Yokogawa digitalYEWFLODY-FF User Manual

User’s
Model DY
Manual
Vortex Flowmeter Model DYA Vortex Flow Converter
OUNDATION Fieldbus Communication Type
F
IM 01F06F00-01EN
7th Edition
Model DY Vortex Flowmeter Model DYA Vortex Flow Converter
OUNDATION Fieldbus Communication Type
F
IM 01F06F00-01EN 7th Edition
Contents
1. INTRODUCTION ........................................................................................ 1-1
1.1 Using This Instrument Safety .......................................................................... 1-2
1.2 Warranty ............................................................................................................. 1-3
1.3 ATEX Documentation .......................................................................................1-4
2. AMPLIFIER FOR FIELDBUS COMMUNICATION ................................... 2-1
3. ABOUT FIELDBUS ................................................................................... 3-1
3.1 Outline ................................................................................................................ 3-1
3.2 Internal Structure of digitalYEWFLO ..............................................................3-1
3.2.1 System/Network Management VFD ..................................................3-1
3.2.2 Function Block VFD ........................................................................... 3-1
3.3 Logical Structure of Each Block ..................................................................... 3-2
3.4 Wiring System Confi guration ..........................................................................3-2
i
4. GETTING STARTED ................................................................................. 4-1
4.1 Connection of Devices ..................................................................................... 4-1
4.2 Host Setting ....................................................................................................... 4-2
4.3 Power-on of digitalYEWFLO and Bus............................................................. 4-2
4.4 Integration of DD ............................................................................................... 4-3
4.5 Reading the Parameters ................................................................................... 4-3
4.6 Continuous Record of Values .......................................................................... 4-3
4.7 Generation of Alarm .......................................................................................... 4-4
5. CONFIGURATION ..................................................................................... 5-1
5.1 Network Design ................................................................................................. 5-1
5.2 Network Defi nition ............................................................................................ 5-1
5.3 Function Block Link Defi nitions ......................................................................5-2
5.4
5.5 Communication Setting ................................................................................... 5-4
5.6 Block Setting ..................................................................................................... 5-6
Setting of Tags and Addresses .............................................................................. 5-3
5.5.1 VCR Setting ....................................................................................... 5-4
5.5.2 Function Block Execution Control ...................................................... 5-5
5.6.1 Link Objects ....................................................................................... 5-6
5.6.2 Trend Objects ..................................................................................... 5-6
5.6.3 View Objects ...................................................................................... 5-7
5.6.4 Function Block Parameters................................................................ 5-7
7th Edition: Oct. 2013 (KP) All Rights Reserved, Copyright © 2003, Yokogawa Electric Corporation
IM 01F06F00-01EN
6. EXPLANATION OF BASIC ITEMS ........................................................... 6-1
6.1 Setting and Changing Parameters for the Whole Process ..........................6-1
6.2 Transducer Block Parameters ......................................................................... 6-2
6.3 AI Function Block Parameters .........................................................................6-4
6.4 Parameters of DI Function Block .................................................................... 6-6
6.5 Integral LCD Indicator ...................................................................................... 6-6
7. IN-PROCESS OPERATION ...................................................................... 7-1
7.1 Mode Transition ................................................................................................ 7-1
7.2 Generation of Alarm .......................................................................................... 7-1
7.2.1 Indication of Alarm.............................................................................. 7-1
7.2.2 Alarms and Events ............................................................................. 7-3
7.3 Simulation Function ......................................................................................... 7-3
8. DEVICE STATUS ....................................................................................... 8-1
9. GENERAL SPECIFICATIONS .................................................................. 9-1
9.1 Standard Specifi cations ................................................................................... 9-1
9.2 Model and Suffi x Codes ................................................................................... 9-3
9.3 Optional Specifi cations .................................................................................... 9-3
ii
10. EXPLOSION PROTECTED TYPE INSTRUMENT ................................. 10-1
10.1 ATEX ................................................................................................................. 10-1
10.2 FM ..................................................................................................................... 10-5
10.3 IECEx .............................................................................................................. 10-11
10.4 CSA .................................................................................................................10-13
10.5 TIIS ..................................................................................................................10-14
APPENDIX 1. LIST OF PARAMETERS
FOR EACH BLOCK OF digitalYEWFLO ...............................................A1-1
A1.1 Resource Block .................................................................................................... A1-1
A1.2 Al Function Block ................................................................................................. A1-3
A1.3 Transducer Block ................................................................................................. A1-6
A1.4 DI Function Block ................................................................................................A1-11
APPENDIX 2. APPLICATION, SETTING AND CHANGE OF BASIC
PARAMETERS ........................................................................................A2-1
A2.1 Applications and Selection of Basic Parameters ............................................. A2-1
A2.2 Setting and Change of
Basic Parameters ........................................................................................... A2-2
A2.3 Setting the AI Function Blocks ........................................................................... A2-2
A2.4 Setting the Transducer Block ............................................................................. A2-4
A2.5 Setting the DI Function Blocks ........................................................................... A2-6
APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE ...A3-1
APPENDIX 4. FUNCTION DIAGRAMS OF FUNCTION BLOCKS .................A4-1
A4.1 AI Function Block ........................................................................................... A4-1
A4.2 DI Function Block ........................................................................................... A4-1
IM 01F06F00-01EN
APPENDIX 5. INTEGRATOR (IT) BLOCK .......................................................A5-1
A5.1 Schematic Diagram of Integrator Block ..................................................... A5-1
A5.2 Input Process Section ................................................................................... A5-2
A5.2.1 Determining Input Value Statuses ...................................................A5-2
A5.2.2 Converting the Rate .........................................................................A5-2
A5.2.3 Converting Accumulation .................................................................A5-3
A5.2.4 Determining the Input Flow Direction...............................................A5-3
A5.3 Adder ............................................................................................................... A5-4
A5.3.1 Status of Value after Addition ...........................................................A5-4
A5.3.2 Addition ............................................................................................A5-4
A5.4 Integrator ........................................................................................................ A5-4
A5.5 Output Process .............................................................................................. A5-6
A5.5.1 Status Determination .......................................................................A5-6
A5.5.2 Determining the Output Value ..........................................................A5-7
A5.5.3 Mode Handling ................................................................................A5-8
A5.6 Reset ................................................................................................................ A5-8
A5.6.1 Reset Trigger....................................................................................A5-8
A5.6.2 Reset Timing ....................................................................................A5-8
A5.6.3 Reset Process ..................................................................................A5-9
A5.7 List of Integrator Block Parameters ........................................................... A5-10
iii
APPENDIX 6. Enhanced ARITHMETIC (AR) BLOCK ...................................A6-1
A6.1 Schematic Diagram of Arithmetic Block ................................................... A6-1
A6.2 Input Section .................................................................................................. A6-2
A6.2.1 Main Inputs ......................................................................................A6-2
A6.2.2 Auxiliary Inputs ................................................................................A6-2
A6.2.3 INPUT_OPTS .................................................................................A6-3
A6.2.4 Relationship between the Main Inputs and PV ...............................A6-3
A6.3 Computation Section .................................................................................... A6-4
A6.3.1 Computing Equations .....................................................................A6-4
A6.3.2 Enhanced Computing Equations ....................................................A6-4
A6.3.3 Compensated Values ......................................................................A6-5
A6.3.4 Average Calculation ........................................................................A6-5
A6.4 Output Section .............................................................................................. A6-5
A6.4.1 Mode Handling ................................................................................A6-6
A6.4.2 Status Handling ...............................................................................A6-6
A6.5 List of the Arithmetic Block Parameters ..................................................... A6-7
A6.6 Example of Connection ................................................................................. A6-9
A6.7 Setting Procedure of the Mass Flow Rate Calculation ............................ A6-10
IM 01F06F00-01EN
APPENDIX 7. LINK MASTER FUNCTIONS ....................................................A7-1
A7.1 Link Active Scheduler.................................................................................... A7-1
A7.2 Link Master ..................................................................................................... A7-1
A7.3 Transfer of LAS .............................................................................................. A7-2
A7.4 LM Functions .................................................................................................. A7-3
A7.5 LM Parameters ............................................................................................... A7-4
A7.5.1 LM Parameter List ............................................................................A7-4
A7.5.2 Descriptions for LM Parameters ......................................................A7-6
A7.6 Trouble Shooting ........................................................................................... A7-8
APPENDIX 8. PID BLOCK ................................................................................A8-1
A8.1 Function Diagram .......................................................................................... A8-1
A8.2 Functions of PID Block .................................................................................. A8-1
A8.3 Parameters of PID Block ............................................................................... A8-2
A8.4 PID Computation Details ............................................................................... A8-4
A8.5 Control Output ................................................................................................ A8-4
A8.6 Direction of Control Action ........................................................................... A8-4
A8.7 Control Action Bypass .................................................................................. A8-5
A8.8 Feed-forward .................................................................................................. A8-5
A8.9 Block Modes ................................................................................................... A8-5
A8.10 Bumpless Transfer ......................................................................................... A8-6
A8.11 Setpoint Limiters ............................................................................................ A8-6
A8.11.1 When PID Block is in AUTO Mode ..................................................A8-6
A8.11.2 When PID Block is in CAS or RCAS Mode......................................A8-6
A8.12 External-output Tracking .............................................................................. A8-7
A8.13 Measured-value Tracking .............................................................................. A8-7
A8.14 Initialization and Manual Fallback (IMAN) ................................................... A8-7
A8.15 Manual Fallback ............................................................................................. A8-8
A8.16 Auto Fallback .................................................................................................. A8-8
A8.17 Mode Shedding upon Computer Failure ..................................................... A8-8
A8.18 Alarms ............................................................................................................. A8-9
A8.18.1 Block Alarm (BLOCK_ALM) .............................................................A8-9
A8.18.2 Process Alarms ................................................................................A8-9
A8.19
Example of Block Connections ............................................................................. A8-10
iv
APPENDIX 9. DD MENU ...................................................................................A9-1
APPENDIX 10. METHOD ................................................................................A10-1
A10.1 Transducer Block ......................................................................................... A10-1
A10.2 Enhanced AR Block ..................................................................................... A10-5
IM 01F06F00-01EN
APPENDIX 11. SOFTWARE DOWNLOAD (Option /EE) ..............................A11-1
A11.1 Benefi ts of Software Download ...................................................................A11-1
A11.2 Specifi cations ................................................................................................A11-1
A11.3 Preparations for Software Downloading ....................................................A11-1
A11.4 Software Download Sequence ....................................................................A11-2
A11.5 Download Files ..............................................................................................A11-2
A11.6 Steps after Activating a Field Device ..........................................................A11-3
A11.7 Troubleshooting ............................................................................................A11-4
A11.8 Resource Block’s Parameters Relating to Software Download ..............A11-4
A11.9 System/Network Management VFD Parameters Relating to Software
Download .......................................................................................................A11-6
A11.9.1 Parameter List ................................................................................ A11-6
A11.9.2 Descriptions for Parameters .......................................................... A11-7
APPENDIX 12. DEVICEVIEWER WINDOW EXECUTED FROM PRM
(Plant Resource Manager) ...................................................................A12-1
Revision Information ...............................................................................................i
v
IM 01F06F00-01EN
<1. INTRODUCTION>

