Xylem AC5660 User Manual

Installation, Operation,
and Maintenance Manual
Series A-C 1500
Table of Contents
Introduction and Safety..................................................................................................................3
Introduction..................................................................................................................................3
Safety.............................................................................................................................................3
Safety terminology and symbols........................................................................................... 3
Safety instruction decals......................................................................................................... 4
User safety................................................................................................................................ 5
Environmental safety...............................................................................................................6
Product warranty......................................................................................................................... 7
Transportation and Storage.......................................................................................................... 8
Inspect the delivery.....................................................................................................................8
Inspect the package................................................................................................................8
Inspect the unit........................................................................................................................ 8
Pump lifting.................................................................................................................................. 8
Long-term storage.......................................................................................................................9
Product Description......................................................................................................................10
General description.................................................................................................................. 10
Operational specifications....................................................................................................... 10
Installation......................................................................................................................................12
Preinstallation............................................................................................................................ 12
Pump location guidelines.....................................................................................................12
Piping checklist......................................................................................................................13
Typical installation.....................................................................................................................14
Commissioning, Startup, Operation, and Shutdown...............................................................15
Preparation for startup............................................................................................................. 15
Check the rotation.................................................................................................................15
Prime the pump.........................................................................................................................16
Start the pump...........................................................................................................................16
Pump operation precautions...................................................................................................17
Shut down the pump................................................................................................................ 17
Note on the packed pump operation.....................................................................................17
Maintenance..................................................................................................................................19
Lubrication................................................................................................................................. 19
Disassembly............................................................................................................................... 19
Disassembly precautions......................................................................................................19
Drain the pump......................................................................................................................19
Remove the pump assembly............................................................................................... 19
Remove the impeller.............................................................................................................20
Remove the mechanical seal (AC-1500 and AC-1500-F).................................................20
Remove the seal or packing rings (AC-1500-S, AC-1500-D, and AC-1500-PF)............ 20
Remove the 2-inch single mechanical seal (AC-1500-S)..................................................20
Pre-assembly inspections.........................................................................................................20
Replacement guidelines.......................................................................................................21
Shaft and sleeve inspection................................................................................................. 21
Reassembly................................................................................................................................ 21
Assemble the standard mechanical seal (AC-1500 and AC-1500-F)............................. 21
Series A-C 1500 Installation, Operation, and Maintenance Manual 1
Assemble the single mechanical seal (AC-1500-S)...........................................................22
Assemble the 2-inch single mechanical seal (AC-1500-S)...............................................23
Assemble the double mechanical seal (AC-1500-D)........................................................24
Assemble the packed stuffing box (AC-1500-PF)............................................................. 25
Install the impeller.................................................................................................................26
Reinstall the pump assembly............................................................................................... 26
Screw torque values..............................................................................................................26
Dealer servicing ....................................................................................................................26
2 Series A-C 1500 Installation, Operation, and Maintenance Manual

Introduction and Safety

Introduction

Purpose of this manual
The purpose of this manual is to provide necessary information for:
• Installation
• Operation
• Maintenance
CAUTION:
Read this manual carefully before installing and using the product. Improper use of the product can cause personal injury and damage to property, and may void the warranty.
NOTICE:
Save this manual for future reference, and keep it readily available at the location of the unit.
Introduction and Safety
Requesting other information
Special versions can be supplied with supplementary instruction leaflets. See the sales contract for any modifications or special version characteristics. For instructions, situations, or events that are not considered in this manual or in the sales documents, please contact the nearest Xylem representative.
Always specify the exact product type and identification code when requesting technical information or spare parts.

Safety

WARNING:
• The operator must be aware of safety precautions to prevent physical injury.
• Any pressure-containing device can explode, rupture, or discharge its contents if it is
over-pressurized. Take all necessary measures to avoid over-pressurization.
• Operating, installing, or maintaining the unit in any way that is not covered in this
manual could cause death, serious personal injury, or damage to the equipment. This includes any modification to the equipment or use of parts not provided by Xylem. If there is a question regarding the intended use of the equipment, please contact a Xylem representative before proceeding.
• Do not change the service application without the approval of an authorized Xylem
representative.
CAUTION:
You must observe the instructions contained in this manual. Failure to do so could result in physical injury, damage, or delays.

