
IM 1E10C1-E
Page 78

8.1.2 Zero Adjustment Using BT200

Display Description
8. ACTUAL OPERATON
MENU A: DISPLAY B: SET C: ADJUST D: DISP SEL E: TOTAL SET F: PULSE SET
HOME SET ADJ ESC
ENTER
PARAM C01: ZERO TUNING INHIBIT C02: MAGFLOW ZERO
0.05 C60: SELF CHECK GOOD
DATA DIAG ESC
ENTER
SET C01: ZERO TUNING ENABLE
ENTER
PARAM C01: ZERO TUNING ENABLE C02: MAGFLOW ZERO
0.05 C60: SELF CHECK GOOD
DATA DIAG ESC
Call up the menu panel and select “C:ADJUST” with the arrow key.
Press ENTER key to call up the panel displaying the parameter subitems. Confirm the inverse video bar is on “C01:ZERO TUNING”.
Press ENTER key to call up the data setup panel and select “ENABLE”.
Press the ENTER key to set the data and return to the parameter sub items panel. Select “C02:MAGFLOW ZERO”with the arrow key.
ENTER
SET C02: MAGFLOW ZERO
0.05 +00.05
CLR ESC
ENTER
SET C02: MAGFLOW ZERO AUTOZERO
FEED NO OK
F4
PARAM C01: ZERO TUNING ENABLE C02: MAGFLOW ZERO
0.02 C60: SELF CHECK GOOD
DATA DIAG ESC
Pressing the ENTER key causes the data setup panel to be displayed.
×2
While “C02:MAGFLOW ZERO” is displayed, press the ENTER key twice at an interval of a few seconds. Then, “AUTO ZERO” is now displayed.
After about 20 seconds, pressing the “F4” [OK] of the function key causes the menu panel to be displayed. The zero correction is displayed. Then the panel returns to data display mode.
8-2
IM 1E10C1-E
Page 79

8.1.3 Zero Adjustment Using HART Communicator

Call up “Zero tuning” display.
1. Device setup 2. Diag/Service 1. Test device 3. Zero tuning
8. ACTUAL OPERATON
ADMAG SE : Zero tuning Enable Inhibit Enable
DEL DEL ESC ENTER
Call up “Auto zero” display.
1. Test device 2. Auto zero
ADMAG SE :
1
About to enter auto zero
DEL DEL ABORT OK
ADMAG SE :
2
waiting for auto zero to complete
DEL DEL ABORT ENTER
ADMAG SE :
3
Auto zero passed
F4
(ENTER)
F2
(SEND)
F4
(OK)
F4
Select “Enable” and press ENTER (F4) and SEND (F2).
Press OK (F4).
Wait for about 20 seconds.
Press OK (F4).
HELP SEND ABORT OK
IMPORTANT
(OK)
This parameter is only for execution.
1. Zero adjustment should be done only when the fluid velocity is completely zero by closing the valve.
2. Do not turn off the power to the ADMAG SE immediately after zero adjustment. Powering off within 20 seconds after zero adjustment will return adjustment to the previous setting.
8-3
IM 1E10C1-E
Page 80

8.2 Self-diagnostics Functions

The self-diagnostics function displays instrument internal errors, input/output signal
abnormalities, setting errors, and other problems.
When an alarm occurs, the alarm number that the error has occurred and normal data
are alternately indicated on the indicator of ADMAG SE. However, alarms are only displayed during flow rate data display mode and when parameter numbers are being changed in the setting mode. (Alarms are not displayed when data items are being changed.)
The current output during the alarm occurrence can be selected from among the
followings. See “8.2.1 Output Status during Alarm Occurence.”
• 2.4mA or less
• 4mA
• HOLD
• 21.6mA or more
When the BT200 is used, alarms are displayed in “A60 to N60:SELF CHECK
parameter.
When the HART Communicator is used, alarms are displayed in “Status group 1 to
3” parameters. There are two methods for self-diagnostics, every transmission and
manually executing the “Self test” command. See “8.2.2 Self-diagnostics Using HART Communicator.”
When an error message appears, follow “8.2.3 Error Description and Countermea-
sure.”.
8. ACTUAL OPERATON

8.2.1 Output Status during Alarm Occurrence

Display detail
Indicator
of SE
--- GOOD Self test OK ON Normal Normal
--- ERROR Error OFF Fixed* Stop Err-02 uP FAULT uP fault OFF 21.6mA or more** Stop Err-03 EEPROM FAULT EEPROM fault OFF 21.6mA or more** Stop Err-05 A/D FAULT A/D fault OFF Fixed* Stop Err-06 SIGNAL OVERFLOW Signal overflow OFF Fixed* Stop Err-07 COIL OPEN Coil open OFF Fixed* Stop Err-08 SPAN VEL.>10m/s V el. span>10m/s OFF Fixed* Stop Err-09 SPAN VEL.<0.3m/s V el. span<0.3m/s OFF Fixed* Stop Err-10 P.SPAN>1000p/s P.span>1000p/s OFF Fixed* Stop Err-11 P.SPAN>500p/s P.span>500p/s OFF Fixed* Stop Err-12 P.SPAN>25p/s P.span>25p/s OFF Fixed* Stop Err-13 P.SPAN>15p/s P.span>15p/s OFF Fixed* Stop Err-14 P.SPAN>10p/s P.span>10p/s OFF Fixed* Stop Err-15 P.SPAN>5p/s P.span>5p/s OFF Fixed* Stop Err-16 P.SPAN<.0001p/s P.span<.0001p/s OFF Fixed* Stop Err-17 T.SPAN>1000p/s T.span>1000p/s OFF Fixed* Stop Err-18 T.SPAN>.0001p/s T.span<.0001p/s OFF Fixed* Stop Err-19 4-20 LMT ERROR Analog lmt error OFF Fixed* Stop Err-20 EMPTY PIPE Empty pipe OFF Fixed* Stop Err-21 MULTIRANGE ERROR Multi range err OFF Fixed* Stop Err-22 COIL SHORT Excitation failure OFF Fixed* Stop Err-23 EEPROM NO SET EEPROM no set OFF 21.6mA or more** Stop Err-24 EEPROM DEFAULT EEPROM default OFF Fixed* Stop Err-25 Dev id not entered OFF Fixed* Stop
Note) *Depending on the setting in “4-20 ALM OUT (Analog alarm out)”.
**When optional code /C1 is selected, current output becomes 2.4mA or less.
BRAIN Terminal
HART
Communicator
Alarm
Contact
Output
Current Output
Total/Pulse
Output
8-4
IM 1E10C1-E
Page 81