1. INTRODUCTION

1-1
Thank you for purchasing FOUNDATION Fieldbus communication type of digitalYEWFLO vortex owmeter. To ensure correct use of the instrument, please read this manual thoroughly and fully understand how to operate the instrument before operating it.
This manual describes only those topics that are required for operation of the FOUNDATION Fieldbus communication type. For other topics, please refer to User’s Manual for vortex fl owmeter (IM 01F06A00-01EN). Regarding identical items, this manual has priority over IM 01F06A00-01EN.
Regarding This Manual
• This manual should be provided to the end user.
• The contents of this manual may be changed without prior notice.
• All rights are reserved. No part of this manual may be reproduced in any form without Yokogawa's written permission.
• Yokogawa makes no warranty of any kind with regard to this material, including, but not limited to, implied warranties of merchantability and suitability for a particular purpose.
• All reasonable effort has been made to ensure the accuracy of the contents of this manual. However, if any errors or omissions are found, please inform Yokogawa.
• The specifi cations covered by this manual are limited to those for the standard type under the specifi ed model number break-down and do not cover custom-made instruments.
• Please note that this manual may not be revised for any specifi cation changes, construction changes or operating part changes that are not considered to affect function or performance.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
Safety and Modi cation Precautions
• The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specifi c WARNINGS given elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. Yokogawa assumes no liability for the customer's failure to comply with these requirements. If this instrument is used in a manner not specifi ed in this manual, the protection provided by this instrument may be impaired.
• Yokogawa will not be liable for malfunctions or damage resulting from any modifi cation made to this instrument by the customer.
• The following safety symbol marks are used in this manual and instrument.
WARNING
A WARNING sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in injury or death of personnel.
CAUTION
A CAUTION sign denotes a hazard. It calls attention to procedure, practice, condition or the like, which, if not correctly performed or adhered to, could result in damage to or destruction of the product.
IMPORTANT
An IMPORTANT sign denotes that attention is required to avoid damage to the instrument or system failure.
NOTE
A NOTE sign denotes information necessary for essential understanding of operation and features.
IM 01F06F00-01EN
<1. INTRODUCTION>
1-2

1.1 Using This Instrument Safety

(1) Installation
WARNING
• Installation of the vortex fl owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to installation.
• The vortex fl owmeter must be installed within the specifi cation conditions.
• The vortex fl owmeter is a heavy instrument. Be careful that no damage is caused to personnel through accidentally dropping it, or by exerting excessive force on the vortex fl owmeter. When moving the vortex owmeter, always use a trolley and have at least two people carry it.
• When the vortex fl owmeter is processing hot fl uids, the instrument itself may become extremely hot. Take suffi cient care not to get burnt.
• Where the fl uid being processed is a toxic substance, avoid contact with the fl uid and avoid inhaling any residual gas, even after the instrument has been taken off the piping line for maintenance and so forth.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• Do not apply excessive weight, for example, a person stepping on the vortex fl owmeter.
• All procedures relating to installation must comply with the electrical code of the country where it is used.
(2) Wiring
WARNING
• The wiring of the vortex fl owmeter must be performed by expert engineer or skilled personnel. No operator shall be permitted to perform procedures relating to wiring.
• When connecting the wiring, check that the supply voltage is within the range of the voltage specifi ed for this instrument before connecting the power cable. In addition, check that no voltage is applied to the power cable before connecting the wiring.
(3) Operation
WARNING
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• When opening the cover, wait for more than 3 minutes after turning off the power.
(4) Maintenance
WARNING
• Maintenance of the vortex fl owmeter should be performed by the trained personnel having knowledge of safety standard. No operator shall be permitted to perform any operations relating to maintenance.
• Do not open the cover in wet weather or humid environment. When the cover is open, stated enclosure protection is not applicable.
• When opening the cover, wait for more than 3 minutes after turning off the power.
• Always conform to maintenance procedures outlined in this manual. If necessary, contact Yokogawa.
(5) Explosion Protected Type Instrument
WARNING
• The instruments are products which have been certifi ed as explosion proof type instruments. Strict limitations are applied to the structures, installation locations, external wiring work, maintenance and repairs, etc. of these instruments. Suffi cient care must be taken, as any violation of the limitations may cause dangerous situations. Be sure to read Chapter 10 “EXPLOSION PROTECTED TYPE INSTRUMENT” before handling the instruments. For TIIS ameproof type instruments, be sure to read “INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT” at the end of manual for the vortex fl owmeter (IM 01F06A00-01EN).
• Only trained persons use this instrument in the industrial location.
• Take care not to generate mechanical spark when access to the instrument and peripheral devices in hazardous locations.
IM 01F06F00-01EN
<1. INTRODUCTION>