Safety terminology and symbols

About safety messages
It is extremely important that you read, understand, and follow the safety messages and regulations carefully before handling the product. They are published to help prevent these hazards:
Series A-C 1500 Installation, Operation, and Maintenance Manual 3
Introduction and Safety
Hazard levels
• Personal accidents and health problems
• Damage to the product
• Product malfunction
Hazard level Indication
DANGER:
A hazardous situation which, if not avoided, will result in death or serious injury
Hazard categories
WARNING:
CAUTION:
NOTICE:
Hazard categories can either fall under hazard levels or let specific symbols replace the ordinary hazard level symbols.
Electrical hazards are indicated by the following specific symbol:
Electrical Hazard:
These are examples of other categories that can occur. They fall under the ordinary hazard levels and may use complementing symbols:
• Crush hazard
• Cutting hazard
• Arc flash hazard
A hazardous situation which, if not avoided, could result in death or serious injury
A hazardous situation which, if not avoided, could result in minor or moderate injury
• A potential situation which, if not avoided, could result in undesirable conditions
• A practice not related to personal injury

Safety instruction decals

WARNING:
The maximum working pressure of the pump is listed on the nameplate. Do not exceed this pressure. Failure to follow these instructions can result in serious personal injury, death, and/or property damage.
Alert symbol
This safety alert symbol is used in manuals and on the safety instruction decals on the pump to draw attention to safety-related instructions.
When used, the safety alert symbol means that failure to follow the instructions may result in a safety hazard.
4 Series A-C 1500 Installation, Operation, and Maintenance Manual
Decals
P70643
P70644
P70642
Introduction and Safety
Make sure your pump has these safety instruction decals and that they are located as this figure shows. If the decals are missing or illegible, contact your local sales and service representative for a replacement.
Make sure that all safety instruction decals are always clearly visible and readable.

User safety

General safety rules
These safety rules apply:
• Always keep the work area clean.
• Pay attention to the risks presented by gas and vapors in the work area.
• Avoid all electrical dangers. Pay attention to the risks of electric shock or arc flash hazards.
• Always bear in mind the risk of drowning, electrical accidents, and burn injuries.
Safety equipment
Use safety equipment according to the company regulations. Use this safety equipment within the work area:
• Hard hat
• Safety goggles, preferably with side shields
• Protective shoes
• Protective gloves
• Gas mask
• Hearing protection
Series A-C 1500 Installation, Operation, and Maintenance Manual 5
Introduction and Safety
• First-aid kit
• Safety devices
Electrical connections
Electrical connections must be made by certified electricians in compliance with all international, national, state, and local regulations. For more information about requirements, see sections dealing specifically with electrical connections.
Precautions before work
Observe these safety precautions before you work with the product or are in connection with the product:
• Provide a suitable barrier around the work area, for example, a guard rail.
• Make sure that all safety guards are in place and secure.
• Make sure that you have a clear path of retreat.
• Make sure that the product cannot roll or fall over and injure people or damage
• Make sure that the lifting equipment is in good condition.
• Use a lifting harness, a safety line, and a breathing device as required.
• Allow all system and pump components to cool before you handle them.
• Make sure that the product has been thoroughly cleaned.
• Disconnect and lock out power before you service the pump.
• Check the explosion risk before you weld or use electric hand tools.
NOTICE:
Never operate a unit unless safety devices are installed. Also see specific information about safety devices in other chapters of this manual.
property.
Wash the skin and eyes
Follow these procedures for chemicals or hazardous fluids that have come into contact with your eyes or your skin:
Condition Action Chemicals or hazardous fluids in
eyes
Chemicals or hazardous fluids on skin

Environmental safety

The work area
Always keep the station clean.
Waste and emissions regulations
Observe these safety regulations regarding waste and emissions:
• Appropriately dispose of all waste.
• Handle and dispose of the processed liquid in compliance with applicable environmental regulations.
• Clean up all spills in accordance with safety and environmental procedures.
• Report all environmental emissions to the appropriate authorities.
1. Hold your eyelids apart forcibly with your fingers.
2. Rinse the eyes with eyewash or running water for at least 15 minutes.
3. Seek medical attention.
1. Remove contaminated clothing.
2. Wash the skin with soap and water for at least 1 minute.
3. Seek medical attention, if necessary.
WARNING:
Radiation Hazard. Do NOT send the product to Xylem if it has been exposed to any nuclear radiation.
6 Series A-C 1500 Installation, Operation, and Maintenance Manual
Electrical installation
For electrical installation recycling requirements, consult your local electric utility.
Recycling guidelines
Always follow local laws and regulations regarding recycling.

Product warranty

Coverage
Xylem undertakes to remedy defects in products from Xylem under these conditions:
• The faults are due to defects in design, materials, or workmanship.
• The faults are reported to a local sales and service representative within the warranty period.
• The product is used only under the conditions that are described in this manual.
• The monitoring equipment that is incorporated in the product is correctly connected and in use.
• All service and repair work that is done by Xylem authorized personnel.
• Genuine Xylem parts are used.
• Only Ex-approved spare parts and accessories that are authorized by an Ex-approved Xylem representative are used in Ex-approved products.
Limitations
The warranty does not cover defects that are caused by these situations:
Deficient maintenance
• Improper installation
Modifications or changes to the product and installation that are made without consulting a Xylem authorized representative
• Incorrectly executed repair work
• Normal wear and tear
Xylem assumes no liability for these situations:
• Bodily injuries
• Material damages
• Economic losses
Introduction and Safety
Warranty claim
Xylem products are high-quality products with expected reliable operation and long life. However, should the need for a warranty claim arise, contact your local sales and service representative.
Series A-C 1500 Installation, Operation, and Maintenance Manual 7

Transportation and Storage

Transportation and Storage

Inspect the delivery

Inspect the package

1. Inspect the package for damaged or missing items upon delivery.
2. Note any damaged or missing items on the receipt and freight bill.
3. File a claim with the shipping company if anything is out of order. If the product has been picked up at a distributor, make a claim directly to the
distributor.

