Thank you for purchasing the µR1800 Recorder.
To take full advantage of all functions of the µR1800 Industrial Recorder, and to operate
this instrument correctly and efficiently, please read this Instruction Manual carefully
before use.
NOTES• YOKOGAWA reserves the right to change this manual at any time without notice.
• If you find any ambiguities or errors in this manual, please inform YOKOGAWA.
• This manual is the eighth edition, July 1998.
Previous editions were released as follows:
November ’92first edition
May ’93second edition
October ’93third edition
April ’94fourth edition
October ’95fifith edition
April ’96sixth edition
May ’98seventh edition
July ’98eighth edition
• The µR1800 is a Component Type instrument and should be mounted on a panel.
• The µR1800(except portable type) is a Safety ClassI instrument (provided with
terminal for protective earthing).
• The µR1800(except portable type) is an EN55011(EMI standard) Group 1, Class A
instrument.
• This instrument complies with Inatallation Category ll.
The following general safety precautions must be observed during all phases of
operation, service, and repair of this instrument. Failure to comply with these
precautions or with specific WARNINGS given elsewhere in this manual violates safety
standards of design, manufacture, and intended use of the instrument.
YOKOGAWA Electric Corporation assumes no liability for the customer’s failure to
comply with these requirements.
General definitions of safety symbols used on equipment and in manuals
Explanation: To avoid injury, death of personnel or damage to the instrument, the
operator must refer to an explanation in the instruction manual.
Protective grounding terminal: To protect against electrical shock in case of a fault.
This symbol indicates that the terminal must be connected to ground before operation of
equipment.
WARNING
CAUTION
High temperature: To avoid injury caused by hot surface, don't touch the heatsink.
A WARNING sign denotes a hazard. It calls attention to a procedure, practice,
condition or the like, which, if not correctly performed or adhered to, could result
in injury or death of personnel.
A CAUTION sign denotes a hazard. It calls attention to a procedure, practice,
condition or the like, which, if not correctly performed or adhered to, could result
in damage to or destruction of part of the product.
2IM 4H3B1-01E
WARNING
Power Supply
Ensure the source voltage matches the voltage of the power supply before
turning on the power.
Protective Grounding
Make sure to connect the protective grounding to prevent an electric shock
before turning on the power.
Necessity of Protective Grounding
Never cut off the internal or external protective grounding wire or disconnect the
wiring of protective grounding terminal. Doing so poses a potential shock
hazard.
Defect of Protective Grounding and Fuse
Do not operate the instrument when protective grounding or fuse might be
defective.
Fuse
To prevent a fire, make sure to use the fuse with specified standard (current,
voltage, type). Before replacing the fuse, turn off the power and disconnect the
power source. Do not use a different fuse or short-circuit the fuse holder.
Do not Operate in an Explosive Atmosphere
Do not operate the instrument in the presence of flammable liquids or vapors.
Operation of any electrical instrument in such an environment constitutes a
safety hazard.
Never Touch the Interior of the Instrument
Inside this instrument there are areas of high voltage; therefore, never touch the
interior if the power supply is connected. This instrument has an internal
changeable system; however, internal inspection and adjustments should be
done by qualified personnel only.
External Connection
To ground securely, connect the protective grounding before connecting to
measurement or control unit.
This manual describes the standard functions, operation procedures and some of the
optional functions of the pen model and dot printing model of the µR1800 recorder.
To use this manual in the most efficient way, please refer to the following table. In this
table the aim of the user is broken down into five broad categories. Please check which
are applicable to you and refer to the corresponding chapters.
Purchase &
Installation
First Time
Setting
Daily
Operation
Changing
Settings
Maintenance
& Trouble-
shooting
Chapters
Safety Precautions
1 Features and
Functions
2 Before Operation
3 Installation
4 Component Names
and Functions
5 Daily Operation
6 How to Enter
Settings
7 Basic Settings
8 Auxiliary Settings
(AUX)
9 Changing Initial
Settings
10 General
Specifications
11
Maintenance
Troubleshooting
12
necessary to readoptional to read
::
For operation procedures of options, which are not described in this manual, refer to
specific option manuals.
6IM 4H3B1-01E
1.1 Features
Chapter 1 FEATURES AND FUNCTIONS
1.1 Features
This chapter describes the main features and functions of the µR1800 recorder. The
µR1800 is equipped with all the functions which can be expected in a modern recorder,
whereas its functions also reflect the latest user requirements.
The µR1800 recorder is a precision measuring instrument that is equipped with many
outstanding features:
Compact sized, high reliability: Its compact size (depth 220mm) allows you to
install the µR1800 where only a limited space is available. In case of the pen model, a
contact-free potentiometer and a brushless-DC servomotor contribute to its high
reliability. In case of the dot printing model, high reliability is obtained by the use of
high break down voltage solid-state relays.
