General
Specications
Model SDAU (Style R)
Digital Alarm Unit
GS 01B04K03-02E
GENERAL
The SDAU Digital Alarm Unit accepts two input signals
(freely selectable from 1 to 5 V, mV, thermocouple
and RTD), and six detection results in alarm detecting
sections are freely connected to AND or to OR. Then
they are output to alarm relays (two points, or four
points for option).
Each alarm detecting section detects upper limit and
lower limit alarms of input absolute value, input rateof-change and 2-input deviation. Either a normally
energized or de-energized is selectable for alarm
output relays.
The display setter on the front panel can display input
values and set/change parameters such as an alarm
setpoint. A PC (VJ77) or the JHT200 Handy Terminal
can also set/ change parameters.
With the VJ77 Parameter Setting Tool you can do the
following:
· Read/write all parameters at once
·Savereadparameterstoale
· Copy parameters to other devices of the same model
andsuxcode.
*1: The BT200 BRAIN Terminal of YOKOGAWA
Electric Corporation can also be connected.
The adapter for modular jack (E9786WH) is
required for connecting a PC (VJ77) or the
JHT200 Handy Terminal or BT200 to the Digital
Alarm Unit.
INPUT/OUTPUT SIGNALS
Input Signals:
DCV Input
Input Signal
DC Voltage
Input
Measuring
Range
1 to 5 V DC Input Resistance: 1 MΩ
-50 to 150 mV DC
Input Resistance:1 MΩ
Input External Resistance:
Remarks
500 Ω or less
*1: ITS-90, JIS’95
*2: ASTM E988 Standard: W97Re3-W75Re25
(tungsten97% rhenium3%-tungsten75%
rhenium25%)
*3: ASTM E988 Standard: W95Re5-W74Re26
(tungsten95% rhenium5%-tungsten74%
rhenium26%)
RTD Input
Input Signal Measuring Range (°C)
JPt100 (JIS’89) -200.0 to 510.0 °C
Pt100 (ITS-90, JIS’97) -200.0 to 850.0 °C
Pt100 (IPTS-68, JIS’89) -200.0 to 660.0 °C
Pt50 (JIS’81) -200.0 to 649.0 °C
Input lead resistance : 10 Ω/lead or less
Number of Input Points
• Two points each 1 to 5 V DC (not
Two points
(SDAU-1 type)
Two points
(SDAU-2 type)
isolated between inputs mutually) or
• One point 1 to 5 V DC, and one point
mV, thermocouple or RTD (isolated
between inputs mutually)
Two points each universal inputs
(not isolated between inputs mutually)
mV, thermocouple or RTD freely selectable
Thermocouple Input
Input Signal
(*1)
Type K
(*1)
Type T
(*1)
Type J
(*1)
Type E
(*1)
Type B
(*1)
Type R
(*1)
Type S
(*1)
Type N
Type W3
Type W5
(*2)
(*3)
Measuring
Range(°C)
-270.0 to 1372.0
-270.0 to 400.0
-210.0 to 1200.0
-270.0 to 1000.0
100.0 to 1820.0
-50.0 to 1768.0
-50.0 to 1768.0
-270.0 to 1300.0
0 to 2315
0 to 2315
Remarks
Input Resistance:
1 MΩ
Input External Resistance:
500 Ω or less
Output Signals: Relay contact
Contact Capacity
100V AC 2A (Resistive load)
220V AC 0.5A (Resistive load)
30V DC 2A (Resistive load)
125V DC 0.5A (Resistive load)
Contact life expectancy: 600,000 times
GS 01B04K03-02E
7th Edition Jan. 2021
Number of Output Points:
Two sets of transfer contacts
Four sets of NC or NO contacts when
Alarm Output
Failure Output
Retransmission
Output
(Option)
/RLY4 option is selected.
Specify normally energized/normally de-
energized by parameter.
One set of NC or NO contact
Always normally energized
Not available when /RLY4, /VLT or /CUR
option is selected.
One point 1 to 5 V DC or 4 to 20 mA DC
/VLT: 1 to 5 V DC
/CUR: 4 to 20 mA DC
Failure output is not available.
Can not be combined with /RLY4
ALARM FUNCTIONS
Alarm Detecting Sections 3 (each independent)
Input Mode
Alarm Setting Upper and lower limit values, -19999 to 32000 (in engineering units)
Hysteresis 0 to 32000 (in engineering units)
Rate-of-Change Alarm
Sampling Time
Alarm Output Sections
(each independent)
Alarm Output Connection Six detection results are freely connected to AND or to OR.
Alarm Timer Mode
Timer Setting
Direction of Relay Action Set normally energized / de-energized.
Contact
Indicator Lamp Yellow lamp (ALMn) lights up on alarm.
Input absolute alarm
2-input deviation alarm
Input rate-of-change alarm
1 to 9999 s
2 or 4 when /RLY4 option is selected.
Alarm output (delay) timer
ON/OFF delay timer
Alarm output timer
Alarm ON/OFF delay
(dead time) timer
Two sets of transfer contacts or
Four sets of NC or NO contacts when /RLY4 option is selected.
0 to 600 s (in 1-second increment)
However, about a 0.2 second delay is added to the above set time to
prevent wrong operation.
0 to 999 s (in 1-second increment)
2
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
ALARM FUNCTION BLOCK DIAGRAM
Note 2: Any of six types of HI Alarm / LO Alarm can be connected.
F01.ai
3
PV1 PV2
Alarm
Detecting
Section
Alarm
Connection/
Output
Section
Note 1: Select one of them to use.
Deviation
(PV1-PV2)
(Note 1)
Alarm
Detection 1
HI Alarm LO Alarm
(Note 2)
AND/OR Connection
Alarm timer
Alarm Output 1
Rate-of-
change
PV1
Rate-of-
change
PV2
(Same as Alarm
(Same as Alarm
Detection 1)
Alarm
Detection 2
HI Alarm LO Alarm
HI Alarm LO Alarm
/RLY4
only
(Same as
Alarm Output 1)
Alarm Output 2 Alarm Output 3 Alarm Output 4
(Same as
Alarm Output 1)
Alarm Output 1)
Detection 1)
Alarm
Detection 3
/RLY4
only
(Same as
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00