Inspect the unit

1. Remove packing materials from the product. Dispose of all packing materials in accordance with local regulations.
2. Inspect the product to determine if any parts have been damaged or are missing.
3. If applicable, unfasten the product by removing any screws, bolts, or straps. For your personal safety, be careful when you handle nails and straps.
4. Contact the local sales representative if there is any issue.

Pump lifting

WARNING:
• Assembled units and their components are heavy. Failure to properly lift and support this equipment can result in serious physical injury and/or equipment damage. Lift equipment only at the specifically identified lifting points. Lifting devices such as eyebolts, slings, and spreaders must be rated, selected, and used for the entire load being lifted.
• Crush hazard. The unit and the components can be heavy. Use proper lifting methods and wear steel-toed shoes at all times.
In order to lift the entire pump, use slings placed around the unit as shown.
8 Series A-C 1500 Installation, Operation, and Maintenance Manual
Transportation and Storage
Figure 1: Proper lifting method

Long-term storage

If the unit is stored for more than 6 months, these requirements apply:
• Store in a covered and dry location.
• Store the unit free from heat, dirt, and vibrations.
• Rotate the shaft by hand several times at least every three months.
Treat bearing and machined surfaces so that they are well preserved. Refer to the drive unit and coupling manufacturers for their long-term storage procedures.
For questions about possible long-term storage treatment services, please contact your local sales and service representative.
Series A-C 1500 Installation, Operation, and Maintenance Manual 9

Product Description

Product Description

General description

The pump is a centrifugal, close-coupled pump. These features make the pump easy to install, operate, and service:
• High efficiency
• Rugged bronze-fitted construction
• Horizontal or vertical in-line mounting
Intended applications
WARNING:
California Proposition 65 warning! This product contains chemicals known to the state of California to cause cancer and birth defects or other reproductive harm.
NOTICE:
This product is not intended for potable water applications.
The pump is intended for use with these pumped fluids:
• Unheated domestic and fresh water
• Boiler feed water
• Condensate
• Hydronic cooling or heating
• Benign liquids
• Pressure boosting
• General liquid transfer
Rotation
Pump rotation is clockwise when viewed from the back of the motor. An arrow is also located on the pump to show the direction of rotation.
Operational
Mechanical seal specifications
specifications
This table describes the specifications of each mechanical seal type.
Seal type Parameter Value Standard seals, BUNA
Standard seals, EPT Optional seals, EPR carbon/tungsten
carbide
Flushed single seals
Flushed double seals
5
5
1,3,4
1,3,4
pH range limits for BUNA pH 7–9 Liquid temperature range that
complies with the pH range limits for BUNA
pH range limits for EPT pH 7–11 Liquid temperature range that
complies with the pH range limits for EPT
pH range limits pH 7–9 Liquid temperature range 0˚F to 250˚F (-18˚C to 121˚C) pH range limits pH 7–9 Liquid temperature range 0˚F to 250˚F (-18˚C to 121˚C)
-20˚F to 225˚F (-29˚C to 107˚C)
-20˚F to 250˚F (-29˚C to 121˚C)
10 Series A-C 1500 Installation, Operation, and Maintenance Manual
Product Description
Seal type Parameter Value
2
Packing
pH range pH 7–9 Liquid temperature range 0˚F to 200˚F (-18˚C to 93˚C)
Table notes
1. An external flush is required on low pressure systems that contain a high concentration of abrasives.
2. Use packing on open or closed systems which require a large amount of makeup water, as well as systems that are subjected to a wide variety of chemical conditions and solids buildup.
3. For operating temperatures above 250°F, a cooled flush is required and is recommended for temperatures above 225°F for optimum seal life. On closed systems, cooling is accomplished by inserting a small heat exchanger in the flush line to cool the seal flushing fluid.
4. Flush-line filters and sediment separators are available on request.
5. Use a standard seal on closed or open systems that are relatively free of dirt and/or other abrasive particles.
Series A-C 1500 Installation, Operation, and Maintenance Manual 11

Installation

Installation

Preinstallation

Precautions
WARNING:
• When installing in a potentially explosive environment, make sure that the motor is properly certified.
• You must earth (ground) all electrical equipment. This applies to the pump equipment, the driver, and any monitoring equipment. Test the earth (ground) lead to verify that it is connected correctly.
• Motors without built-in protection must be provided with contactors and thermal overload protection for single-phase motors, or starters with heaters for three-phase motors. (See the nameplate on the drive unit to select properly-sized overloads.)
NOTICE:
Supervision by an authorized Xylem representative is recommended to ensure proper installation. Failure to do so may result in equipment damage or decreased performance.
Evaluate the installation in order to determine that the Net Positive Suction Head Available (NPSHA) meets or exceeds the Net Positive Suction Head Required (NPSHR), as stated by the pump performance curve.

