Yokogawa SDAU General Specifications

General
Specications
Model SDAU (Style R) Digital Alarm Unit
GS 01B04K03-02E
GENERAL
The SDAU Digital Alarm Unit accepts two input signals (freely selectable from 1 to 5 V, mV, thermocouple and RTD), and six detection results in alarm detecting sections are freely connected to AND or to OR. Then they are output to alarm relays (two points, or four points for option).
Each alarm detecting section detects upper limit and lower limit alarms of input absolute value, input rate­of-change and 2-input deviation. Either a normally energized or de-energized is selectable for alarm output relays.
The display setter on the front panel can display input values and set/change parameters such as an alarm setpoint. A PC (VJ77) or the JHT200 Handy Terminal can also set/ change parameters.
With the VJ77 Parameter Setting Tool you can do the following:
· Read/write all parameters at once
·Savereadparameterstoale
· Copy parameters to other devices of the same model
andsuxcode.
*1: The BT200 BRAIN Terminal of YOKOGAWA
Electric Corporation can also be connected. The adapter for modular jack (E9786WH) is required for connecting a PC (VJ77) or the JHT200 Handy Terminal or BT200 to the Digital Alarm Unit.
INPUT/OUTPUT SIGNALS
Input Signals:
DCV Input
Input Signal
DC Voltage Input
Measuring
Range
1 to 5 V DC Input Resistance: 1 MΩ
-50 to 150 mV DC
Input Resistance:1 MΩ
Input External Resistance:
Remarks
500 Ω or less
*1: ITS-90, JIS’95 *2: ASTM E988 Standard: W97Re3-W75Re25
(tungsten97% rhenium3%-tungsten75% rhenium25%)
*3: ASTM E988 Standard: W95Re5-W74Re26
(tungsten95% rhenium5%-tungsten74% rhenium26%)
RTD Input
Input Signal Measuring Range (°C)
JPt100 (JIS’89) -200.0 to 510.0 °C Pt100 (ITS-90, JIS’97) -200.0 to 850.0 °C Pt100 (IPTS-68, JIS’89) -200.0 to 660.0 °C Pt50 (JIS’81) -200.0 to 649.0 °C
Input lead resistance : 10 Ω/lead or less
Number of Input Points
• Two points each 1 to 5 V DC (not
Two points (SDAU-1 type)
Two points (SDAU-2 type)
isolated between inputs mutually) or
• One point 1 to 5 V DC, and one point mV, thermocouple or RTD (isolated between inputs mutually)
Two points each universal inputs (not isolated between inputs mutually) mV, thermocouple or RTD freely selectable
Thermocouple Input
Input Signal
(*1)
Type K
(*1)
Type T
(*1)
Type J
(*1)
Type E
(*1)
Type B
(*1)
Type R
(*1)
Type S
(*1)
Type N Type W3 Type W5
(*2)
(*3)
Measuring Range(°C)
-270.0 to 1372.0
-270.0 to 400.0
-210.0 to 1200.0
-270.0 to 1000.0
100.0 to 1820.0
-50.0 to 1768.0
-50.0 to 1768.0
-270.0 to 1300.0 0 to 2315 0 to 2315
Remarks
Input Resistance:
1 MΩ
Input External Resistance:
500 Ω or less
Output Signals: Relay contact
Contact Capacity
100V AC 2A (Resistive load) 220V AC 0.5A (Resistive load)
30V DC 2A (Resistive load)
125V DC 0.5A (Resistive load)
Contact life expectancy: 600,000 times
GS 01B04K03-02E
7th Edition Jan. 2021
Number of Output Points:
Two sets of transfer contacts Four sets of NC or NO contacts when
Alarm Output
Failure Output
Retransmission Output (Option)
/RLY4 option is selected. Specify normally energized/normally de-
energized by parameter. One set of NC or NO contact
Always normally energized
Not available when /RLY4, /VLT or /CUR
option is selected. One point 1 to 5 V DC or 4 to 20 mA DC
/VLT: 1 to 5 V DC /CUR: 4 to 20 mA DC
Failure output is not available.
