Type: CIMR-VU
Models: 200 V Class, Three-Phase Input: 0.1 to 18.5 kW
200 V Class, Single-Phase Input: 0.1 to 3.7 kW
400 V Class, Three-Phase Input: 0.2 to 18.5 kW
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or
omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Table of Contents
i.PREFACE & GENERAL SAFETY.................................................................. 11
Motor ............................................................................................................................................... 486
or equipment damage. Yaskawa is not responsible for the consequences of ignoring
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
11
TERMSTERMS
TERMSTERMS
i.1 Preface
i.1Preface
Yaskawa manufactures
products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
u
Applicable Documentation
The following manuals are available for V1000 series drives:
V1000 Series AC Drive Quick Start Guide
Read this manual first. This guide is packaged together with the product. It contains basic information
required to install and wire the drive. This guide provides basic programming and simple setup and
adjustment.
V1000 Series AC Drive Technical Manual
This manual describes installation, wiring, operation procedures, functions, troubleshooting,
maintenance, and inspections to perform before operation.
u
Symbols
Note:Indicates a supplement or precaution that does not cause drive damage.
Indicates a term or definition used in this manual.
u
Terms and Abbreviations
• Drive: Yaskawa V1000 Series Drive
• PM motor: Permanent Magnet Synchronous Motor (an abbreviation for IPM motor or SPM motor)
• IPM motor: Interior Permanent Magnet Motor (e.g., Yaskawa SSR1 Series motor)
• SPM motor: Surface Mounted Permanent Magnet Motor (e.g., Yaskawa SMRA Series SPM motor)
• PG: Pulse Generator
• r/min: Revolutions per Minute
• V/f: V/f Control
• OLV: Open Loop Vector Control
• OLV/PM: Open Loop Vector Control for PM
12
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
i.2 General Safety
i.2General Safety
u
Supplemental Safety Information
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Restore covers or shields before operating
the drive and run the drive according to the instructions described in this manual.
•
Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to
which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice
to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales
office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result
in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety message.
u
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
13
i.2 General Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Before servicing,
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock,
wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
all
Clear
machine loads before applying power to the drive.
When using DriveWorksEZ to create custom programming, the drive I/O terminal functions change from factory
settings and the drive will not perform as outlined in this manual.
Unpredictable equipment operation may result in death or serious injury.
Take special note of custom I/O programming in the drive before attempting to operate equipment.
personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Crush Hazard
Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental dropping
of the load.
The drive does not possess built-in load drop protection for lifting applications.
Failure to comply could result in death or serious injury from falling loads.
Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
14
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
i.2 General Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive
(200 V Class) and 480 Vac maximum (400 V Class).
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
is suitable for circuits capable of delivering not more than 31,000 RMS symmetrical Amperes, 240 Vac maximum
u
Drive Label Warnings
Always heed the warning information listed in Figure i.1 in the position shown in Figure i.2 .
WARNING
Read manual before installing.
Wait 5 minutes for capacitor discharge after
sconnecting po
di
To conform to requirements, make sure
to ground the supply neutral for 400V class.
Figure i.1 Warning Information
Risk of electric shock.
wer supply.
Figure i.2 Warning Information Position
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Warning
Label
15
i.2 General Safety
u
Warranty Information
Restrictions
n
The
drive was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or
health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health
care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa
representatives or the nearest Yaskawa sales office.
This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any
location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility
where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of
any accident.
u
Quick Reference
Easily Set Application-Specific Parameters
Preset parameter defaults are available for many applications. Refer to Application Selection on page
96.
Run a Motor of One-Frame Larger Capacity
When using this drive for variable torque loads such as fans and pumps, a motor one frame size larger can be used. Refer to C6-01: Drive Duty
Selection
The functions listed below affect the safe operation of the drive. Ensure that the settings fit the application requirements prior to operation.
Operation of digital outputs during Auto-tuning. Rotational
not allow for normal digital output operation.
Safe operations. Run by power on. Parameter setting b1-17.
LOCAL/REMOTE key effective during stop in drive mode. Parameter o2-01.
LED operator stop key priority selection. Parameter o2-02.
Enter press required after changing the keypad frequency reference. Parameter o2-05.
Operation interlock when program mode is selected. Parameter b1-08.
