Yokogawa EJX930A User Manual

User’s Manual
EJX910A and EJX930A Fieldbus Communication Type
IM 01C25R03-01E
IM 01C25R03-01E
10th Edition
EJX910A and EJX930A Fieldbus Communication Type
IM 01C25R03-01E 10th Edition
Contents
1. Introduction ............................................................................................... 1-1
Regarding This Manual ................................................................................................1-1
1.1 Safe Use of This Product ................................................................................. 1-2
1.2 Warranty .............................................................................................................1-3
1.3 ATEX Documentation .......................................................................................1-4
2. Handling Cautions .................................................................................... 2-1
2.1 Installation of an Explosion-Protected Instrument .......................................2-1
2.1.1 FM approval .......................................................................................2-1
2.1.2 CSA Certication ................................................................................2-5
2.1.3 ATEX Certication ..............................................................................2-6
2.1.4 IECEx Certication .............................................................................2-9
i
3. About Fieldbus ......................................................................................... 3-1
3.1 Outline ................................................................................................................ 3-1
3.2 Internal Structure of EJX Multivariable Transmitter ......................................3-1
3.2.1 System/network Management VFD ..................................................3-1
3.2.2 Function Block VFD ...........................................................................3-1
3.3 Logical Structure of Each Block .....................................................................3-2
3.4 Wiring System Conguration .......................................................................... 3-2
4. Getting Started .......................................................................................... 4-1
4.1 Connection of Devices .....................................................................................4-1
4.2 Host Setting .......................................................................................................4-2
4.3 Bus Power ON ...................................................................................................4-3
4.4 Integration of DD ...............................................................................................4-3
4.5 Setting Parameters with Using DTM ...............................................................4-4
4.6 Reading the Parameters ...................................................................................4-4
4.7 Continuous Record of Values .......................................................................... 4-4
4.8 Generation of Alarm ..........................................................................................4-4
5. Conguration ............................................................................................ 5-1
5.1 Network Design .................................................................................................5-1
5.2 Network Denition ............................................................................................5-1
5.3 Denition of Combining Function Blocks ...................................................... 5-2
5.4 Setting of Tags and Addresses .......................................................................5-3
10th Edition: June 2013 (YK) All Rights Reserved, Copyright © 2006, Yokogawa Electric Corporation
5.5 Communication Setting ...................................................................................5-4
5.5.1 VCR Setting .......................................................................................5-4
5.5.2 Function Block Execution Control ......................................................5-5
5.6 Block Setting .....................................................................................................5-5
5.6.1 Link Object .........................................................................................5-5
5.6.2 Trend Object ......................................................................................5-6
5.6.3 View Object ........................................................................................5-7
5.6.4 Function Block Parameters..............................................................5-12
6. Explanation of Basic Items...................................................................... 6-1
6.1 Outline ................................................................................................................ 6-1
6.2 Setting and Changing Parameters for the Whole Process .......................... 6-1
6.3 SENSOR Transducer Block ............................................................................. 6-1
6.3.1 Functional Block .................................................................................6-2
6.3.2 Block Mode ........................................................................................6-2
6.3.3 Functions Relating to Differential Pressure .......................................6-3
6.3.4 Functions Relating to Static Pressure................................................6-4
6.3.5 Functions Relating to External Temperature .....................................6-5
6.3.6 Simulation Function ...........................................................................6-5
6.3.7 Functions Relating to Capsule and Amplier Temperature ...............6-6
6.3.8 Functions Relating to Flange Temperature (option code: /DG1) .......6-7
6.3.9 BLOCK_ERR .....................................................................................6-7
6.3.10 XD_ERROR .......................................................................................6-7
6.4 FLOW Transducer Block ..................................................................................6-7
6.4.1 Outline of the Functions .....................................................................6-7
6.4.2 Block Mode ........................................................................................6-7
6.4.3 Calculation of the Flow .......................................................................6-7
6.4.4 Flow Unit/Decimal Point Digit ............................................................6-8
6.4.5 Flow Type Selection ...........................................................................6-8
6.4.6 BLOCK_ERR .....................................................................................6-8
6.4.7 XD_ERROR .......................................................................................6-8
6.5 LCD Transducer Block .....................................................................................6-9
6.5.1 Outline of the Functions .....................................................................6-9
6.5.2 Block Mode ........................................................................................6-9
6.5.3 Display Contents of the Integral Indicator ..........................................6-9
6.5.4 Example Displays of the Integral Indicator ......................................6-10
6.5.5 Procedure to Set the Built-in Display ............................................... 6-11
6.5.6 Units That Can Be Displayed on the LCD by the Automatic Link
Function ...........................................................................................6-13
6.6 AI Function Block ............................................................................................6-14
6.6.1 Function Blocks ................................................................................6-14
6.6.2 Block Mode ......................................................................................6-15
6.6.3 IO_OPTS .........................................................................................6-15
ii
6.6.4 STATUS_OPT ..................................................................................6-15
6.6.5 OUT_D .............................................................................................6-15
6.6.6 Basic Parameters of the AI Block.....................................................6-16
7. In-Process Operation ............................................................................... 7-1
7.1 Mode Transition ................................................................................................7-1
7.2 Generation of Alarm ..........................................................................................7-1
7.2.1 Indication of Alarm..............................................................................7-1
7.2.2 Alarms and Events .............................................................................7-1
7.3 Simulation Function ......................................................................................... 7-2
8. Device Information ................................................................................... 8-1
8.1 DEVICE STATUS ................................................................................................ 8-1
8.2 Status of Each Parameter in Failure Mode ..................................................... 8-4
9. Parameter Lists......................................................................................... 9-1
9.1 Resource Block .................................................................................................9-1
9.2 SENSOR Transducer Block ............................................................................. 9-3
9.3 FLOW Transducer Block ..................................................................................9-6
9.4 LCD Transducer Block .....................................................................................9-9
9.5 Al Function Block ............................................................................................9-12
9.6 Parameter Names Cross Reference .............................................................9-14
iii
10. General Specications .......................................................................... 10-1
10.1 Standard Specications .................................................................................10-1
10.2 Optional Specications ..................................................................................10-2
10.3 Optional Specications (For Explosion Protected type) ............................10-2
Appendix 1. Signal Characterizer (SC) Block .............................................A1-1
A1.1 Schematic Diagram of Signal Characterizer Block .................................... A1-1
A1.2 Input Section .................................................................................................. A1-2
A1.2.1 Determining the Mode .....................................................................A1-2
A1.2.2 Judging BLOCK_ERR .....................................................................A1-2
A1.3 Line-segment Factor Determination Section .............................................. A1-3
A1.3.1 Conditions for Conguring Valid Coefcients (CURVE_X, CURVE_Y)
.........................................................................................................A1-3
A1.4 List of Signal Characterizer Block Parameters .......................................... A1-4
A1.5 Application Example ..................................................................................... A1-5
A1.5.1 Input Compensation .........................................................................A1-5
A1.5.2 Calorie Flow Compensation ............................................................A1-5
A1.5.3 Backward Control ............................................................................A1-5
Appendix 2. Integrator (IT) Block .................................................................A2-1
A2.1 Schematic Diagram of Integrator Block ..................................................... A2-1
A2.2 Input Process Section ................................................................................... A2-2
A2.2.1 Determining Input Value Statuses ...................................................A2-2
A2.2.2 Converting the Rate .........................................................................A2-2
A2.2.3 Converting Accumulation .................................................................A2-3
A2.2.4 Determining the Input Flow Direction...............................................A2-3