Pump location guidelines

WARNING:
Assembled units and their components are heavy. Failure to properly lift and support this equipment can result in serious physical injury and/or equipment damage. Lift equipment only at the specifically identified lifting points. Lifting devices such as eyebolts, slings, and spreaders must be rated, selected, and used for the entire load being lifted.
Guideline Explanation/comment Keep the pump as close to the liquid source as practically
possible. If the pump is not on a closed system, locate the pump so
that the fewest number of bends or elbows in the suction pipe are needed.
Make sure that the space around the pump is sufficient. This facilitates ventilation, inspection, maintenance,
If you require lifting equipment such as a hoist or tackle, make sure that there is enough space above the pump.
Protect the unit from weather and water damage due to rain, flooding, and freezing temperatures.
This minimizes the friction loss and keeps the suction piping as short as possible.
and service. This makes it easier to properly use the lifting
equipment and safely remove and relocate the components to a safe location.
This is applicable if nothing else is specified.
12 Series A-C 1500 Installation, Operation, and Maintenance Manual

Piping checklist

Installation
Guideline Explanation/comment Do not install and operate the equipment in closed
systems unless the system is constructed with properly­sized safety devices and control devices.
Take into consideration the occurrence of unwanted noise and vibration.
If the pump location is overhead, undertake special precautions to reduce possible noise transmission.
WARNING:
• The heating of water and other fluids causes volumetric expansion. The associated forces can cause the failure of system components and the release of high­temperature fluids. In order to prevent this, install properly sized and located compression tanks and pressure-relief valves. Failure to follow these instructions can result in serious personal injury or death, or property damage.
• Avoid serious personal injury and property damage. Make sure that the flange bolts are adequately torqued.
• Never force piping to make a connection with a pump.
Acceptable devices:
• Pressure relief valves
• Compression tanks
• Pressure controls
• Temperature controls
• Flow controls
If the system does not include these devices, consult the engineer or architect in charge before you operate the pump.
The best pump location for noise and vibration absorption is on a concrete floor with subsoil underneath.
Consider a consultation with a noise specialist.
Check Explanation/comment Checked Check that a section of straight pipe, with a length that
is five times its diameter, is installed between the suction side of the pump and the first elbow, or that a B&G Suction Diffuser is installed.
Check that the suction and discharge pipes are supported independently by use of pipe hangers near the pump .
Check that there is a strong, rigid support for the suction and discharge lines.
For pumps with flanges, check that the bolt holes in the pump flanges match the bolt holes in the pipe
flanges.
For pumps mounted in vertical piping with the motor in the horizontal position, check that adequate support is provided.
Check that the suction or discharge lines are not forced into position.
Check that fittings for absorbing expansion are installed in the system when considerable temperature changes are expected.
This reduces suction turbulence by straightening the flow of liquid before it enters the pump.
This eliminates pipe strain on the pump .
As a rule, ordinary wire or band hangers are not adequate to maintain proper alignment.
This prevents strain on the pump parts and piping. Do not mount the pump with the motor vertically downward. Do not use motor lift rings to suspend the pump.
Coupling and bearing wear will result if suction or discharge lines are forced into position.
The code for Pressure Piping (A.S.A.B. 31.1) lists many types of supports available for various applications.
This helps to avoid strain on the pump.
Series A-C 1500 Installation, Operation, and Maintenance Manual 13
1
2
3
4
5
6
7
8
9
10
11
Installation
Check Explanation/comment Checked Check that you have a foot valve of equal or greater
area than the pump suction piping when you use in an open system with a suction lift.
Check that flexible piping is used on both the suction and discharge sides of the pump when you use an isolation base.
Check that a triple duty valve is installed in the discharge line.
Check that the pipeline has isolation valves around the pump and has a drain valve in the suction pipe.
Use PTFE tape sealer or a high quality thread sealant when you install the suction and discharge connections to a threaded pump housing.