The removable terminal block with parameter backup function allows the transfer of parameter settings
after drive replacement. Refer to Dismantling the Removable Terminal Block
on page 155
Know the Details of Safety Measures
Auto-tuning allows for normal digital output operation. Non-rotational Auto-tuning does
Replace the Drive
on page 319.
Drive a Synchronous PM Motor
The V1000 drive can operate synchronous PM motors. Refer to Subchart A3: Operation with
Permanent Magnet Motors on page 94.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to
The maintenance period of fans and capacitors can be checked with drive monitors. Refer to Performance Life Monitors on page 314
16
Auto-Tuning
Check the Maintenance Period Using Drive Monitors
on page 102.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Drive or Motor Faults are Displayed on a Digital Operator
Refer to Fault Displays, Causes, and Possible Solutions on page 267 and Refer to
.
282
Standards Compliance
i.2 General Safety
Detailed Alarm Codes, Causes, and Possible Solutions on page
Refer to European Standards on page 466 and Refer to UL and CSA Standards
on page 474
.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
17
i.3 Application Precautions
i.3Application Precautions
u
General Application Precautions
Selecting a Reactor
n
An AC reactor or DC link choke can be used for the following:
•
to suppress harmonic current.
• to smooth peak current that results from capacitor switching.
• when the power supply is above 600 kVA.
• when the drive is running from a power supply system with thyristor converters.
Note:A DC link choke is built in to 200 V and 400 V class models with a capacity of 22 kW and higher (HD rating).
4000
Power supply harmonics
reactor required
Power Supply
Capacity (kVA)
600
Reactor
unnecessary
0
60400
Drive Capacity (kVA)
Figure i.3 Installing a Reactor
Drive Capacity
n
Make sure that the motor rated current is less than the rated nameplate output current of the drive. When running more than
one
in parallel from a single drive, the drive rated current should 1.1 times larger than the total motor rated current for
motor
all connected motors or nuisance drive faults may occur.
Starting Torque
n
The overload rating of the drive determines the starting and accelerating characteristics of the motor. Expect lower running
torque than when running the motor from line power. To get more starting torque, use a larger drive or increase both the motor
and drive capacity.
Emergency/Fast Stop
n
During a drive fault condition, a protective circuit is activated and drive output is shut off. The motor may coast to a stop or
attempt to decelerate depending on parameter settings. If the emergency/fast stop cannot stop the load as fast as desired, a
customer-supplied mechanical brake may be required. Test emergency stop circuitry before putting drive into operation.
Options
n
The B1, B2, +1, +2, and +3 terminals are used to connect optional power devices. Connect only devices compatible with the
drive.
Repetitive Starting/Stopping
n
Applications with frequent starts and stops often exceed 150% of their rated current values. Heat stress generated from
repetitive high current can shorten the life span of the IGBTs. The expected lifetime for the IGBTs is about 8 million start and
stop cycles with a 4 kHz carrier frequency and a 150% peak current.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. The user can also
choose to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive. This will help keep
peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the
initial test run, and make adjustments accordingly.
18
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
i.3 Application Precautions
u
Installation Environment
Enclosure Panels
n
Keep the drive in a clean environment by either selecting an area free of airborne dust, lint, and oil mist, or install the drive
in
an enclosure panel. Be sure to leave the required space between drives to provide for cooling, and that proper measures are
taken so that the ambient temperature remains within allowable limits. Keep flammable materials away from the drive. If the
drive must be used in an area where it is subjected to oil mist and excessive vibration, protective designs are available. Contact
Yaskawa or your Yaskawa agent for details.
Installation Direction
n
The drive should be installed upright as specified in the manual.
u
Settings
Motor Code
n
If
using OLV/PM designed for permanent magnet motors (A1-02 = 5), make sure that the proper motor code is set in parameter
E5-01 before performing a trial run.
Upper Limits
n
The drive is capable of running the motor up to 400 Hz. Due to the danger of accidentally operating the motor at high speed,
be sure to set the upper frequency limit. The default setting for the maximum output frequency is 60 Hz.
DC Injection Braking
n
Motor overheat can result if there is too much current used during DC Injection Braking, or if the DC Injection Braking time
is too long.