8.2.2 Self-diagnostics Using HART Communicator

Self-diagnostics of the ADMAG SE and check of incorrect data setting can be carried out with the HART Communicator. There are two methods for self-diagnostics of the ADMAG SE, self-diagnostics for every transmission and manually executing the “Self test” command. When an error message appears, follow “8.2.3 Error Description and Countermeasure.”
Call up “Test/Status” setting display.
1. Device setup 2. Diag/Service 1. Test device 1. Test/Status
ADMAG SE :
1
Test/Status 1 Status 2 Self test
HELP SAVE HOME ENTER
VWX
2
Select “Self test”.
8. ACTUAL OPERATON
ADMAG SE :
2
Self test OK
DEL DEL ABORT OK
ADMAG SE :
3
Test/Status 1 Status 2 Self test
HELP SAVE HOME OK
ADMAG SE :
4
Status 1 Status group 1 2 Status group 2 3 Status group 3
HELP SAVE HOME OK
ADMAG SE :
5
group 1 Error OFF uP fault OFF EEPROM fault OFF A/D fault OFF Signal overflow OFF
HELP DEL ABORT EXIT
F4
(OK)
STU
1
If there is no error detected, “Self test OK” will be displayed. Press OK (F4). When an error occurs, an error message appears and the results of self-diagnostics appear in the “Status”.
Call up “Status”.
The status menu is separated 3 groups. About items of each group, see “8.2.3 Error Description and Countermeasure”.
Select the desired group. If there is no error, the result of diagnostics is indicated as
OFF”. If “ON” is indicated, a countermeasure for that error is necessary.
8-5
IM 1E10C1-E
Page 82

8.2.3 Error Description and Countermeasure

Display detail
Indicator
BRAIN T erminal HART Communicator
of SE
--- GOOD
--- ERROR
Err-02 uP FAULT Err-03 EEPROM FAULT Err-05 A/D FAULT
Err-06 SIGNAL
OVERFLOW
Err-07 COIL OPEN
Err-08 SPAN VEL.>10m/s
Err-09 SPAN VEL.<0.3m/s
Err-10 P.SPAN>1000p/s
Err-11 P.SPAN>500p/s
Err-12 P.SPAN>25p/s
Err-13 P.SPAN>15p/s
Err-14 P.SPAN>10p/s
Err-15 P.SPAN>5p/s
Err-16 P.SPAN<.0001p/s
Err-17 T.SPAN>1000p/s
Err-18 T.SPAN>.0001p/s
Err-19 4-20 LMT ERROR
Err-20 EMPTY PIPE
Err-21
MULTIRANGE ERROR
Err-22 COIL SHORT Err-23 EEPROM NO SET
Err-24 EEPROM
DEFAULT
Err-25 ---
Status group 1
Status group 2
Status group 3
Self test OK Error
uP fault EEPROM fault A/D fault Signal overflow
Coil open
Vel. span>10m/s
Vel. span<0.3m/s
P.span>1000p/s
P.span>500p/s
P.span>25p/s
P.span>15p/s
P.span>10p/s
P.span>5p/s
P.span<.0001p/s
T.span>1000p/s
T.span<.0001p/s
Analog lmt error
Empty pipe
Multi range err
Excitation failure EEPROM no set
EEPROM default
Dev id not entered
8. ACTUAL OPERATON
Description Countermeasure
Normal status Alarm occurrence
(At occurrence of error No.2 to 25)
Microprocessor failure EEPROM failure A/D converter failure Excessive input signal
Flow tube coil open-circuit
Span velocity setting exceeds 11m/s.
Span velocity setting is
0.2m/s or less. Pulse output rate exceeds
1100p/s at 50% duty. It exceeds 1000p/s at
0.5ms pulse width. Pulse output rate exceeds
500p/s at 1ms pulse width. Pulse output rate exceeds
25p/s at 20ms pulse width. Pulse output rate exceeds
15p/s at 33ms pulse width. Pulse output rate exceeds
10p/s at 50ms pulse width. Pulse output rate exceeds
5p/s at 100ms pulse width Pulse output rate is
0.00005p/s or less. Totalization rate exceeds
1100p/s. Totalization rate is
0.00005p/s or less. Analog low limit setting
exceeds analog high limit setting.
Pipe is not filled with fluid or insulating material attached to electrodes.
“Span” setting exceeds “Forward span2” setting at Auto 2 ranges.
Excitation circuit failure Default values have not
been set in EEPROM. EEPROM has been
initialized. Device ID has not been
entered.
Contact the nearest Yokogawa office or service center.
Check the followings:
Mix of the signal, power supply, excitation and other cables
• Stray currents in the measured fluid
Incorrect grounding
Contact the nearest Yokogawa office or service center.
Change settings.
Fill the flow tube with fluid or clean the flow tube inside.
Change settings.
Contact the nearest Yokogawa office or service center.
— —
8-6
IM 1E10C1-E
Page 83
9. MAINTENANCE

9.1 Loop Test (Test output)

This function enables you to set up any desired value, and to output it from the con­verter for test. Since this function corresponds to flow rate totalization display and pulse output, this makes it possible to check operation of individual function. The test functions of status output are also provided.
• Test outputs take priority of the flow signal. Do not forget to return to the normal operation mode after the loop test.
• In case "BI DIRECTION" is set at OUTPUT FUNCTION (Parameter No. b10), the
IMPORTANT
setting range is available -108 to +108. Please set the loop test value in +/- percent­age based on the larger flow span within forward and reverse flow span.
• In case "AUTO 2 RANGES" is set at OUTPUT FUNCTION (Parameter No.b10), the loop test setting value should be set in percentage based on the second range.