Typical installation

Prevent clogging by using a strainer at the suction inlet next to the foot valve. Make sure that the strainer has an area three times that of the suction pipe with a mesh hole diameter of no less than 0.25 in. (0.64 cm).
This valve serves as a check valve that protects the pump from water hammer, and serves as an isolation valve for servicing and for throttling.
1. Compression tank (located in the suction piping)
2. Air separator
3. System supply
4. Circuit setter
5. Triple duty valve
6. Pump
7. Suction diffuser
8. Isolation valve
9. Pipe from boiler, chiller, or converter
10. Cold water supply
11. Reducing valve
Check that the control and safety devices have these characteristics:
• Properly sized for their purpose
• Placed correctly in the system before putting the system into operation
14 Series A-C 1500 Installation, Operation, and Maintenance Manual

Commissioning, Startup, Operation, and Shutdown

Commissioning, Startup, Operation, and Shutdown

Preparation for startup

WARNING:
• Failure to follow these precautions before you start the unit will lead to serious personal injury and equipment failure.
• Do not operate the pump below the minimum rated flows or with the suction or discharge valves closed. These conditions can create an explosive hazard due to vaporization of pumped fluid and can quickly lead to pump failure and physical injury.
• If the pump, motor, or piping operate at extremely high or low temperatures, then guarding or insulation is required. Failure to follow these instructions can result in serious personal injury or death, and property damage.
• Always disconnect and lock out power to the driver before you perform any installation or maintenance tasks. Failure to disconnect and lock out driver power will result in serious physical injury.
• Operating the pump in reverse rotation can result in the contact of metal parts, heat generation, and breach of containment.
NOTICE:
You must follow these precautions before you start the pump:
At initial startup, do not adjust the variable-speed drivers or check for speed governor or over-speed trip settings while the variable-speed driver is coupled to the pump. If the settings have not been verified, then uncouple the unit and refer to instructions supplied by the driver manufacturer.

Check the rotation

WARNING:
• Verify the driver settings before you start any pump.
• Make sure that the warm-up rate does not exceed 2.5°F (1.4°C) per minute.
• Flush and clear the system thoroughly to remove dirt or debris in the pipe system in order to prevent premature failure at initial startup.
• Bring variable-speed drivers to the rated speed as quickly as possible.
• Run a new or rebuilt pump at a speed that provides enough flow to flush and cool the close-running surfaces of the stuffing-box bushing.
• If temperatures of the pumped fluid will exceed 200°F (93°C), then warm up the pump prior to operation. Circulate a small amount of fluid through the pump until the casing temperature is within 100°F (38°C) of the fluid temperature.
• Operating the pump in reverse rotation can result in the contact of metal parts, heat generation, and breach of containment.
• Always disconnect and lock out power to the driver before you perform any installation or maintenance tasks. Failure to disconnect and lock out driver power will result in serious physical injury.
Series A-C 1500 Installation, Operation, and Maintenance Manual 15
Commissioning, Startup, Operation, and Shutdown
1. Unlock power to the driver.
2. Make sure that everyone is clear, and then jog the driver long enough to determine that the direction of rotation corresponds to the arrow on the pump.
3. Lock out power to the driver.

Prime the pump

CAUTION:
Do not run the pump dry.
Make sure that the pump body is full of liquid before startup. If the system does not automatically fill the pump body with liquid, then you must manually prime the pump.
1. Loosen the vent plugs on the pump body.
2. While venting the air from the pump body, rotate the pump shaft a few times by hand.
3. After all air has been purged from the pump, close the vent plugs.

Start the pump

CAUTION:
• Observe the pump for vibration levels, bearing temperature, and excessive noise. If normal levels are exceeded, shut down the pump and resolve the issue.
Before you start the pump, you must perform these tasks:
• Open the suction valve.
• Open any recirculation or cooling lines.
1. Fully close or partially open the discharge valve, depending on system conditions.
2. Start the driver.
3. Slowly open the discharge valve until the pump reaches the desired flow.
4. Immediately check the pressure gauge to ensure that the pump quickly reaches the correct discharge pressure.
5. If the pump fails to reach the correct pressure, perform these steps: a) Stop the driver.
b) Prime the pump again. c) Restart the driver.
6. Monitor the pump while it is operating: a) Check the pump for bearing temperature, excessive vibration, and noise.
b) If the pump exceeds normal levels, then shut down the pump immediately and
correct the problem.
7. Repeat steps 5 and 6 until the pump runs properly.
16 Series A-C 1500 Installation, Operation, and Maintenance Manual