Universal inputs: Inputs like DC-voltage, Thermocouple (TC), Resistance
Temperature Detector (RTD), and Digital Input (contact) can all be conveniently used.
There is no need to change any dipswitches; the type of input can be set using the keyboard.
Easy interactive setting: The setting procedure has been made very easy, by using
only panel keys. The µR1800 asks you to select the desired settings, without the need
for remembering difficult setting-codes.
Large informative operator display: The large sized, VFD, display shows the
measured data (including the engineering units) or clock, and bargraph at the same time.
There are two types of bargraph available: percentage-display, and center-zero display.
Because of its 1%-resolution, the bargraph displays very accurately.
1. FEATURES AND FUNCTIONS
Continuous pen recording for up to four channels (pen model only):
Depending on your µR1800 model type, the µR1800 can measure up to four channels
simultaneously. This allows you to decrease the number of recorders you require.
Universal power supply (except for /P1 model): The µR1800 accepts 90 to
250VAC (except 132 to 180VAC), and 50/60Hz without any problems, or need to turn
switches. Therefore the µR1800 is compatible with a wide variety of power supplies.
High performance: The sampling speed of the µR1800 pen model is high at 125 ms,
whereas the recording cycle of the µR1800 dot printing model is 6 ch./10 seconds, or
12ch./15sec., 18ch./20sec. or 24ch./30sec. depending on the model.
The µR1800 is equipped with many functions. Special functions can be ordered as an
option. Furthermore, its power consumption is low (4pen model; 30VA under normal
operation conditions).
Easy maintenance: Because of the use of many contact-free parts, the need for
maintenance has been decreased. The µR1800 is designed in modules, which decreases
the time needed for maintenance extensively.
Closed case: The closed case of the µR1800 allows it to be used in many
environments. The front door is in accordance with DIN 40050-IP54.
Computer interface and memory card: If equipped with this option, the µR1800
can store and retrieve measured data as well as setting data, using an IC memory card or
directly from your PC. The available interface is RS-422-A.
IM 4H3B1-01E
Based on international safety standards: The µR1800 (except portable type) is
based on international safety standards, such as the IEC 348.
1 - 1
1.2 Summary of Functions
This paragraph describes a summary of the main functions, together with a recording
example.
RECORDING
Trend: records in a way that the dots do not overlap (dot model only)
Zone: records on different bands (zones) for individual channels
Partial: expands part of the recording range for detailed examination
POC: Pen Offset Compensation: removes the time-axis offset between pens (pen model only)
PRINTOUT
Channel printout: contains channel No. besides analog recording (dot model only)
List printout: contains date, time, chart speed (1 & 2), channel No. or tag, range, span values, scale
values, partial values and contents of messages (for example, see 5.3.4)
Manual printout: contains date and time, channel No., type of alarm, latest measured values, units (for all
channels)
Alarm printout: contains channel or tag No., type of alarm, level, mark ( for occurence, for recover;
in case of the dot model, red and blue respectively) and alarm ON/OFF-time
Periodic printout: contains date & time, tag or channel No., POC ON mark ( ; for pen model only), unit,
scale markings (may not be printed while alarm occurs), chart speed, measured values
and recording color (for pen model) and time tick (for dot model)
Message printout: contains time and message
Recording start printout: contains time when recording starts
Chart speed change: contains time and new chart speed
SET UP List printout: contains initial settings concerning analog recording, digital printing, alarms, burnout,
change printout depend on the chart speed. The size of the characters varies depending
on the chart speed.
Manual printout
Time tick cancel mark (!)
appears when chart feed/speed
has been changed during
periodic printout
POC ON mark
Periodic printout
Scale printout an Recording
color
Chart speed change printout
Message printout
Alarm printout
Note: When an asterisk appears
( ), the memory buffer is full
and some data will not be printed.
This asterisk may appear in the
alarm printout, message printout,
recording start time printout and
the chart speed change printout.
Recording start time
Time tick (–)
Figure 1.1 Recording Example for Pen Model
always corresponding to pen No.1 when POC is OFF.
Corresponding to all pens when POC is ON.
1 - 2IM 4H3B1-01E
1.2 Summary of Functions
Alarm printout
Note: When an asterisk
appears (✴), the memory
buffer is full and some data will
not be printed. This asterisk
may appear in the alarm
printout, message printout,
recording start time printout
and the chart speed change
printout.
Message printout
Chart speed change
printout
Time tick (–)*
Manual printout
1
1. FEATURES AND FUNCTIONS
Periodic printout
Channel printout
Recording start time
✴1: will not be printed when the time does not correspond with the correct place on the chart.