1.2 Warranty

• The terms of this instrument that are guaranteed are described in the quotation. We will make any repairs that may become necessary during the guaranteed term free of charge.
• Please contact our sales offi ce if this instrument requires repair.
• If the instrument is faulty, contact us with concrete details about the problem and the length of time it has been faulty, and state the model and serial number. We would appreciate the inclusion of drawings or additional information.
• The results of our examination will determine whether the meter will be repaired free of charge or on an at-cost basis.
The guarantee will not apply in the
following cases:
• Damage due to negligence or insuffi cient maintenance on the part of the customer.
• Problems or damage resulting from handling, operation or storage that violates the intended use and specifi cations.
• Problems that result from using or performing maintenance on the instrument in a location that does not comply with the installation location specifi ed by Yokogawa.
• Problems or damage resulting from repairs or modifi cations not performed by Yokogawa or someone authorized by Yokogawa.
• Problems or damage resulting from inappropriate reinstallation after delivery.
• Problems or damage resulting from disasters such as fi res, earthquakes, storms, fl oods, or lightning strikes and external causes.
1-3
Trademarks:
• ‘digitalYEWFLO’, ‘DY’, ‘DYA’, ‘DYC’ and ‘BRAIN TERMINAL’ are registered trademarks of Yokogawa Electric Corporation. Company names and product names used in this material are registered trademarks or trademarks of their respective owners.
• In this manual, trademarks or registered trademarks are not marked with ™ or ®.
IM 01F06F00-01EN
<1. INTRODUCTION>

1.3 ATEX Documentation

This is only applicable to the countries in European Union.
1-4
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
P
F
D
S
SLO
H
BG
RO
M
GR
IM 01F06F00-01EN
<2. AMPLIFIER FOR FIELDBUS COMMUNICATION>

2. AMPLIFIER FOR FIELDBUS COMMUNICATION

Refer to IM 01F06A00-01EN for the details of the amplifier. This section encompasses topics applicable to only the Fieldbus communication type.
(1) The Fieldbus communication type has no local
key access function.
(2) The Fieldbus communication type has no
BT200 (BRAIN TERMINAL) connection pin.
(3) The Fieldbus communication type has a
simulation function. The SIMULATE_ENABLE switch is mounted on the amplifi er. Refer to Section 7.3 “Simulation Function” for details of the simulation function.
Amplifier unit
2-1
SIMULATE_ENABLE switch
2 1
Figure 2.1 Amplifi er for Fieldbus Communication
F0201.ai
IM 01F06F00-01EN
<3. ABOUT FIELDBUS>

3. ABOUT FIELDBUS

3-1

3.1 Outline

Fieldbus is a bi-directional digital communication protocol for fi eld devices, which offers an advancement in implementation technologies for process control systems and is widely employed by numerous fi eld devices. The Fieldbus communication type of the digitalYEWFLO employs the specifi cation standardized by the Fieldbus FOUNDATION, and provides interoperability between Yokogawa devices and those produced by other manufacturers. Featuring two AI and two DI function blocks in each, the Fieldbus communication type’s software enables a fl exible instrumentation system to be implemented. For information on other features, engineering, design, construction work, startup and maintenance of Fieldbus, refer to “Fieldbus Technical Information” (TI 38K03A01-01E).
3.2 Internal Structure of
digitalYEWFLO
Each digitalYEWFLO contains two Virtual Field Devices (VFDs) that share the following functions.

3.2.1 System/Network Management VFD

• Sets node addresses and Physical Device tags (PD Tag) necessary for communication.
• Controls the execution of function blocks.
• Manages operation parameters and communication resources (Virtual Communication Relationship: VCR).

3.2.2 Function Block VFD

(1) Resource (RS) block
• Manages the status of digitalYEWFLO hardware.
• Automatically informs the host of any detected faults or other problems.
(2) Transducer (TR) block
• Converts the fl ow sensor output to the volumetric fl ow rate signal and transfers to an AI function block (AI1).
• With the option /MV
- Converts temperature sensor output to the
process fl uid temperature and calculates the uid density.
- Calculates the mass fl ow rate from the fl uid
density thus obtained and the volumetric fl ow rate obtained with the fl ow sensor.
- Transfers these calculation results to AI
function blocks.
• Transfers limit switch signals to DI function blocks.
(3) AI function blocks (three)
• Output fl owrate and temperature.
• Condition raw data from the TR block.
• Carry out scaling and damping (with a fi rst- order lag), and allow input simulation.
(4) DI function blocks (two)
• Limit switches for the fl ow rate and temperature (option /MV).
(5) IT function block (one)
• Accumulate given values.
(6) AR function block (one)
• Calculate input values.
(7) PID function block (option /LC1)
• Performs the PID computation based on the deviation of the measured value from the setpoint.
IM 01F06F00-01EN
<3. ABOUT FIELDBUS>

3.3 Logical Structure of Each Block

digital YEWFLO
Sensor
input
(option /MV)
Temp. sensor
Sensor
input
Flow sensor
Figure 3.1 Logical Structure of Each Block
System/network management VFD
PD tag
Node address
Link master
Function block VFD
DI1 function
Transducer
block
Block tag
Parameters
Block tag
Parameters
Temp. signal
(option
/MV)
Flow rate signal
AI3
function block
AI2 function block
(outputting the
temperature for a
model with the option
/MV)
AI1 function
block
Block tag
Parameters
Resource block
Communication parameters
VCR
Function block
execution schedule
PID function block
(option /LC1)
IT function
block
AR
function
block
DI2 function
block
block
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
OUT
Output
F0301.ai
3-2
Various parameters, the node address, and the PD tag shown in Figure 3.1 must be set before using the device. Refer to Chapter 4 and onward for the setting procedures.
3.4 Wiring System Confi guration
The number of devices that can be connected to a single bus and the cable length vary depending on system design. When constructing systems, both the basic and overall design must be carefully considered to achieve optimal performance.
IM 01F06F00-01EN
<4. GETTING STARTED>

4. GETTING STARTED

4-1
Fieldbus is fully dependent upon digital communication protocol and differs in operation from conventional 4 to 20 mA transmission and the BRAIN communication protocol. It is recommended that novice users use fi eldbus devices in accordance with the procedures described in this section. The procedures assume that fi eldbus devices will be set up on a bench or in an instrument shop.

4.1 Connection of Devices

The following instruments are required for use with Fieldbus devices:
• Power supply:
Fieldbus requires a dedicated power supply. It
is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
• Terminator:
Fieldbus requires two terminators. Refer to
the supplier for details of terminators that are attached to the host.
• Cable:
Used for connecting devices. Refer to “Fieldbus
Technical Information” (TI 38K03A01-01E) for details of instrumentation cabling. For laboratory or other experimental use, a twisted pair cable two to three meters in length with a cross section of 0.9 mm2 or more and a cycle period of within 5 cm (2 inches) may be used. Termination processing depends on the type of device being deployed. For the digitalYEWFLO, use terminal lugs applicable to M4 screw terminals. Some hosts require a connector.
Refer to Yokogawa when making arrangements to purchase the recommended equipment. Connect the devices as shown in Figure 4.1. Connect the terminators at both ends of the trunk, with a minimum length of the spur laid for connection. The polarity of signal and power must be maintained.
Fieldbus power
Terminator
supply
digitalYEWFLO
+
HOST
• Field devices:
Connect your Fieldbus communication type
digitalYEWFLO to a fi eldbus. Two or more digitalYEWFLOs and other fi eld devices can be connected. For the terminal assignment on the digitalYEWFLO, see Table 4.1.
Table 4.1 Terminal Connection for
Terminal Symbols Description
SUPPLY
SUPPLY
digitalYEWFLO
+
Fieldbus Communication Signal Terminals
Grounding Terminal
• Host:
Used for accessing fi eld devices. A
dedicated host (such as DCS) is used for an instrumentation line while dedicated communication tools are used for experimental purposes. For operation of the host, refer to the instruction manual for each host. No other details on the host are given in this manual.
Terminator
F0401.ai
Figure 4.1 Device Connection
IMPORTANT
Connecting a Fieldbus confi guration tool to a loop with its existing host may cause communication data scrambling resulting in a functional disorder or a system failure. Disconnect the relevant control loop from the bus if necessary.
IM 01F06F00-01EN
<4. GETTING STARTED>
4-2