Acceleration/Deceleration Times
n
Acceleration and deceleration times are affected by how much torque the motor generates, the load torque, and the inertia
moment ((GD2)/4). Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for
as long as the Stall Prevention function is operating. For faster acceleration and deceleration, install a braking option or increase
the capacity of the drive.
u
General Handling
NOTICE: Wiring Check.
sure to perform a final check of all control wiring and other connections before applying line power. Make sure there are no short circuits on
the control terminals (+V, AC, etc.), as this could damage the drive.
Selecting a Molded Case Circuit Breaker (MCCB) or Ground Fault Circuit Interrupter (GFCI)
n
Yaskawa recommends installing a GFCI on the line power supply to protect drive wiring and prevent damage in the event of
component failure. An MCCB may also be used if permitted by the power system.
The GFCI should be designed for use with an AC drive (i.e., protected against harmonics)
MCCB selection depends on the power factor for the drive, determined by the power supply voltage, output frequency, and
load.
Refer to Installing Peripheral Devices on page 330 for more information on breaker installation. Note that a larger capacity
breaker is needed when using a fully electromagnetic MCCB, as operation characteristics vary with harmonic current.
Never connect the power supply lines to output terminals U/T1, V/T2, or W/T3. Doing so will destroy the drive. Be
Magnetic Contactor (MC) Installation
n
Use an MC to ensure that line power to the drive can be completely shut off when necessary. The MC should be wired so that
it opens when the drive fault output is triggered.
Avoid switching the MC on the power supply side more frequently than once every 30 minutes. Frequent switching can cause
damage to the drive.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
19
i.3 Application Precautions
Inspection and Maintenance
n
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury.
safe level, and check for unsafe voltages before servicing to prevent electrical shock. The internal capacitor remains charged even after the
power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power
to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and make sure the heatsink has cooled to a safe
level.
WARNING! Electrical Shock Hazard. Wait for at least the time specified on the drive warning label after opening the load switch on the
output side before any inspection or maintenance of permanent magnet (PM) motors. Failure to comply could result in death or serious
injury.
WARNING! Sudden Movement Hazard. Install a switch disconnect between the motor and the drive in applications where the machine can
still rotate even though the drive has fully stopped. Unpredictable equipment operation may result in death or serious injury.
WARNING! Sudden Movement Hazard. Do not attempt to move a load that could potentially rotate the motor faster than the maximum
allowable r/min when the drive has been shut off. Unpredictable equipment operation may result in death or serious injury.
NOTICE: Do not open and close the motor disconnect switch while the motor is running, as this may damage the drive.
NOTICE: If the motor is coasting, make sure the power to the drive is turned on and the drive output has completely stopped before closing
the load switch.
Wiring
n
Disconnect all power to the drive, wait at least five minutes after all indicators are OFF, measure the DC bus voltage to confirm
All wire ends should use ring terminals for UL/cUL compliance. Use only the tools recommended by the terminal manufacturer
for crimping.
Transporting the Drive
n
NOTICE: Prevent the drive from contact with salts, fluorine, bromine, phthalate ester, and other such harmful chemicals. Never steam clean
the drive. Failure to comply may cause damage to the drive components.
u
Notes on Motor Operation
Using a Standard Motor
n
Low Speed Range
The cooling fan of a standard motor is usually designed to sufficiently cool the motor at the rated speed. As the self-cooling
capability of such a motor reduces with the speed, applying full torque at low speed will possibly damage the motor. To prevent
motor damage from overheat, reduce the load torque as the motor slows. Figure i.4 shows the allowable load characteristics
for a Yaskawa standard motor. A motor designed specifically for operation with a drive should be used when 100% continuous
torque is needed at low speeds.
25% ED (or 15 min)
40% ED (or 20 min)
60% ED (or 40 min)
100
90
80
70
(%)
60
50
Continuous operation
Torque
3 6
Figure i.4 Allowable Load Characteristics for a Yaskawa Motor
20
Frequency (Hz)
Insulation Tolerance
Consider motor
voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly
long wiring distances. Contact Yaskawa or your Yaskawa agent for consultation.
20
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
60
i.3 Application Precautions
High Speed Operation
Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated
speed. Contact the motor or machine manufacturer.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full
understanding of the load torque characteristics for the application.
Vibration and Shock
The drive settings allow the user to choose between high carrier PWM control and low carrier PWM. Selecting high carrier
PWM can help reduce motor oscillation.