Figure 1.2 Recording Example for Dot Model
Time tick (–)*
ALARM
Type of alarms: H: high limit
L: low limit
h: high difference limit
l: low difference limit
R: rate-of-change limit on increasing signal
r: rate-of-change limit on decreasing signal
Hysteresis: hysteresis value as a % of span which can be 0% or approx. 0.5%
Alarm output relay: when alarm occurs, the relay will be activated (optional)
Reflash: monitors repeating alarm occurrences among a group of alarms sharing the
same output relay (optional)
FAIL/Chart-end output: output relay is activated when chart reaches its end and/or when failure of
equipment occurs (optional)
INPUT
Type of inputs: TC: Thermocouple
RTD: Resistance Temperature Detector
DC-voltage
DC-current: using optional external shunt resistor
DI: Digital Input (contact)
Burnout: when TC-wire is broken, pens will move to left or right side
Filter: (signal damping) selects the time constant of signal damping (for pen model)
Moving average: selects the number of samples for moving average (for dot model)
1
IM 4H3B1-01E
1 - 3
DISPLAY
Left-referenced bargraph: measured data are displayed as a %, on a 0 to 100% scale
Center-zero bargraph: center of the recording span is reference and deviation is displayed as a bargraph
Clock: year/month/day and hours/minutes/seconds
Measured data: AUTO: all channels will be shown alternately
MAN: a specified channel only will be shown
Alarm: channel No., type of alarm (display), channel No. (underneath bargraph, for dot model)
Status indicators: RCD: illuminated when recording is in progress
POC: illuminated when POC is being used (for pen model)
SET:illuminated when in SET Mode
AUTO:illuminated when AUTO display is used
MAN: illuminated when Manual display is used
CLK: illuminated when Clock display is used
ALM: illuminated/flashing when alarm occurs
CHT: illuminated when approx. 2cm are left till chart end (option)
BAT: illuminated/flashing when battery needs to be replaced
CALCULATION
Difference calc (DELT): takes the difference between the measured values of two channels
Linear scaling (SCL): sets different scale (and unit) to a specific range
Square root (SQRT): takes the square root of measured data
This chapter describes the preparations to be made before you can operate the µR1800
recorder. To use the µR1800, it is necessary to read this chapter first.
2.1 Handling Precautions
Cleaning
The µR1800 contains many plastic parts, like door window and panels. Therefore never
attempt to clean the µR1800 with chemicals like benzene or thinner.
Static electricity
Do not bring any objects charged with static electricity near the signal terminals. This
might cause malfunction.
Insecticide sprays, etc.
Do not allow any volatile substances such as insecticides etc. to come in contact with
the front door, the operation panel, etc. Do not allow rubber or vinyl to remain in
contact with the recorder for long periods.
After use
Ensure that the power switch is turned to the OFF position.
2.1 Handling Precautions
2. BEFORE OPERATION
In case of malfunction
Never continue to use the instrument if there are any symptoms of malfunction such as
unusual sounds, smell, or smoke coming from the instrument. Immediately disconnect
the power supply and stop further use of the instrument. If such abnormal symptoms
occur, contact your sales representative or nearest service center.
IM 4H3B1-01E
2 - 1
2.2 Checking the Contents
This µR1800 was thoroughly inspected before it was shipped from the factory.
However, when you receive the µR1800, check that all accessories are present and in
the correct quantities. Also check the external appearance of the µR1800 to ascertain
that no damage has occurred.
2.2.1 Checking Accessories and Appearance
The µR1800 should be accompanied by the accessories indicated in figure 2.1.
Check that all are present in the correct quantities. Also check the external appearance
of the µR1800 to ascertain that no damage has occurred. If you discover any problem
concerning the quantity of accessories or external appearance, please contact your sales
representative or the nearest service center. Addresses may be found on the back cover
of this Instruction Manual.
1
2
No. DescriptionQuantity Remarks
1.
disposable felt pen (for pen model)
• 1 pen model
• 2 pen model
• 3 pen model
• 4 pen model
2.
plotter pen (for pen model)
3.
ribbon cassette (for dot model)
4.
fuse
key
5.
mounting brackets
6.
Z-fold chart paper
7.
Instruction Manual and Quick
8.