A2.3 Adder ............................................................................................................... A2-3
A2.3.1 Status of Value After Addition ...........................................................A2-3
A2.3.2 Addition ............................................................................................A2-4
A2.4 Integrator ........................................................................................................ A2-4
A2.5 Output Process .............................................................................................. A2-5
A2.5.1 Status Determination .......................................................................A2-5
A2.5.2 Determining the Output Value ..........................................................A2-6
A2.5.3 Mode Handling ................................................................................A2-7
A2.6 Reset ................................................................................................................ A2-7
A2.6.1 Reset Trigger....................................................................................A2-7
A2.6.2 Reset Timing ....................................................................................A2-8
A2.6.3 Reset Process ..................................................................................A2-8
A2.7 List of Integrator Block Parameters ............................................................. A2-9
Appendix 3. Input Selector (IS) Block ..........................................................A3-1
A3.1 Input Selector Function Block Schematic .................................................. A3-1
A3.2 Input Section .................................................................................................. A3-3
A3.2.1 Mode Handling ................................................................................A3-3
A3.2.2 MIN_GOOD Handling .....................................................................A3-4
A3.3 Selection ........................................................................................................ A3-5
A3.3.1 OP_SELECT Handling ...................................................................A3-5
A3.3.2 SELECTION Handling ....................................................................A3-6
A3.4 Output Processing ...................................................................................... A3-12
A3.4.1 Handling of SELECTED ................................................................A3-12
A3.4.2 OUT Processing ............................................................................A3-13
A3.4.3 STATUS_OPTS ............................................................................A3-14
A3.5 List of Input Selector Block Parameters ................................................... A3-14
A3.6 Application Example ................................................................................... A3-16
iv
Appendix 4. Arithmetic (AR) Block .............................................................A4-1
A4.1 Arithmetic Function Block Schematic ........................................................ A4-1
A4.2 Input Section .................................................................................................. A4-2
A4.2.1 Main Inputs ......................................................................................A4-2
A4.2.2 Auxiliary Inputs ................................................................................A4-2
A4.2.3 INPUT_OPTS .................................................................................A4-3
A4.2.4 Relationship between the Main Inputs and PV ...............................A4-3
A4.3 Computation Section .................................................................................... A4-4
A4.3.1 Computing Equations .....................................................................A4-4
A4.3.2 Compensated Values ......................................................................A4-4
A4.3.3 Average Calculation ........................................................................A4-4
A4.4 Output Section .............................................................................................. A4-4
A4.4.1 Mode Handling ................................................................................A4-5
A4.4.2 Status Handling ...............................................................................A4-5
A4.5 List of the Arithmetic Block Parameters ..................................................... A4-6
Appendix 5. PID Block ...................................................................................A5-1
A5.1 Function Diagram .......................................................................................... A5-1
A5.2 Functions of PID Block .................................................................................. A5-1
A5.3 Parameters of PID Block ............................................................................... A5-2
A5.4 PID Computation Details ............................................................................... A5-4
A5.4.1 PV-proportional and -derivative Type PID (I-PD) Control Algorithm
.........................................................................................................A5-4
A5.4.2 PID Control Parameters ...................................................................A5-4
A5.5 Control Output ................................................................................................ A5-4
A5.5.1 Velocity Type Output Action .............................................................A5-4
A5.6 Direction of Control Action ........................................................................... A5-4
A5.7 Control Action Bypass .................................................................................. A5-5
A5.8 Feed-forward .................................................................................................. A5-5
A5.9 Block Modes ................................................................................................... A5-5
A5.9.1 Mode Transitions ..............................................................................A5-5
A5.10 Bumpless Transfer ......................................................................................... A5-6
A5.11 Setpoint Limiters ............................................................................................ A5-6
A5.11.1 When PID Block Is in Auto Mode .....................................................A5-6
A5.11.2 When PID Block Is in Cas or RCas Mode .......................................A5-6
A5.12 External-output Tracking .............................................................................. A5-7
A5.13 Measured-value Tracking .............................................................................. A5-7
A5.14 Initialization and Manual Fallback (IMan) .................................................... A5-7
A5.15 Manual Fallback ............................................................................................. A5-8
A5.16 Auto Fallback .................................................................................................. A5-8
A5.17 Mode Shedding upon Computer Failure ..................................................... A5-8
A5.17.1 SHED_OPT......................................................................................A5-8
A5.18 Alarms ............................................................................................................. A5-9
A5.18.1 Block Alarm (BLOCK_ALM) .............................................................A5-9
A5.18.2 Process Alarms ................................................................................A5-9
A5.19 Example of Block Connections .................................................................... A5-9
A5.20 View Object for PID Function Block ........................................................... A5-10
v
Appendix 6. Link Master Functions .............................................................A6-1
A6.1 Link Active Scheduler.................................................................................... A6-1
A6.2 Link Master ..................................................................................................... A6-1
A6.3 Transfer of LAS .............................................................................................. A6-2
A6.4 LM Functions .................................................................................................. A6-3
A6.5 LM Parameters ............................................................................................... A6-4
A6.5.1 LM Parameter List ............................................................................A6-4
A6.5.2 Descriptions for LM Parameters ......................................................A6-6
A6.6 FAQs ................................................................................................................ A6-8
Appendix 7. Software Download ..................................................................A7-1
A7.1 Benets of Software Download .................................................................... A7-1
A7.2 Specications ................................................................................................. A7-1
A7.3 Preparations for Software Downloading ..................................................... A7-1
A7.4 Software Download Sequence ..................................................................... A7-2
A7.5 Download Files ............................................................................................... A7-2
A7.6 Steps After Activating a Field Device........................................................... A7-3
A7.7 Troubleshooting ............................................................................................. A7-3
A7.8 Resource Block’s Parameters Relating to Software Download ............... A7-4
A7.9 System/Network Management VFD Parameters Relating to Software
Download ........................................................................................................ A7-5
A7.10 Comments on System/Network Management VFD Parameters Relating to
Software Download ....................................................................................... A7-6
Appendix 8. Advanced Diagnostics ............................................................A8-1
A8.1 Multi-sensing Process Monitoring ............................................................... A8-1
A8.2 Impulse Line Blockage Detection (ILBD) .................................................... A8-1
A8.2.1 Blockage Detection ..........................................................................A8-3
A8.2.2 Combination of Reference Result and Blockage Detection ............A8-5
A8.2.3 Operating Parameters .....................................................................A8-6
A8.2.4 Operating Procedure .......................................................................A8-7
A8.2.5 Alarm and Alert Setting ....................................................................A8-8
A8.2.6 Condition Check .............................................................................A8-10
A8.2.7 Obtain Reference Values ...............................................................A8-10
A8.2.8 Capability Test of Blockage Detection Operation ..........................A8-11
A8.2.9 Start ILBD Operation ......................................................................A8-12
A8.2.10 Tuning ............................................................................................A8-12
A8.2.11 Reset of Reference Value ..............................................................A8-13
A8.2.12 ILBD Parameter Lists .....................................................................A8-14
A8.2.13 Checklist .........................................................................................A8-17
A8.3 Heat Trace Monitoring ................................................................................. A8-22
A8.3.1 FLG_TEMP_COEF Setting ...........................................................A8-23
A8.3.2 Alert and Alarm Setting ..................................................................A8-23
A8.3.3 Assignment of FLG_TEMP_VAL to Process Value (PV) in AI Function
block ..............................................................................................A8-23
A8.3.4 Analog Alert ....................................................................................A8-23
A8.3.5 Out of Temperature Measurement Range .....................................A8-23
A8.3.6 Status Error ....................................................................................A8-24
A8.3.7 Parameter Lists for Heat Trace Monitoring Function .....................A8-24
vi
Revision Information
<1. Introduction>