Can not be combined with /RLY4
ALARM FUNCTIONS
Alarm Detecting Sections 3 (each independent)
Input Mode
Alarm Setting Upper and lower limit values, -19999 to 32000 (in engineering units) Hysteresis 0 to 32000 (in engineering units) Rate-of-Change Alarm
Sampling Time Alarm Output Sections
(each independent) Alarm Output Connection Six detection results are freely connected to AND or to OR.
Alarm Timer Mode
Timer Setting
Direction of Relay Action Set normally energized / de-energized.
Contact
Indicator Lamp Yellow lamp (ALMn) lights up on alarm.
Input absolute alarm 2-input deviation alarm Input rate-of-change alarm
1 to 9999 s
2 or 4 when /RLY4 option is selected.
Alarm output (delay) timer
ON/OFF delay timer
Alarm output timer
Alarm ON/OFF delay
(dead time) timer
Two sets of transfer contacts or
Four sets of NC or NO contacts when /RLY4 option is selected.
0 to 600 s (in 1-second increment) However, about a 0.2 second delay is added to the above set time to prevent wrong operation.
0 to 999 s (in 1-second increment)
2
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
ALARM FUNCTION BLOCK DIAGRAM
Note 2: Any of six types of HI Alarm / LO Alarm can be connected.
F01.ai
3
PV1 PV2
Alarm
Detecting
Section
Alarm
Connection/
Output Section
Note 1: Select one of them to use.
Deviation
(PV1-PV2)
(Note 1)
Alarm
Detection 1
HI Alarm LO Alarm
(Note 2)
AND/OR Connection
Alarm timer
Alarm Output 1
Rate-of-
change
PV1
Rate-of-
change
PV2
(Same as Alarm
(Same as Alarm
Detection 1)
Alarm
Detection 2
HI Alarm LO Alarm
HI Alarm LO Alarm
/RLY4
only
(Same as
Alarm Output 1)
Alarm Output 2 Alarm Output 3 Alarm Output 4
(Same as
Alarm Output 1)
Alarm Output 1)
Detection 1)
Alarm
Detection 3
/RLY4
only
(Same as
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
4
MOUNTING AND APPEARANCE
Mounting: Mount on an indoor rack. Signal Connection: M4 screw terminals Power Supply Connection: Grounded two-pole plug,
or M4 screw terminals
External Dimensions: 180 x 48 x 300 (mm)
(Height x Width x Depth from the mounting face)
Weight: Approx. 2 kg (including rack case)
DISPLAY FUNCTIONS
Display Setter: 5 digits, 2 lines, 11-segment LED
Indicator Lamps: For all except /RLY4 option
Alarm status indication: ALM1,2 (yellow) 2 FAIL status indication: F (red) 1
Error indication: E (yellow) 1
For /RLY4 option
Alarm action indication: ALM1,2,3,4 (yellow) 4
Example of Display Data
Parameter Code Description
PVn Displays PVn MODn Species input mode n nH Sets upper-limit alarm nH
nL Sets lower-limit alarm nL
AN.OR.n Species AND/OR connection
n: Number of input point, number of alarm detection
In engineering units: -19999 to 32000 Decimal point position selectable
or number of alarm connection.
SETTING FUNCTIONS
Parameters can be set using the following three ways. (1) Display setter on the front panel
(2) VJ77 Parameters Setting Tool or JHT 200 Handy
Terminal
*1: The BT200 BRAIN Terminal of YOKOGAWA
(3) RS-485 Communication (when /COM option is
specied)
Key switches 4 (→ (SHIFT), ↑ (INCR), SET, ) Setting enable switch 1
(*1)
Electric Corporation can also be connected. The adapter for modular jack (E9786WH) is required for connecting a PC (VJ77), the JHT200 Handy Terminal or BT200 to the Digital Alarm Unit.