Take particular caution when using a variable speed drive for an application that is conventionally run from line power at a
constant speed. If mechanical resonance occurs, install shock-absorbing rubber around the base of the motor and enable the
Jump frequency selection parameter to prevent continuous operation in the resonant frequency range.
Audible Noise
Noise created during run varies by the carrier frequency setting. When using a high carrier frequency, audible noise from the
motor is comparable to the motor noise generated when running from line power. Operating above the rated r/min, however,
can create unpleasant motor noise.
Using a Synchronous Motor
n
• Synchronous motors cannot be started directly from line power. Applications requiring line power to start should use an
induction motor with the drive.
• A single drive is not capable of running multiple synchronous motors at the same time. Use a standard induction motor for
such setups.
• At start, a synchronous motor may rotate slightly in the opposite direction of the Run command depending on parameter
settings and motor type.
• The amount of starting torque that can be generated differs by each control mode and by the type of motor being used. Set
up the motor with the drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and
speed control range.
Contact Yaskawa or your Yaskawa agent if you plan to use a motor that does not fall within these specifications.
• Braking Torque: In Open Loop Vector Control for PM motors, braking torque is less than 125% when running between
20% to 100% speed, even with a braking resistor. Braking torque drops to less than half when running at less than 20%
speed.
• Load Inertia: In Open Loop Vector Control for PM motors, the allowable load inertia moment is approximately 50 times
higher than the motor inertia moment or less. Contact Yaskawa or your Yaskawa agent concerning applications with a larger
inertia moment.
• Holding Brake: When using a holding brake in Open Loop Vector Control for PM motors, release the brake prior to starting
the motor. Failure to set the proper timing can result in speed loss. Not for use with conveyor, transport, or hoist type
applications.
• Restarting a Coasting Motor: To restart a coasting motor rotating at over 200 Hz while in the V/f control mode, use the Short
Circuit Braking function to first bring the motor to a stop. Short Circuit Braking requires a special braking resistor. Contact
Yaskawa or your Yaskawa agent for details.
Speed Search can be used to restart a coasting motor rotating slower than 200 Hz. If the motor cable is relatively long,
however, the motor should instead be stopped using Short Circuit Braking, which forces the motor to stop by creating a
short-circuit in the motor windings.
Applications with Specialized Motors
n
Multi-Pole Motor
Because the rated current will differ from a standard motor, be sure to check the maximum current when selecting a drive.
Always stop the motor before switching between the number of motor poles. If a regen overvoltage (oV) fault occurs or if
overcurrent protection (oC) is triggered, the motor will coast to stop.
Submersible Motor
Because motor rated current is greater than a standard motor, select the drive capacity accordingly. Be sure to use a large
enough gauge motor cable to avoid decreasing the maximum torque level on account of voltage drop caused by a long motor
cable.
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
21
i.3 Application Precautions
Explosion-Proof Motor
Both the motor and drive need to be tested together to be certified as explosion-proof. The drive is not designed for explosion
proof areas.
Furthermore, if an encoder is attached to an explosion-proof motor make sure the encoder is also explosion-proof. Use an
insulating signal converter for connecting the encoder signal lines to the drives speed feedback option card.
Geared Motor
To avoid gear damage when operating at low speeds or very high speeds, make sure that both the gear and lubricant are rated
for the desired speed range. Consult with the manufacturer for applications that require operation outside the rated speed range
of the motor or gear box.
Single-Phase Motor
Variable speed AC drives are not designed for operation with single phase motors. Using capacitors to start the motor causes
excessive current to flow and can damage drive components. A split-phase start or a repulsion start can end up burning out
the starter coils because the internal centrifugal switch is not activated. The drive is for use with 3-phase motors only.
Motor with Brake
Caution should be taken when using a drive to operate a motor with a built-in holding brake. If the brake is connected to the
output side of the drive, it may not release at start due to low voltage levels. A separate power supply should be installed for
the motor brake. Motors with a built-in brake tend to generate a fair amount of noise when running at low speeds.
Power Driven Machinery (decelerators, belts, chains, etc.)
n
Continuous operation at low speeds wears on the lubricating material used in gear box type systems to accelerate and decelerate
power driven machinery. Caution should also be taken when operating at speeds above the rated machine speed due to noise
and shortened performance life.
22
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
1
Receiving
This chapter describes the proper inspections to perform after receiving the drive and illustrates the
different enclosure types and components.