Pump operation precautions

General considerations
CAUTION:
• Vary the capacity with the regulating valve in the discharge line. Never throttle the flow from the suction side since this can result in decreased performance, unexpected heat generation, and equipment damage.
• Do not overload the driver. Driver overload can result in unexpected heat generation and equipment damage. The driver can overload in these circumstances:
• The specific gravity of the pumped fluid is greater than expected.
• The pumped fluid exceeds the rated flow rate.
• Make sure to operate the pump at or near the rated conditions. Failure to do so can result in pump damage from cavitation or recirculation.
Operation at reduced capacity
WARNING:
Never operate any pumping system with a blocked suction and discharge. Operation, even for a brief period under these conditions, can cause confined pumped fluid to overheat, which results in a violent explosion. You must take all necessary measures to avoid this condition.
Commissioning, Startup, Operation, and Shutdown
CAUTION:
Avoid excessive vibration levels. Excessive vibration levels can damage the bearings, stuffing box or seal chamber, and the mechanical seal, which can result in decreased performance.
NOTICE:
• Avoid increased radial load. Failure to do so can cause stress on the shaft and bearings.
• Avoid heat build-up. Failure to do so can cause rotating parts to score or seize.
• Avoid cavitation. Failure to do so can cause damage to the internal surfaces of the pump.
Operation under freezing conditions
NOTICE:
Do not expose an idle pump to freezing conditions. Drain all liquid that is inside the pump and the flush lines. Failure to do so can cause liquid to freeze and damage the pump.

Shut down the pump

1. Slowly close the discharge valve.
2. Shut down and lock the driver to prevent accidental rotation.

Note on the packed pump operation

Tighten the gland nuts
Before you start the pump, back off the packing gland nuts or screws until the gland is loose.
Hand tighten until the gland is snug against the freely run from the packing. This is normal and should be allowed to continue for a period of time before you continue to tighten the gland. Tighten the gland nuts slowly and one flat at a time.
Series A-C 1500 Installation, Operation, and Maintenance Manual 17
first packing ring. Initially, water might
Commissioning, Startup, Operation, and Shutdown
Leakage rate
An adequate leakage rate is not one single value for all pumps and installations, but is the amount required to provide adequate cooling and lubrication. The required leakage is influenced by operating pressure, fluid temperature, shaft speed, and so forth. For fluid temperatures in the range of 32°F to 190°F (0°C to 88°C), average leakage rates of 60 to 80 drops per minute are recommended. However, each individual pump and installation has unique operating conditions that result in widely-variable leakage rate requirements.
Maximum fluid temperature
At fluid operating temperatures near the upper limit of 190°F (88°C), the maximum temperature rise of the leakage is important. Never operate a packed pump with steam forming at the gland. This limits the temperature rise to a maximum of about 20°F (-7°C). If the formation of steam persists at higher leakage rates, you must provide cooling water by means of an external supply, or a heat exchanger used to cool the bypass flush.
18 Series A-C 1500 Installation, Operation, and Maintenance Manual

Maintenance

Lubrication

The pump motor has been lubricated at the factory. Keep the motor properly lubricated in accordance with the motor manufacturer's instructions.

Disassembly

Disassembly precautions

This manual clearly identifies accepted methods for disassembling units. These methods must be adhered to.
WARNING:
• Make sure that the pump is isolated from the system and that pressure is relieved before you disassemble the pump, remove plugs, open vent or drain valves, or disconnect the piping.
• Always disconnect and lock out power to the driver before you perform any installation or maintenance tasks. Failure to disconnect and lock out driver power will result in serious physical injury.
• Crush hazard. The unit and the components can be heavy. Use proper lifting methods and wear steel-toed shoes at all times.
Maintenance

Drain the pump

NOTICE:
Make sure that all replacement parts are available before you disassemble the pump for overhaul.
CAUTION:
• Allow all system and pump components to cool before you handle them to prevent physical injury.
1. Close the isolation valves on the suction and discharge sides of the pump. You must drain the system if no valves are installed.
2. Open the drain valve. Do not proceed until liquid stops coming out of the drain valve. If liquid continues to
flow from the drain valve, the isolation valves are not sealing properly and you must repair them before you proceed.
3. Leave the drain valve open and remove the drain plug located on the bottom of the pump housing.
Do not reinstall the plug or close the drain valve until the reassembly is complete.
4. Drain the liquid from the piping and flush the pump if it is necessary.
5. Disconnect all auxiliary piping and tubing.

Remove the pump assembly

1. Loosen the volute capscrews but do not remove them.
2. Use the capscrews in the jackscrew holes in order to loosen the pump assembly from the volute.
Series A-C 1500 Installation, Operation, and Maintenance Manual 19
Maintenance
3. Remove the seal flushing tube if it is used.
4. Remove the volute capscrews.
5. Remove the pump assembly from the volute.

Remove the impeller

WARNING:
Never apply heat to remove an impeller. The use of heat may cause an explosion due to trapped liquid, resulting in severe physical injury and property damage.
CAUTION:
Wear heavy work gloves when you handle impellers. The sharp edges can cause physical injury.
1. Remove the impeller capscrew.
2. Remove the lockwasher and the washer.
3. Remove the impeller.
WARNING:
Pressurized device. Make sure that the internal pressure is relieved before you continue.

Remove the mechanical seal (AC-1500 and AC-1500-F)

1. Remove the rotating portion of the seal. If necessary, use a screwdriver to loosen the rubber ring.
2. Remove the seal insert, the insert gasket, and the retainer if it is used.