1. Introduction

1-1
This manual is for the DPharp EJX Multivariable Transmitter Fieldbus Communication Type. The Fieldbus communication type is based on the same silicon resonant sensing technology used in the HART communication type, and is similar to the communication types in terms of basic performance and operation.
This manual describes only those topics that are required for operation of the Fieldbus communication type. For information on the installation, wiring, and maintenance of EJX series pressure transmitters, refer to the user’s manual for each model.
This IM is applicable for EJX910A and EJX930A whose device revision is ‘2.’ Device revision of the products can be conrmed on the Device Information sheet which is attached to the transmitter upon shipment. (See Figure 4.4)
Transmitter Handling IM 01C25R01-01E FSA110/FSA111 Versatile
Device Management Wizard (FieldMate)
FSA120 Flow Conguration Software (Flow Navigator)
IM 01R01A01-01E
IM 01C25R51-01E
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION

Regarding This Manual

• This manual should be passed on to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
<1. Introduction>
1-2

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process uids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process uids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the uid and the interior of the meter.
(c) Operation
• Wait 5 min. after the power is turned off, before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
• Users of explosion proof instruments should refer rst to section 2.1 (Installation of an Explosion Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
(f) Modication
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.
• All installation work shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please conrm that there is no current owing through the cables and that the power supply to the instrument is switched off.
<1. Introduction>

1.2 Warranty

• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
1-3
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
<1. Introduction>

1.3 ATEX Documentation

This is only applicable to the countries in the European Union.
1-4
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
P
F
D
S
SLO
H
BG
RO
M
GR
<2. Handling Cautions>

2. Handling Cautions

2-1
2.1 Installation of an Explosion­Protected Instrument
If a customer makes a repair or modication to an intrinsically safe or explosionproof instrument and the instrument is not restored to its original condition, its intrinsically safe or explosionproof construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modication to an instrument.
CAUTION
This instrument has been tested and certied as being intrinsically safe or explosionproof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
WARNING