MODEL NUMBER AND NAMEPLATE CHECK....................................................25
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
23
1.1 Section Safety
1.1Section Safety
CAUTION
Do not carry the drive by the front cover.
Failure to comply may cause the main body of the drive to fall, resulting in minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor
speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for drive duty and/or the motor service factor is adequate to accommodate the additional
heating with the intended operating conditions.
connected to a PWM drive may operate at a higher temperature than a utility-fed motor and the operating
24
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
MODEL
MAX APPLI. MOTOR : 0.75kW / 0.4kW REV : A
INPUT
OUTPUT
MASS
O / N
S / N
FILE NO
J
I
H
G
E
B
A
YASKAWA ELECTRIC CORPORATION MADE IN JAPAN
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
D
F
C
CIMR - V U 2 A 0001 F A A
Drive
V1000
Series
No.
Customized
Specifications
A Standard model
Design
Revision
Order
No.
Region
Code
No.Voltage Class
B
1-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 200-240 Vac
2
4
UUSA
<1> Refer to manual TOBPC71060635 for more information on these models.
<2> Refer to manual TOBPC71060621 for more information on these models.
<3> Drives with these specifications do not guarantee complete protection for the specified environmental condition.
No.
Environmental
Specification <3>
A
M
S
Standard
Humidity- and
dust-resistant
Vibration-resistant
No.
Enclosure Type
IP00/Open-Chassis
B
A
IP20/Open-Chassis
F IP20/NEMA Type 1
J
IP20/Finless <2>
L IP00/Finless <2>
NEMA 4X/IP66 <1>G
Refer to the tables below.
1.2 Model Number and Nameplate Check
1.2Model Number and Nameplate Check
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage.
If the drive appears damaged upon receipt, contact the shipper immediately.
Verify receipt of the correct model by checking the information on the nameplate.
•
• If you have received the wrong model or the drive does not function properly, contact your supplier.
u
Nameplate
A – Normal Duty Amps / Heavy Duty
Amps
B – Software version
C – CE and TÜV Certification
D – Enclosure type
E –
Address
<1>
F – Serial number
G – Lot number
H – Output specifications
I – Input specifications
J – AC drive model
Figure 1.1 Nameplate Information Example
<1> The address of the head office of Yaskawa Electric Corporation (responsible for product liability) is shown on the nameplate.
Receiving
1
Single-Phase 200 V Class
n
Normal DutyHeavy Duty
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Model
BA00010.21.20.10.8
BA00020.41.90.21.6
BA00030.753.30.43.0
BA00061.16.00.755.0
BA00102.29.61.58.0
BA00123.012.02.211.0
Max. Motor Capacity kW Rated Output Current A Max. Motor Capacity kW Rated Output Current A
25
1.2 Model Number and Nameplate Check
Model
BA0018
<1> Available with Heavy Duty rating only.
Three-Phase 200 V Class
n
Three-Phase 400 V Class
n
<1>
Model
2A00010.21.20.10.8
2A00020.41.90.21.6
2A00040.753.50.43.0
2A00061.16.00.755.0
2A00102.29.61.58.0
2A00123.012.02.211.0
2A00205.519.63.717.5
2A00307.530.05.525.0
2A00401140.07.533.0
2A00561556.01147.0
2A006918.569.01560.0
Model
4A00010.41.20.21.2
4A00020.752.10.41.8
4A00041.54.10.753.4
4A00052.25.41.54.8
4A00073.06.92.25.5
4A00093.78.83.07.2
4A00115.511.13.79.2
4A00187.517.55.514.8
4A00231123.07.518.0
4A00311531.01124.0
4A003818.538.01531.0
Max. Motor Capacity kW Rated Output Current A Max. Motor Capacity kW Rated Output Current A
Max. Motor Capacity kW Rated Output Current A Max. Motor Capacity kW Rated Output Current A
Max. Motor Capacity kW Rated Output Current A Max. Motor Capacity kW Rated Output Current A
Normal DutyHeavy Duty
––3.717.5
Normal DutyHeavy Duty
Normal DutyHeavy Duty
Note:Refer to Component Names on page 28 for differences regarding enclosure protection types and component descriptions.
26
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
1.3Drive Models and Enclosure Types
The following table describes drive enclosures and models.