Remove the seal or packing rings (AC-1500-S, AC-1500-D, and AC-1500-PF)

1. Remove the hex nuts from the seal cap bolts.
2. For the AC-1500-PF, remove the hex nuts that hold the packing gland to the box.
3. Remove the coverplate screws.
4. Remove the coverplate from the bracket.
5. Remove the seal assembly or packing rings.

Remove the 2-inch single mechanical seal (AC-1500-S)

1. Remove the screws from the seal gland.
2. Remove the coverplate screws.
3. Remove the coverplate from the bracket.
4. Remove the seal assembly.

Pre-assembly inspections

Guidelines
Before you assemble the pump parts, make sure you follow these guidelines:
• Inspect the pump parts according to the information in these pre-assembly topics before you reassemble your pump. Replace any part that does not meet the required criteria.
• Make sure that the parts are clean. Clean the pump parts in solvent in order to remove oil, grease, and dirt.
stuffing
20 Series A-C 1500 Installation, Operation, and Maintenance Manual
NOTICE:
Protect machined surfaces while you clean the parts. Failure to do so may result in equipment damage.

Replacement guidelines

Impeller replacement
This table shows the criteria for replacing the impeller:
Impeller parts When to replace Impeller vanes • When grooved deeper than 1/16 in. (1.6 mm), or
Vane edges When you see cracks, pitting, or corrosion damage
Gaskets, O-rings, and seatsreplacement
• Replace all gaskets and O-rings at each overhaul and disassembly.
• Inspect the seats. They must be smooth and free of physical defects.
• Replace parts if the seats are defective.

Shaft and sleeve inspection

Inspection criteria
Inspect the shaft and sleeve according to this criteria:
• Thoroughly clean the shaft and sleeve.
• Thoroughly clean the coverplate seal cavity.
• Inspect the surface for damage such as pitting, corrosion, nicks, and scratches.
Replace these parts if they are damaged.
Maintenance
• When worn evenly more than 1/32 in. (0.8 mm)

Reassembly

Assemble the standard mechanical seal (AC-1500 and AC-1500-F)

1. Lubricate the shaft sleeve and coverplate seal cavity with soapy water. Do not use a petroleum lubricant.
2. Install a new insert gasket.
3. Install a new seal insert and make sure that the indentation is against the insert gasket.
4. Slide a new rotating seal assembly onto the shaft sleeve.
5. Push the top of the compression ring with a screwdriver until the seal is tight against the seal insert.
6. Install the seal spring and point the narrow end toward the seal.
Series A-C 1500 Installation, Operation, and Maintenance Manual 21
1
2
3
4
5
6
7
8
9
10
11
12
13
Maintenance
1. Slinger
2. Bracket coverplate
3. Seal assembly
4. Impeller key
5. Volute capscrew
6. Impeller
7. Impeller lockwasher
8. Volute
9. Impeller capscrew
10. Volute gasket
11. Impeller washer
12. Shaft sleeve
13. Shaft
Figure 2: Standard mechanical seal

Assemble the single mechanical seal (AC-1500-S)

1. Lubricate the shaft sleeve and seal cap with soapy water. Do not use a petroleum lubricant.
2. Insert a stationary seal with an O-ring into the seal cap and slide it onto the shaft.
3. Replace the seal cap gasket.
4. Slide the rotating portion of the seal assembly onto the shaft sleeve and lock it in place.
ID seal size Distance between collar and impeller end of the shaft sleeve 1-1/4 in. (3.175 cm) 1-13/32 in. (3.571 cm) 1-5/8 in. (4.128 cm) 1-1/4 in. (3.175 cm)
5. Assemble the coverplate onto the bracket.
6. Tighten the capscrews according to the Capscrew torque table.
7. Attach the seal cap to the coverplate.
8. Tighten the hex nuts on the seal cap bolts according to the Capscrew torque table.
22 Series A-C 1500 Installation, Operation, and Maintenance Manual
2
3
4
5
6
7
9
1
8
1. O-ring
2
3
5
6
1
4
2. Coverplate
3. For 1-1/4 in. seal: 1-13/32 in. (3.571 cm)
4. For 1-5/8 in. seal: 1-1/4 in. (3.175 cm)
5. Seal locking collar
6. Seal cap bolt
7. Seal cap
8. O-ring
9. Motor end
Figure 3: Single mechanical seal (AC-1500–S)
Maintenance

Assemble the 2-inch single mechanical seal (AC-1500-S)