Reference power cord
345678
red
1
red, green
2
red, green, blue
3
red, green, blue, violet
4
purple
1
1
250V 750mA time lag
1
(except for /P1 model)
250V 5A time lag
1
(for /P1 model)
Recorders with a gray power switch
250V 800mA time lag
1
(except for /P1 model)
250V 5A time lag
1
(for /P1 model)
Recorders with a white power switch
(1 chart/unit), order quantity: 6 units
red (3 pcs./unit), order quantity: 1 unit
green (3 pcs./unit), order quantity: 1 unit
blue (3 pcs./unit), order quantity: 1 unit
violet (3 pcs./unit), order quantity: 1 unit
(3 pcs./unit), order quantity: 1 unit
(1 pc./unit), order quantity: 1 unit
(4pcs./unit), order quantity : 1 unit
250V 750mA time lag
(except for /P1 model)
(4pcs. /unit), order quantity : 1 unit
250V 5A time lag
(for /P1 model)
Recorders with a gray power switch
(4pcs. /unit), order quantity : 1 unit
250V 800mA time lag
(except for /P1 model)
(4pcs. /unit), order quantity : 1 unit
250V 5A time lag
(for /P1 model)
Recorders with a white power switch
(1 pc./unit), order quantity: 2 units
(1 pc./unit), order quantity: 2 units
(1 pc./unit), order quantity: 1 unit
2 - 2IM 4H3B1-01E
2.2.2 Removing Packings
The internal assembly is secured in position by packings to safeguard against damages
during transit. When you unpack the recorder, remove the packings as follows:
Open the µR1800 front door and swing open the display by grabbing the tabs located at
the lower right and left side of the display and pulling these tabs up. See figure 2.2a.
Figure 2.2a Swinging Up the DisplayFigure 2.2b Closing the Display
Then remove all the packings as shown in figure 2.3.
2.2 Checking the Contents
2. BEFORE OPERATION
Figure 2.3a Removing Packings in
After having removed the packings, close the display by pulling the 'release'-handle
until this handle is at the same level as the display. Then push the display back into
its normal position until the tabs click shut. See figure 2.2b.
2.2.3 Checking Model Code
When you receive your µR1800, check the information on the nameplate to make sure
that it is as specified by your order. If you open the front door and remove the chart
cassette, you will find the model code mentioned on the nameplate located as shown in
figure 2.4. Please check if model code (MODEL) is correct.
case of Pen Model
Packings
Nameplate
Packings
Figure 2.3b Removing Packings in
case of Dot Model
IM 4H3B1-01E
Figure 2.4 Checking Model Code
2 - 3
Chapter 3 INSTALLATION
This chapter describes the installation of the µR1800, like the installation site, the
mounting and wiring. To install the µR1800 properly, it is necessary to read this
chapter.
3.1 Installation Site/Mounting
3.1.1 Installation Site
The µR1800 installation site should be chosen to meet the following conditions as close
as possible:
Installation site should be panel-mounted only. The µR1800 is especially designed for
panel mounting.
The µR1800 should be placed in a well ventilated area.
The µR1800 will be adversely affected if the unit is exposed to direct sunlight or
installed near a heater. Choose a location near room temperature (23°C) with minimal
temperature fluctuations.
3.1 Installation Site/Mounting
3. INSTALLATION
To expose the µR1800 to soot, steam, moisture, dust, corrosive gases etc. will adversely
affect it.
To use the µR1800 within strong electro-magnetic fields may cause malfunction. Please
avoid installing near electro-magnetic objects.
To install the µR1800 in a location susceptible to mechanical vibrations will adversely
affect the mechanical parts and the quality of recording. Please choose an installation
site characterized by minimal mechanical vibrations.
This µR1800 must be installed horizontally (however, mounting may be inclined up to
30° backwards from vertical).
To use the µR1800 within domestic establishments and within establishments directly
connected to a low voltage power supply network which supplies buildings used for
domestic purposes may cause malfunction of other equipments. Please avoid using in
domestic environment.
IM 4H3B1-01E
3 - 1
3.1.2 Mounting
1 The µR1800 should be mounted on at least 2mm (and up to 26mm) thick steel panel.
2 Insert the µR1800 into the panel cutout.
3 Hold the bottom of the µR1800 and mount it on the panel using the mounting brackets
supplied, as shown in figure 3.1. (If still in place, remove the seals covering the holes
for the mounting brackets.)
Mounting bracket
Figure 3.1 Mounting
3 - 2IM 4H3B1-01E
3.1.3 Dimensional Drawings
3.1 Installation Site/Mounting
3. INSTALLATION
Figure 3.2 Panel Cutout and Spacing (including mounting brackets)
NOTE• The µR1800 should be mounted by only two brackets, either on the top & bottom of
the recorder, or on the left & right side of the recorder.
• The portable type has different dimensions.
IM 4H3B1-01E
3 - 3
3.2 Wiring
!
This paragraph describes the wiring at the rear panel.
3.2.1 Rear panel arrangement
3.2.2 Power supply wiring
3.2.3 Input wiring
3.2.4 Alarm output wiring
3.2.5 FAIL/Chart end output wiring
3.2.6 Remote control wiring
CAUTION
employ some kind of strain relief between the rear wall and the recorder.