NORMAL OPERATING CONDITIONS
Ambient Temperature
Ambient Humidity
Power Supply Voltage
0 to 50°C
5 to 90%RH (no condensation)
AC / DC both usage
100V version DC 20 to 130 V, no polarity
100V version AC
220V version DC
220V version AC
80 to 138 V, 47 to 63 Hz
120 to 340 V, no polarity
138 to 264 V, 47 to 63 Hz
STANDARD PERFORMANCE
Performance in the standard operating condition (at 23°C±2°C, 50±10%RH)
Input Accuracy See the table: Input accuracy in page 4. Alarm Action
Repeatability
E󰀨ect of ambient
temperature Maximum
Current or Power Consumption
Insulation Resistance
Withstanding Voltage
Burnout Time Within 60 s
Same as input accuracy
Twice of input accuracy / 10°C
240 mA for 24 V DC 17 VA for 100 V AC 22 VA for 220 V AC
Between I/O terminals and ground pin:
100 MΩ/500 V DC
Between power pins and ground pin:
100 MΩ/500 V DC
Between input terminal and ground pin:
500 V AC for 1 minute Between output terminal, power pins and ground pin: 1000 V AC for 1 minute (100 V version) 1500 V AC for 1 minute (220 V version)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
5
RECOVERY FROM POWER FAILURE
HOT Start: Continues the operation from the alarm
COLD Start: Power-on restart
* HOT start or COLD start is selectable by parameter.
Table: Input Accuracy
Input signal Accuracy
DCV input
T/C Accuracy (*
Type K
Type T
Type J
Type E
Type B
Type R
Type S
Type N
Type W3 0.0 to 2315.0 °C ±2.0 °C Type W5 0.0 to 2315.0 °C ±2.0 °C
JPt100 (JIS’89) -200.0 to 510.0 °C Pt100 (ITS-90,JIS’97) -200.0 to 850.0 °C Pt100 (IPTS-68,JIS’89) -200.0 to 660.0 °C Pt50 (JIS’81) -200.0 to 649.0 °C
(*1) Note 1: E󰀨ect of ambient temperature:
Note 2: For thermocouple inputs except type B, add
Add the following (1) or (2), whichever is the larger:
(1) All types except types R and S: 0.5°C Types R and S: 1°C (2) Multiply the value in (1) by K, where
status immediately prior to power failure. (Hot start cannot be made for input rate-of-change alarms. When the alarm timer mode is set to alarm output
timer, ALM3 and ALM4 cannot be HOT
started.)
1 to 5V DC ±0.1%
-50.0 to 150.0mV DC ±20µV
1)
-270.0 to 0 .0 °C ±{0.5+A
0.0 to 1300.0 °C ±0.5 °C
1300.0 to 1372.0 °C ±1.0 °C
-270.0 to 0.0 °C ±{0.3+A
0.0 to 400.0 °C ±0.3 °C
-210.0 to 0.0 °C ±{0.3+A
0.0 to 1100.0 °C ±0.3 °C
1100.0 to 1200.0 °C ±1.0 °C
-270.0 to 0.0 °C ±{0.3+A
0.0 to 900.0 °C ±0.3 °C
900.0 to 1000.0 °C ±1.0 °C
100.0 to 600.0 °C ±{3.0+A
600.0 to 1820.0 °C ±3.0 °C
-50.0 to 0.0 °C ±4.0 °C
0.0 to 400.0 °C ±2.0 °C
400.0 to 1768.0 °C ±1.0 °C
-50.0 to 0.0 °C ±4.0 °C
0.0 to 400.0 °C ±2.0 °C
400.0 to 1768.0 °C ±1.0 °C
-270.0 to 0.0 °C ±{1.0+A
0.0 to 1300.0 °C ±1.0 °C
RTD Accuracy
±0.01%/°C of measuring range
the reference junction compensation error (see below) to the accuracy above.
K=(Thermocouple output change/°C near normal
temperature) ÷ (Thermocouple output change
/°C near input temperature.)
(*2)
} °C
(*2)
} °C
(*2)
} °C
(*2)
} °C
(*3)
} °C
(*2)
} °C
±0.25°C
(*2) For measured temperatures below 0 °C, add the following A to the accuracy above.
- Measured temperature : -200 °C to below 0 °C A = 0.0025 x | measured temperature |
- Measured temperature : below -200 °C A = 0.1 x | measured temperature | (*3) For measured temperatures below 600 °C, add the following B to the accuracy above.
- Measured temperature : 300 °C to below 600 °C B = 0.02 x | measured temperature - 600 |
- Measured temperature : below 300 °C B = 0.1 x | measured temperature - 300 | + 6
SELF-DIAGNOSTIC FUNCTIONS
F Lamp ON: CPU failure, A/D conversion failure,
E Lamp ON: Input signal overrange
*1: When more than 106.25%, or -6.25% or less of
input range upper limit (RH) and input range lower
limit (RL).
