To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise,
without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality
products, the information contained in this manual is subject to change without notice. Every precaution has
been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
YAS KAWA ELE CTR IC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual3
Page 4
1 Preface and Safety
DO
1Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa products remain the responsibility
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a
product manufactured by Yaskawa must be supplied to the end user with appropriate
warnings and instructions as to the safe use and operation of that part. Any warnings
provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express
warranty only as to the quality of its products in conforming to standards and specifications
published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS
OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses,
or claims arising from misapplication of its products.
◆ Applicable Documentation
The following manuals are available for the option:
4YASKAWA ELECTRIC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual
Read this manual first.
The installation manual is packaged with the
option and contains information required to install
the option and set up related unit parameters.
The unit manuals cover basic installation, wiring,
operation procedures, functions, troubleshooting,
and maintenance information.
The manuals also include important information
about parameter settings and unit tuning.
Access these sites to obtain Yaskawa instruction
manuals:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: contact a Yaskawa representative.
Page 5
1 Preface and Safety
DANGER
W ARNING
CAUTION
◆ Terms
Note:Indicates supplemental information that is not related to safety messages
Option: Yaskawa 1000-Series Option Digital Output DO-A3
• Yaskawa AC Drive 1000-Series
Unit:
• Yaskawa Energy-Saving Unit Series D1000 High-Power-Factor Converter with Power
Regeneration
◆ Registered Trademarks
Trademarks are the property of their respective owners.
◆ Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. Install
the option according to this manual and local codes.
The following conventions indicate safety messages in this manual. Failure to heed these
messages could cause fatal injury or damage products and related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation, which, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or
moderate injury.
• The diagrams in this book may include options and units without covers or safety shields to illustrate
details. Be sure to reinstall covers or shields before operating any devices. Use the option according
to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and
may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the
manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa
sales office and provide the manual number shown on the front cover.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting
from failure to heed the warnings in this manual.
Do not modify the unit or option circuitry.
Failure to comply could result in damage to the unit or option and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This
product must not be modified.
Do not expose the unit or option to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the unit or option.
Do not pack the unit in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
• A Phillips screwdriver (M3 metric / #1, #2 U.S. standard size <1>) is required to install the
option.
• A straight-edge screwdriver (blade depth: 0.4 mm, width: 2.5 mm) is required to wire the
option terminal block.
• A pair of diagonal cutting pliers. (required for some unit models)
• A small file or medium grit sandpaper. (required for some unit models)
Note: Tools required to prepare option cables for wiring are not listed in this manual.
<1> Select a screwdriver appropriate for the unit capacity.
8YASKAWA ELECTRIC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual
Page 9
4Option Components
DO
P1 P2 P3 P4 P5 P6 PC
M1 M2 M3 M4
TB2
TB1
DO
◆ Digital Output DO-A3 Option
Figure 1
F
4 Option Components
A
B
Underside
E
A – Connector (CN5)D – Model number
B – Installation holeE – Ground terminal and installation
C – Terminal block TB2F – Terminal block TB1
<1> The ground wires provided in the option shipping package must be connected during installation.
DO-A3
C
D
Figure 1 Digital Output DO-A3 Option Components
hole
<1>
◆ Terminal Blocks TB1 and TB2
Refer to Ta bl e 4 on page 22 for details on TB1 and TB2 terminal functions and signal levels.
YASKAWA ELECTRIC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual9
Page 10
5 Installation Procedure
W ARNING
5Installation Procedure
◆ Section Safety
DANGER
Electric Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the unit and wait at least the amount of time specified on the unit
front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing. The internal capacitor
remains charged after the power supply is turned off.
Electrical Shock Hazard
Do not remove the front covers of the unit while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and units without covers or safety
shields to show details. Be sure to reinstall covers or shields before operating any devices.
Use the option according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the unit is on.
Failure to comply could result in death or serious injury.
10YASKAWA ELECTRIC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual
Page 11
5 Installation Procedure
NOTICE
W ARNING
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to
overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option,
unit, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the unit is running or outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the unit.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Tighten all terminal screws to the specified tightening torque.
Failure to comply could result in damage to the terminal block.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the unit.
Prior to installing the option, wire the unit, make the necessary connections to the unit
terminals, and verify that the unit functions normally. Refer to the instruction manual
packaged with the unit for information on wiring and connecting the unit.
Figure 2 shows an exploded view of the unit with the option and related components for
reference.
Figure 2
A – Insertion point for CN5G – Included screws
B – Option cardH – Ground wire
C – Front coverI – Unit grounding terminal (FE)
D – Digital operatorJ – Connector CN5-A
E – Terminal coverK – Connector CN5-B
F – Removable tabs for wire routingL – Connector CN5-C
Refer to the instructions below to install the option.
1. Shut off power to the unit, wait the appropriate amount of time for voltage to
dissipate, then remove the digital operator (D), front cover (C), and terminal cover
(E). Cover removal varies depending on unit size. Refer to the instruction manual
packaged with the unit for directions on removing the covers.
DANGER! Electrical Shock Hazard. Disconnect all power to the unit and wait at least the amount of time
specified on the unit front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal
capacitor remains charged even after the power supply is turned off.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, unit, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
Figure 3 Remove the Front Cover, Terminal Cover, and Digital Operator
3. Connect one end of the ground wire (H) to the ground terminal (I) using one of the
remaining screws (G). Connect the other end of the ground wire (H) to the
remaining ground terminal and installation hole on the option (B) using the last
Figure 5
remaining provided screw (G).
Figure 5 Connect the Ground Wire
Note: 1. The option package includes three ground wires. Use the longest wire when plugging the option into
connector CN5-C on the unit side. Use the next longest wire when plugging the option into connector
CN5-B. Use the shortest wire when plugging the option into connector CN5-A. Refer to Option
Package Contents on page 8 for more information.
2. There are two screw holes on the unit for use as ground terminals (J). When connecting three options,
two ground wires will need to share the same unit ground terminal.
4. Prepare and connect the wire ends as shown in Figure 6 and Figure 7. Refer to
Wire Gauges and Tightening Torques on page 21 to confirm that the proper
tightening torque is applied to each terminal. Take particular precaution to ensure
that each wire is properly connected and wire insulation is not accidentally pinched
into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose
electrical connections could result in death or serious injury by fire due to overheating electrical connections.
Tightening screws beyond the specified tightening torque may cause erroneous operation, damage the
terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not
contact other wiring. Insufficient insulation may cause a short circuit and damage the option or unit.
Figure 6
Option terminal
Figure 6 Preparing Ends of Shielded Cable
Figure 7
Insulation
To customer
circuit
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Preparing wire ends:
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
about 5.5 mm (7/32”)
When not using
crimped insulated
sleeves
Screwdriver blade size
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Loosen the screws and
insert the wire into the
opening on the terminal block.
Depending on the unit model, some units may require routing the wiring through the
side of the front cover to the outside. In these cases, cut out the perforated openings
on the left side of the unit front cover as shown in Figure 9-A and leave no sharp
edges to damage wiring.
Route the wiring inside the enclosure as shown in Figure 9-B for units that do not
require routing through the front cover.
Refer to the Peripheral Devices & Options section of the unit Instruction Manual for
◆ Wire Gauges, Tightening Torques, and Ferrule-Type Terminals
■Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in Table 2.
Table 2 Wire Gauges and Tightening Torques
Ter min al
signal
P1 to P6,
PC
M1 to M4M3
■
Ferrule-Type Terminals
Screw
Size
M2
Tightening
Tor que
Nxm (inxlb)
0.22 to 0.25
(1.95 to 2.21)
0.5 to 0.6
(4.43 to 5.31)
(24 to 17 AWG)
(24 to 16 AWG)
(24 to 16 AWG)
(24 to 13 AWG)
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent ferrule-type
terminals with the specifications listed in Table 3 for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
The parameters outlined in the following sections are used to set up the unit for operation
with the option. Set parameters as needed. Parameter setting methods can be found in the
drive unit Instruction Manual.
◆ Parameter F5-09
Set parameter F5-09 to select the option output mode.
Ta bl e 5 shows the changes in the output terminal contents according to the output mode set
in F5-09.
Table 5 F5-09 and Output Mode
Ter mi nal
Block
TB1
TB2
F5-09 = 0
Ter min al
M1-M2 Zero speedDuring runDetermined by F5-07
M3-M4 Speed agreeAlarm (excluding bb)Determined by F5-08
P1-PCoC, GF (Overcurrent)
P2-PCov (Overvoltage)Determined by F5-02
P3-PC
P4-PCNot usedDetermined by F5-04
P5-PCoS (Overspeed)Zero speedDetermined by F5-05
P6-PC
Individual Output
(Default when Installed to
oH2 (Unit overheat)
or oL2 (overload)
oH, oH1 (Unit overheat)
or oL1 (Overload)
Drive)
F5-09 = 1
Binary Code Output
Binary code output
(Refer to Table 6)
Speed agreeDetermined by F5-06
F5-09 = 2
Multi-Function Output
(Default when Installed
to D1000)
Determined by F5-01
Determined by F5-03
Table 6 Binary Coded Output (F5-09 = 1)
Coded OutputDescription
0Normal operation (no fault)0000
1oC, GF (Overcurrent)1000
2ov (Overvoltage) 0100
3oL2 (Unit overload)1100
4oH, oH1 (Unit overheat)0010
5oS (Overspeed)1010
6Not used 0110
7rr, rH (Braking resistor overheat) 1110
8EF1 to EF12 (External fault)0001
YASKAWA ELECTRIC TOBP C730600 41E 1000-Series Option DO-A3 Installation Manual23
P1-PCP2-PCP3-PCP4-PC
TB2
Page 24
6 Related Parameters
Coded OutputDescription
9
AoL1 (Motor overload)0101
BNot used1101
CUv1, Uv2, Uv3 (Undervoltage)0011
DdEv (Speed deviation)1011
EPGo (PG disconnect)0111
FNot used1111
CPF, oFA, oFb, oFC
(Unit hardware fault)
P1-PCP2-PCP3-PCP4-PC
1001
TB2
◆ Parameter Table
Table 7 Related Parameters
No.
(Addr.
Hex)
F5-01
Terminal P1-PC Output Selection
(399)
F5-02
Terminal P2-PC Output Selection
(39A)
F5-03
Terminal P3-PC Output Selection
(39B)
F5-04
Terminal P4-PC Output Selection
(39C)
NameDescriptionValu es
Sets the function for contact output terminals
M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
<1>
When installed to drive
Default: 0
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: 1
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: 2
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: 4
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
<1> Refer to the unit Instruction Manual for more information on setting the F5 parameters.
NameDescriptionValu es
Sets the function for contact output terminals
M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
0: Output terminals are each assigned
separate output functions.
1: Binary code output
2: Multi-function output (set functions in
parameters F5-01 through F5-08)
<1>
When installed to drive
Default: 6
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: 37
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: F
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: F
Range: 0 to 1A7
When installed to D1000
Default: F
Range: 0 to 160
When installed to drive
Default: 0
Range: 0 to 2
When installed to D1000
Default: 2
Range: 2
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
YASKAWA ELECTRIC INDIA PRIVATE LIMITED
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India
Phone: 91-80-4244-1900
http://www.yaskawaindia.in
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
Fax: 91-80-4244-1901
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.