3.2.1 Rear Panel Arrangement
Power supply
terminal Block
Make sure to fasten the wiring at the rear wall of the mounting panel and
for /P1 model
Each terminal block can be
removed for easy wiring
by loosening these screws.
To ensure proper contact,
make sure to fasten the
screws properly.
Used terminal screws:
ISO M4, length: 6mm
DC24V
+
−
/B
+/A
-/b
1
2
3
4
Figure 3.3a Rear Panel Arrangement in case of Pen Model
Power supply
terminal block
for /P1 model
Each terminal block can be
removed for easy wiring
by loosening these screws.
To ensure proper contact,
make sure to fasten the
screws properly.
Do NOT change the place of
the terminal block!
Used terminal screws:
ISO M4, length: 6mm
Figure 3.3b Rear Panel Arrangement in case of Dot Model
+
−
DC24V
3 - 4IM 4H3B1-01E
3.2 Wiring
3.2.2 Power Supply Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the
rear of the µR1800.
2 Connect the power supply wires and the protective ground wire to the power terminals
and the ground terminals as shown in figure 3.4.
3 Replace the transparent cover.
for /P1 model
+
−
DC24V
Figure 3.4 Power Supply Wiring
NOTE• Do not apply power supply of 132 to 180VAC. This might affect the measuring
accuracy.
• In case of portable type, plug the female end of power cord into the socket on the rear
panel.
• To prevent an emission of electromagnetic disturbances, separate the power supply
wires from the other wires at least 0.1m. Over 0.5m is recommended.
!
Power supply wires
L
N
Protective ground wire
3. INSTALLATION
WARNING
To prevent an electric shock, ensure the main power supply is turned OFF and
connect the ground terminal using a class 3 resistance of 100Ω or less.
For power and ground wiring termination, use “crimp on” lugs (for 4mm screws)
with insulation sleeves (see figure 3.5).
To prevent fire, use 600V PVC insulated wire (AWG18) for power and ground
wiring (cross sectional area of 0.83mm2 or thicker, anti-galvanic corrosion finish,
insulation thickness should be more than 0.8mm, insulation resistance should
be more than 50MΩKm at 20°C, approved EN60 320 (VDE0625), and do not
remove the transparent cover.
Make sure to apply a power switch in the power supply cord with the following
characteristics:
Others than /P1 model
• rated power current > 1A
• rated rush current > 60A
• fuse(s) of 2A to 15A is (are) necessary.
/P1 model
• rated power current > 3A
• rated rush current > 70A
• fuse(s) of 5A to 15A is (are) necessary.
The power switch and fuse used in the power supply cord should be
• CSA approved (for use in North America)
• VDE approved (for use in Europe).
IM 4H3B1-01E
3 - 5
3.2.3 Input Wiring
!
1 Make sure the power switch is turned OFF and remove the transparent cover at the
rear of the µR1800.
2 Connect the input wires to the input terminal.
3 Replace the transparent cover.
It is recommended that “crimp on” lugs (for 4mm screws) with insulation sleeves be
used for leadwire ends. See figure 3.5.
Figure 3.5 “Crimp on” Lugs
In case of clamped input terminals, do not use “crimp on” lugs.
Since the input terminal will be affected by changes in temperature (e.g. because of
wind), make sure to replace the transparent cover after wiring.
Even after replacement, take care not to expose the terminals to fans, etc.
Suggestions to minimize noise pickup:
• The measuring circuit wiring should be run as remote as possible from the power
and ground wires.
• It is recommended that shielded wires be used to minimize noise pickup from an
electrostatic induction source. The shielding wire of the cable should be connected
to the µR1800 ground terminal (only one ground line).
• To minimize noise from an electromagnetic induction source, twist the measuring
line cables in short and equal spaces.
• The to be measured object should be free from noise. However, if it isn’t, make
sure the measuring circuit is isolated and the to be measured object is grounded.
WARNING
CAUTION
If TC and RJC is used, the temperature of the input terminals should be as stable as
possible. Therefore, make sure to use the transparent cover. The thermal capacity of
the wiring should be small (recommended ø ≤ 0.3mm).
Refrain from wiring the input parallel. However, if you do, then
• do not use the burnout function
• ground the equipments at the same point
•turning ON/OFF the power might cause malfunction
• RTD cannot be wired parallel.
To prevent an electric shock, ensure the main power supply is turned OFF
and connect the ground terminal using a class 3 resistance of 100Ω or less.
If you have an input of DC ≤ 2V or a TC, don’t apply an input voltage exceeding ±10VDC.
Do not apply a max. common mode voltage more than 250VAC rms (50/
60Hz). The recorder and measured values will be adversely affected.
Add following to 'CAUTION'
This instrument complies with Inatallation Category ll.
NOTETo prevent an emission of electromagnetic disturbances, separate the input wires from
the other wires at least 0.1m. Over 0.5m is recommended.