4.2 Host Setting

To activate Fieldbus, the following settings are required for the host.
IMPORTANT
Do not turn off the power immediately after setting. When the parameters are saved to the EEPROM, the redundant processing is executed for the improvement of reliability. If the power is turned off within 60 seconds after setting is made, the modifi ed parameters are not saved and the settings may return to the original values.
Table 4.2 Operation Parameters
Symbol Parameter Description and Settings
V (ST) Slot-Time Indicates the time necessary
V (MID) Minimum-Inter-
PDU-Delay
V (MRD) Maximum-Reply-
Delay
V (FUN) First-Unpolled-Node Indicate the address next
V (NUN) Number-of-
consecutive­Unpolled-Node
for immediate reply of the device. Unit of time is in octets (256 μs). Set maximum specifi cation for all devices. For digitalYEWFLO, set a value of 4 or greater.
Minimum value of communication data intervals. Unit of time is in octets (256 μs). Set the maximum specifi cation for all devices. For digitalYEWFLO, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slot-time; set the value so that V (MRD) x V (ST) is the maximum value of the specifi cation for all devices. For digitalYEWFLO, the setting must be a value of 12 or greater.
to the address range used by the host. Set 0x15 or greater.
Unused address range.
0x00
Not used
0x0F 0x10
0x13 0x14
V(FUN)
V(FUN)+V(NUN)
0xF7 0xF8
0xFB 0xFC
0xFF
Note 1: LM device: with bus control function (Link Master function) Note 2: BASIC device: without bus control function
Bridge device
LM device
Unused V(NUN)
BASIC device
Default address
Portable device address
F0402.ai
Figure 4.2 Available Address Range

4.3 Power-on of digitalYEWFLO and Bus

Turn on the power to the host, bus, and digitalYEWFLO. If any segments do not light, or if a current anomaly occurs, check the voltage of the power supply for the digitalYEWFLO. The device information, including PD tag, Node address, and Device ID, is described on the sheet attached to digitalYEWFLO. The device information is given in duplicate on this sheet. Using the host device display function, check that the digitalYEWFLO is in operation on the bus.
DEVICE INFORMATION
Device ID:5945430009XXXXXXXX PD Tag:XXXXXX Device Revision:X Node Address:0xXX Serial No.:XXXXXXXXXXXXXXXXX Physical Location: Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English)
http://www.yokogawa.co.jp/fld/ (Japanese)
DEVICE INFORMATION
Device ID:5945430009XXXXXXXX PD XXXXXX Device Revision:X Node Address:0xXX Serial No.:XXXXXXXXXXXXXXXXX Physical Location: Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld/ (English)
http://www.yokogawa.co.jp/fld/ (Japanese)
F0403.ai
Figure 4.3 Device Information Sheet Attached to
digitalYEWFLO
IM 01F06F00-01EN
<4. GETTING STARTED>
Unless otherwise specifi ed, the following settings are in effect when shipped from the factory. If no digitalYEWFLO is detected, check the available address range. If the node address and PD Tag are not specifi ed when ordering, default value is factory set. If two or more digitalYEWFLOs are connected at a time with default value, only one digitalYEWFLO will be detected from host as digitalYEWFLOs have the same initial address. Connect the digitalYEWFLOs one by one and set a unique address for each.
NOTE
When using a capabilities fi le (CFF), make sure you use the right fi le for the intended device. The digitalYEWFLO is offered in two types in terms of capabilities:
• General type: AI function blocks (three), DI function blocks (two), AR function block (one), and IT function block (one).
• With the option /LC1: A PID function block
4-3

4.4 Integration of DD

If the host supports DD (Device Description), the DD of the digitalYEWFLO needs to be installed. Check if host has the following directory under its default DD directory.
594543 : the manufacturer number of
Yokogawa Electric Corporation
0009 : the device number of digitalYEWFLO
If this directory is not found, the DD for the digitalYEWFLO has not yet been installed. Create this directory and copy the DD fi les (0m0n.ffo and 0m0n.sym to be supplied separately where m and n are numerals) to it. If you do not have the DD fi les for the digitalYEWFLO, you can download them from our web site. Visit the following web site.
http://www.yokogawa.com/fl d/
Once the DD is installed in the directory, the name and attribute of all parameters of the digitalYEWFLO are displayed.
Off-line confi guration is possible using the capabilities fi le.
Using the wrong CFF fi le may result in an error when downloading the confi gured data to the device. Also, use the right DD fi les that accommodate the revision of the intended device.

4.5 Reading the Parameters

To read digitalYEWFLO parameters, select the AI block of the digitalYEWFLO from the host screen and read the OUT parameter. The current fl ow rate is displayed. Check that MODE_BLK of the function block and resource block is set to AUTO.

4.6 Continuous Record of Values

If the host has a function of continuously records the indications, use this function to list the indications (values). Depending on the host being used, it may be necessary to set the schedule of Publish (the function that transmits the indication on a periodic basis).
IM 01F06F00-01EN
<4. GETTING STARTED>

4.7 Generation of Alarm

If the host is allowed to receive alarms, generation of an alarm can be attempted from the digitalYEWFLO. In this case, set the reception of alarms on the host side. The digitalYEWFLO’s VCR-7 is factory-set for this purpose. For practical purposes, all alarms are placed in a disabled status; for this reason, it is recommended that you fi rst use one of these alarms on a trial basis. Set the value of link object-3 (index 30002) as “0, 299, 0, 6, 0”. Refer to Subsection 5.6.1 “Link Objects” for details. Since the LO_PRI parameter (index 4029) of the AI block is set to “0”, try setting this value to “3”. Select the Write function from the host in operation, specify an index or variable name, and write “3” to it. The LO_LIM parameter (index 4030) of the AI block determines the limit at which the lower bound alarm for the process value is given. In usual cases, a very small value is set to this limit. Set smaller value than 100% value of XD_SCALE (same unit). Since the fl ow rate is almost 0, a lower bound alarm is raised. Check that the alarm can be received at the host. When the alarm is confi rmed, transmission of the alarm is suspended.
4-4
IM 01F06F00-01EN
<5. CONFIGURATION>

5. CONFIGURATION

5-1
This chapter describes how to adapt the function and performance of the digitalYEWFLO to suit specifi c applications. Because multiple devices are connected to Fieldbus, it is important to carefully consider the device requirements and settings when confi guring the system. The following steps must be taken.
(1) Network design
Determines the devices to be connected to
Fieldbus and checks the capacity of the power supply.
(2) Network defi nition
Determines the PD tag and node addresses for
all devices.
(3) Defi nition of combining function blocks
Determines how function blocks are combined.
(4) Setting tags and addresses
Sets the PD Tag and node addresses for each
device.
(5) Communication setting
Sets the link between communication
parameters and function blocks.
(6) Block setting
Sets the parameters for function blocks.
The following section describes in sequence each step of this procedure. The use of a dedicated confi guration tool signifi cantly simplifi es this procedure. Refer to APPENDIX 7 “LINK MASTER FUNCTIONS” when the digitalYEWFLO is used as Link Master.

5.1 Network Design

Select the devices to be connected to the Fieldbus network. The following are essential for the operation of Fieldbus.
• Power supply
Fieldbus requires a dedicated power supply. It
is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as power supply.
• Terminator
Fieldbus requires two terminators. Refer to
the supplier for details of terminators that are attached to the host.
• Field devices
Connect the fi eld devices necessary for
instrumentation. The digitalYEWFLO has passed the interoperability test conducted by The Fieldbus Foundation. In order to properly start Fieldbus, it is recommended that the devices used satisfy the requirements of the above test.
• Host
Used for accessing fi eld devices. A minimum of
one device with bus control function is needed.
• Cable
Used for connecting devices. Refer to “Fieldbus
Technical Information” (TI 38K03A01-01E) for details of instrumentation cabling. Provide a cable suffi ciently long to connect all devices. For eld branch cabling, use terminal boards or a connection box as required.
First, check the capacity of the power supply. The power supply capacity must be greater than the sum of the maximum current consumed by all devices to be connected to Fieldbus. For the digitalYEWFLO, the maximum current (power supply voltage: 9 to 32 VDC) is 15 mA. The cable used for the spur must be of the minimum possible length.
5.2 Network Defi nition
Before connection of devices with Fieldbus, defi ne the Fieldbus network. Allocate PD tags and node addresses to all devices (excluding such passive devices as terminators). The PD tags are the same as conventional tag numbers assigned to devices. Up to 32 alphanumeric characters may be used for defi nition of the PD tag for each device. Use hyphens as delimiters as required.
IM 01F06F00-01EN
<5. CONFIGURATION>
5-2
The node addresses are used to locate devices for communication purposes. Since a PD tag is too long a data value, the host substitutes the node addressed for PD tags in communication. Node addresses can be set to numbers in a range of decimal 20 to 247 (hexadecimal 14 to F7). Assign devices having link master functionality (i.e., LM devices) from the smallest address number (0x14) in order, and other devices (i.e., basic devices) from the largest (0xF7). Assign an address in the range for basic devices to a digitalYEWFLO. Only when using a digitalYEWFLO with LM function as an LM device, assign an address in the range for LM devices to it. These address ranges are determined by the following parameters.
Table 5.1 Parameters for Setting Address Range
Symbol Parameters Description
V (FUN) First-Unpolled-Node Indicates the address next
V (NUN) Number-of-
consecutive­Unpolled-Node
to the address range used for the host or other LM device.
Unused address range
Any devices within an address range written as “Unused” in Figure 5.1 cannot join the fi eldbus. Other address ranges are periodically scanned to nd any devices newly joining the fi eldbus. Do not widen the available address ranges unnecessarily; the fi eldbus communication performance may be severely degraded.
0x00
0x0F
0x10
0x13 0x14
V(FUN)
V(FUN)+V(NUN)
0xF7 0xF8
0xFB
0xFC
0xFF
Figure 5.1 Available Range of Node Addresses
Unused
Bridge device
LM devices
Unused V(NUN)
Basic devices
Default addresses
Portable device addresses
F0501.ai
To ensure stable operation of Fieldbus, determine the operation parameters and set them to the LM devices. While the parameters in Table 5.2 are to be set, the worst-case value of all the devices to be connected to the same Fieldbus must be used. Refer to the specifi cation of each device for details.
Table 5.2 Operation Parameter Values of
Symbol Parameters Description and Settings
V (ST) Slot-Time Indicates the time
V (MID) Minimum-Inter-
V (MRD) Maximum-
digitalYEWFLO to be Set to LM Device
necessary for immediate reply of the device. Unit of time is in octets (256 s). Set maximum specifi cation for all devices. For a digitalYEWFLO, set a value of 4 or greater.
PDU-Delay
Response-Delay
Minimum value of communication data intervals. Unit of time is in octets (256 s). Set the maximum specifi cation for all devices. For a digitalYEWFLO, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slot-time; set the value so that V (MRD) x V (ST) is the maximum value of the specifi cation for all devices. For a digitalYEWFLO, value of V(MRD) x V (ST) must be 12 or greater.
5.3 Function Block Link Defi nitions
Link the input/output parameters of function blocks to each other as necessary. For a digitalYEWFLO, the output parameters of three AI blocks (OUTs), those of two DI blocks (OUT_Ds), input/output parameters of AR block, IT block and optional PID block (option /LC1) should be linked to parameters of different function blocks. Specifi cally, link settings must be written to the link object in the digitalYEWFLO. For details, refer to Section 5.6 “Block Setting.” It is also possible to read values from the host at appropriate intervals instead of linking the outputs of digitalYEWFLO’s function blocks to other blocks. The linked blocks need to be executed synchronously with other blocks and the communication schedule. In this case, change the schedule of the digitalYEWFLO according to Table 5.3, in which factory settings are shown in parentheses.
IM 01F06F00-01EN
<5. CONFIGURATION>
5-3
Table 5.3 Function Block Execution Schedule of
the digitalYEWFLO
Index Parameters
269 (SM) MACROCYCLE_
276 (SM) FB_START_ENTRY.1 Start time of the AI1
277 (SM) FB_START_ENTRY.2 Start time of the PID block
278 (SM)
289 (SM)
DURATION
FB_START_ENTRY.3 to
to
FB_START_ENTRY.14
Setting (Factory Setting
in Parentheses)
Repetition period of control or measurement, i.e., macrocycle; to be set as a multiple of 1/32 ms (32000 = 1 second)
block represented as the elapsed time from the start of each macrocycle; to be set as a multiple of 1/32 ms (0 = 0 ms)
(optional) represented as the elapsed time from the start of each macrocycle; to be set as a multiple of 1/32 ms (9600 = 300 ms)
Not set.
A maximum of 29 ms is taken for execution of each AI block. Arrange the communication schedule for an AI block’s data that is to be transferred to its downstream block in such a way that it starts after a lapse of longer than 30 ms. Figure 5.3 shows typical function block and communication schedules for the loop shown in Figure 5.2.
FIC100
digitalYEWFLO
#1
FI100
FIC200
Macrocycle (Control Period)
FI103
FC100
FC200
FI200
Function
Schedule
Commu-
nication
Schedule
Block
FI100
OUT
IN
FIC100
BKCAL_IN
FI200
OUT
CAS_IN
FIC200
IN
BKCAL_IN
Unscheduled
Communication
BKCAL_OUT
FC100
BKCAL_OUT
Scheduled Communication
F0503.ai
Figure 5.3 Function Block Schedule and
Communication Schedule
When the control period (macrocycle) is set to more than 4 seconds, set the following interval to be more than 1% of the control period.
- Interval between “end of block execution” and “start of sending CD from LAS”
- Interval between “end of block execution” and “start of the next block execution”
5.4

Setting of Tags and Addresses

This section describes the steps in the procedure to set the PD tags and node address in the digitalYEWFLO. There are three states of Fieldbus devices as shown in Figure 5.4, and if the state is other than the lowest SM_OPERATIONAL state, no function block is executed. Whenever you have changed the PD tag or address of a digitalYEWFLO, transfer its state to SM_ OPERATIONAL.
digitalYEWFLO
#2
FI200
FC100
F0502.ai
Figure 5.2 Example of Loop Connecting Function
Blocks of Two digitalYEWFLOs with Other Devices
UNINITIALIZED
(No tag nor address is set)
Tag clear Tag setting
INITIALIZED
(Only tag is set)
Address clear
SM_OPERATIONAL (Tag and address are retained, and the function block can be executed.)
Address setting
F0504.ai
Figure 5.4 Status Transition by Setting PD Tag and
Node Address
IM 01F06F00-01EN
<5. CONFIGURATION>
5-4
In each digitalYEWFLO, the PD tag and node address are set to “FT1003” and 242 (hexadecimal F2), respectively, before shipment from the factory unless otherwise specifi ed. To change only the node address, clear the address once and then set a new node address. To set the PD tag, fi rst clear the node address and clear the PD tag, then set the PD tag and node address again. Devices whose node address have been cleared will await at the default address (randomly chosen from a range of 248 to 251, or from hexadecimal F8 to FB). At the same time, it is necessary to specify the device ID in order to correctly specify the device. The device ID of the YF100 is 5945430009xxxxxxxx. (The xxxxxxxx at the end of the above device ID is a total of 8 alphanumeric characters. Available characters are as follws.)
ABCDEF 0123456789

5.5 Communication Setting

To set the communication function, it is necessary to change the database residing in SM (System Management)-VFD.