2.1.1 FM approval

a. FM Explosionproof Type
Caution for FM Explosionproof type
Note 1. EJX multivariable transmitter with
optional code /FF1 is applicable for use in hazardous locations:
• Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.
• Enclosure rating: NEMA TYPE 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60ºC
• Supply Voltage: 32V dc max.
• Current Draw: 15 mA dc
Note 2. Wiring
• All wiring shall comply with National Electrical Code ANSI/NFPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Maintaining the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair. Please read the following sections very carefully.
WARNING
The range setting switch must not be used in a hazardous area.
IMPORTANT
All the blind plugs which accompany the EJX transmitters upon shipment from the factory are certied by the applicable agency in combination with the EJX series transmitters. The plugs which are marked with the symbols “◊ Ex” on their surfaces are certied only in combination with the EJX series transmitters.
Note 3. Operation
• Keep the “WARNING” nameplate attached to the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED, CONDUIT SEAL NOT REQUIRED. INSTALL IN ACCORDANCE WITH THE USERS MANUAL IM 01C25.
• Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
<2. Handling Cautions>
2-2
b. FM Intrinsically safe and Nonincendive
Type
EJX multivariable transmitter with optional code /FS15.
• Applicable standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA250, IEC60079-27
• FM Intrinsically Safe Approval
[Entity Model] Class I, II & III, Division 1, Groups A, B, C,
D, F & G, Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 0, AEx ia IIC, Temperature Class T4 Ta=60ºC, Type 4X
[FISCO Model] Class I, II & III, Division 1, Groups A, B, C,
D, F & G, Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 0, AEx ia IIC, Temperature Class T4 Ta=60ºC, Type 4X
• Nonincendive Approval
Class I, Division 2, Groups A, B, C & D
Temperature Class T4 Ta=60ºC, Type 4X and Class II, Division 2, Groups F & G Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 2, Group IIC, Temperature Class T4 Ta=60ºC, Type 4X and Class III, Division 1, Temperature Class T4 Ta=60ºC, Type 4X
• Electrical Connection: 1/2 NPT female, M20 female
• Caution for FM Intrinsically safe type. (Following contents refer to “DOC. No. IFM026-A12 p.1 to p.4.”)
■ IFM026-A12
Installation Diagram for Intrinsically safe (Division 1 Installation)
Terminator
+
Pressure
Transmitter
+
Field Instruments
+
Field Instruments
Hazardous Location
Terminator
+
Safety Barrier
+
Non-Hazardous Location
F0201.ai
Note 1. Barrier must be installed in an enclosure
that meets the requirements of ANSI/ISA 61010-1.
Note 2. Control equipment connected to the Associ
ated Apparatus must not use or generate more than 250 Vrms or Vdc.
Note 3. Installation should be in accordance
with ANSI/ISA 12.06.01 “Installation of Intrinsi cally Safe Systems for Hazardous (Classied) Locations” and the National Electrical Code (ANSI/NFPA 70) Sections 504 and 505.
Note 4. The conguration of Associated Apparatus
must be Factory Mutual Research Approved under FISCO Concept.
Note 5. Associated Apparatus manufacturer’s
installa tion drawing must be followed when installing this equipment.
Note 6. No revision to drawing without prior
Factory Mutual Research Approval.
Note 7. Terminator must be FM Approved.
Note 8. Note a warning label worded “SUBSTITU
TION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY”, and “INSTALL IN ACCORDANCE DOC.NO.IFM026-A12 P.1 TO 4.”
Electrical Data:
• Rating 1 (Entity) For Groups A, B, C, D, F, and G or Group IIC Maximum Input Voltage Vmax: 24 V Maximum Input Current Imax: 250 mA Maximum Input Power Pmax: 1.2 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 mH or
• Rating 2 (FISCO) For Groups A, B, C, D, F, and G or Group IIC Maximum Input Voltage Vmax: 17.5 V Maximum Input Current Imax: 380 mA Maximum Input Power Pmax: 5.32 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 mH or
• Rating 3 (FISCO) For Groups C, D, F, and G or Group IIB Maximum Input Voltage Vmax: 17.5 V Maximum Input Current Imax: 460 mA Maximum Input Power Pmax: 5.32 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 mH
<2. Handling Cautions>
2-3
Sensor Circuit: Uo=6.51 V, Io=4 mA, Po=6 mW, Co=34 µF, Lo=500 mH
Note: In the rating 1, the output current of the barrier must
be limited by a resistor “Ra” such that Io=Uo/Ra. In the rating 2 or 3, the output characteristics of the barrier must be the type of trapezoid which are certied as the FISCO model (See “FISCO Rules”). The safety barrier may include a terminator. More than one eld instruments may be connected to the power supply line.
FISCO Rules
The FISCO Concept allows the interconnection of intrinsincally safe apparatus to associated apparatus not specically examined in such combination. The criterion for such interconnection is that the voltage (Ui), the current (Ii) and the power (Pi) which intrinsically safe apparatus can receive and remain intrinsically safe, considering faults, must be equal or greater than the voltage (Uo, Voc, Vt), the current (Io, Isc, It) and the power (Po) which can be provided by the associated apparatus (supply unit).
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii
In addition, the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than the terminators) connected to the eldbus must be less than or equal to 5 nF and 10 µH respectively.
Ci ≤ 5nF, Li ≤ 10µH
In each I.S. eldbus segment only one active source, normally the associated apparatus, is allowed to provide the necessary power for the eldbus system. The allowed voltage(Uo, Voc,Vt) of the associated apparatus used to supply the bus cable must be limited to the range of 14 V dc to 17.5 V dc. All other equipment connected to the bus cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system, except to a leakage current of 50 µA for each connected device.
Supply unit
Trapezoidal or rectangular output characteristic only
Cable
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15...150 Ω/km Inductance per unit length L': 0.4...1 mH/km Capacitance per unit length C': 45...200 nF/km. C'=C' line/line + 0.5 C' line/screen, if both lines are oating or C'=C' line/line + C' line/screen, if the screen is connected to one line. Length of spur cable: max. 60 m Length of trunk cable: max. 1 km (Group IIC) or 5 km (Group IIB) Length of splice: max.1m
Terminators
At each end of the trunk cable an FM approved line terminator with the following parameters is suitable:
R = 90...100 Ω C = 0...2.2 mF
System evaluations
The number of passive device like transmitters, actuators, hand held terminals connected to a single bus segment is not limited due to I.S. reasons. Furthermore, if the above rules are respected, the inductance and capacitance of the cable need not to be considered and will not impair the intrinsic safety of the installation.
SAFE AREAHAZARDOUS AREA
Terminator (FISCO Model)
Ex i
Hand-
held-
Terminal
Field Instruments
(Passive)
I.S. eldbus system complying with FISCO model
Supply Unit and Safety Barrier (FISCO Model)
U
I
Terminator
Data
F0202.ai
U
Uo = 14...17.5 V (I.S. maximum value)
Io according to spark test result or other
assessment. No specication of Lo and Co is required on the certicate or label.
<2. Handling Cautions>
2-4
Installation Diagram for Nonincendive (Division 2 Installation)
Terminator
+
SUPPLY
Pressure Transmitter
+
Transmitter
+
Transmitter
Hazardous Location
Non-Hazardous Location
Terminator
FM Approved
+
General Purpose
Equipment
+
Associated Nonincendive Field Wiring Apparatus Vt or Voc It or Isc Ca La
F0203.ai
Note 1. Installation should be in accordance with
the National Electrical Code ® (ANSI/NFPA
70) Article 500.
Note 2. The conguration of Associated
Nonincendive Field Wiring Apparatus must be FM Approved.
Note 3. Approved under FNICO Concept.
Note 4. Dust-tight conduit seal must be used
when installed in Class II and Class III environments.
Note 5. Associated Apparatus manufacturer’s
installation drawing must be followed when installing this apparatus.
Note 6. No revision to drawing without prior FM
Approvals.
Note 7. Terminator must be FM Approved.
Note 8. The nonincendive eld wiring circuit
concept allows interconection of nonincendive eld wiring apparatus with associated nonincendive eld wiring apparatus, using any of the wiring methods permitted for unclassied locations.
Note 9. Installation requirements;
Vmax ≥ Voc or Vt Imax = see note 10. Ca ≥ Ci + Ccable La ≥ Li + Lcable
Note 10. For this current controlled circuit, the
parameter (Imax) is not required and need not be aligned with parameter (Isc) of the barrier or associated nonincendive eld wiring apparatus.
Note 11. If ordinary location wiring methods are
used, the transmitter shall be connected to FM Approved associated nonincendive eld wiring apparatus.
Electrical data:
Vmax: 32V Ci:1.76 nF Li: 0 µH
FNICO Rules
The FNICO Concept allows the interconnection of nonincendive eld wiring apparatus to associated nonincendive eld wiring apparatus not specically examined in such combination. The criterion for such interconnection is that the voltage (Vmax), the current (Imax) and the power (Pmax) which nonincendive eld wiring apparatus can receive and remain nonincendive, considering faults, must be equal or greater than the voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the power (Po) which can be provided by the associated nonincendive eld wiring apparatus (supply unit). In addition the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than terminators) connected to the Fieldbus must be less than or equal to 5nF and 20uH respectively.
In each N.I. Fieldbus segment only one active source, normally the associated nonincendive eld wiring apparatus, is allowed to provide the necessary power for the Fieldbus system. The allowed voltage (Uo, Voc or Vt) of the associated nonincendive eld wiring apparatus used to supply the bus cable must be limited to the range 14Vdc to 17.5Vdc. All other equipment connected to the bus cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system, except a leakage current of 50 µA for each connected device. Separately powered equipment needs galvanic isolation to ensure the nonincendive eld wiring Fieldbus circuit remains passive.
<2. Handling Cautions>
2-5
Cable
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15...150 Ω/km Inductance per unit length L': 0.4...1 mH/km
Capacitance per unit length C': 45....200 nF/km
C' =C' line/line+0.5 C' line/screen, if both lines are oating or C' = C' line/line + C' line/screen, if the screen is connected to one line. Length of spur cable: max. 60 m Length of trunk cable: max. 1 km (Group IIC) or 5 km (Group IIB) Length of splice: max = 1 m
Terminators
At the end of each trunk cable an FM Approved line terminator with the following parameters is suitable:
R= 90...100 Ω
C = 0 ....2.2 mF
2.1.2 CSA Certication
a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. EJX multivariable transmitter with
optional code /CF1 is applicable for use in hazardous locations:
Certicate: 2014354
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.61010.1-01, C22.2 No.60079-0, C22.2 No.60079-1
[For CSA C22.2]
• Explosion-proof for Class I, Groups B, C and D.
• Dustignition-proof for Class II/III, Groups E, F and G.
• Enclosure: TYPE 4X
• Temperature Code: T6...T4
[For CSA E60079]
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66 and IP67
• Maximum Process Temperature: 120ºC (T4), 100ºC (T5), 85ºC (T6)
• Ambient Temperature: –50* to 75ºC (T4), –50* to 80ºC (T5), –50* to 72ºC (T6)
* –15ºC when /HE is specied.
• Supply Voltage: 32 V dc max.
• Output Signal: 15 mA dc
Note 2. Wiring
• All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the gure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉÀ
MOINS DE 50cm DU BOîTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65ºC,
USE THE HEAT-RESISTING CABLES ≥ 90ºC.
QUAND LA TEMPÉRATURE AMBIANTE
≥ 65ºC, UTILISEZ DES CÂBLES RÉSISTANTES Á LA CHALEUR ≥ 90ºC.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Explosionproof Certication.
<2. Handling Cautions>
2-6
Non-Hazardous
Locations
Non-hazardous Location Equipment
32 V DC Max. 15 mA DC Signal
Non-Hazardous
Locations
Non-hazardous Location Equipment
32 V DC Max. 15 mA DC Signal
Hazardous Locations Division 1
50 cm Max.
PULSE
PULSE
SUPPLY
SUPPLY
CHECK
CHECK
ALARM
Sealing Fitting
Conduit
Multivariable Transmitter
Hazardous Locations Division 2
Sealing Fitting
Multivariable Transmitter
ALARM
PULSE
PULSE
SUPPLY
SUPPLY
CHECK
CHECK
ALARM
ALARM
F0204.ai
2.1.3 ATEX Certication
(1) Technical Data
a. ATEX Intrinsically Safe Type
Caution for ATEX Intrinsically safe type.
Note 1. EJX multivariable transmitter with optional
code /KS26 for potentially explosive atmospheres:
• No. KEMA 06ATEX0278 X
• Applicable Standard: EN 60079-0:2009, EN 60079-11:2012, EN 60079-26:2007
Note 2. Ratings
Type of Protection and Marking Code:
Ex ia IIC/IIB T4 Ga Ex ia IIIC T85°C T100°C T120°C Db
Group: II Category: 1G, 2D Ambient Temperature for EPL Ga:
–40 to 60°C
Ambient Temperature for EPL Db:
–30* to 60°C
* –15°C when /HE is specied.
Maximum Process Temperature (Tp.): 120°C Maximum Surface Temperature for EPL Db.
T85°C (Tp.: 80°C) T100°C (Tp.: 100°C) T120°C (Tp.: 120°C)
Ambient Humidity: 0 to 100% (No condensation) Degree of Protection of the Enclosure:
IP66/IP67
Electrical Data
• When combined with Trapezoidal or Rectanglar output characteristic FISCO model IIC barrier
[Supply circuit (terminals + and -)]
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W, Ci = 3.52 nF, Li = 0 µH
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W, Co = 4.8 µF, Lo = 100 mH
• When combined with Linear characteristic barrier
[Supply circuit (terminals + and -)]
Ui = 24 V, Ii = 250 mA, Pi = 1.2 W, Ci = 3.52 nF, Li = 0 µH
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W, Co = 4.8 µF, Lo = 100 mH
• When combined with Trapezoidal or Rectanglar output characteristic FISCO model IIB barrier
[Supply circuit (terminals + and -)]
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W, Ci = 3.52 nF, Li = 0 µH
[Sensor circuit]
Uo = 7.63 V, Io = 3.85 mA, Po = 0.008 W, Co = 4.8 µF, Lo = 100 mH
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void DEKRA Intrinsically safe Certication.
Note 5. Special Conditions for Safe Use
<2. Handling Cautions>
• In the rating 1(*1), the output current of the
WARNING
barrier must be limited by a resistor ‘Ra’ such that Io = Uo/Ra.
• In the case where the enclosure of the Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 1G apparatus is required, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
• Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the generation of electrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• In the case where the enclosure of the Pressure Transmitter is made of aluminum, if it is mounted in an area where the use of category 2D apparatus is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid ow of dust is avoided.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
• When the lightning protector option is specied, the apparatus is not capable of withstanding the 500V insulation test required by EN60079-11.
This must be taken into account when
installing the apparatus.
• In the rating 2(*2), the output of the barrier must be the characteristics of the trapezoid or the rectangle and this transmitter can be connected to Fieldbus equipment which are in according to the FISCO model.
• The terminators may be built in by a barrier.
• More than one transmitter may be connected to the power supply line.
• The terminator and the safety barrier shall be certied.
Electrical data: Supply circuit
Maximum Input Voltage Ui: 24 V Maximum Input Current Ii: 250 mA Maximum Input Power Pi: 1.2 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 μH
or Maximum Input Voltage Ui: 17.5 V Maximum Input Current Ii: 380 mA Maximum Input Power Pi: 5.32 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 μH
or Maximum Input Voltage Ui: 17.5 V Maximum Input Current Ii: 460 mA Maximum Input Power Pi: 5.32 W Maximum Internal Capacitance Ci: 3.52 nF Maximum Internal Inductance Li: 0 μH
Note 6. Installation instructions
[Installation Diagram]
Sensor circuit Maximum Output Voltage Uo: 7.63 V
Terminator
+
SUPPLY
RTD Pt100.3wire
Pressure
Transmitter
Maximum Output Current Io: 3.85 mA Maximum Output Power Po: 0.008 W Maximum Internal Capacitance Co: 4.8 μF Maximum Internal Inductance Lo: 100 mH
2-7
*1: Rating 1
*2: Rating 2
Terminator
+
Safety Barrier
+
+
Transmitter
+
Transmitter
Hazardous Location
Non-Hazardous Location
• RTD sensor is prepared by the user.
The sensor signal line must suited a test
voltage of 500Vac.
F0308.ai
<2. Handling Cautions>
b. ATEX Flameproof Type
Caution for ATEX ameproof type
WARNING
2-8
Note 1. Model EJX Series pressure transmitters
with optional code /KF22 for potentially explosive atmospheres:
• No. KEMA 07ATEX0109 X
• Applicable Standard: EN 60079-0:2009, EN 60079-1:2007, EN 60079-31:2009
• Type of Protection and Marking Code:
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
• Group: II
• Category: 2G, 2D
• Enclosure: IP66 / IP67
• Temperature Class for gas-poof: T6, T5, and T4
• Ambient Temperature for gas-proof: –50 to 75°C (T6), –50 to 80°C (T5), and –50 to 75°C (T4)
• Maximum Process Temperature (Tp.) for gas-proof:
85°C (T6), 100°C (T5), and 120°C (T4)
• Maximum Surface Temperature for dust­proof: T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specied.
• Electrostatic charge may cause an exlosion hazard. Avoid any actions that cause the gerenation of eletrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• In the case where the enclosure of the Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 2D apparatus is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid ow of dust is avoided.
• The instrument modication or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certication.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
(2) Electrical Connection
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation requirement.
• The cable entry devices shall be of a certied ameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the transmitter.
WARNING: AFTER DE-ENERGIZING,
DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP.≥65°C, USE HEAT-RESISTING CABLE AND CABLE GLAND ≥90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 5. Special Conditions for Safe Use
A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as follows.
MarkingScrew Size
ISO M20×1.5 female
ANSI 1/2 NPT female
Location of the mark
M
N or W
F0207.ai
(3) Installation
WARNING
• All wiring shall comply with local installation requirements and the local electrical code.
• There is no need for a conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory.
<2. Handling Cautions>
2-9
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER’S MANUAL
• Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in a hazardous location.
(5) Maintenance and Repair
WARNING
The instrument modication or part replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certication.
(6) Name Plate
● Name plate
MODEL: Specied model code. STYLE: Style code. SUFFIX: Specied sufx code. SUPPLY: Supply voltage. OUTPUT: Output signal. MWP: Maximum working pressure. CAL RNG: Specied calibration range. NO.: Serial number and year of production*1. TOKYO 180-8750 JAPAN: The manufacturer name and the address*2.
*1: The rst digit in the nal three numbers of the serial
number appearing after “NO.” on the name plate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010:
91K819857 032
The year 2010
*2: “180-8750” is the Zip code for the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identication number of Notied Body.
2.1.4 IECEx Certication
a. IECEx Flameproof Type
Tag plate for flameproof type
No. KEMA 07ATEX0109 X Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db Enlcosure : IP66, IP67 TEMP. CLASS T6 T5 T4 MAX PROCESS TEMP.(Tp.) 85 100 120 °C Tamb. -50 to 75 80 75 °C T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)
WARNING
D
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C POTENTIAL ELECTROSTATIC CHARGING HAZARD
*3
Tag plate for intrinsically safe type
No. KEMA 06ATEX0278 X Ex ia IIC/IIB T4 Ga Ta: -40 to 60°C Ex ia IIIC T85°C T100°C T120°C Db Ta: -30(-15) to 60°C MAX PROCESS TEMP.(Tp.): 120°C T85°C (Tp.: 80°C), T100°C (Tp.: 100°C), T120°C (Tp.: 120°C) ENCLOSURE: IP66/IP67 Supply circuit FISCO field device(IIC/IIB) Entity Parameter Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH Sensor circuit Uo=7.63V, Io=3.85mA, Po=0.008W, Co=4.8uF, Lo=100mH
*3
POTENTIAL ELECTROSTATIC CHARGING HAZARD-SEE USER'S MANUAL.
Caution for IECEx ameproof type.
Note 1. EJX multivariable transmitters with optional
code /SF2 are applicable for use in hazardous locations:
• No. IECEx CSA 07.0008
• Applicable Standard: IEC60079-0:2004, IEC60079-1:2003
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66 and IP67
• Maximum Process Temperature: 120ºC (T4), 100ºC (T5), 85ºC (T6)
• Ambient Temperature: –50 to 75ºC (T4), –50 to 80ºC (T5), –50 to 75ºC (T6)
• Supply Voltage: 32 V dc max.
• Output Signal: 15 mA dc
F0208.ai
<2. Handling Cautions>
Note 2. Wiring
• In hazardous locations, the cable entry devices shall be of a certied ameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable ameproof certied blanking elements.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65ºC,
USE THE HEAT-RESISTING CABLES ≥ 90ºC.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
2-10
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void IECEx Certication.
<3. About Fieldbus>

3. About Fieldbus

3-1

3.1 Outline

Fieldbus is a widely used bi-directional digital communication protocol for eld devices that enable the simultaneous output to many types of data to the process control system.
The EJX multivariable transmitter Fieldbus communication type employs the specication standardized by The Fieldbus Foundation, and provides interoperability between Yokogawa devices and those produced by other manufacturers. Fieldbus comes with software consisting of ve AI function blocks that enable the exible implementation of systems.
For information on other features, engineering, design, construction work, startup and maintenance of Fieldbus, refer to “Fieldbus Technical Information” (TI 38K03A01-01E).

3.2 Internal Structure of EJX Multivariable Transmitter

(2) SENSOR Transducer block
• Converts sensor output to pressure, static pressure, and capsule temperature signals, and transfers to the AI function blocks and ow transducer blok.
(3) FLOW Transducer block
• Accepts differential pressure, static pressure and external temperature data from the transducer block, calculates ow, and transfer to the AI function block.
(4) LCD Transducer block
• Controls the display of the integral indicator.
(5) AI function block
• Condition raw data from the Transducer block.
• Output differential pressure, static pressure and capsule temperature signals.
• Carry out scaling, damping and square root extraction.
(6) SC function block
The EJX Multivariable transmitter contains two virtual eld devices (VFD) that share the following functions.

3.2.1 System/network Management VFD

• Sets node addresses and Physical Device tags (PD Tag) necessary for communication.
• Controls the execution of function blocks.
• Manages operation parameters and communication resources (Virtual Communication Relationship: VCR).

3.2.2 Function Block VFD

(1) Resource block
• Manages the status of EJX hardware.
• Automatically informs the host of any detected faults or other problems.
• Converts the input signal value based on the segment table function.
(7) IT function block
• Integrates one or two input signals and outputs the result.
(8) IS function block
• Selects one of multiple input signals according to the specied selection method and outputs the signal.
(9) AR function block
• Performs ten types of calculations on a combination of two main input signals and three auxiliary input signals.
(10) PID function block
• Performs the PID control computation based on the deviation of the measured value from the setpoint.
<3. About Fieldbus>

3.3 Logical Structure of Each Block

EJX Multivariable Transmitter Fieldbus
LCD
Sensor
input
Sensor
System/network management VFD
PD Tag
Node address
Link Master
Function block VFD
LCD
Transducer block
Block tag
Parameters
Flow
Transducer block
Block tag
Parameters
SENSOR
Transducer block
Block tag
Parameters
Communication
parameters
VCR
Function block
execution schedule
PID function
block (option)
AR function
block
IS function
block
IT function
block
SC function
block
AI function
block
AI function
block
AI function
block
AI function
block
AI function
block
Block tag
Parameters
OUT_D
Output
OUT
3-2
Resource block
Block tag
Parameters
F0301.ai
Figure 3.1 Logical Structure of Each Block
Setting of various parameters, node addresses, and PD Tags shown in Figure 3.1 is required before starting operation.
3.4 Wiring System Conguration
The number of devices that can be connected to a single bus and the cable length vary depending on system design. When constructing systems, both the basic and overall design must be carefully considered to achieve optimal performance.
<4. Getting Started>

4. Getting Started

4-1
Fieldbus is fully dependent upon digital communication protocol and differs in operation from conventional 4 to 20 mA transmission and the HART communication protocol. It is recommended that novice users use eld devices in accordance with the procedures described in this section. The procedures assume that eld devices will be set up on a bench or in an instrument shop.

4.1 Connection of Devices

The following are required for use with Fieldbus devices:
• Power supply:
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
• Terminator:
period of within 5 cm (2 inches) may be used. Termination processing depends on the type of device being deployed. For EJX multivariable transmitter, use an M4 screw terminal claw. Some hosts require a connector.
Refer to Yokogawa when making arrangements to purchase the recommended equipment.
Connect the devices as shown in Figure 4.1. Connect the terminators at both ends of the trunk, with a minimum length of the spur laid for connection.
The polarity of signal and power must be maintained.
Fieldbus power supply
Terminator
EJX
HOST
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
• Field devices:
Connect Fieldbus communication type EJX multivariable transmitter. Two or more EJX devices or other devices can be connected.
• Host:
Used for accessing eld devices. A dedicated host (such as DCS) is used for an instrumentation line while dedicated communication tools are used for experimental purposes. For operation of the host, refer to the instruction manual for each host. No other details on the host are given in this manual.
• Cable:
Used for connecting devices. Refer to “Fieldbus Technical Information” (TI 38K03A01-01E) for details of instrumentation cabling. For laboratory or other experimental use, a twisted pair cable two to three meters in length with a cross section of 0.9 mm2 or more and a cycle
Figure 4.1 Cabling
RTD cable connection
Communication terminals connection hook
SUPPLY +
SUPPLY
SUPPLY
CHECK
PULSE
Figure 4.2 Terminal Conguration
+
Power supply and output terminal
– +
Not available for Fieldbus communication type
+ –
Ground terminal
PULSE
SUPPLY
CHECK
ALARM
PULSE − / CHECK
Terminator
F0401.ai
Check meter connection hook
PULSE +
CHECK +
F0404.ai
<4. Getting Started>
Table 4.1 Operation Parameters
NOTE
No CHECK terminal is used for Fieldbus EJX multivariable transmitter. Do not connect the eld indicator and check meter.
Before using a Fieldbus conguration tool other than the existing host, conrm it does not affect the loop functionality in which all devices are already installed in operation. Disconnect the relevant control loop from the bus if necessary.
IMPORTANT
Connecting a Fieldbus conguration tool to a loop with its existing host may cause communication data scrambling resulting in a functional disorder or a system failure.