3 - 6IM 4H3B1-01E
Pen Model
3.2 Wiring
+
–
max. wiring ø ≤ 2.5mm
1 ch.
2 ch.
+
2 ch.
3 ch.
4 ch.
Standard Input TerminalClamped Input Terminal (/H2 option)
Figure 3.6 DC V, Thermocouple and Contact Input in case of Pen Model
A
b
B
–
+
4 ch.3 ch.
–
max. wiring ø ≤ 2.5mm
+
–
+
–
1 ch.
1 ch.
2 ch.
A
b
1 ch.
B
3 ch.
2 ch.
A
b
B
3. INSTALLATION
4 ch.
4 ch.
A
b
B
Standard Input Terminal
Figure 3.7 Resistance Temperature Detector Input in case of Pen Model
DC Voltage Input/DI Input (contact)
+
–
Resistance Temperature Detector InputDC Current Input
B
A
b
+
DC voltage input
–
B
A
b
Clamped Input Terminal (/H2 option)
Thermocouple Input
+
–
+
–
A
b
B
Compensation lead
DC current input
3 ch.
+
–
IM 4H3B1-01E
Leadwire resistance:
10Ω max./leadwire
Three wire resistances
should be approx. equal.
Figure 3.8 Wiring Input Terminals in case of Pen Model
Shunt resistor
NOTE: For 4 to 20mA input, shunt resistance
value should be 250Ω ±0.1%.
3 - 7
Dot Printing Model
+
–
max.wiring ø ≤ 2.5mm
1 ch.
+
1 ch.
–
2 ch.
2 ch.
+
–
3 ch.
4 ch.
5 ch.
4 ch.
6 ch.
+
–
+
–
6 ch.
Standard Input Terminal
Figure 3.9 DC V, Thermocouple and Contact Input in case of Dot Model
BAb
Clamped Input Terminal (/H2 option)
max.wiring ø ≤ 2.5mm
1 ch.
A
2 ch.
2 ch.
B
b
3 ch.
A
B
4 ch.
5 ch.
6 ch.
4 ch.
6 ch.
b
A
B
b
+
3 ch.
–
+
5 ch.
–
A
1 ch.
B
b
A
B
3 ch.
b
A
5 ch.
B
b
Standard Input Terminal
Figure 3.10 Resistance Temperature Detector Input in case of Dot Model
DC Voltage Input/DI Input (contact)
DC voltage input
Resistance Temperature Detector InputDC Current Input
Leadwire resistance:
10Ω max./leadwire
Three wire resistances
should be approx. equal.
Clamped Input Terminal (/H2 option)
Thermocouple Input
Compensation lead
NOTE: For 4 to 20mA input, shunt resistance
value should be 250Ω ±0.1%.
DC current input
Shunt resistor
NOTE: In case of 3 leg isolated RTD (/N2 option), there is no difference between B and b.
However, A and b are designated to be the current line for measurements.
Figure 3.11 Wiring Input Terminals in case of Dot Model
3 - 8IM 4H3B1-01E
3.2 Wiring
3.2.4 Alarm Output Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the rear
of the µR1800.
2 Connect the alarm output wires to the alarm output terminal. Do NOT change the place
of the therminal block!
3 Replace the transparent cover.
Depending on your option, your alarm output terminal will be arranged like one of the
following:
ALARM
NONCC
1
NONCC
2
!
ALARM
NONCC
1
NONCC
2
NONCC
3
NONCC
4
ALARM
NONCC
1
NONCC
2
NONCC
3
NONCC
4
NONCC
5
NONCC
6
3. INSTALLATION
WARNING
!
option /A1
2 contacts
Figure 3.12 Alarm Output Terminals
option /A2
4 contacts
!
option /A3
6 contacts
!
CHARACTERISTICS:
Output type:relay transfer contact (energize/de-energize type switchable)
Output capacity:250VAC (50 or 60Hz), 3A
250VDC, 0.1A (resistive load)
Dielectric strength: 1500VAC (50 or 60Hz) for one minute between output terminal
and ground terminal
To adjust initial settings, see 9.1.
• To prevent an electric shock, ensure the main power supply is turned OFF
during wiring and ensure the ground terminal is connected using a class 3
resistance of 100Ω or less.
• Ensure the ground terminal is connected using a class 3 resistance of 100Ω or
less.
• Use "crimp-on" lugs with insulation sleeves for all connections if a voltage of
more than 30 VAC or 60 VDC is applied to the alarm output or fail/memory end
output. Furthermore, use doubleinsulated wires (withstand voltage
performance: more than 2300VAC) for those wires which apply 30 VAC or
60VDC. All other wires can be basic-insulated (withstand voltage performance:
more than 1350VAC). To prevent electric shock, do not touch the terminal after
wiring and make sure to re-attach the cover.