5.5.1 VCR Setting

Set VCR (Virtual Communication Relationship), which specifi es the called party for communication and resources. Each digitalYEWFLO has 33 VCRs whose application can be changed, except for the rst VCR, which is used for management. Each digitalYEWFLO has VCRs of four types: Server (QUB) VCR A server responds to requests from a host. This
communication needs data exchange. This type of communication is called QUB (Queued User-
triggered Bidirectional) VCR. Source (QUU) VCR A source multicasts alarms or trends to other
devices. This type of communication is called
QUU (Queued User-triggered Unidirectional)
VCR. Publisher (BNU) VCR A publisher multicasts outputs of the AI blocks, DI
blocks, AR block, IT block and PID block to other
function blocks. This type of communication
is called BNU (Buffered Network-triggered
Unidirectional) VCR. Subscriber (BNU) VCR A subscriber receives output of another function
block(s) by AR block, IT block and PID block.
Each VCR has the parameters listed in Table 5.4. Parameters must be changed together for each VCR because modifi cation for each parameter may cause a contradiction.
IM 01F06F00-01EN
<5. CONFIGURATION>
5-5
Table 5.4 VCR Static Entry
Sub-
index
1 FasArTypeAndRole Indicates the type and role of
2 FasDllLocalAddr Sets the local address
3 FasDllConfi gured
4 FasDllSDAP Specifi es the quality of
5 FasDllMaxConfi rm
6 FasDllMaxConfi rm
Parameter Description
communication (VCR). The following 4 types are used for the digitalYEWFLO. 0x32: Server (Responds to
requests from host.)
0x44: Source (Transmits
alarm or trend.)
0x66: Publisher (Sends AI,
DI block output to other blocks.)
0x76: Subscriber (Receives
output of other blocks by PID block.)
to specify a VCR in the digitalYEWFLO. A range of 20 to F7 in hexadecimal.
RemoteAddr
DelayOnConnect
Sets the node address of the called party for communication and the address (DLSAP or DLCEP) used to specify VCR in that address. For DLSAP or DLCEP, a range of 20 to F7 in hexadecimal is used. Addresses in Subindex 2 and 3 need to be set to the same contents of the VCR as the called party (local and remote are reversed).
communication. Usually, one of the following types is set. 0x2B: Server 0x01: Source (Alert) 0x03: Source (Trend) 0x91: Publisher/Subscriber
To establish connection for communication, a maximum wait time for the called party’s response is set in ms. Typical value is 60 seconds (60000).
For request of data, a
DelayOnData
maximum wait time for the called party’s response is set in ms. Typical value is 60 secounds (60000).
7 FasDllMaxDlsduSize Specifi es maximum DL
8 FasDllResidual
ActivitySupported
9 FasDllTimelinessClass Not used for the
10 FasDllPublisherTime
WindowSize
11 FasDllPublisher
SynchronizaingDlcep
12 FasDllSubscriberTime
WindowSize
13 FasDllSubscriber
SynchronizationDlcep
Service Data unit Size (DLSDU). Set 256 for Server and Trend VCR, and 64 for other VCRs.
Specifi es whether connection is monitored. Set TRUE (0xff) for Server. This parameter is not used for other communication.
digitalYEWFLO. Not used for the
digitalYEWFLO. Not used for the
digitalYEWFLO. Not used for the
digitalYEWFLO. Not used for the
digitalYEWFLO.
Sub-
index
14 FmsVfdId Sets VFD for the
15 FmsMaxOutstanding
16 FmsMaxOutstanding
17 FmsFeatures
Parameter Description
digitalYEWFLO to be used.
0x1: System/network
0x1234: Function block
ServiceCalling
ServiceCalled
Supported
Set 0 to Server. It is not used for other applications.
Set 1 to Server. It is not used for other applications.
Indicates the type of services in the application layer. In the digitalYEWFLO, it is automatically set according to specifi c applications.
management VFD
VFD
These 33 VCRs are factory-set as shown in Table
5.5.
Table 5.5 VCR List
Index
(SM)
293 1 For system management (Fixed) 294 2 Server (LocalAddr = 0xF3) 295 3 Server (LocalAddr = 0xF4) 296 4 Server (LocalAddr = 0xF7) 297 5 Trend Source (LocalAddr = 0x07,
298 6 Publisher (LocalAddr = 0x20) 299 7 Alert Source (LocalAddr = 0x07,
300 8 Server (LocalAddr = 0xF9)
301 to 325 9 to 33 Not set
VCR
Number
Factory Setting
Remote Address=0x111)
Remote Address=0x110)

5.5.2 Function Block Execution Control

According to the instructions given in Section 5.3 “Function Block Link Defi nitions”, set the execution cycle of the function blocks and schedule of execution.
IM 01F06F00-01EN
<5. CONFIGURATION>
5-6

5.6 Block Setting

Set the parameter for function block VFD.

5.6.1 Link Objects

A link object combines the data voluntarily sent by the function block with the VCR. Each digitalYEWFLO has 40 link objects. A single link object specifi es one combination. Each link object has the parameters listed in Table 5.6. Parameters must be changed together for each VCR because the modifi cations made to each parameter may cause inconsistent operation.
Table 5.6 Link Object Parameters
Sub-
index
1 LocalIndex Sets the index of function block
2 VcrNumber Sets the index of VCR to be
3 RemoteIndex Not used in the digitalYEWFLO.
4 ServiceOperation Set one of the following. Set
5 StaleCountLimit Set the maximum number of
Link objects are not factory-set. Set link objects as shown in Table 5.7.
Parameters Description
parameters to be combined; set “0” for Trend and Alert.
combined. If set to “0”, this link object is not used.
Set to “0”.
only one each for link object for Alert or Trend. 0: Undefi ned 2: Publisher 3: Subscriber 6: Alert 7: Trend
consecutive stale input values which may be received before the input status is set to Bad. To avoid the unnecessary mode transition caused when the data is not correctly received by subscriber, set this parameter to “2” or more.

5.6.2 Trend Objects

It is possible to make settings so that a function block automatically transmits the trend. For this, each digitalYEWFLO has ten trend objects: eight for trends of analog parameters and two for discrete parameters. For each trend object, specify a single parameter, the trend of which is to be transmitted. Each trend object has the parameters listed in Table 5.8. For the fi rst four parameters, setting is mandatory. Before writing parameter settings to a trend object, parameter WRITE_LOCK of the resource block must be modifi ed to unlock the write-lock.
Table 5.8 Parameters for Trend Objects
Sub-
index
1 Block Index Sets the leading index of the
2 Parameter Relative
3 Sample Type Specifi es how trends are taken.
4 Sample Interval Specifi es sampling intervals in
5 Last Update The last sampling time.
6 to 21 List of Status Status part of a sampled
21 to 37 List of Samples Data part of a sampled
Parameters Description
function block that takes a trend.
Index
Sets the index of parameters taking a trend by a value relative to the beginning of the function block. In the digitalYEWFLO, the following three types of trends are possible. 7: PV 8: OUT 19: FIELD_VAL
Choose one of the following 2 types:
1: Sampled upon execution of
a function block.
2: The average value is
sampled.
units of 1/32 ms. Set the integer multiple of the function block execution cycle.
parameter.
parameter.
Table 5.7 Settings of Link Objects (example)
Index Link Object # Settings(example)
30000 1 AI. OUT 30001 2 Trend 30002 3 Alert
30003 to 30039 4 to 40 No used
VCR#6
VCR#5
VCR#7
Ten trend objects are not factory-set.
Table 5.9 Trend Objects
Index Parameter Factory Setting
32000 to
32007 32008 TREND_DIS.1 Not set (these parameters
32009 TREND_DIS.2
TREND_FLT.1 to TREND_FLT.8
Not set.
are used with a DI block or optional PID block).
IM 01F06F00-01EN
<5. CONFIGURATION>
5-7
System Management Information Base (SMIB)
Network Management Information Base (NMIB)
Link object
VCR
digital YEWFLO
DLSAP
0xF8 0xF3 0xF4 0xF7
DLCEP
Fieldbus Cable
block
#2
Transducer
block
FBOD
#3
Resource
#1
Host 1 Host 2
AI2 OUT
AI1 OUT
#1 #3
#4 #8
0xF9
Device
#6
0x20
OUT
DI1
OUT
Alert
#7
DI2
Trend
#2
#5
0x07
F0505.ai
Figure 5.5 Example of Default Confi guration