Failure Output: Failure contact output when F
EEPROM failure, EEPROM SUM failure or RJC error
(*1)
, input
burnout, HOT start unavailable
lamp or E lamp lights up. However, failure output action is in E lamp ON selected by parameter. (Note: Only
when /CUR, /VLT or /RLY4 option is
not selected.)
CALIBRATION FUNCTIONS
Allow 0% and 100% points to be calibrated with an accuracy of 1% or better when input signal is 1 to 5 V by display setter on the front panel.
WIRING RESISTANCE CORRECTION
FUNCTIONS
If an error occurs because of input wiring resistance when mV DC, thermocouple or RTD input, input wiring resistance can be corrected.
OPTIONS
/A2ER: 220 V version with power supply plug /TB/A2: 220 V version power supply terminal /NHR: Without case /FBP: Power supply fuse bypass /LOCK: Power supply plug with lock /WSW: With spring washer /REK: Mount to same line with EK series rack /TB: With power supply terminal /VLT: With 1 to 5 V output /CUR: With 4 to 20 mA output /RLY4: Four points of alarm outputs /COM: With RS-485 communication function /BU: Burnout upscale /BD: Burnout downscale
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
COMMUNICATION FUNCTIONS
(/COM OPTION)
Input read and parameter read/write are possible.
Communication Interface: 1 channel
Standards: EIA RS-485 Communication System: 2-wire, half-duplex Baud Rate: 1200, 2400, 4800 and 9600 bps
Communication Protocol: MODBUS, PC link, and
Ladder
Maximum Units Connectable: 31 units Maximum Communication Distance: 1200 m Communication cable: Shielded twisted-pair cables
(AWG24 or the equivalent) for communication wiring cables.
RETRANSMISSION OUTPUT
FUNCTIONS (/VLT and /CUR OPTIONS)
/VLT: 1 to 5 V output of measured value or 2-input
deviation
/CUR: 4 to 20 mA output of measured value or
2-input deviation
6
Accuracy: ±0.1% of span
Load resistance:
2 kΩ or more
Accuracy: ±0.1% of span
Load resistance:
750 Ω or less
Retransmission Output Accuracy (Option)
1 to 5 V DC
(/VLT)
4 to 20 mA
(/CUR)
Retransmission Output Accuracy Guaranteed Range:
mV Input
Span 10 to 100 mV DC
Three times
Zero Elevation
the span, or within ±50 mV, whichever is the smaller
Retransmission output accuracy guaranteed range is
within the range above and within 0.0% to 100.0% of span.
Thermocouple
Input
10 to 63 mV (converted based on thermo electromotive force)
Three times the span, or within ±25 mV, whichever is the smaller
RTD Input
50 to 500°C
Within ve
times the span
ACCESSORIES
Label sheet: 1 sheet
Reference junction bracket :
For SDAU-120-xx*R/NHR or SDAU-270-xx*R/NHR
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
MODEL AND SUFFIX CODES
Model Su󰀩x Codes Optional Su󰀩x Codes Description
SDAU Digital Alarm Unit
Input Signal 2
Input Signal 1
Always 0 0 Always 0
Auxiliary Codes
Available Combination
Standard Specications:
SDAU-100, SDAU-110 SDAU-120, SDAU-130 SDAU-270
Auxiliary Codes: SDAU-100: -SV SDAU-110: -MV SDAU-120: from -TK to -TS SDAU-130: from -PA to -PD SDAU-270: -UN
Style Code *R Style R
Common Options
Note 1: /VLT, and /CUR options can be combined with only –UN auxiliary code.
/RLY4 option can be combined with only –SV or –UN auxiliary codes. /VLT, /CUR and RLY4 options can not be combined with each other.
Note 2: For two points of 1 to 5 V inputs (-SV), burnout upscale or burnout downscale is not selectable. Note 3: For universal inputs, 1 to 5 V is not selectable.
Note 4: Specify the option codes /TB and /A2 at the same time.
Note: There is no di󰀨erence between the latest and the previous temperature tables as far as applying them to the YEWSERIES.