IM 4H3B1-01E
NOTETo prevent an emission of electromagnetic disturbances, separate the alarm output wires
from the power supply and input wires at least 0.1m. Over 0.5m is recommended.
3 - 9
3.2.5 FAIL/Chart End Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the rear
of the µR1800.
2 Connect the FAIL/Chart end output wires to the FAIL/Chart end output terminal.
3 Replace the transparent cover.
The FAIL/Chart end terminals (option) are arranged as follows:
CHART
NONCC
FAIL
NONCC
!
WARNING
!
Figure 3.13 FAIL/Chart End Output Terminal
The FAIL/Chart End output relay is of the de-energize type. See 5.3.9 for details.
• To prevent an electric shock, ensure the main power supply is turned OFF
during wiring and ensure the ground terminal is connected using a class 3
resistance of 100Ω or less.
• Ensure the ground terminal is connected using a class 3 resistance of 100Ω or
less.
• Use "crimp-on" lugs with insulation sleeves for all connections if a voltage of
more than 30 VAC or 60 VDC is applied to the alarm output or fail/memory end
output. Furthermore, use doubleinsulated wires (withstand voltage
performance: more than 2300VAC) for those wires which apply 30 VAC or
60VDC. All other wires can be basic-insulated (withstand voltage performance:
more than 1350VAC). To prevent electric shock, do not touch the terminal after
wiring and make sure to re-attach the cover.
NOTETo prevent an emission of electromagnetic disturbances, separate the FAIL/Chart end
wires from the power supply and input wires at least 0.1m. Over 0.5m is recommended.
3 - 10IM 4H3B1-01E
3.2 Wiring
3.2.6 Remote Control Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the rear
of the µR1800.
2 Connect the REMOTE output wires to the REMOTE output terminal. Make sure to
connect every terminal with the c(ommon) terminal. Use shielded wires to prevent
electromagnetic interference.
3 Replace the transparent cover.
The remote control terminal (option) is arranged as follows:
REMOTE
132
4C5
!
3. INSTALLATION
WARNING
!
Figure 3.14 Remote Control Terminal
CHARACTERISTICS:
Input signals:dry contact or open-collector (TTL or transistor)
Input types for each function
(1) recording start/stoplevel
(2) change chart speedlevel
(3) start/stop TLOG computationlevel
(4) printout messagestrigger
(5) get a manual printouttrigger
(6) get a periodic printouttrigger
250 ms minimum
(7) trigger IC Memory Cardtrigger
Input conditions:ON voltage (0.5V maximum) (30mA DC)
Leakage current in OFF state (0.25mA maximum)
Signal duration (250 msec minimum)
Input type:Photocoupler isolation (one side common)
Internal isolated power source (5V ±5%)
Dielectric strength: 500VDC between input terminal and ground terminal, 1min.
To adjust initial settings, see 9.8.
To prevent an electric shock, ensure the main power supply is turned OFF
during wiring and ensure the ground terminal is connected using a class 3
resistance of 100Ω or less.
The outer conductor must be grounded at the ground terminal.
IM 4H3B1-01E
NOTETo prevent an emission of electromagnetic disturbances, separate the remote control
wires from the power supply and input wires at least 0.1m. Over 0.5m is recommended.
3 - 11
Chapter 4COMPONENT NAMES AND
FUNCTIONS
This chapter describes the names of components, together with a short summary of their
functions.
4. COMPONENT NAMES AND FUNCTIONS
IM 4H3B1-01E
Figure 4.1 External View (pen model)
4 - 1
4.1 Front Panel
3
6
4
2
1
Figure 4.2 Front Panel (4 pen model)
5
1 Power switch
Pressing this button will result in switching the power ON or OFF.
2 Keyboard
The keyboard consists of six keys:
RCD
(RCD-key)
Pressing this key will result in starting or stopping the recording.
ESC
MENU
(Menu-key/Esc-key)
The MENU function is to select the type of display (see 5.3.8), to start SET UP List
printout and message printout (see 5.3.5, 5.3.6) etc., and to switch between Operation
and SET modes (see 6.1).
The ESC function is to escape to the previous level in the (setting) flow while entering
parameters.
PRINT
(Print-key/Cursor Up-key)
The PRINT function is used to get a manual printout or list printout printed onto the
chart (see 5.3.3, 5.3.4).
The function: The display is designed in an interactive way, which means that it
will ask you to enter the necessary data. In case there are several possibilities to
choose from (e.g. ON or OFF), use this key to show the next choice.
4 - 2IM 4H3B1-01E
4.1 Front Panel
ALARM
ACK
(Ack-key/Cursor Down-key)
The ‘ACK’-function is used to acknowledge alarms. Note that this function is only
effective if the alarm relay is in the hold-mode (see 5.3.7), and if the indicator status
is in the hold-mode (see 5.3.7). When you press this key in case an alarm occurs and
the ALM-indicator is flashing, the current alarm situation will be indicated and the
relay will be reset.
The function: The display is designed in an interactive way, which means that it
will ask you to enter the necessary data. In case there are several possibilities to
choose from (e.g. ON or OFF), use this key to show the previous choice.
FEED
(Feed-key/Move to Next Digit-key)
The ‘FEED’-function feeds the chart paper until this key is released (see also 5.3.2).
The function moves the cursor to the next digit while setting parameters. Please
note that there is not a back-space key provided. For that reason, the cursor moves
from the last digit to the first digit again (see 6.2).
(Ent-key)
The ‘ENT’-function allows you to keep the data you entered during the setting
procedure. Pressing ‘ENT’ results in moving to the next display in the same
(setting-) flow. Pressing ‘ENT’ after the ‘SET OK’-display appears, results in
starting the same (setting-) flow again.
3 Large sized VFD (Vacuum Fluorescent Display)
The display can show characters, bargraphs, and functions.
The backside of this display also illuminates the chart.
4 Chart and chart cassette
The recorder uses a Z-fold chart, 20 meter in length, with an effective analog trend
recording width of 180mm. The chart is stored inside a chart cassette.
5IC Memory card slot (optional)
IC Memory cards are inserted into this slot for use.
6 Key-lock
The key supplied with the recorder should be removed from the key-hole to lock the
recorder. See 5.4. To use the key-lock, see 9.10.
Used for data display, clock display, monitor display and setting display (see also 5.3.8).
Data display:Channel No. or tag, type of alarm, measured data, units
Clock display:(year, month, day) and (hour, minutes, seconds)
Monitor display:Operating conditions of IC Memory Card and TLOG function
Setting display:Every parameter can be set by interactive display.
ALM
CHT
BAT
ALM
CHT
BAT
3
3
2 Bargraph
Measured values of each channel will be displayed with 1% resolution (analog display).
The alarm set points will also be displayed. The colors of the bargraph correspond to
the colors of the pens. Two ways of display can be selected:
Left-referenced (%) bargraphCenter-zero bargraph
(center of the recording span is reference
and the deviation is displayed as a bargraph)
1
2
The squares underneath the bargraph show the occurrence of an alarm in the
corresponding channel. They illuminate/flash in the same way as the ALM-indicator.
3Status indicators
RCD: Illuminated when recording is in progress.
POC: Illuminated when Pen Offset Compensation is being used (only for pen model).
SET: Illuminated when you are working in the SET Mode.
AUTO: Illuminated when the AUTO display is used.
MAN: Illuminated when the Manual display is used.
CLK: Illuminated when the Clock display is used.
ALM: This VFD will flash or illuminate when an alarm occurs.
Hold-mode:If the ACK-key is pressed, the flashing will stop and the VFD
will illuminate. After the alarm stops, the VFD will turn off. (If
the ACK-key is not pressed, the flashing stays even if the alarm
recovers, see also 5.3.7).
Non-hold-mode: VFD will illuminate until the alarm recovers (pressing the
ACK-key in this case will have no effect, see also 5.3.7).
CHT: Illuminated when there are approx. 2cm left till chart end (option).
BAT: Illuminated when the battery for setting data backup needs to be replaced.
Flashes when the battery of the IC Memory Card needs to be replaced.
4 - 4IM 4H3B1-01E
5.1 How to Switch the Power ON/OFF
Chapter 5 DAILY OPERATION
This chapter describes the daily operation of the µR1800, excluding settings.
Please read this chapter carefully before operation.
5.1 How to Switch the Power ON/OFF
The power switch is located behind the door, at the front side, in the middle of the lower
front (see figure 5.1a.). The power is supplied to the instrument when the power switch
is in the position as shown in figure 5.1b. The power is OFF when the power switch is
in the position as shown in figure 5.1b. The power can be turned ON/OFF by alternately
pressing the switch. When you do not use the instrument, please turn ‘OFF’ the power.
ON
5. DAILY OPERATION
CAUTION
Power switch
OFF
Figure 5.1a Figure 5.1b
NOTEAfter turning ON the power, the µR1800 will first perform a self diagnostic check for
several seconds.
The warm-up time is approx. 30 minutes. (However, just after finishing the
wiring, it might take longer. Especially if you removed the input terminals during
wiring.)
If the input wiring is connected parallel with other equipments, switching the
power ON/OFF should not be done.
If error message appears on the display or is printed on the chart, please refer
to the Error Message Table at sect.12.1.
IM 4H3B1-01E
5 - 1
Loading...
+ 99 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.