5.6.3 View Objects

View objects are used to group parameters. This reduces the load of data transactions. Each digitalYEWFLO supports four view objects for each of the Resource block, Transducer block, three AI blocks, two DI blocks, one IT block, one AR block, and PID block (option /LC1). Each view object contains a group of the parameters listed in Tables
5.11 to 5.17.
Table 5.10 Purpose of Each View Object
Description
VIEW_1 Set of dynamic parameters required by operator for
VIEW_2 Set of static parameters which need to be shown to
VIEW_3 Set of all the dynamic parameters. VIEW_4 Set of static parameters for confi guration or
plant operation. (PV, SV, OUT, Mode etc.)
plant operator at once. (Range etc.)
maintenance.

5.6.4 Function Block Parameters

Function block parameters can be read from the host or can be set. For details of the function blocks, refer to APPENDIX.
IM 01F06F00-01EN
<5. CONFIGURATION>
Table 5.11 View Objects for Resource Block
Relative
Index
1 ST_REV 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7 RS_STATE 1 1 8 TEST_RW
9 DD_RESOURCE 10 MANUFAC_ID 4 11 DEV_TYPE 2 12 DEV_REV 1 13 DD_REV 1 14 GRANT_DENY 2 15 HARD_TYPES 2 16 RESTART 17 FEATURES 2 18 FEATURE_SEL 2 19 CYCLE_TYPE 1 20 CYCLE_SEL 2 21 MIN_CYCLE_T 4 22 MEMORY_SIZE 2 23 NV_CYCLE_T 4 24 FREE_SPACE 4 25 FREE_TIME 4 4 26 SHED_RCAS 4 27 SHED_ROUT 4 28 FAIL_SAFE 1 1 29 SET_FSAFE 30 CLR_FSAFE
Parameter Mnemonic
VIEW_1VIEW_2VIEW_3VIEW_
Relative
4
Index
31 MAX_NOTIFY 4 32 LIM_NOTIFY 1 33 CONFIRM_TIME 4 34 WRITE_LOCK 1 35 UPDATE_EVT 36 BLOCK_ALM 37 ALARM_SUM 88 38 ACK_OPTION 2 39 WRITE_PRI 1 40 WRITE_ALM 41 ITK_VER 42 SOFT_REV 43 SOFT_DESC 44 SIM_ENABLE_MSG 45 DEVICE_STATUS_1 4 46 DEVICE_STATUS_2 4 47 DEVICE_STATUS_3 4 48 DEVICE_STATUS_4 4 49 DEVICE_STATUS_5 4 50 DEVICE_STATUS_6 4 51 DEVICE_STATUS_7 4 52 DEVICE_STATUS_8 4 53 54 55 SOFTDWN_COUNT 2 56 57 58 SOFTDWN_ERROR 2
Parameter Mnemonic
SOFTDWN_PROTECT SOFTDWN_FORMAT
SOFTDWN_ACT_AREA SOFTDWN_MOD_REV
Total bytes 22 30 73 35
VIEW_1VIEW_2VIEW_3VIEW_
5-8
4
1 1
1
16
IM 01F06F00-01EN
<5. CONFIGURATION>
Table 5.12 View Objects for Transducer Block
Relative
Index
Parameter Mnemonic
VIEW_1 VIEW_2
1 ST_REV 2 2 2 2 2 2 2 2 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7 UPDATE_EVT 8 BLOCK_ALM
TRANSDUCER_
9
DIRECTORY 10 TRANSDUCER_TYPE 2 2 2 2 11 XD_ERROR 1 1
COLLECTION_ 12
DIRECTORY 13 PRIMARY_VALUE_TYPE 2 14 PRIMARY_VALUE 5 5
PRIMARY_VALUE_ 15
RANGE 16 CAL_POINT_HI 4 17 CAL_POINT_LO 4 18 CAL_MIN_SPAN 4 19 CAL_UNIT 2 20 SENSOR_TYPE 2 21 SENSOR_RANGE 11 22 SENSOR_SN 4 23 SENSOR_CAL_METHOD 2 24 SENSOR_CAL_LOC 32 25 SENSOR_CAL_DATE 7 26 SENSOR_CAL_WHO 32 27 LIN_TYPE 1 28 SECONDARY_VALUE 5
SECONDARY_VALUE_ 29
UNIT 30 PRIMARY_FTIME 4 31 TERTIARY_VALUE 5 32 TERTIARY_VALUE_UNIT 2 33 LIMSW_1_VALUE_D 2 34 LIMSW_1_TARGET 1 35 LIMSW_1_SETPOINT 4
LIMSW_1_ACT_ 36
DIRECTION 37 LIMSW_1_HYSTERESIS 4 38 LIMSW_1_UNIT 2 39 LIMSW_2_VALUE_D 2 40 LIMSW_2_TARGET 1 41 LIMSW_2_SETPOINT 4
LIMSW_2_ACT_ 42
DIRECTION 43 LIMSW_2_HYSTERESIS 4 44 LIMSW_2_UNIT 2 45 ALARM_PERFORM 2 46 ARITHMETIC_BLOCK 1 1 47 SENSOR_STATUS 1 1 48 FUNCTION 1 1 49 FLUID_TYPE 1 1
VIEW_3
st
1
VIEW_3
nd
2
VIEW_3
rd
3
VIEW_3
th
4
VIEW_4
st
1
11
2
VIEW_4
nd
2
VIEW_4
rd
3
VIEW_4
th
4
1
1
VIEW_4
5-9
VIEW_4
th
5
th
6
* Continued on next page
IM 01F06F00-01EN
<5. CONFIGURATION>
5-10
Relative
Index
Parameter Mnemonic
VIEW_1 VIEW_2
VIEW_3
st
1
VIEW_3
nd
2
VIEW_3
rd
3
VIEW_3
th
4
VIEW_4
st
1
VIEW_4
nd
2
VIEW_4
rd
3
VIEW_4
th
4
50 TEMP_UNIT 2 2 51 PROCESS_TEMP 4 4 52 BASE_TEMP 4 4 53 DENSITY_UNIT 2 2 54 PROCESS_DENSITY 4 4 55 BASE_DENSITY 4 4 56 PRESSURE_UNIT 2 2 57 PROCESS_PRESSURE 4 4 58 BASE_PRESSURE 4 4 59 DEVIATION 4 4 60 SECONDARY_FTIME 4 61 CABLE_LENGTH 4 62 FIRST_TEMP_COEF 4 63 SECOND_TEMP_COEF 4 64 SIZE_SELECT 1 1 65 BODY_TYPE 1 1
VORTEX_SENSOR_ 66
TYPE
11
67 K_FACTOR_UNIT 1 1 68 K_FACTOR 4 4 69 LOWCUT 4 70 UPPER_DISPLAY_MODE 1 71 LOWER_DISPLAY_MODE 1 72 DISPLAY_CYCLE 1 73 USER_ADJUST 4 74 REYNOLDS_ADJUST 1 75 VISCOSITY_VALUE 4 76 GAS_EXPANSION_FACT 1 77 FLOW_ADJUST 1