4.2 Host Setting

To activate Fieldbus, the following settings are required for the host. Set the available address range to cover the address set for EJX multivariable transmitter's.
Symbol Parameter Description and Settings
V (ST) Slot-Time Indicates the time
necessary for immediate reply of the device. Unit of time is in octets (256 μs). Set maximum specication for all devices. For EJX, set a value of 4 or greater.
V (MID) Minimum-Inter-
PDU-Delay
V (MRD) Maximum-
Reply-Delay
V (FUN) First-Unpolled-
Node
V (NUN) Number-of-
consecutive­Unpolled-Node
Minimum value of communication data intervals. Unit of time is in octets (256 μs). Set the maximum specication for all devices. For EJX, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slot-time; set the value so that V (MRD) × V (ST) is the maximum value of the specication for all devices. For EJX, the setting must be a value of 12 or greater.
Indicate the address next to the address range used by the host. Set 0 × 15 or greater.
Unused address range.
IMPORTANT
0x00
Do not turn off the power immediately after setting. When the parameters are saved to the EEPROM, the redundant processing is executed for an improvement of reliability. If the power is turned off within 60 seconds after setting is made, the modied parameters are not saved and the settings may return to the original values.
V(FUN)
0x0F 0x10
0x13 0x14
Not used
Bridge device
LM device
Unused V(NUN)
4-2
V(FUN)+V(NUN)
0xF7 0xF8
0xFB 0xFC
0xFF
Note 1: Bridge device: A linking device which brings data
from one or more H1 networks.
Note 2: LM device: with bus control function
(Link Master function)
Note 3: BASIC device: without bus control function
Figure 4.3 Available Address Range
BASIC device
Default address
Portable device address
F0402.ai
<4. Getting Started>
4-3

4.3 Bus Power ON

Turn on the power of the host and the bus. Where the EJX multivariable transmitter is equipped with an LCD indicator, rst all segments are lit, then the display begins to operate. If the indicator is not lit, check the polarity of the power supply.
Using the host device display function, check that the EJX multivariable transmitter is in operation on the bus.
The device information, including PD tag, Node address, and Device ID, is described on the sheet attached to the device. The device information is given in duplicate on this sheet.
Device ID : 594543000EXXXXXXXX PD Tag : FT1001 Device Revision : 1 Node Address : 0xf5 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
DEVICE INFORMATION

4.4 Integration of DD

If the host supports DD (Device Description), the DD of the EJX multivariable transmitter needs to be installed. Check if host has the following directory under its default DD directory.
594543\000E
(594543 is the manufacturer number of Yokogawa Electric Corporation, and 000E is the EJX multivariable transmitter device number,
respectively.) If this directory is not found, the DD of the EJX910A has not been included. Create the above directory and copy the DD le (0m0n.ffo, 0m0n.sym) (m, n is a numeral) into the directory. "0m" in the le name shows the device revision, and "0n" shows the DD revision. If you do not have the DD or capabilities les, you can download them from our web site:
http://www.yokogawa.com/d/
Once the DD is installed in the directory, the name and attribute of all parameters of the EJX multivariable transmitter are displayed.
Off-line conguration is possible by using capabilities les.
Device ID : 594543000EXXXXXXXX PD Tag : FT1001 Device Revision : 1 Node Address : 0xf5 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English) or
http://www.yokogawa.co.jp/fld/ (Japanese)
DEVICE INFORMATION
F0403.ai
Figure 4.4 Device Information Sheet Attached to
EJX
If no EJX multivariable transmitter is detected, check the available address range and the polarity of the power supply. If the node address and PD tag are not specied when ordering, default value (0xF5) is factory set. If two or more devices are connected at a time with default value, only one device will detected from the host keep the default address and the others’ address will become default address of 0xF8 or later. Separately connect each device and set a different address for each.
EJX has two capabilities levels, "1" and "2".
Select "Capabilities level = 1" when the EJX don't have LC1(PID function) option.
Select "Capabilities level = 2" when the EJX has LC1(PID function) option.
The capabilities level denes the kind and the number of function blocks that can be used.
The table below shows the relation.
The relation between and function blocks that can be used
Capabilities
Level
1 5 1 1 1 1 0 2 5 1 1 1 1 1
AI SC IT IS AR PID
<4. Getting Started>

4.5 Setting Parameters with Using DTM

When setting parameters with using FieldMate (a software for conguring and adjusting the eld devices), please use applicable DTM (Device Type Manager) listed in below.
Table 4.2 DTM
DTM EJX Multivariable Transmitters
Name Model Device Type
EJX910
V2.1
EJX910A EJX930A
EJX910
(0x000E)
Device
Revision
2

4.6 Reading the Parameters

To read EJX multivariable transmitter parameters, select the AI1 block of the transmitter from the host screen and read the OUT parameter. The current selected signal is displayed. Check that MODE_ BLOCK of the function block and resource block is set to AUTO, and change the signal input and read the parameter again. A new designated value should be displayed.
4-4

4.7 Continuous Record of Values

If the host has a function that continuously records the indications, use this function to list the indications (values). Depending on the host being used, it may be necessary to set the schedule of Publish (the function that transmits the indication on a periodic basis).

4.8 Generation of Alarm

Generation of an alarm can be attempted from EJX multivariable transmitter. Block alarm, Output limit alarm, and Update alarm are informed to the host. When generating alarm, a Link Object and a VCR Static Entry need to be set. For details of Link Object and VCR Static Entry, refer to section 5.6.1 Link object and section 5.5.1 VCR Setting.
<5. Conguration>
5. Conguration
5-1
This chapter describes how to adapt the function and performance of the EJX multivariable transmitter to suit specic applications. Because multiple devices are connected to Fieldbus, it is important to carefully consider the device requirements and settings when conguring the system. The following steps must be taken.
(1) Network design
Determines the devices to be connected to Fieldbus and checks the capacity of the power supply.
(2) Network denition
Determines the tag and node addresses for all devices.
(3) Denition of combining function blocks
Determines how function blocks are combined.
(4) Setting tags and addresses
Sets the PD Tag and node addresses for each device.
(5) Communication setting
Sets the link between communication parameters and function blocks.
(6) Block setting
Sets the parameters for function blocks.
The following section describes in sequence each step of this procedure. The use of a dedicated conguration tool signicantly simplies this procedure. Refer to Appendix 6 when the EJX multivariable transmitter is used as Link Master.
• Terminator
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
• Field devices
Connect the eld devices necessary for instrumentation. The EJX multivariable transmitter has passed the interoperability test conducted by The Fieldbus Foundation. In order to properly start Fieldbus, it is recommended that the devices used satisfy the requirements of the above test.
• Host
Used for accessing eld devices. A minimum of one device with the bus control function is needed.
• Cable
Used for connecting devices. Refer to “Fieldbus Technical Information” for details of instrumentation cabling. Provide a cable sufciently long to connect all devices. For eld branch cabling, use terminal boards or a connection box as required.
First, check the capacity of the power supply. The power supply capacity must be greater than the sum of the maximum current consumed by all devices to be connected to Fieldbus. The maximum current consumed (power supply voltage 9 V to 32 V) for the EJX multivariable transmitter is 15 mA (24 mA in Software download operation). The cable used for the spur must be of the minimum possible length.

5.1 Network Design

Select the devices to be connected to the Fieldbus network. The following are essential for the operation of Fieldbus.
• Power supply
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
5.2 Network Denition
Before connection of devices with Fieldbus, dene the Fieldbus network. Allocate PD Tag and node addresses to all devices (excluding such passive devices as terminators).
The PD Tag is the same as the conventional one used for the device. Up to 32 alphanumeric characters may be used for denition. Use a hyphen as a delimiter as required.
<5. Conguration>
5-2
The node address is used to specify devices for communication purposes. Because this data is too long for a PD Tag, the host uses the node address in place of the PD Tag for communication. A range of 20 to 247 (or hexadecimal 14 to F7) can be set. The device (LM device) with bus control function (Link Master function) is allocated from a smaller address number (20) side, and other devices (BASIC device) without bus control function allocated from a larger address number (247) side respectively. Place the EJX multivariable transmitter in the range of the BASIC device. When the EJX multivariable transmitter is used as Link Master, place it in the range of the LM device. Set the range of addresses to be used to the LM device. Set the following parameters.
Table 5.1 Parameters for Setting Address Range
Symbol Parameters Description
V (FUN) First-Unpolled-
Node
V (NUN) Number-of-
consecutive­Unpolled-Node
Indicates the address next to the address range used for the host or other LM device.
Unused address range
The devices within the address range written as “Unused” in Figure 5.1 cannot be used on a Fieldbus. For other address ranges, the range is periodically checked to identify when a new device is mounted. Care must be taken to keep the unused device range as narrow as possible so as to lessen the load on the Fieldbus.
To ensure stable operation of Fieldbus, determine the operation parameters and set them to the LM devices. While the parameters in Table 5.2 are to be set, the worst-case value of all the devices to be connected to the same Fieldbus must be used. Refer to the specication of each device for details. Table 5.2 lists EJX specication values.
Table 5.2 Operation Parameter Values of the EJX
to be Set to LM Devices
Symbol Parameters
V (ST)
V (MID)
V (MRD)
Slot-Time Indicates the time
Minimum-Inter­PDU-Delay
Maximum­Reply-Delay
Description and
Settings
necessary for immediate reply of the device. Unit of time is in octets (256 μs). Set maximum specication for all devices. For EJX, set a value of 5 or greater.
Minimum value of communication data intervals. Unit of time is in octets (256 μs). Set the maximum specication for all devices. For EJX, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slottime; set the value so that V (MRD) × V (ST) is the maximum value of the specication for all devices. For EJX, the setting must be a value of 12 or greater.
0x00
Not used
0x0F 0x10
0x13 0x14
V(FUN)
V(FUN)+V(NUN)
0xF7 0xF8
0xFB 0xFC
0xFF
Figure 5.1 Available Range of Node Addresses
Bridge device
LM device
Unused V(NUN)
BASIC device
Default address
Portable device address
F0501.ai
5.3 Denition of Combining Function Blocks
The input/output parameters for function blocks are combined. As required, they can be combined with the input of the control block. The setting is written to the EJX link object. See “Block setting” in Section 5.6 for the details. It is also possible to read values from the host at proper intervals instead of connecting the EJX block output to other blocks.
The combined blocks need to be executed synchronously with other blocks on the communications schedule. In this case, change the EJX schedule according to the following table. The values in the table are factory-settings.
<5. Conguration>
5-3
Table 5.3 Execution Schedule of the EJX
Function Blocks
Index
269
MACROCYCLE_
(SM)
DURATION
Parameters
Setting (Enclosed is
factory-setting)
Cycle (MACROCYCLE) period of control or measurement. Unit is 1/32 ms. (16000 = 0.5 s)
276
(SM)
FB_START_ ENTRY.1
AI1 block startup time. Elapsed time from the start of MACROCYCLE specied in 1/32 ms. (0 = 0 s)
277
(SM)
FB_START_ ENTRY.2
AI2 block startup time. Elapsed time from the start of MACROCYCLE specified in 1/32 ms. (8000 = 250 ms)
278
(SM)
FB_START_ ENTRY.3
AI3 block startup time. Elapsed time from the start of MACROCYCLE specified in 1/32 ms. (16000 = 500 ms)
279
(SM)
FB_START_ ENTRY.4
AI4 block startup time. Elapsed time from the start of MACROCYCLE specified in 1/32 ms. (24000 = 750 ms)
280
to
289
(SM)
FB_START_ ENTRY.5 to FB_START_
Not used.
ENTRY.14
Macrocycle (Control Period)
LI100
OUT
Commu-
nication
Schedule
IN
LIC100
BKCAL_IN
FI100
OUT
CAS_IN
FIC100
IN
BKCAL_IN
Unscheduled
Communication
BKCAL_OUT
FC100
BKCAL_OUT
Scheduled Communication
F0503.ai
Figure 5.3 Function Block Schedule and
Communication Schedule
When the control period (macrocycle) is set to more than 4 seconds, set the following intervals to be more than 1% of the control period.
- Interval between “end of block execution” and “start of sending CD from LAS”
- Interval between “end of block execution” and “start of the next block execution”
A maximum of 30 ms is taken for execution of AI block. For scheduling of communications for combination with the next function block, the execution is so arranged as to start after a lapse of longer than 30 ms. In no case should function blocks of the EJX be executed at the same time (execution time is overlapped).
Figure 5.3 shows an example of schedule based on the loop shown in Figure 5.2.
LIC100
EJX
#1
LI100
EJX
#2
FI100
Figure 5.2 Example of Loop Connecting
Function Block of Two EJX with Other Instruments
FIC100
FC100
F0502.ai

5.4 Setting of Tags and Addresses

This section describes the steps in the procedure to set PD Tags and node addresses in the EJX multivariable transmitter. There are three states of Fieldbus devices as shown in Figure 5.4, and if the state is other than the lowest SM_OPERATIONAL state, no function block is executed. EJX must be transferred to this state when an EJX tag or address is changed.
UNINITIALIZED
(No tag nor address is set)
Tag clear Tag setting
INITIALIZED
(Only tag is set)
Address clear
SM_OPERATIONAL
(Tag and address are retained, and
the function block can be executed.)
Figure 5.4 Status Transition by Setting PD Tag and
Node Address
Address setting
F0504.ai
Loading...
+ 145 hidden pages