987654321
1412 131110
171615
101
MAIN DISCONNECT
102
AA
103
FROM
CUSTOME R'S
104
A.C. LINES
105
L1
L2
L3
106
UTILITY
GROUND
GND LUG
SEE
NOTE 1
GND LUG
SEE
NOTE 1
L1
L2
L3
CIRCUIT BREAKER
107
BB
108
INPUT POWER
EARTH G ROUND
109
110
111
CC
112
113
114
115
DD
121
from 224
116
117
118
119
EE
NEUTRAL
120
121
122
123
FF
124
125
126
127
GG
128
129
130
131
HH
132
133
134
135
JJJJ
136
137
S1
(L1) (T1)
(L2) (T2)
(L3) (T4)
STANDARD
DISCONN ECT SWITCH
SEE NOTE 4
OR
CB1
(1)
(2)
(3)
OPTION PC
SHUNT TRIP
COIL
OPTION SP
OVER VOLTAGE
PROTECTION
MAIN BONDING
JUMPER
1L1
1L2
1L3
1L1
1L2
1L3
L1
(R)L2(S)L3(T)
CN5-A
FE
CN5-B
CN5-C
FE
U1000 IQPUMP
(Factory Defaults Shown)
Analog Input Selection
Terminating Resistor
(Off)
Terminal AM/FM
(U)T2(V)T3(W)
T1
1T1
TB3
T1
OPTION TD
ETHERNET/IP
OPTION CA RD
CN5
SI-EN3
E
SEE THE APPROPRIATE
TECHNICAL MANUAL FOR
EXT ER NA L CONN ECT I ONS
A1
DRIVE
DIP Switch S1
A2
A3
A1
V
I
DIP Switch S2
On
Jumper S5
VI
AM
FM
1T2
1T3
T2
T3
A6
EXTERNAL PUMP
MOTOR
EARTH
GROUND
1L1
(4)
1L2
(5)
1L3
(6)
1L1 1L1
1L2 1L2
1L3 1L3
DOOR
MOUNTED
DIGITAL
OPERATOR
SEE
NOTE 7
p1
n1
MAIN
CIRCUIT
CN2-2
CONTROL
BOARD
OPTION TZ
A7
A8 A9
(C2)(C1)
100
to 224
OPTION
SURGE SUPPRESSOR
P7 OR P9
1TBN1
HAND MODE SPEE D PO T
MANUAL SPEED POT
ASSEMBLY
PART NO. URSN0010
MANUAL
SPEED
R1
4.7K
OHM
AUTO M ODE
4-20mADC
0-10VDC
FEEDBACK DEVICE
(2 WIRE)
NOTE:
FOR 3 WIRE FEEDBACK
DEVICE, SEE
TECHNICAL MANUAL
FOR WIRING.
OR
OPTION PK
LOAD
REAC TOR 5 %
Z2
V
Z1
SH
from 126
2T1
(A2)
U2
R
B
W
1TB1ISOLATED
R
2TB1
B
3TB1
W
from 116
(EXIST ING
JUMPER)
ANALOG
OUTPUTS
CUSTOMER
4TB1
SH
to 113
2T2
2T3
(B2)
(C2)
W2
V2
FOR
USE
+V
A3
AC
24V
A2
AC
SH
TB3
V+
A3
AC
A1
24V
A2
AC
RP
FM
AC
AM
TB4
E(G)
IG
R+
R-
S+
S-
+10.5VDC
20MA MAX.
ANALOG INPUT 3
(H3-05 TO H3-08)
ANALOG
COMMON
ANALOG INPUT 1
0-10VDC (20k OHM)
(H3-01 TO H3-04)
+24 VDC TRANSDUCER
POWER SUPPLY (150mA MAX.)
ANALOG INPUT 2
4-20MADC (250 OHM)
(H3-09 TO H3-12)
ANALOG
COMMON
PULSE TRAIN
INPUT (H6-01 TO H6-08)
MULTIFUNCTION
ANALOG OUTPUT 1
0-10VDC, 2mA MAX.
ANALOG
COMMON
MULTIFUNCTION
ANALOG OUTPUT 2
0-10VDC, 2mA MAX.
OPTION CARD/
SHI E LD GND
COMMUNICATIONS
GROUND
COMMUNICATIONS
INP U T (+)
COMMUNICATIONS
INPUT (-)
COMMUNICATIONS
OUTPUT (+)
COMMUNICATIONS
OUTPUT (-)
L4
U1
(A1)
1T1
W1
V1
(B1)
(C1)
1T2
1T3
OPTION P8
OUTPUT
TERMINAL
BLOCKS
FWD
USED
FAUL T ( N .O.)
FAULT
RESET
MUL T I-STEP
SPEED REF 1
HAND
MODE
HAND
MODE 2
USED
24VDC
COMMON
INPUT
COMMON
+24VDC
DRIVE
FAULT
FAULT
DRIVE
RUN
FREQ
DETECT 2
EGEG
PG1
RUN
NOT
NOT
TB1
S1
S2
S3
S4
SEE SH. 2
FOR
S5
RUN/STOP
CONTROL
WIRING
S6
S7
S8
(EXIST ING
JUMPER)
SN
SC
SP
TB2
MA
MB
MC
MD
ME
MF
M1
M2
M3
M4
SEE
NOTE 1
to 121
JUMPER
DRY CONTACTS
FOR CUSTOMER USE.
RATED:
1A, 250VAC
1A, 30VDC
CUSTOMER MUST
PROVIDE PROPER SHORT
CIRCUIT PROTECTION AND
MEANS OF DISCONNECT.
110
110
to 213
113
113
from 213
1L1
1L2
1L3
L1 L2
VOLTAGE
MONITOR
RELAY
21 22
120
120
to 224
L3
K8
OPTION SP
OVER
VOLTAGE
PROTECTION
121
121
to 224121 100
NOTES:
1. CONNECTED TO THE CABINET. CUSTOMER TO
CONNECT THE CABINET GROUND LUGS TO
EARTH GROUND AND UTILITY GROUND.
2. INSULATED TWISTED SHIELDED WIRE IS
REQUIRED. SHIELD TO CONNECT TO PROPER
TERMINAL AS SHOWN. CONNECT THE SHI ELD
ONLY AT THIS END. STUB AND ISO LATE THE
OTHER END. DO NOT RUN THESE WIRES IN THE
SAME CONDUIT AS THE AC POWER AND THE AC
CONTROL WIRES. KEEP ALL WIRING UNDER 50m
IN LENGTH.
3. W ITH A CONTROL TRA NSFORMER, T1, POWER
RATING 350VA OR GREATER, SECONDARY FUSE
F6 IS ADDED.
4. WITHOUT THE INPUT CIRCUIT BREAKER OPTION
PC, O R WHEN NOTED ON T HE CABIN ET
NAMEPLATE , BRANCH CIRCUIT PR O TECTIO N
MUST THE SUPPLIED BY THE INST ALL ER.
5. CUST O MER TO ADJUST THE THERMOSTAT ON
THE SPACE HE A TER HR1 FOR TH E MINIMUM
DESIRED TEMPERATURE INSIDE THE DRIVE
CABINET. THIS SET TEMPERATURE IS NORMALLY
SELECTED TO BE SLIGHTLY HIGHE R THAN THE
MINIMUM AMBIENT TEMPERATURE OF THE AIR
SURROUNDING THE CABINET AND IS THE
TEMPERATURE AT WHICH THE SPACE HEATER
HR1 WILL SHUT OFF.
6. CONDUIT FITTI NG S / HUB S S H AL L COMPL Y W ITH
THE 'STA ND A RD FOR CONDUIT, TUBI N G, AND
CABLE FITTINGS, UL 514B' OR CONDUI T FITTINGS
HAVING THE SAME ENVIRONMENTAL R ATIN G AS
THE ENCLOSURE SHALL BE USED.
7. TERMINALS p1 AND n1 ARE FOR MOMENTARY
POWER LOSS RECOVERY UNI T . DO NOT
CONNE C T TO AC POWER SUPPLY .
8. CUSTOMER TO REPLACE THE JUMPER WITH
NORMALLY CLOSED SAFETY INTERLOCKS, IF
APPLICABLE.
- INDICATES COMPONENTS NOT SUPPLIED BY YASKAWA
- INDICATES CUSTOMER WIRING
- CONN ECTE D TO THE CABIN E T OR P ANEL
SEE DRAWING UDE00538 FOR DRIVE PARAMETERS.
SEE DRAWING UDE00539 FOR CUSTOMER CONNE CTIONS.
1L1
to 202
1L2
to 203
AA
B
B
CC
DD
EE
FF
GG
HH
JJJJ
138
DRAWN BY:
139
KK
140
141
REV. DATEDRAWN B YECO #DESCRIPTION
02
01
321
87654 1716
9
UPDATED DRIVE BLOCK AND SPEED POT
FIXED CB1 CONNECTIONS
REVISIONS
11109
9683
N. LAWS
N. LAWS
01/29/21
06/24/19
1412 131110
A. ME ILAHN
CHECKED:
N. LAWS 02/10/17
TEC H:
APPROVED:
K. FL IERL 02/15/17
ORIGINAL DESIGN:
A. ME ILAHN 01/05/17
15
TITLE:
DATE
SCHEMATIC DIAGRAM
01/05/17
DATE
U1000 IQPUMP CONFIGURED
TYPE 3R, 240V
DATE
DATE
DATE
SIZE
D 02 1 2
DRAWING #:
DS.Q1E3 .12
REVIS ION
PAGE
KK
of
Prepared by nathan_laws 2/22/2021 12:45:05 PM
987654321
1412 131110
171615
201
202
AA
203
204
1L1
from 103
1L2
from 104
1L1
1L2
205
206
207
BB
208
110
211 115
209
210
211
CC
212
213
110
214
215
DD
110
216
217
218
219
EE
110
F1
F2
RUN
F10
F6
SEE
NOTE 3
F7
(H1)
(H2)(H3)
(H4)
210211
(X1) (X2)
CONTROL
TRANSFORMER
TS1
CABINET THERMOSTAT
(FACTORY SETTING: 90°F)
K4
T1
111
112
100
PG2
K4
(A2)(A1)
RC
CABINET FANS
B1 - B14
(QTY. AS REQ'D)
100
100
NO
NC
211
FWD
24VDC
COMMON
SHIELD
GROUND
S1
SN
E
(14)(11)
TO DRIVE RUN
110
from 127
K5
114
113
to 128
CABINET FANS
B15 - B18
(QTY. AS REQ'D)
113
(14)(11)
11TB1
12TB1
OPTION TK
200VA EXTRA CAPACITY
K5
100
(A2)(A1)
RC
100
NO
NC
214
FWD
HAND
MODE
24VDC
COMMON
SHIELD
GROUND
RUN
S1
S6
SN
E
100
220
221
110
222
223
FF
224
110
K9
(18)(15)
MONITOR RELAY K8
120
120
from 112
TO VOLTAGE
121
from 112
TO CIRCUIT BREAKER
CB1 SHUNT TRI P COI L
121
121
to 114
100
from 114
225
226
227
GG
110
(L1) (N)
228
229
OPTION P3
SPACE HEATER
230
231
HH
232
233
234
235
JJJJ
236
OPTION SF
FUSE BLOCK FOR
EXTERNAL 115V
SUPPLY
1L1
1L2
FACTORY SUPPLIED
CLASS CC FUSES
F8
F9
T1L1
T2L2
25A
237
223
FAN
CABINET SPACE HEATER
RANGE: (0 - 100) ° F
FACTORY SETTING: 40 ° F
SEE NOTE 5
(H1)
(X1) (X2)
(GND)
CUSTOMER SUPPLIED
COMPONENTS TO COMPLY WITH
LOCAL CODES AS REQ UIRED.
CONT R OL
TRAN SF O RME R
2.0 kVA
(A1) (A2)
PG3
SEE
NOTE 1
(H2)(H3)
K9
100
RC
100
100
RANGE:
1 - 10 SEC.
FACTORY SET TO 2 SEC.
NO
224
NC
OPTION SP
OVER VOLTAGE
PROTECTION
MULTI-STEP
SPEED REF 1
HAND
MODE
24VDC
COMMON
SHIELD
GROUND
S5
S6
SN
E
FUSES
F8
15AF915A
(H4)
RUN/STOP CONTROL (FROM SHEET 1)
S1
(WITHOUT SERIAL
COMM. OPTON TD)
SN
OPTIONAL AUTO MODE
RUN/STOP CONTACT
(CLOSED = RUN)
SHIELD
SEE
NOTE 2
OR
S2
OFF
AUTO
HAND
S1
(1L3) (1L4)
S6
(1R3) (1R4)
SN
E
OOX
XOO
5TB1
1
6TB1
7TB1
SHIELD
SEE
NOTE 2
OR
S2
OFF
AUTO
S5
S6
SN
E
HAND
OOX
(1L3) (1L4)
XOO
(1R3) (1R4)
XOO
(1R3) (1R4)
5TB1
1
6TB1
7TB1
SHIELD
SEE
NOTE 2
NOTE:
IF CUSTOMER DOES NOT
SUPPLY THE OPTIO N AL
RUN.STOP CONTACT IN THE
AUTO MODE, THEN ADD A
JUMPER BETWEEN DRIVE
TERMINALS S1 AND S N .
AUTO MO DE
RUN/S TOP CONTACT
(CLOSED = RUN)
NOTE:
IF CUSTOMER DOES NOT SUPPLY
THE OPTIONAL RUN/STOP
CONTACT I N THE AUTO MODE,
THEN ADD A JUMPER BETWEEN
TERMINAL BLOCK TB1 TERMINALS
5 AND 6.
SAFETY
INTERLOCK
JUMPER
SEE NOTE 8
CONTACT SEQUENCE CHART FOR S2
X - INDICATES CONTACT CLOSED
CONTACT
1
2
·SCHEMATIC SHOWS THIS POSITION.
OPTION TY,
AND WITHOUT
OPTION TD SERIAL
COMMUNICATION
CONTACT SEQUENCE CHART FOR S2
CONTACT
1
2
3 X 2RO
·SCHEMATIC SHOWS THIS POSITION.
POSITION
HAND OFF AUTO
·
X
X - INDICATES CONTACT CLOSED
POSITION
HAND OFF AUTO
·
X
OPTION TY,
AND WITH
OPTION TD SERIAL
COMMUNICATION
X 1LO
X 1LO
MANUF.
LOCATION
/TYPE
1RO
MANUF.
LOCATION
/TYPE
1RO
AA
B
B
CC
DD
EE
FF
GG
HH
JJJJ
238
DRAWN BY:
239
KK
240
241
SEE SHEET 1 FOR NOTES.
321
15A
115VAC
87654 1716
9
1412 131110
A. ME ILAHN
CHECKED:
N. LAWS 02/10/17
TEC H:
APPROVED:
K. FL IERL 02/15/17
ORIGINAL DESIGN:
A. ME ILAHN 01/05/17
15
Prepared by nathan_laws 2/22/2021 2:12:42 PM
TITLE:
DATE
SCHEMATIC DIAGRAM
01/05/17
DATE
U1000 IQPUMP CONFIGURED
TYPE 3R, 240V
DATE
DATE
DATE
SIZE
D 02 2 2
DRAWING #:
DS.Q1E3 .12
REVIS ION
PAGE
KK
of