9. MAINTENANCE

9.1.1 Settings for Test Output Using Data Setting Keys

(1) Current Output (Corresponding to flow rate, totalization display and pulse output value)
Display Description
Call up “H01” (TEST MODE) on the setting mode and touch SET key to make the data display.
SET
Set “01” and touch SET key twice.
SET
×2
SET
SET
×2
Setting value:
–8 (–108) to 108%
Code
00 01
Call up “H02” (OUTPUT VALUE) and touch SET key.
Set the value in % span. (The figure shows a 100% setting.) Flow rate, totalization display and pulse output functions correspond to this set value.
Content
Normal operation Test output
9-1
IM 1E10C1-E
Page 84
(2) Status Output (For status output, alarm output or pulse output )
Display Description
Call up “H01” (TEST MODE) on the setting mode and touch SET key to make the data display.
SET
9. MAINTENANCE
Set “01” and touch SET key twice.
SET
Code
00 01
×2
Content
Normal operation Test output
Call up “H03” (STATUS OUT) and touch SET key.
SET
Select the output status and touch SET key twice.
SET
Code
Normal operation
00
Contact output status (ON)
01
Contact output status (OFF)
×2
02
Content

9.1.2 Setting for Test Output Using BT200

(1) Current Output (Corresponding to flow rate, totalization display and pulse output value)
Display Description
Select “TEST” in “H01: TEST MODE”.
PARAM H01:TEST MODE TEST H02:OUTPUT VALUE 100 % H03:STATUS OUT NORMAL
DATA
DIAG ESC
Code
NORMAL
TEST
Set the value in % of span in “H02:OUTPUT VALUE”. (The figure shows a 100% setting.) Flow rate, totalization display and pulse output functions correspond to this set value.
Content
Normal operation Test output
(2) Status Output (For status output, alarm output or pulse output status)
Display Description
Call up “H01: TEST MODE” on the setting mode and select “TEST”.
PARAM H01:TEST MODE TEST H02:OUTPUT VALUE 100 % H03:STATUS OUT NORMAL
DATA
DIAG ESC
Code
NORMAL
TEST
Select the status to be output in “H03: STATUS OUT”.
Code
NORMAL
CLOSED(ON)
OPEN(OFF)
Content
Normal operation Test output
Normal operation Contact output status (ON) Contact output status (OFF)
9-2
Content
IM 1E10C1-E
Page 85

9.1.3 Setting for Test Output Using HART Communicator

(1) Loop Test
This feature can be used to output a fixed current from 2.72 mA to 21.28 mA for loop check.
Setting of Loop Test
Example: Set “12mA (50%)” as test output.
2. Loop test
Call up “Loop test” display.
1. Device setup 2. Diag/Service 2. Loop test
ADMAG SE :
1
WARN-Loop should be removed from automatic control
DEL DEL ABORT OK
F4
(OK)
Set the control loop in manual mode, and press OK (F4).
9. MAINTENANCE
ADMAG SE :
2
Choose analog output level 1 4mA 2 20mA 3 Other 4 End
DEL DEL ABORT ENTER
ADMAG SE :
3
Output
4.000
HELP DEL ABORT ENTER
ADMAG SE :
4
Fld dev output is fixed at 12.000 mA
DEL DEL ABORT OK
F4
(ENTER)
‘1 2’
F4
(ENTER)
F4
(OK)
Select “Other”, and press ENTER (F4).
×2
1. 4mA: Outputs a 4mA current signal
2. 20mA: Outputs a 20mA current signal
3. Other: Sets a desired output with the alphanumeric keys
4. End: Exits
Enter “12”, and press ENTER (F4).
Press OK (F4). A fixed current of 12mA is output.
NOTE
1. In case “Bi direction” is set at “Output function”, the setting range is available with –108 to +108%. Please set the loop test value in +/– percentage based on the larger flow span within forward and reverse flow span.
2. In case “Auto 2 ranges” is set at “output function”, the loop test setting value should be set in percentage based on the second range.
9-3
IM 1E10C1-E
Page 86
Releasing from Loop Test:
On “Loop test” display.
ADMAG SE :
1
Choose analog output level 1 4mA 2 20mA 3 Other 4 End
DEL DEL ABORT ENTER
ADMAG SE :
2
NOTE-loop may be Returned to automatic control
DEL DEL ABORT OK
9. MAINTENANCE
There are four methods which cause the simulated output to return to a normal flow reading.
1. Wait 10 minutes to automatically release from the test mode.
2. Turn the power off to the ADMAG SE.
3. Execute “End”. (See the following for this procedure.)
4. Abort “Loop Test”. Press ABORT (F3).
To finish the loop test, select “End”, and press ENTER (F4).
×3
F4
(ENTER)
F4
(OK)
Press OK (F4).
(2) Status Output Test
ADMAG SE has one status output for alarm or other functions. It can be output for test. After the status output test, return the status output parameter to “Normal”.
Call up “Status out” display.
1. Device setup 2. Diag/Service 3. Status out
ADMAG SE :
1
Status out Normal Normal Close (on) Open (off)
DEL DEL ESC ENTER
ADMAG SE :
2
Diag/Service 1 Test device 2 Loop test 3 Status out
DEL SEND HOME ENTER
NOTE
When the status output test is executed, the current output is fixed 4 mA.
F4
(ENTER)
F2
(SEND)
Select “Closed” (example) and press ENTER (F4).
Press SEND (F2).
9-4
IM 1E10C1-E
Page 87

9.2 Trouble Shooting

Although magnetic flowmeters rarely require maintenance, failures occur when the instrument is not operating correctly. The following trouble shooting are described from the viewpoint of receiving instrument indication.
Please avoid removing the converter unit from the case, replacing fuse and alter LCD
CAUTION

9.2.1 No Indication

orientation. When these procedures are needed, please contact the nearest Yokogawa offce.
START
Examine the converter display flashing whether an error is displayed.
9. MAINTENANCE
Is an error displayed?
YES
Deal with the error according to "8.2.3 Error Description and Countermeasure."
NO
Is other display appearing?
YES
Does the flow arrow
on flow tube agree with the
flow direction?
YES
Check that the flow tube is filled with the liquid.
Is the flow
tube filled with the liquid?
YES
Check the resistance between the meter signal terminals A, B and C with a multimeter.
NO
NO
NO
Contact the nearest Yokogawa office or service center.
Execute either of the followings. a. Install flow tube to make
flow arrow agree with the flow direction.
b. Change the set value in
"B14: FLOW DIR".
Change the piping or mounting to fill the flow tube with the liquid. Vertical mounting is effective.
Is the resistance 100M
or more for each?
YES
Demount the flow tube and check the inside.
Is foreign matter
sticking to the liner and
electrode?
YES
Remove foreign matter.
9-5
NO
NO
Contact the nearest Yokogawa office or service center.
IM 1E10C1-E
Page 88

9.2.2 Unstable Zero

9. MAINTENANCE
START
Examine whether or not the meter tube is filled with liquid and the liquid does not contain bubbles.
*1
Is the flow tube filled
with liquid completely?
YES
Are bubbles
contained in the liquid?
NONO
Examine whether or not the valves leak.
Are valves leaking?
NO
• Confirm the flow tube
grounding.
• Confirm whether or not the
grounding wire is disconnected from the earth terminal.
Is grounding complete?
YES
Recheck liquid property.
NO
YES
YES
NO
It is better to provide a vent
*1
hole on the downstream side of the flow tube to check bubbles.
Change the piping or mounting to fill the flow tube with the liquid. Vertical mounting is effective.
Mount a defoaming device on the upstream side of the flow tube.
Stop the leak by repairing valves.
Complete grounding (The resistance must be 100 or less.) See “3.2.1 Protective Ground”.
• Does the liquid conductivity vary or is it easy to change?
• Is liquid conductivity sometimes below 5µS/cm?
NO
Is the liquid
likely to cause deposits?
NO
Is the flowmeter
located near motors,
transformers, or other
electric equipmets.
NO
Insulation deterioration is suspected. Contact the nearest Yokogawa office or service center.
YES
YES
YES
a. Insure that the liquid
conductivity does not change beyond fluid limits.
b. Do not use the ADMAG
SE for liquid has conductivity below 5µS/cm.
c. Decrease flow velocity
near the conductivity low limit as much as possible.
• Remove dirt and scale on near electrodes.
• Change to vertical mounting.
Sufficiently shield the flow tube. Locate the flow tube as far as possible from these equipments.
9-6
IM 1E10C1-E
Page 89

9.2.3 Disagreement of Indication with Actual Flow Rate

START
9. MAINTENANCE
Are parameters
correctly set?
YES
Examine filling with liquid in the flow tube, bubbles and correct grounding.
Is zero adjustment
completed?
YES
Is the flow tube
completely filled with
liquid?
YES
Is the liquid free of
bubbles?
YES
Is grounding complete?
YES
Check whether or not the AM011 cable is used for the signal cable, if there is contact between any two of the cable conductors (A, B), inner shield (SA, SB), and outer shield (C), and that they are securely connected to the terminal board.
NO
NO
NO
NO
NO
Set the parameters correctly.
Adjust zero when the flow tube is completely filled with liquid and the velocity is zero.
Change the piping or mounting to fill the flow tube with the liquid. Vertical mounting is effective.
Provide a defoaming device on the upstream side of the flow tube.
Complete grounding. (The resistance must be 100Ω or less.) See “3.2.1 Protective Ground”
Is the signal
cable completely end-
treated?
YES
Recheck the liquid property.
Is the liquid
likely to cause deposits?
NO
Examine whether or not a valve exists immediately before the flow tube (on the upstream side).
Is a valve located
immediately upstream of
the meter?
NO
Check the operation with the AM012/SE calibrator, and you will be able to confirm the error of the converter or of Flow Tube.
Contact the nearest Yokogawa office or service center.
NO
YES
YES
Completely perform end­treatment of the signal cable with PVC tubes or insulation tape so that the conductors, inner shields, and outer shield do not contact each other or with the case.
a. Remove scales. Especially
clean the electrodes and their vicinity.
b. Remove scales with a soft
brush or a piece of soft cloth. Never claw or scratch the lining.
a. If a valve located immediately
upstream of the flow tube is used half opened, the indication may be affected with flow turbulency.
b. Move the valve downstream of
the flow tube.
c. If the valve must be located on
the upstream side, allow for a minimum distance to the flow tube of 10 times the flow tube diameter or use the valve fully open.
9-7
IM 1E10C1-E
Page 90
10. OUTLINE

10. OUTLINE

STANDARD SPECIFICATIONS
Note •For models with no setting switches, a hand-
held terminal is necessary to set parameters.
•Pulse output, status output and alarm output use commom terminals, therefore, these functions are not av ailable at the same time .
Excitation method: Pulsed DC excitation Output Signal:
Current Output: 4 to 20 mA DC
(Load resistance 600 maximum)
Transistor Contact Output(Open-collector):
Pulse, alarm or status output selected by parameter setting (Contact rating : 30V DC(OFF), 200mA*(ON))
* In case of FM-Nonincendive type, 135mA
Communication:
HART or BRAIN (Superimposed on the 4 to 20mA DC signal)
Conditions of Communication Line:
Load Resistance: (including cable resistance) HART:230 to 600, depending on q’ty of field devices connected to the loop (multidrop mode) BRAIN:250 to 600 Load Capacitance: 0.22 µF maximum Load Inductance: 3.3 mH maximum Distance from Power Line: 15 cm(0.6 ft) or more
(Parallel wiring should be avoided.) Input Impedance of Receiver Connected to the Receiving Resistance: 10kor larger (at 2.4kHz)
(only for HART)
Maximum Cable Length: 2 km* (6500 ft) (when
polyethylene-insulated PVC-sheathed
* In case of FM-Nonincendive type, 1.5km(4875ft)
Instantaneous Flow Rate Display Function:
Flow rate can be displayed either in engineering units or in percent of span. (for models with indicator)
Totalizer Display Function:
Totalized volume in engineering units can be displayed by setting a totalizing factor. (for models with indicator)
Span Setting Function:
Volumetric flow setting is available by setting volume unit, time unit, flow rate value and flow tube size. Volume Unit: m barrel(=158.987L) Velocity Unit: m, ft Time Unit: sec., min., hour, day Flow Tube Size: mm, inch
Data Security During Power Failure:
Data storage in EEPROM - no back-up battery required.
Damping Time Constant:
Settable from 0.5 second to 200 seconds. (63% response time)
control cables (CEV cables) are used)
3
, l, cm3, gallon(US),
Pulse Output Function:
Scaled pulse can be output by setting a pulse factor. Pulse Width: Duty 50% or fixed pulse width (0.5, 1, 20, 33, 50, or 100ms) - user selectable. Output Rate: 0.0001 to 1000pps (when pulse output function is selected.)
Status Output Function:
One of the followings is selected by parameter setting.
• Auto 2 Ranges Status Output :
Indicates the selected range for automatic
dual range function.
• Forward and Reverse Status Output :
Indicates the flow direction for forward and reverse flow measurement mode.
• Totalization Status Output :
Indicates that the internal totalized value ex­ceeds the set value.
• Low Limit Alarm :
Indicates that flow rate under the low limit set value.
Alarm Output Function :
Indicates that an alarm occurs (Normal Close Fixed).
Self Diagnostics Function:
Converter failure, flow tube failure, erroneous setting, etc. can be diagnosed and displayed (for models with indicator).
Touch Control:
Parameter setting operation by infrared switches. (for models with indicator and setting switches)
Electrical Connection:
ANSI 1/2NPT female, DIN Pg13.5 female, ISO M20 X 1.5 female, JIS G1/2 female
Terminal Connection: M4 size screw terminal Case Material: Aluminum alloy Coating: Polyurethane corrosion-resistant coating
Deep sea moss green (Munsell 0.6GY3.1/2.0)
Protection: IP67, NEMA 4X, JIS C0920
water tight type
Mounting: 2-inch pipe mounting Grounding: 100 or less
*In case of explosion proof type, the protective grounding must be connected to a suitable IS grounding system.
STANDARD PERFORMANCE
SE***DJ/EJ+SE14(Up to 300m cable length)
Accuracy :
Size in mm
(inch)
15 to 400
(0.5 to 16)
Repeatability: 0.1% of flowrate (1mm/s minimum)
Span in m/s
(ft/s)
0.3 to 1 (1 to 3)
1 to 10
(3 to 33)
Accuracy
0.5% of span
0.25% of span (at indications below 50% of span)
0.5% of rate (at indications 50% of span or more)
T01.EPS
10-1
IM 1E10C1-E
Page 91
10. OUTLINE
Maximum Power Consumption:
11W for SE***DJ/EJ+SE14
Insulation Resistance:
• 100M between power terminals and ground terminal at 500V DC.
• 100M between power terminals and each output terminal at 500V DC.
• 20M between each output terminal (except for EX1 and EX2) and ground terminal at 100V DC.
• 20MΩ between (EX1 or EX2) and ground ter- minal at 50V DC.
Withstand Voltage:
• 1500V AC between power terminals and ground terminal for 1 minute. (for -A1/A2 power supply)
• 500V AC between power terminals and ground terminal for 1 minute. (for -D1 power supply)
CAUTION
When performing the Voltage Breakdown Test, Insulation Resistance Test or any unpowered electrical test, wait 10 seconds after the power supply is turned off before removing the housing cover. Be sure to remove the Short Bar at terminal “G”. After testing, return the Short Bar to its correct position. Screw tightening torque should be 1.18N­m(0.88ft-lb)or more, because the G-terminal is thought as a protective grounding and should
conform to the Safety Requirements.
Safety Requirement Standard:
IEC1010, EN61010
EMC Conformity Standard:
EN61326 EN61000-3-2, EN61000-3-3 AS/NZS 2064
NORMAL OPERATING CONDITION
Ambient Temperature: -20 to 60 °C (-4 to 140 °F) Ambient Humidity: 5 to 95%RH (no condensation) Rated Power Supply Voltage:
100V AC/DC Version: Range 80 to 127V AC, 47 to 63Hz
90 to 110V DC 230V AC Version: Range 180 to 264V AC 24V DC/AC Version: Range 20.4 to 28.8 V DC/AC
Supplied Power and Max. Cable Length for 24V
DC version:
Allowable cable length m(ft)
1000(3300)
900(2970) 800(2640) 700(2310) 600(1980) 500(1650) 400(1320)
300(990) 200(660) 100(330)
0
20 22 24 26 28 (V)
Cable cross section area: 1.25 mm Cable cross section area: 2 mm
2
2
F01.EPS
Altitude at installation side:
Max.2000m above sea level
Installation category based on IEC1010:
II (See Note)
Pollution level based on IEC1010: 2(See Note)
Note: • The “Installation category” implies the regulation f or
impulse withstand voltage. It is also called the “Overvoltage category”.“II” applies to electrical equipment.
• “Pollution lev el” describes the degree to which a solid, liquid or gas which deteriorates dielectric strength is adhering. “2” applies to a normal indoor atmosphere.
Fuse: 2A 250V (Time-Lag type)
TERMINAL CONNECTION
Terminal Symbols
PLS/ALM OUT
CUROUT
POWER SUPPLY
SA
SB
EX1 EX2
P+
P­I+
L/+ N/-
A B
C
I-
G
Description
A shield
Flow signal input
B shield Common
Excitation current output
Pulse, alarm or status output Current output 4 to 20mA DC
Power supply and
Ground
Protective grounding
T03-1.EPS
ACCESSORIES
Data sheet 1
Unit labels sheet 1 Hexagonal wrench 1 (for special screw of terminal cover/display cover.) Plug 1 (in case of DC power supply version)
Mounting bracket 1set
MODEL AND SUFFIX CODE
Magnetic Flow Converter:
Model
Suffix code Description
SE14
...........................
Aux.Cod -J.........................
Output D .....................
E .....................
Indicator
Power Supply -A1 .............
Electrical Connection (Refer to Note1)
Optional Codes
Note1 : Only ANSI 1/2NPT electrical connection is available for FM or CSA explosion proof type. JIS G1/2 electrical connection is not available for any explosion proof type.
NN ...............
H1 ................
H2 ................
-A2 .............
-D1 ............
Dedicated Signal Cable:
Model Suffix Code Description
AM011 ..............................
End treatment
Cable length Style code Optional specification
Note 1 : A user provided two conductor cable is required for coil excitaiton. Note 2 : The maximum temperature for the signal cable is 80C(176F).
-0 ..........................
-4 ..........................
Magnetic Flow Converter Always J 4-20mA and Pulse or Alarm, Simultaneous 2-output (BRAIN)
4-20mA and Pulse or Alarm, Simultaneous 2-output (HART)
Non Indicator With Indicator With Indicator and Setting SW
80 to 127V AC / 90 to 110 VDC 180 to 264 V AC
20.4 to 28.8V DC/AC
0 ......
JIS G1/2 Female
2 ......
ANSI 1/2NPT Female
3 ......
DIN Pg 13.5 Female
4 ......
ISO M20X1.5 Female
/ ...
Dedicated cable for magnetic flowmeter
Non termination Terminated
-L .........
*A ............
Enter the length in m (Max 300m) Style A Number of end treatment parts
/C ..
T05.EPS
T10.EPS
10-2
IM 1E10C1-E
Page 92
Optional Specification
10. OUTLINE
Item
Specification
Code
Waterproof Glands Waterproof glands are attached to all wiring ports. For JIS G1/2 only. /ECG Waterproof Glands with Union Joints Waterproof glands (union joints) are attached to all wiring ports. For JIS G1/2 only. /ECU DC Noise Suppression Eliminating DC Noise (Size 15mm(0.5in.) or larger; Conductivity 50µS/cm or higher) /ELC Burn Out Down Current output at CPU failure is set to "Downward(2.4mA DC or less)"
Without /C1 : Upward(21.6mA DC or more) /C1
Lightning Protector Built-in Lightning Protector /A
Painting Color Change Black, Munsell code; N1.5 /P1
Jade Green, Munsell code; 7.5BG4/1.5 /P2
Metallic Silver /P7 Epoxy Coating Coating is changed to Epoxy coating. /X1
High Anti-corrosion Coating Coating is changed to three-layer coating.
(Urethane coating on two-layer Epoxy coating) /X2 Calibration Certificate Level 2: Declaration and Calibration Equipment List /L2
Level 3: Declaration and Primary Standard List /L3
Level 4: Declaration and YOKOGAWA Measuring Instruments Control System /L4 CENELEC ATEX (KEMA) Explosion proof EExdIICT6 ; Group II Category 2 G
Explosion Proof Type (only for size 15 to 200mm) /KF2 FM Explosion Proof Type Explosion proof/Nonincendive (only for size 15 to 200mm) /FF1/FN1
CSA Explosion Proof Type Explosion proof (only for size 15 to 200mm) /CF1 SAA Explosion Proof Type Explosion proof ExdIICT6 (only for size 15 to 200mm) /SF1 GOST Certificate Calibration Certificate for GOST (Only for products produced at YMF) /GOS
Note : In case of requirement of EN10204 3.1B for Material Certificate, contact YOKOGAWA office.
EXTERNAL DIMENSION
Magnetic Flow Converter
230 (9.1)
31
(1.2)
133 (5.2)
31
(1.2)
160 (6.3)
40
(1.6)
123 (4.8)
102(4.02)
48 (1.9)
51 (2.0)
Weight 2.8kg (6.16 lb)
170 (6.7)
240 (9.5)
SD8d.eps
10-3
IM 1E10C1-E
Page 93

11. PARAMETER LIST

11. PARAMETER LIST

11.1 Parameters for ADMAG SE Indicator and BRAIN Terminal

This chapter describes ADMAG SE parameters for its indicator and BRAIN Terminal.
Description of Items
Indicator
BRAIN Terminal
Name
Data Range,
Units
Decimal
Point
Default
Value
R/W
Description
Parameter number for ADMAG SE indicator
Parameter number for BRAIN terminal
Parameter name
The figure in ( ) shows the number for selecting data on ADMAG SE indicator. The desired number can be entered when ADMAG SE indicator is in the setting mode. Indicates the range of allowable settings and the units used.16 alphanumerics can be entered when “16 ASCII characters” is specified.
Numbers indicate the position of decimal point and its range of movement within the data display.
11-1
Example : 0 to 4 : Can be moved in the range 0 to 4 4 : Fixed at 4
Indicate initial set value (When shipped from the factory)
R: Read only W: Write enabled
Describes the nature of the parameter
IM 1E10C1-E
Page 94
List of Parameters for ADMAG SE Indicator and BRAIN Terminal
11. PARAMETER LIST
Indicator Name R/W DescriptionData Range, Units
A00 DISPLAY R A10 A10 FLOW RATE(%) –10.0 to 110.0% 1 R
A20 A20 FLOW RATE ±300.0 0 to 4 R
A30 A30 TOTAL 0 to 999999 0 W
A31 A31 REV.TOTAL 0 to 999999 W
A32 A32 DIF.TORAL –999999 to 999999 R
A60 SELF CHECK GOOD R
BRAIN
Terminal
ERROR µF FAULT EEPROM FAULT A/D FAULT SIGNAL OVERFLOW COIL OPEN SPAN VEL.> 10 m/s SPAN VEL.< 0.3 m/s P.SPAN > 1000 p/s P.SPAN > 500 p/s P.SPAN > 25 p/s P.SPAN > 15 p/s P.SPAN > 10 p/s P.SPAN > 5 p/s P.SPAN < 0001 p/s T.SPAN > 1000 p/s T.SPAN < 0001 p/s 4 - 20 LMT ERROR EMPTY PIPE MULTIRANGE ERROR COIL SHORT EEPROM NO SET EEPROM DEFAULT
Decimal
Point
Default
Value
Major outputs display functions. Displays instantaneous flow rate in %. Displays instantaneous flow rate in
egineering unit. Displays and presets forward direction
totalized flow rate. Displays and resets reverse direction
totalized flow rate. Displays differential totalized flow rate
between forward and reverse. (A32=A30–A31)
Displays self-check result. See “8.2 Self-diagnostics Functions.”
11-2
IM 1E10C1-E
Page 95
11. PARAMETER LIST
Indicator Name R/W DescriptionData Range, Units
BRAIN
Terminal
Decimal
Point
Default
Value
B00 SET R — B01 TAG NO ASC II 16 characters W b02 B02 DAMPING 0.5 to 200 sec 1 3.0 W b03 B03 FLOW SPAN 1 to 3.0000 0 to 4 1.0000 W
3Xm3
3
(10
(liter) (10
)
-2
3
Xm)
b04 B04 FLOW UNIT (00) km
(01) m (02) l (03) cm
3
3
(04) M gal (05) k gal (06) gal (07) m gal (08) k bbl (09) bbl (10) m bbl (11) µ bbl (12) m (13) ft
b05 B05 TIME UNIT (00) / d / s W
(01) / h (02) / m (03) / s
b06 B06 SIZE UNIT (00) mm mm W
(01) inch b07 B07 NOMINAL SIZE 1 to 3000.0 1 100.0 W b08 B08 MF 0.2500 to 3.0000 1.000 W
Major parameter setting. Sets tag no. up to 16 characters. Sets damping time constant of output. Sets flow span in selected unit. Selects volume unit of flow span.
m
Selects time unit of flow span.
Selects flow tube nominal size unit.
Sets flow tube nominal size in selected unit. Sets meter factor.
b10 B10 OUTPUT FUNC (00) PULSE OUT PULSE W
(01) ALARM OUT OUT
(02) BI DIRECTION
(03) AUTO 2 RANGES
(04) LOW ALARM
(05) TOTAL SWITCH b11 B11 4 - 20 ALM OUT (00) 2.4 mA OR LESS 21.6 mA W
(01) 4.0 mA OR
(02) HOLD MORE
(03) 21.6 mA OR MORE b12 B12 POWER FREQ 47.00 to 63.00 Hz 2 50.00 W
Selects status output functions.
Selects current output during alarm occurrence.
Sets AC power frequency for DC power
11-3
IM 1E10C1-E
Page 96
11. PARAMETER LIST
Indicator Name R/W DescriptionData Range, Units
b13 B13 VELOCITY CHK 0 to 32.767 m/s 3 R b14 B14 FLOW DIR (00) FORWARD
b30 B30 REV.SPAN 1 to 3.0000 0 to 4 1.0000 W b31 B31 BI DIREC HYS 0 to 10% 2 W
b33 B33 FOR.SPAN2 1 to 3.0000 0 to 4 1.0000 W
b34 B34 AUTO RNG HYS 0 to 15% 10 W
b36 B36 LOW ALARM –10 to 110% –10 W b37 B37 L. ALARM HYS 0 to 15% 5 W — B60 SELF CHECK GOOD R
C00 ADJUST R C01 C01 ZERO TUNING (00) INHIBIT
C02 C02
C60 SELF CHECK GOOD R
D00 DISP SEL R d01 D01 DISP SELECT (00) RATE(%)
d02 D02 FL USER SEL (00)NOT PROVIDED NOT W
d03 D03 FL USER SPAN 0 to 3000 0 to 4 100 W
D10 FL USER UNIT
D60 SELF CHECK GOOD R
BRAIN
Terminal
MAGFLOW ZERO
(01) REVERSE
to
EEPROM DEFAULT
(01) ENABLE 0 to ±99.99 2 0.00 W
to
EEPROM DEFAULT
(01) RATE (02) FOR. TOTAL (03) REV. TOTAL (04) DIF. TOTAL (05) RATE(%) / FOR. TTL (06) RATE / FOR. TTL (07) RATE / RATE(%) (08) RATE(%) / REV. TTL (09) RATE / REV. TTL (10) RATE(%) / DIF.TTL (11) RATE / DIF.TTL
(01) PROVIDED
to
EEPROM DEFAULT
Decimal
Point
ASCII 8 characters
Default
Value
FORWARD
ENABLE
RATE(%)
PROVIDED
Displays span in m/s.
W
Selects flow direction.
Sets span for reverse direction. Sets hysteresis when change in flow
direction. Sets the second span for forward
direction. Sets hysteresis when change in Auto 2
ranges. Sets low limit alarm. Sets hysteresis for low limit alarm. Displays self-check result.
Automatic zero adjustment functions.
W
Inhibits or enables automatic zero adjustment.
Excecutes automatic zero adjustment and displays zero correction value.
Displays self-check result.
Display functions. Selects display items on flowmeter
W
indicator.
Selects whether “PV” is displayed with user-defined unit.
Sets value displayed in “PV” at 100% output when “Fl user sel” is provided.
Sets user-defined unit displayed in
W
“A20.” Displays self-check result.
11-4
IM 1E10C1-E
Page 97
11. PARAMETER LIST
Indicator Name R/W DescriptionData Range, Units
E00 TOTAL SET R E01 E01 TOTAL UNIT (00) n UNIT / P
E02 E02 TOTAL SCALE 0 to 3.0000 0 to 4 0 W E03 E03 E04 E04 TOTAL SET (00) INHIBIT
E05 E05 TL SET VALUE 0 to 999999 0 W
E06 E06 TOTAL SWITCH 0 to 999999 0 W
E10 TL USER UNIT ASCII 8 characters W — E60 SELF CHECK GOOD R
F00 PULSE SET R F01 F01 PULSE UNIT (00) n UNIT / P
F02 F02 PULSE SCALE 0 to 30000 0 to 4 0 W F03 F03 F04 F04 PULSE WIDTH (00) 50% DUTY
F60 SELF CHECK GOOD R
BRAIN
Terminal
TOTAL LOWCUT
PULSE LOWCUT
(01) µ UNIT / P (02) m UNIT / P (03) UNIT / P (04) k UNIT / P (05) M UNIT / P (06) PULSE / s
0 to 100% 3 W
(01) ENABLE
to
EEPROM DEFAULT
(01) µ UNIT / P (02) m UNIT / P (03) UNIT / P (04) k UNIT / P (05) M UNIT / P (06) PULSE / s
0 to 100% 3 W
(01) 0.5 ms (02) 1 ms (03) 20 ms (04) 33 ms (05) 50 ms (06) 100 ms
to
EEPROM DEFAULT
Decimal
Point
Default
Value
PULSE/s
INHIBIT
PULSE/s
50% DUTY
Totalization functions. Selects totalization rate unit. (“UNIT”
in the selection on the left represents the “Base vol unit” selected.)
Sets totalization rate. Sets low cut width of totalization. Inhibits or enables forward direction
W
totalization and reverse direction totalization from being preset and reset, respectively.
Sets forward direction totalization present value.
Set switching level when using status output function as totalization switch function.
Sets user-defined unit displayed in “A30.” Displays self-check result.
Pulse output functions. Selects pulse rate unit. (“UNIT” in the
W
selection on the left represents the “Base vol unit” selected.)
Sets pulse rate. Sets low cut width of pulse output. Selects pulse width.
W
Displays self-check result.
11-5
IM 1E10C1-E
Page 98
11. PARAMETER LIST
Indicator Name R/W DescriptionData Range, Units
G00 4 - 20 SET R G01 G01 4 - 20 LOW CUT 0 to 10% 0 W G02 G02 4 - 20 LOW LMT –20 to 100% –20 W G03 G03 4 - 20 H LMT 0 to 120% 120 W — G60 SELF CHECK GOOD R
H00 TEST R H01 H01 TEST MODE (00) NORMAL
H02 H02 OUTPUT VALUE –108 to 108 0 W H03 H03 STATUS OUT (00) NORMAL
H60 SELF CHECK GOOD R
L00 OTHER R L01 L01 TUNING (00)INHIBIT
L02 L02 KEY 00 0 W
L60 SELF CHECK GOOD R
N00 APPL SET n01 N01 TOTAL / PULSE (00) NO DAMP DAMP W
n02 N02 OUTPUT MODE (00) ON ON W
n03 N03 RATE LIMIT 0 to 10% 5 W
n04 N04 DEAD TIME 0 to 15 s 0 W
n05 N05 POWER SYNCH (00) YES YES W
n07 N07 EMPTY PIPE (00) ALARM NO W
N60 SELF CHECK GOOD
BRAIN
Terminal
to
EEPROM DEFAULT
(01) TEST
(01) CLOSED (ON) (02) OPEN (OFF)
to
EEPROM DEFAULT
(01) ENABLE
55 << TO “N” >>
to
EEPROM DEFAULT
(01) DAMP
(01) OFF
(01) NO
(01) NO ALARM ALARM
to
EEPROM DEFAULT
Decimal
Point
Default
Value
NORMAL
NORMAL
ENABLE
Current output functions. Sets low cut width of current output. Sets low limit of current output. Sets high limit of current output. Displays self-check result.
Output circuit test mode. Selects test mode.
W
Sets test output value. Selects test status output.
W
Displays self-check result.
Data setting restriction functions.
W
Inhibits or enables data setting with indicator switches or BT200.
Enables “N” items display. Sets “55” for access to “N” items.
Displays self-check result.
Special application. Selects whether instantaneous flow rate
values or damped ones are used for totalization and pulse output.
Selects active level of status output set in “B10.” (except “ALARM OUT”)
Sets the level to reduce output fluctua­tion.
Sets dead time to reduce output fluctua­tion. When “0” is set, “Rate limit” is not available.
Selects synchronization between excita­tion frequency and power frequency.
Selects alarm effectiveness when flow tube is not filled with fluid.
Displays self-check result.
11-6
IM 1E10C1-E
Page 99

11.2 Parameters for HART Communicator

This chapter describes ADMAG SE parameters for HART Communicator. Note the differences between parameters on ADMAG SE indicator and those on HART Commu­nicator.
Description of Items
11. PARAMETER LIST
Name
Data Range,
Units
Default
Value
R/W Description
Indicator
of SE
Parameter name
For numeric values, settable ranges are shown. For selection items, selectable items are shown. The figure in ( ) shows the number for selecting data on ADMAG SE indicator. The described number can be entered when ADMAG SE indicator is in the setting mode.
Default value is shown. *As for “Span”, “Pulse unit”, “Pulse scale”, “Total unit” and “Total scale”, the data specified at order have been already set.
R: Read only W: Write enabled
Describes the nature of the parameter.
Equivalent ADMAG SE indicator parameter number
11-7
IM 1E10C1-E
Page 100
11. PARAMETER LIST
List of Parameters for HART Communicator
Name Data Range, Units
PV –32400 to 32400 R Displays instantaneous flow rate in engineering unit. A20 Totl 0 to 999999 0 W Displays and presets forward direction totalized flow rate. A30 PV AO 2.40 to 21.6 mA R Displays current output. — Span 0.0001 to 30000 1.0000 W Sets flow span in selected unit. b03 Status group 1 Error R Displays self-diagnostics result.
µP fault “ON” shows error status. EEPROM fault “OFF” shows normal status. A/D fault See “8.2 Self-diagnostics Functions.” Signal overflow Coil open Vel. span> 10 m/s Vel. span< 0.3 m/s
Status group 2 P. span> 1000p/s R Ditto
P. span> 500p/s P. span> 25p/s P. span> 15p/s P. span> 10p/s P. span> 5p/s P. span< .0001p/s T. span> 1000p/s
Status group 3 T. span< .0001p/s R Ditto
Analog lmt error Empty pipe Multi range err Coil short EEPROM no set EEPROM default
Dev id not entered Self test W Excecutes self-diagnostics. — Auto zero W Executes automatic zero adjustment. C02
Zero tuning (00) Inhibit Enable W Inhibits or enables automatic zero adjustment. C01
(01) Enable D/A trim ZERO: 3.2 to 5.6 mA W Performs fine adjustments of zero and span of current output.
SPAN: 18.4 to 21.6 mA Scaled D/A trim ZERO: 3.2 to 5.6 mA W Performs fine adjustments of zero and span of scaled analog
SPAN: 18.4 to 21.6 mA output. Loop test 4 mA 4 mA W Sets test output value. H02
20 mA
Other (2.72 to 21.28 mA)
End Status out (00) Normal Normal W Selects test status output. H03
(01) Closed (on)
(02) Open (off) PV Unit gal/min m/s W Selects engineering unit of “PV”. Displays “Spcl” in case of
L/min setting unit except 5 units on the left.
Cum/h
ft/s
m/s
(Spcl)
Default
Value
R/W Description
Indicator
of SE
11-8
IM 1E10C1-E
Loading...