- TC: Latest version; IEC60584-1: 2013/JIS C1602:2015 Previous version; IEC60584-1: 1995/JIS C1602:1995
- RTD Latest version; IEC60751- 2008/JIS C1604:2013 Previous version; IEC751- 1995/JIS C1604:1997
-1 Input signal 2: 1 to 5 V
-2 Input signal 2: Universal 0 1 to 5 V 1 mV 2 TC (Thermocouple) 3 RTD 7 Universal
(Note 3)
-SV Two points of 1 to 5 V inputs
-MV mV input
-TK Type K (ITS-90,JIS’95)
-TT Type T (ITS-90,JIS’95)
-TJ Type J (ITS-90,JIS’95)
-TE Type E (ITS-90,JIS’95)
-TB Type B (ITS-90,JIS’95)
-TR Type R (ITS-90,JIS’95)
-TS Type S (ITS-90,JIS’95)
-PA JPt 100 (JIS’89)
-PB Pt50 (JIS ’81)
-PD Pt100 (ITS-90, JIS’97)
-UN Universal (SDAU-270 only)
/A2ER 220 V version power supply plug /TB/A2 220 V version power supply terminal /NHR Without case /FBP Power supply fuse bypass /LOCK Power supply plug with lock /WSW With spring washer /REK Mount to same line with EK series rack /TB With power supply terminal /VLT With 1 to 5 V output
(Note 1)
/CUR With 4 to 20 mA output /RLY4 Four points of alarm outputs /COM With RS-485 communication function /BU Burnout upscale /BD Burnout downscale
(Note 2)
(Note 2)
(Note 1)
7
(Note 3)
(Note 3)
(Note 4)
(Note 1)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01B04K03-02E Jan.12, 2021-00
ORDERING INSTRUCTIONS
F02.ai
F03.ai
1. Model, su󰀩x codes and auxiliary codes, and optional su󰀩x codes if necessary
2. SDAU-110, -120, -130: Upper limit of input range (RH1), lower limit of input range (RL1). Specify RH1 and RL1 within the measuring range of Input/output signal specications, where RL1<RH1.
Initial values
RH1 parameter; 100.0 when mV input, maximum value of measuring range when temperature input RL1 parameter; 0.0 when mV input, minimum value of measuring range when temperature input
3. SDAU-270: Select the sensor type from the input signals in Input/Output Signals on Page 1. However, 1 to 5 V is
not selectable. Initial value: Pt100 (ITS90, JIS’97) (Note: Sensor type is selectable for input 1 and input 2 respectively.)
TERMINAL CONNECTIONS
● Input/Output Terminals
8
6
Terminal Designation
(*1)
Excluding /RLY4, /VLT and /CUR /RLY4 /VLT or /CUR
A
NC
B
COM NC, NO
C
COM
D
NC
F
COM
H J
NO
K
NO
1 2 3 4 5 6 7 8
*1: Terminal for connecting the reference junction bracket. *2: Switch NC/NO using jumper.
+
-
+
-
NC: Relay normally closed contact (closed when relay de-energized). NO: Relay normally open contact (open when relay de-energized).
Alarm output 1
(*2)
Failure output
Alarm output 2
1 to 5 V, mV, TC Input RTD Input
Input 1
Input 2
J K
B BDH
A
F
C
Refer to External Dimensions
1
5
3
4
2
8
7
● RS485 Communication Terminals (/COM Option)
NC, NO COM NC, NO COM NC, NO COM
COM NC, NO
Description
(*2)
(*2)
(*2)
(*2)
B+
A-
Alarm output 1
Alarm output 4
Alarm output 2
Alarm output 3
A
B
B
A B B
NC COM
+
-
NC COM
NO NO
Input 1
Alarm output 1
Retransmission output 1 to 5 V or 4 to 20 mA Alarm output 2
Input 2
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
COM
GS 01B04K03-02E Jan.12, 2021-00
<<Contents>> <<Index>>
Without/COM With/COM
F04.ai
Unit: mm
Without/COM With/COM
F05.ai
EXTERNAL DIMENSIONS
● Power Supply Plug Connection Type
9
9
180
Electric Electric
48
48 52 300
● Power Supply Terminal Type
Electric Electric
180
180
220V Power supply plug
180
100V Power supply plug
22 136
13622
48 48 71 300
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
Subject to change without notice.
Power supply terminals
GS 01B04K03-02E Jan.12, 2021-00
Loading...