FLOW_ADJ_ 78
FREQUENCY 79 FLOW_ADJ_DATA 20 80 TLA_VALUE 4 81 NOISE_BALANCE_MODE 1 82 NOISE_RATIO 4 4 83 SIGNAL_LEVEL 4 84 FLOW_VELOCITY 4 85 SPAN_VELOCITY 4 86 VORTEX_FREQ 4 87 SPAN_FREQ 4 88 FLUID_DENSITY 4
SENSOR_ERROR_ 89
RECORD
2
90 MODEL 32 91 ALARM_SUM 8
153 VOLUME_FLOW 5 154 VOLUME_FLOW_UNIT 2
VIEW_4
th
5
20
VIEW_4
th
6
Total bytes 16 62 57 2 2 2 54 75 67 50 88 2
IM 01F06F00-01EN
<5. CONFIGURATION>
5-11
Table 5.13 View Objects for Each AI Function
Block
Relative
Index
1 ST_REV 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7PV 5 5 8 OUT 5 5
9 SIMULATE 10 XD_SCALE 11 11 OUT_SCALE 11 12 GRANT_DENY 2 13 IO_OPTS 2 14 STATUS_OPTS 2 15 CHANNEL 2 16 L_TYPE 1 17 LOW_CUT 4 18 PV_FTIME 4 19 FIELD_VAL 5 5 20 UPDATE_EVT 21 BLOCK_ALM 22 ALARM_SUM 8 8 23 ACK_OPTION 2 24 ALARM_HYS 4 25 HI_HI_PRI 1 26 HI_HI_LIM 4 27 HI_PRI 1 28 HI_LIM 4 29 LO_PRI 1 30 LO_LIM 4 31 LO_LO_PRI 1 32 LO_LO_LIM 4 33 HI_HI_ALM 34 HI_ALM 35 LO_ALM 36 LO_LO_ALM 37 TOTAL 4 38 TOTAL_START 39 TOTAL_RATE_VAL 40 TOTAL_RESET
Parameter Mnemonic
VIEW_1VIEW_2VIEW_3VIEW_
Table 5.14 View Objects for Each DI Function
Block
Relative
4
Index
1 ST_REV 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7 PV_D 2 2 8 OUT_D 2 2 9 SIMULATE_D
10 XD_STATE 2
11 OUT_STATE 2 12 GRANT_DENY 2 13 IO_OPTS 2 14 STATUS_OPTS 2 15 CHANNEL 2 16 PV_FTIME 4 17 FIELD_VAL_D 2 2 18 UPDATE_EVT 19 BLOCK_ALM 20 ALARM_SUM 8 8 21 ACK_OPTION 2 22 DISC_PRI 1 23 DISC_LIM 1 24 DISC_ALM
Parameter Mnemonic
Total bytes 22 8 22 19
VIEW_1VIEW_2VIEW_3VIEW_
4
Total bytes 31 26 35 46
Note: AI2 and AI3 blocks do not have parameters after index
No. 37 (TOTAL) inclusive.
IM 01F06F00-01EN
<5. CONFIGURATION>
Table 5.15 View Objects for PID Function Block (option /LC1)
Relative
Index
1 ST_REV 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7PV 5 5 8SP 5 5
9 OUT 5 5 10 PV_SCALE 11 11 OUT_SCALE 11 12 GRANT_DENY 2 13 CONTROL_OPTS 2 14 STATUS_OPTS 2 15 IN 5 16 PV_FTIME 4 17 BYPASS 1 18 CAS_IN 5 5 19 SP_RATE_DN 4 20 SP_RATE_UP 4 21 SP_HI_LIM 4 22 SP_LO_LIM 4 23 GAIN 4 24 RESET 4 25 BAL_TIME 4 26 RATE 4 27 BKCAL_IN 5 28 OUT_HI_LIM 4 29 OUT_LO_LIM 4 30 BKCAL_HYS 4 31 BKCAL_OUT 5 32 RCAS_IN 5 33 ROUT_IN 5 34 SHED_OPT 1 35 RCAS_OUT 5 36 ROUT_OUT 5 37 TRK_SCALE 11 38 TRK_IN_D 2 2 39 TRK_VAL 5 5 40 FF_VAL 5
Parameter Mnemonic
VIEW_1VIEW_2VIEW_3VIEW_
Relative
4
Index
41 FF_SCALE 11 42 FF_GAIN 4 43 UPDATE_EVT 44 BLOCK_ALM 45 ALARM_SUM 8 8 46 ACK_OPTION 2 47 ALARM_HYS 4 48 HI_HI_PRI 1 49 HI_HI_LIM 4 50 HI_PRI 1 51 HI_LIM 4 52 LO_PRI 1 53 LO_LIM 4 54 LO_LO_PRI 1 55 LO_LO_LIM 4 56 DV_HI_PRI 1 57 DV_HI_LIM 4 58 DV_LO_PRI 1 59 DV_LO_LIM 4 60 HI_HI_ALM 61 HI_ALM 62 LO_ALM 63 LO_LO_ALM 64 DV_HI_ALM 65 DV_LO_ALM
Parameter Mnemonic
Total bytes 43 43 83 104
VIEW_1VIEW_2VIEW_3VIEW_
5-12
4
IM 01F06F00-01EN
<5. CONFIGURATION>
Table 5.16 View Objects for Enhanced Arithmetic (AR) Block
Relative
Index
1 ST_REV 2
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Parameter Mnemonic
TAG_DESC
STRATEGY 2
ALERT_KEY 1
MODE_BLK 4 4
BLOCK_ERR 2 2
PV 5 5
OUT 5 5
PRE_OUT 5 5
PV_SCALE 11
OUT_RANGE 11
GRANT_DENY 2
INPUT_OPTS 2
IN 5
IN_LO 5
IN_1 5
IN_2 5
IN_3 5
RANGE_HI 4
RANGE_LO 4
BIAS_IN_1 4
GAIN_IN_1 4
BIAS_IN_2 4
BIAS_IN_2 4
BIAS_IN_3 4
BIAS_IN_3 4
COMP_HI_LIM 4
COMP_LO_LIM 4
ARITH_TYPE 1
VIEW_1VIEW_2VIEW_3VIEW_
4
2 2 2
Relative
Index
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
Parameter Mnemonic
BAL_TIME 4
BIAS 4
GAIN 4
OUT_HI_LIM 4
OUT_LO_LIM 4
UPDATE_EVT
BLOCK_ALM
AR_VOLUME_ FLOW_UNIT
AR_TEMP_UNIT 2
AR_BASE_TEMP 4
AR_PRESSURE_ UNIT
AR_BASE_ PRESSURE
AR_DEVIATION 4
AR_DENSITY_ UNIT
AR_BASE_ DENSITY
AR_FIRST_TEMP_ COEF
AR_SECOND_ TEMP_COEF
AR_FLOW_ CONFIG
AR_DENSITY_ FACTOR
AR_DENSITY_ FACTOR_UNIT
AR_CONFIG_ SOFT_REV
AR_CONFIG_DATE
AR_CONFIG_WHO
AR_CONFIG_ STATUS
AR_CONFIG_ VSTRING32
AR_CONFIG_ VSTRING16
AR_CONFIG_ OSTRING32
AR_CONFIG_ OSTRING2
VIEW_1VIEW_2VIEW_3VIEW_
5-13
4
2
2
4
2
4
4
4
5
2
Total bytes 23 26 53 102
IM 01F06F00-01EN
Loading...
+ 138 hidden pages