1. Lubricate the shaft sleeve with soapy water. Do not use a petroleum lubricant.
2. Slide the stationary seal with an O-ring onto the shaft.
3. Slide the rotating portion of the seal assembly onto the shaft sleeve and lock it in place a distance of 55/64 in. (2.813 cm) from the seal collar to the impeller end of the shaft sleeve.
4. Assemble the coverplate onto the bracket.
5. Tighten the capscrews according to the Capscrew torque table.
6. Attach the seal gland to the coverplate.
7. Tighten the capscrews to the seal gland according to the Capscrew torque table.
Series A-C 1500 Installation, Operation, and Maintenance Manual 23
1
2
1
Maintenance
1. Seal gland
2. Coverplate
3. For 2 in. seal: 55/64 in. (2.813 cm)
4. Seal locking collar
5. O-ring
6. Seal gland capscrew
Figure 4: 2-inch single mechanical seal

Assemble the double mechanical seal (AC-1500-D)

1. Lubricate the shaft sleeve, seal cap, and coverplate cavity with soapy water. Do not use a petroleum lubricant.
2. Insert a stationary seal and O-ring into the seal cap. For the 1-1/4 in. ID seal, both parts are housed in the coverplate. A seal cap gasket is
not used.
1. O-rings
2. Motor end
Figure 5: Double mechanical seal
3. Insert another stationary seal and O-ring into the coverplate.
4. Slide the seal cap onto the shaft.
5. Replace the seal cap gasket.
6. Slide the rotating portion of the seal assembly onto the shaft sleeve.
7. Assemble the coverplate onto the bracket.
8. Tighten the capscrews according to the Capscrew torque values table.
9. Attach the seal cap to the coverplate.
10. Tighten the hex nuts on the seal cap bolts according to the Capscrew torque values table.
24 Series A-C 1500 Installation, Operation, and Maintenance Manual
Assemble the packed stuffing box (AC-1500-PF)
1
2 3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Maintenance
1. Slinger
2. Shaft sleeve
3. Packing gland
4. Flush line
5. Coverplate capscrew
6. Impeller key
7. Volute capscrew
8. Impeller washer
9. Impeller
10. Impeller capscrew
11. Volute
12. Impeller lockwasher
13. Volute gasket
14. Coverplate
15. Drip drain
16. Lantern ring
17. Packing
18. Gland bolt
19. Bracket
20. Shaft
Figure 6: Packed stuffing box
1. Insert two packing rings into the
stuffing box.
2. Insert the lantern ring and the last two pieces of packing. Make sure that the joints on the packing rings are staggered 90º.
3. Install, but do not tighten, the packing gland.
4. Install the coverplate over the pump shaft.
5. Tighten the capscrews according to the Capscrew torque table in the Maintenance chapter.
6. Tighten the packing gland to compress the packing. See the note on the packed pump operation in the Operations chapter for more
information.
Series A-C 1500 Installation, Operation, and Maintenance Manual 25
Maintenance

Install the impeller

1. Install the impeller, impeller washer, lockwasher, and capscrew.
2. Tighten the capscrew according to the Capscrew torque values table.

Reinstall the pump assembly

1. Install a new volute gasket.
2. Install the pump assembly into the volute.
3. Tighten the volute capscrews according to the Capscrew torque table.
4. Install a seal flushing tube if it is used.
5. Install the drain plug and close the drain valve.
6. Open the isolation valves and inspect the pump for leaks.
7. Return the pump to service if it is not leaking.

Screw torque values

Capscrew torque in ft-lb (Nm)
Capscrew
type
SAE grade 2
Brass and stainless steel
SAE grade 5
Head
marking
or

Dealer servicing

Capscrew diameter (in inches)
1/4 5/16 3/8 7/16 1/2 5/8 3/4 7/8 1
6 (8) 13 (18) 25 (34) 38 (52) 60 (81) 120 (163) 190 (258) 210 (285) 300 (407)
4 (5) 10 (14) 17 (23) 27 (37) 42 (57) 83 (113) 130 (176) 200 (271) 300 (407)
10 (14) 20 (27) 35 (47) 60 (81) 90 (122) 180 (244) 325 (440) 525 (712) 800 (1085)
If trouble occurs that cannot be rectified, contact your local sales and service representative and be prepared to provide this information:
1. Complete nameplate data of pump and motor
2. Suction and discharge pipe pressure gauge readings
3. Ampere draw of the motor
4. A sketch of the pump hook-up and piping
26 Series A-C 1500 Installation, Operation, and Maintenance Manual
Xylem |’zīləm|
1) The tissue in plants that brings water upward from the roots
2) A leading global water technology company
We're 12,000 people unified in a common purpose: creating innovative solutions to meet our world's water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to xyleminc.com
Xylem Inc. 2881 East Bayard Street Seneca Falls, NY 13148 Tel: (866) 325-4210 Fax: (888) 322-5877 www.gouldswatertechnology.com
AC5660_en-US_2013-07_IOM_SeriesA-C1500
Visit our Web site for the latest version of this document and more information
The original instruction is in English. All non-English instructions are translations of the original instruction.
©
2013 Xylem Inc
Goulds is a registered trademark of Goulds Pumps, Inc. and is used under license.