Table 1.1 Drive Models and Enclosure Types
Enclosure Type
Voltage Class
Single-Phase
200 V Class
Three-Phase
200 V Class
Three-Phase
400 V Class
IP20/Open-Chassis
Drive Model
BA0001B–BA0001F
BA0002B–BA0002F
BA0003B–BA0003F
BA0006B–BA0006F
BA0010B–BA0010F
BA0012B–BA0012F
BA0018B–BA0018F
2A0001B–2A0001F
2A0002B–2A0002F
2A0004B–2A0004F
2A0006B–2A0006F
2A0010B–2A0010F
2A0012B–2A0012F
2A0020B–2A0020F
–2A0030A2A0030F
–2A0040A2A0040F
–2A0056A2A0056F
–2A0069A2A0069F
4A0001B–4A0001F
4A0002B–4A0002F
4A0004B–4A0004F
4A0005B–4A0005F
4A0007B–4A0007F
4A0009B–4A0009F
4A0011B–4A0011F
–4A0018A4A0018F
–4A0023A4A0023F
–4A0031A4A0031F
–4A0038A4A0038F
IP00/Open-Chassis
Drive Model
1.3 Drive Models and Enclosure Types
IP20/NEMA Type 1
Drive Model
Receiving
1
Two types of enclosures are offered for V1000 drives.
• IP20/Open-Chassis and IP00/Open-Chassis models are often placed inside a large enclosure panel where the front of the
drive is covered to prevent someone from accidentally touching charged components.
IP20/NEMA Type 1 models mount to an indoor wall and not inside a large enclosure panel.
•
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
27
1.4 Component Names
1.4Component Names
This section illustrates the drive components as they are mentioned in this manual.
u
IP20/Open-Chassis
Single-Phase AC 200 V BA0001B to BA0003B
n
Three-Phase AC 200 V 2A0001B to 2A0006B
A
L
K
J
B
C
H
I
D
E
F
G
A –
Fan cover
B – Mounting hole
C – Heatsink
D – Optional 24 VDC power supply
connector cover
E – Terminal board Refer to Control
Circuit Terminal Block Functions
on page 64
F – Terminal cover
Figure 1.2 Exploded View of IP20/Open-Chassis Type Components (Model 2A0006B)
<1> Models BA0001B to BA0003B and 2A0001B to 2A0004B do not have a cooling fan or a cooling fan cover.
<1>
G – Front cover screw
H – Front cover
I – Comm port
J – LED operator Refer to Using the
Digital LED Operator on page 80
K – Case
L –
Cooling fan
<1>
28
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
Single-Phase AC 200 V BA0006B to BA0018B
n
Three-Phase AC 200 V 2A0010B to 2A0020B
Three-Phase AC 400 V 4A0001B to 4A0011B
L
K
J
I
1.4 Component Names
A
M
B
C
A –
Fan cover
B – Mounting hole
C – Heatsink
D – Optional 24 VDC power supply
connector cover
E – Comm port
F – Terminal board Refer to Control
Circuit Terminal Block Functions
on page 64
G – Front cover screw
Figure 1.3 Exploded View of IP20/Open-Chassis Type Components (Model 2A0012B)
<1> Models BA0006B
fans.
H
D
E
F
G
<1>
and 4A0001B to 4A0004B do not have a cooling fan or a cooling fan cover. Model BA0018B has two cooling
H – Front cover
I – Terminal cover
J – Bottom cover
K – LED operator Refer to Using the
Digital LED Operator on page 80
L – Case
M –
Cooling fan
<1>
Receiving
1
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
29
1.4 Component Names
u
IP00/Open-Chassis
Three-Phase AC 200 V 2A0030A to 2A0069A
n
Three-Phase AC 400 V 4A0018A to 4A0038A
A
B
M
C
L
D
J
I
K
E
H
F
G
A – Fan cover
Cooling Fan
B –
C – Mounting hole
D – Heatsink
E – Optional 24 VDC power supply
connector cover
F – Terminal board Refer to Control
Circuit Terminal Block Functions
on page 64
G – Bottom cover
Figure 1.4 Exploded View of IP00/Open-Chassis Type Components (Model 4A0018A)
H – Front cover screw
I – Front cover
J – Terminal cover
K – Comm port
L – LED operator Refer to Using the
Digital LED Operator on page 80
M – Case
30
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual