Wilo Sevio AIR Installation And Operating Instructions Manual

Pioneering for You
Wilo-Sevio AIR
de Einbau- und Betriebsanleitung US Installation and operating instructions hu Beépítési és üzemeltetési utasítás
6068088 Ed.0.5-11/2012 no ofcial version
10
3
2
1
4
2
5
6
8
7
9
1
2
3
4
5
6
7
8
1
2
3
4
2
Fig. 5Fig. 4
6
8
7
5
7
5
6
4
3
2
6
5
8
4
3
2
1
1
2
1
4
3
5
5
5
3
1
3
2
2
4
5
2
1
3
1
Fig. 10
3
2
1
Fig. 11
Fig. 12.1
min. 800 mm
±5° ±1°
Fig. 12.2
10 cm
Fig. 12.3
10 cm
English
1. Introduction 44
1.1. About this document 44
1.2. Structure of the manual 44
1.3. Personnel qualications 44
1.4. Abbreviations 44
1.5. Illustrations 45
1.6. Copyright 45
1.7. Rights of alteration 45
1.8. Warranty 45
2. Safety 46
2.1. Instructions and safety information
47
2.2. General safety information 48
2.3. CE marking 49
2.4. Ground connection 49
2.5. Safety rules during operation 49
2.6. Liquids 49
2.7. Sound pressure 50
3. Transport and storage 50
3.1. Delivery 50
3.2. Transport 50
3.3. Storage 50
6. Start-up 63
6.1. Initial start-up 63
6.2. Before switching on 65
6.3. Starting up the aeration 65
6.4. After switching on 65
7. Shutdown/disposal 66
7.1. Temporary shutdown 66
7.2. Shutdown for maintenance work or
storage 66
7.3. Starting up again 67
7.4. Disposal 67
8. Maintenance 68
8.1. Maintenance intervals 69
8.2. Maintenance tasks 70
8.3. Repairs 71
4. Product description 51
4.1. Proper use 51
4.2. Construction 51
4.3. Function 53
4.4. Technical data 53
4.5. Scope of delivery 53
5. Installation 54
5.1. General requirements 54
5.2. Types of installation 55
5.3. The operating area 55
5.4. Work steps 56
Installation and operating instructions Wilo-Sevio AIR 43
English INTRODUCTION
1. Introduction
1.1. About this document
The language of the original operating manual is German. All other language versions are translations of the original German manual. The operating manual contains a copy of the EC Declaration of Conformity. Any unauthorized or unapproved changes made to the design specied in it will nullify this declaration.
1.2. Structure of the manual
The manual is divided into individual sections. Each section has a heading which clearly describes its content. The table of contents also serves as a brief reference, since all the important sections have their own headers. All the important operating and safety instructions are highlighted. For detailed infor­mation on the structure of these texts, see “Safety” in section 2.
1.3. Personnel qualications
All personnel who work on or with the product must be qualied for such work; elec­trical work, for example, may only be carried out by a qualied electrician. All personnel must be of legal age.
Operating and maintenance personnel must also observe national accident prevention regulations. It must be ensured that the personnel have read and understood the instructions in this operating and maintenance handbook; if necessary, this manual must be ordered from the manufacturer in the required language.
This product is not intended to be used by persons (including children) with limited physical, sensory or mental capacities or without the relevant experience or knowledge, unless they are supervised by a person responsible for their safety and receive instruc­tions from this person on how to use the product.
Children must be supervised in order to ensure that they do not play with the product.
1.4. Abbreviations
p.t.o. = please turn over
re. = regarding
approx. = approximately
i.e. = that means
incl. = including
min. = minimum
max. = maximum
etc. = and so on
s.a. = see also
e.g. = for example
44 WILO SE 11/2012 Ed.03 DIN A5
INTRODUCTION English
1.5. Illustrations
Dummies and original drawings of the products are used in the illustrations. This is the only sensible solution given our wide range of products and the differing sizes offered by the modular system. More exact drawings and specications can be found on the dimension sheet, the planning information and the installation plan.
1.6. Copyright
This operation and maintenance manual has been copyrighted by the manufacturer. The operation and maintenance handbook is intended for use by assembly, operating and maintenance personnel. It contains technical specications and diagrams which may not be reproduced or distributed, either completely or in part, or used for any other purpose without the express consent of the manufacturer.
1.7. Rights of alteration
The manufacturer reserves the right to make technical alterations to systems or com­ponents. This operating and maintenance manual refers to the product indicated on the title page.
1.8. Warranty
This section contains the general information on the warranty. Contractual agreements have the highest priority and are not superseded by the information in this section. The manufacturer is obliged to correct any defects found in the products it sells, provid­ed that the following requirements have been fullled:
1.8.1. General requirements
The defects are caused by the materials used or the way the product was manufactured or designed.
The defects were reported in writing to the manufacturer within the agreed warranty period.
The product was used only as prescribed.
All safety and control devices were connected and inspected by qualied personnel.
1.8.2. Warranty period
If no other provisions have been made, the warranty period covers the rst 12 months after initial start-up or up to 18 months after the delivery date. Other agreements must be made in writing in the order conrmation. These remain valid at least until the agreed warranty period of the product has expired.
1.8.3. Spare parts, add-ons and modications
Only genuine spare parts from the manufacturer may be used for repairs, replacements, add-ons and modications. These are the only parts that guarantee a long service life and maximum safety. These parts have been specially designed for our products. Unau-
Installation and operating instructions Wilo-Sevio AIR 45
English SAFETY
thorized add-ons and modications or the use of non-original spare parts can seriously damage the product and injure personnel.
1.8.4. Maintenance
The prescribed maintenance and inspection work should be carried out regularly. This work may only be carried out by qualied, trained and authorized personnel. Mainte­nance not listed in this operation and maintenance manual, and any type of repair work may only be performed by the manufacturer and authorized service centers.
1.8.5. Damage to the product
Damage and malfunctions that endanger safety must be eliminated immediately by trained personnel. The product may only be operated if it is in proper working order. During the agreed warranty period, the product may only be repaired by the manufac­turer or an authorized service center. The manufacturer reserves the right to ask the operator to return the damaged product to the factory for inspection.
1.8.6. Exclusion from liability
No liability will be assumed for product damage if any of the following items apply:
The manufacturer deems that information provided by the operator or customer is insufcient or incorrect
Failure to observe the safety instructions, the regulations and requirements of German law or the applicable local laws, or of this operating and maintenance manual
Improper use
Incorrect storage and transport
Improper assembly or dismantling
Insufcient maintenance
Improper repairs
Inadequate construction site or construction work
Chemical, electrochemical and electrical inuences
Wear
This means the manufacturer’s liability excludes all liability for personal, material or nancial injury.
2. Safety
This section lists all the generally applicable safety instructions and technical informa­tion. All instructions and information must be observed and followed during the various phases of the product’s life cycle (installation, operation, maintenance, transport, etc.)! The operator is responsible for ensuring that personnel follow these instructions and guidelines.
46 WILO SE 11/2012 Ed.03 DIN A5
SAFETY English
2.1. Instructions and safety information
This manual uses instructions and safety information to prevent injury and damage to property. To clearly identify them for personnel, the instructions and safety information are distinguished as follows:
2.1.1. Instructions
Instructions are displayed in bold type. Instructions contain text that refers to the previ­ous text or particular sections, or highlights short instructions. Example:
Note that products stored with drinking water must be protected from frost.
2.1.2. Safety information
Safety information is slightly indented and displayed in bold type. It always commences with a signal word. Information that only refers to material damage is printed in gray, without safety sym­bols. Information that refers to personal injury is printed in black and is always accompa­nied by a safety symbol. Danger, prohibition or instruction symbols are used as safety symbols.
Example:
DANGER symbol: General hazard
DANGER symbol, for example, electrical current
PROHIBITION symbol, for example, Keep out!
INSTRUCTION symbol, for example, wear protective equipment
The safety symbols used conform to the generally valid directives and regulations, such as DIN and ANSI. Each safety instruction begins with one of the following signal words:
Danger
Serious or fatal injuries can occur!
Installation and operating instructions Wilo-Sevio AIR 47
English SAFETY
Warning
Serious injuries can occur!
Caution
Injuries can occur!
Caution (instruction without symbol) Substantial material damage can occur. Irreparable damage is possible! Safety instructions begin with a signal word and description of the hazard, followed by its cause and potential consequences, and end with advice on prevention. Example:
Beware of rotating parts! The moving impeller can crush and sever limbs. Switch off the device and let the impeller come to a halt.
2.2. General safety information
When installing or removing the product, never work alone in rooms and shafts. A sec­ond person must always be present.
Sufcient ventilation must be provided in enclosed rooms.
When welding or working with electrical devices, make sure there is no risk of explosion.
During work in environments hazardous to health (liquid containing fecal matter, acti-
vated sludge with bacteria, etc.), special caution is required:
Open wounds must be immediately cleaned and treated.
Eating and drinking are strictly prohibited.
Proper protective equipment must be worn!
Upon leaving the system, disinfect persons and tools.
The product must always be switched off before any work is performed on it (assembly,
dismantling, maintenance, installation). The product must be secured against being switched back on.
The person operating the product must notify his or her supervisor immediately should any defects or irregularities occur.
Tools and other objects should be kept in a place reserved for them so that they can be found quickly.
Only use lashing equipment which is legally dened as such and ofcially approved.
The lashing equipment must be kept safely and must be suitable for the conditions of
use (weather, hooking device, load, etc).
Mobile equipment for lifting loads should be used in such a way that it always remains stable during operation.
When using mobile equipment for lifting non-guided loads, take action to prevent tipping, sliding, etc.
Measures should be taken to ensure that no person is ever directly beneath a suspended load. Furthermore, it is also prohibited to move suspended loads over workplaces where people are present.
48 WILO SE 11/2012 Ed.03 DIN A5
SAFETY English
If mobile equipment is used for lifting loads, a second person should be present to coor­dinate the procedure if required (for example, if the operator’s eld of vision is blocked).
The load to be lifted must be transported in such a manner that nobody can be injured in the event of a power outage. Additionally, when working outdoors, such procedures must be stopped immediately if weather conditions worsen.
These instructions must be strictly observed. Non-observance can result in injury or substantial material damage.
2.3. CE marking
If the product is obliged to carry a CE marking,
the marking is attached to the product and
a copy of the EC declaration of conformity is enclosed or is part of this operating man-
ual.
2.4. Ground connection
Products with metallic and/or conductive surfaces must be grounded. If there is a pos­sibility that people can come into contact with the product and the pumped liquid, the connection must be additionally equipped with a residual current circuit breaker.
2.5. Safety rules during operation
When operating the product, always follow the locally applicable laws and regulations for accident prevention and securing the worksite. To help to ensure safe working practice, the responsibilities of employees should be clearly set out by the owner. All personnel are responsible for ensuring that regulations are observed.
2.6. Liquids
Each liquid differs in terms of its composition, corrosiveness, abrasiveness and dry mat­ter content, as well as in many other aspects. Generally, our products can be used for many applications. Please note that if requirements change (density, viscosity or general composition), this can also affect many operational parameters of the product.
When using or replacing the product in a different liquid, observe the following points:
When used in drinking water applications, all the parts that come into contact with the uid must be approved for use with drinking water.
Before being used in drinking water, the corresponding products must be checked to ensure that they have been approved for such use.
Products that have been operated in dirty waste water must be cleaned thoroughly before being used for other liquids.
Products that have been operated in sewage water and/or uids that are hazardous to health must be decontaminated before being used with other liquids.
It must be claried whether the product can be used with another liquid.
Installation and operating instructions Wilo-Sevio AIR 49
English TRANSPORT AND STORAGE
If the product is to be used with highly ammable, explosive and/or aggressive uids, the manufacturer must be consulted.
2.7. Sound pressure
The product itself is generally operated under water and only with air. This means that the sound pressure cannot be measured. However, the air is supplied using a compressor. Depending on its power and environ­mental conditions, this compressor can have elevated sound pressure. For this reason we recommend that the operator carry out an the additional measure­ment in the workplace when the product is operating.
CAUTION: Wear ear protectors! In terms of the applicable laws and regulations, ear protection must be worn if the
sound pressure is greater than 85 dB (A). The owner is responsible for ensuring
compliance with these regulations.
3. Transport and storage
3.1. Delivery
On delivery, immediately check that the product is complete and undamaged. If any parts are damaged or missing, the transport company or the manufacturer must be no­tied on the day of delivery. Claims made after this date cannot be recognized. Damage to parts must be noted on the delivery or freight documentation.
3.2. Transport
Before transport, the product must be packaged in such a way that it is protected from moisture, frost and other damage. It is important to keep the original packaging.
3.3. Storage
The components must be stored in the original packaging.
The store room must be dry and frost-proof. We recommend storage in a room with a
temperature between 10°C and 25°C. The temperature may not exceed +50°C.
The product must be protected from direct sunlight, heat, dust and frost. Furthermore, the product may not be stored in rooms where welding takes place. Heat and cold, as well as the gas and radiation given off during welding, can damage the plastic parts.
New disc aerators may not be stored for more than three months. If they are stored for more than three months, there is a risk that the membranes will become porous and leaky.
50 WILO SE 11/2012 Ed.03 DIN A5
PRODUCT DESCRIPTION English
4. Product description
4.1. Proper use
The Wilo-Sevio AIR disc aerator and aerator systems are used for ne-bubble air inclusion in liquids such as water, waste water or sludges, for the purpose of supplying oxygen to the liquids.
The temperature of the liquid must be between +5°C and 30°C. If the products are to be used in liquid with higher temperatures, the manufacturer must be consulted. The surrounding liquid must also be free of objects with sharp edges. We recommend that the liquid be pre-cleaned with a lter.
The supplied air must be free of oil, dust and solvents. Dust lters must correspond to lter class EU4 according to DIN24185 (degree of separation >90%). All lters and insulating materials in use may not be made of berglass, mineral bers or other materials consisting of ne bers. Rotary slide valves with graphite ns must be equipped with an air lter on the pressure side.
These materials can lead to clogging of or damage to the membranes.
4.2. Construction
A Wilo-Sevio AIR aerator system consists of one or more aerator groups. An aerator group forms the base unit and consists of several components:
Fig. 1.: Aerator system component overview
Air distributor with connecting ange for
1
the intake line (down pipe)
2 Base support for air distributor 7 Basin bottom
Intake line (down pipe); must be installed
3
by the customer. Aerator pipe with pre-assembled disc
4
aerators
5 Base support for aerator pipe 10
6 Disc aerators
Pipe coupling for connecting the individ-
8
ual components
9 Drainage connection
Drainage line; must be installed by the customer.
4.2.1. Piping
The pipes are pre-fabricated in components that can be easily used:
PVC air distributors in the diameters of 90mm, 160mm and 200mm with central or lateral DN80 to DN200 ange connection for the intake line. Larger diameters are available in stainless steel with DN125 to DN350 ange connections.
PVC aerator pipes with 90mm external diameter or made from stainless steel with
88.9mm external diameter with pre-assembled disc aerator
Installation and operating instructions Wilo-Sevio AIR 51
English PRODUCT DESCRIPTION
Drainage connection as the terminating connection of all aerator pipes with a connec­tion for the drainage line. This can be used to drain off the condensate that can form during aeration.
Pipe coupling with rubber ring seal as a plug connection for connecting the individual PVC components. The pipe coupling for securing the aerator pipes on the air distributor must also be equipped with a stainless steel clamping ring.
4.2.2. Base support
All pipes on the basin bottom are secured by the base supports. They also make it pos­sible to level the aerator group. There are two different base supports:
For securing the stainless steel air distributor
For securing the aerator pipes and the PVC drainage connection
4.2.3. Disc aerators
The disc aerators introduce the supplied air into the liquid. The air is distributed across the entire membrane surface and released through the perforated membrane. The disc aerator consists of several components.
Fig. 2.: Disc aerator component overview
1 Threaded ring 5 Non-return valve 2 Separation ring 6 Aerator housing
3 Membrane 7 O ring 4 Membrane support 8 Slide closure
Fiberglass-reinforced plastic threaded ring for securing the membrane to the membrane support. The threaded ring and aerator housing are matched to each other in such a way that the threaded ring can be easily loosened even after years of use, allowing the membrane to be replaced.
The polyacetal separation ring prevents the membrane from sticking to the threaded ring. This ensures that the membrane can be easily replaced.
The EPDM membrane with perforations across its entire surface for optimal air inclusion.
Fiberglass-reinforced plastic membrane support, which holds the membrane in place.
The EPDM non-return valve protects the aerator system from penetration of the liquid if
the membrane is defective.
Fiberglass-reinforced plastic aerator housing with integrated anti-rotation lock
NBR O ring for sealing the disc aerator against the aerator pipe
Fiberglass-reinforced sliding closure for easy installation and removal of the disc aerator
52 WILO SE 11/2012 Ed.03 DIN A5
PRODUCT DESCRIPTION English
4.3. Function
A blower or compressor is used to pump air through the intake line into the air distrib­utor. The air is evenly distributed into the aerator pipes through the air distributor and fed to the disc aerators. The disc aerators distribute the air across the entire membrane surface and introduce this air into the liquid.
4.4. Technical data
Disc aerators
External diameter: 280mm
Membrane diameter: 237mm
Membrane surface: 0.044m²
Oxygen utilization: 6.5 ... 8.5%/m
Size of the air bubbles: 1–3mm
Pressure loss: 22 ... 43mbar
Connection size: 88.9 ... 90mm
Max. air temperature in the system / disc aerator: 100°C
Pressurization range
Air volume range: 1–8Nm³/h*
Min. pressurization: 1.5Nm³/h*
Standard pressurization: 4.0Nm³/h*
Max. pressurization: 6.0Nm³/h*
Pressurization of 7.5Nm³/h* is possible for a brief period (no more than 15 minutes). *The values for the pressurization apply to standardized conditions: 0°C and 1013hPa.
4.5. Scope of delivery
The scope of delivery differs according to whether a complete aerator system or only disc aerators (with the pipes provided by the customer) were ordered.
4.5.1. “Aerator system” scope of delivery
Air distributor with ange connection for intake line
Aerator pipes with pre-assembled disc aerator
Drainage connection
Pipe connections
Base support
Fastening material
Drilling plan for the base supports
Overview and position diagram of the individual components
Special key for easy installation/removal of the threaded ring on the disc aerator
Rubber mallet
4.5.2. “Disc aerator” scope of delivery
Disc aerators
Drilling plan for the connection holes on the pipes for the disc aerators
Installation and operating instructions Wilo-Sevio AIR 53
English INSTALLATION
4.5.3. Material to be provided by the customer
Intake line for the air supply
Blower or compressor
Drainage line with shut-off valve
All pipes if only disc aerators were ordered
5. Installation
In order to prevent damage to the product or serious injury during installation, the following points must be observed:
Installation work – assembly and installation of the machine – may only be carried out by qualied persons. The safety instructions must be followed at all times.
The machine must be inspected for transport damage before carrying out any installa­tion work.
5.1. General requirements
For planning and operation of technical waste water systems, pay attention to the per­tinent local regulations and directives for wastewater technology (such as those of the German Association for Water, Wastewater and Waste).
The following information must be observed when installing the product:
This work must be carried out by qualied personnel.
Check that the available planning documentation (installation plans, layout of the oper-
ating area, drilling plan) is complete and correct.
Observe all regulations, rules and legal requirements for working with and underneath heavy suspended loads.
Wear appropriate protective equipment.
During all work, a second person must always be present. If there is a risk of poisonous
or asphyxiating gases forming, the necessary precautions must be taken.
Please also observe the applicable national accident prevention regulations and trade association safety provisions.
DANGER of falling! Work may be necessary directly at the edge of the shaft and/or basin during instal­lation. Carelessness or wearing inappropriate clothing could result in a fall. There is a risk of fatal injury! Take all necessary safety precautions to prevent this.
54 WILO SE 11/2012 Ed.03 DIN A5
INSTALLATION English
BEWARE of poisonous substances! During work in environments hazardous to health, such as waste water or sewage treatment plants, there is an increased hazard from bacteria and viruses. In order to counteract this elevated risk, please keep the following points in mind:
• Open wounds must be immediately cleaned and treated.
• Eating and drinking are strictly prohibited.
• Proper protective equipment must be worn.
• Upon leaving the system, disinfect persons and tools.
5.2. Types of installation
Aerator group securely xed to the basin bottom
5.3. The operating area
The operating area must be clean, with coarse solid particles removed, dry, frost-free and, if necessary, decontaminated.
During all work, a second person must be present for safety reasons.
If there is a risk of poisonous or asphyxiating gases forming, the necessary precautions
must be taken.
Safe, truck-accessible access must be available to the operating area.
A storage location of sufcient size and with a solid subsurface must be available so
that the complete load can be unloaded and stored in accordance with the specica­tions in the “Transport and storage” section.
Provisioning of the electricity, water and compressed air supply for the installation.
It must be ensured that hoisting gear can be tted without any trouble, since this is re-
quired for assembly and removal of the product. It must be possible to reach the product safely in its operating and storage locations using the hoisting gear.
For transport of the product, load-carrying equipment must be secured to the pipes with approved fastening devices. Here it is necessary to ensure that the load does not shift during transport.
The structural components and foundations must be of sufcient stability in order to allow the product to be anchored securely and functionally. The operator or the supplier is responsible for the provision of the foundations and their suitability in terms of di­mensions, stability and strength.
5.3.1. Material to be provided by the customer
• Intake line for the air supply The aerator group is connected through the air distributor to the intake line. The posi­tion of the intake line may not change after the order is placed, since this can otherwise lead to problems during installation. The intake line also needs to be self-supporting. The weight of the intake line may not be transferred to the air distributor. We also recommend installation of a compensating joint between the intake pipe and
Installation and operating instructions Wilo-Sevio AIR 55
English INSTALLATION
the rest of the pipelines, as well as installation of a manometer in the intake line. These measures allow tension and transmissions of vibration to be reduced and the current air inclusion to be checked.
Blower or compressor The blower or compressor must have sufcient output for introducing the required air volume into the aerator group(s).
• Drainage line with shut-off valve In order to channel off any liquid that has penetrated into the aeration system or con­densate that has formed during operation.
All pipes if only disc aerators were ordered If only disc aerators were ordered, the complete pipe system must be installed in ad­vance.
5.4. Work steps
Installation takes place in the following steps:
1. Checking the operating area
2. Unpacking and checking the components
3. Installing the base supports
4. Aligning the contact surface for the pipes
5. Installing the air distributor
6. Installing the aerator pipes
7. Installing the drainage connection
8. Securing the pipes
9. Installing the drainage line
10. Installing the disc aerators When a complete aerator system is being installed, the disc aerators are already pre-as­sembled. In this case, item 10 is omitted during installation. If the pipe system is being provided by the customer and only disc aerators were ordered, items 3 to 9 are omitted during installation.
5.4.1. Checking the operating area
Before you begin with installation, check the operating area to ensure that it is prepared for installation:
The design of the system as well as the installation and drilling plan match the current conditions.
The operating area is clean and the components to be provided by the customer are appropriately prepared/installed.
PVC becomes brittle when subjected to cold temperatures. For this reason, the ambient temperature must be over +10°C during installation.
Installation with an ambient temperature below +5°C is strictly prohibited.
56 WILO SE 11/2012 Ed.03 DIN A5
INSTALLATION English
5.4.2. Unpacking and checking the components
The pipes are packed in wooden crates, and the installation parts are packed in card­board boxes. Carefully open the packaging so that you do not injure yourself or damage the components.
The individual components must be unpacked in a clean, dry and frost-free place near the installation location. The following components must be included in the scope of delivery:
“Aerator system” scope of delivery
Air distributor with ange connection for intake line
Aerator pipes with pre-assembled disc aerator
Drainage connection
Pipe connections
Base support
Fastening material
Drilling plan for the base supports
Overview and position diagram of the individual components
Special key for easy installation/removal of the threaded ring on the disc aerator
Rubber mallet
“Disc aerator” scope of delivery
Disc aerators
Drilling plan for the air escape holes on the pipes for the disc aerators
Check all components for damage. Do not install defective parts. In this case, contact the manufacturer.
5.4.3. Installing the base supports
The base supports on the bottom of the basin are used to secure and align the aerator group. The drilling plan contains information regarding the position as well as the design (support for air distributor or aerator pipe) of the individual base supports, along with information on the borehole (depth, diameter).
The center of the intake pipe is used as a reference point. The air distributor must be placed here precisely in order to ensure a problem-free connection to the supply line.
Applying borehole markings to the bottom of the basin
Fig. 3.: Applying markings
1 Center of the intake pipe 3 Marking lines for the aerator pipes
Boreholes for the air distributor base
2
support
Boreholes for the base support for the
4
aerator pipes
1. Mark the center of the intake pipe on the bottom of the basin.
2. Mark the boreholes for the air distributor base supports on the bottom of the basin.
Installation and operating instructions Wilo-Sevio AIR 57
English INSTALLATION
3. Using a colored line, mark the center of the individual disc aerators on the bottom of the basin and measure the boreholes for the base supports of the aerator pipes.
The boreholes of the base supports must be precisely on the marking line and match the supplied drilling plan, since there can otherwise be twisting during installation.
4. Before you begin drilling the holes, check the distances of the aerator group to the basin wall. The distances must match the design, since the calculated air inclusion can otherwise not be ensured.
Installation of the stainless steel base supports with drop-in anchors and threaded
rods (for the air distributor)
Fig. 4.: Stainless steel base support component overview
1 Drop-in anchor 5 Flat washer
Pipe clamp:
2 Threaded rod 6
1x support for the air distributor 1x securing of the air distributor
Locknut for securing the height adjust-
3
ment
7 Hexagon nut for securing the pipe clamps
4 Hexagon nut for height adjustment 8 Locknut for securing the attachment
The drop-in anchor may only be used in reinforced or unreinforced normal concrete with a strength class between C20/25 and C50/60 (according to EN206:2000-12).
The drop-in anchor is only suitable for crack-free concrete.
Before the drop-in anchors are used, the strength of the structure must be ascertained
in order to ensure that the reaction forces can be absorbed.
1. Drill the individual holes for the corresponding base supports. Use a drill with a borehole depth marking.
2. Thoroughly clean the boreholes, such as by vacuuming them out.
3. Place the drop-in anchor into the borehole and carefully drive it into the hole using a rubber mallet. The anchor and foundation must be ush with each other.
4. Rotate the threaded rods completely into the anchor.
5. Twist on two hexagon nuts per anchor rod, place one at washer on each, and attach a pipe clamp with the bend pointing downwards.
Installation of the PVC base support with anchor bolt (for the aerator pipes)
Fig. 5.: Stainless steel base support component overview
1 Anchor bolt 5 Extension 2 Foot 6 Upper part with pipe support
58 WILO SE 11/2012 Ed.03 DIN A5
INSTALLATION English
3 Flat washer 7 Elastic band for securing pipe 4 Hexagon nut for attachment 8 PVC adhesive
The anchor bolt may only be used in reinforced or unreinforced normal concrete with a strength class between C20/25 and C50/60 (according to EN206:2000-12).
The anchor bolt is only suitable for crack-free concrete.
Before the anchor bolts are used, the strength of the structure must be ascertained in
order to ensure that the reaction forces can be absorbed.
1. Drill the individual holes for the corresponding base supports. Use a drill with a borehole depth marking.
2. Thoroughly clean the boreholes, such as by vacuuming them out.
3. Place the anchor bolt into the borehole and carefully use a rubber mallet to drive it into the hole until it reaches the insertion depth marking. The threaded rod for securing the components must protrude out of the foundation.
4. Place the foot of the base support onto the threaded rod and secure it with the washer and hexagon nut.
Important: When tightening the hexagon nuts, make sure that the foot doesn’t break.
5. Turn the upper part of the base support with the pipe support onto the foot.
5.4.4. Aligning the contact surface for the pipes
In order to ensure proper aeration, the individual aerator groups must be aligned so that they are precisely horizontal and all aerator groups are the same height. The recom­mended distance between bottom of the basin and the pipe support is 70mm. Within an aerator group, a deviation of no more than ±10mm is permitted. The height of each support can be adjusted between 70mm and 100mm. The precise height can be mea­sured and adjusted using a leveling device (laser).
When carrying out leveling work, also keep in mind the height of the air distributor. The air distributor must be connected to the intake line so that it is free of strain.
Height adjustment of the stainless steel base support with drop-in anchor and threaded rod
The height is adjusted using the two hexagon nuts. The top hexagon nut is used to set the desired height, and the bottom nut is used to secure the adjustment (locknut).
Height adjustment of the PVC base support with anchor bolt
The height is adjusted by turning the pipe support. If this height adjustment is not sufcient, an extension can be installed.
1. Rotate the extension onto the foot and secure the connection using PVC adhesive.
2. Rotate the upper part of the support onto the extension and set the desired height.
Installation and operating instructions Wilo-Sevio AIR 59
English INSTALLATION
5.4.5. Installing the air distributor
Fig. 6.: Installing the air distributor
1 Air distributor 4
Air distributor / intake line ange con­nection
2 Intake line 5 Connection ange of the aerator pipes 3 Base support
1. Place the air distributor into the pipe clamp of the base support so that the ange con­nection is pointing straight upwards.
2. Slide the air distributor to the left or right until the ange connection is positioned directly under the connection ange of the intake line.
Important: The air distributor must be easily slid under the supply pipe. The two
anges may not twist, and the distance between them may not be larger than 1mm.
The height of the base support may need to be adjusted.
3. Screw the two anges onto each other and tighten the screws securely.
4. The connections for the aerator pipes must be precisely horizontal so that the connect­ed aerator pipes run horizontally.
5.4.6. Installing the aerator pipes
The aerator pipes are installed using pipe couplings. A differentiation must be made here between the installations “aerator pipe / aerator pipe” and “aerator pipe / air dis­tributor.” For connecting two aerator pipes, the pipe couplings are used purely as plug connections. When connecting the aerator pipes to the air distributor, the pipe coupling is additionally secured on the side of the air distributor using a pipe clamp.
Aerator pipe / aerator pipe installation
Fig. 7.: Connecting the aerator pipes
1 Pipe coupling 3 Slide-in marking 2 Aerator pipe with disc aerator
1. Clean the outside of the pipe ends of the aerator pipe as well as the inside of the pipe
coupling.
2. Check the round sealing rings in the pipe coupling for damage. Defective seals must be replaced.
3. Wet the outside of the pipe ends of the aerator pipe as well as the inside of the pipe coupling with a liquid soap solution (do not use grease or oil).
4. Fit the pipe coupling onto an aerator pipe. Slide the pipe coupling up to the rst marking on the aerator pipe.
60 WILO SE 11/2012 Ed.03 DIN A5
INSTALLATION English
5. Slide the other aerator pipe into the pipe coupling also up to the rst marking.
6. Continue until the corresponding aerator pipes have all been joined in accordance with
the overview diagram.
7. In each case place a line of aerator pipes onto the base supports.
Aerator pipe / air distributor installation
Fig. 8.: Installing the aerator pipes with the air distributor
1 Pipe coupling with pipe clamp 4
2 Air distributor 5
Pipe coupling: aerator pipe connection side Pipe coupling: connection side with pipe clamp for securing to the air distributor
3 Aerator pipe with disc aerator
1. Clean the outside of the pipe end of the aerator pipe, the outside of the connection ange of the air distributor and the inside of the pipe coupling.
2. Check the round sealing rings in the pipe coupling for damage. Defective seals must be replaced.
1. Wet the outside of the pipe end of the aerator pipe, the outside of the connection ange of the air distributor and the inside of the pipe coupling with a liquid soap solu­tion (do not use grease or oil).
2. Fit the pipe coupling onto the aerator pipe. Slide the pipe coupling up to the rst mark­ing on the aerator pipe. Ensure that the pipe clamp is not needed on this side.
3. Slide the pipe coupling with pipe clamp onto the connection ange of the air distributor and secure the pipe coupling with the pipe clamp.
4. Also attach the other aerator lines to the air distributor in this manner.
5.4.7. Installing the drainage connection
Fig. 9.: Installing the drainage connection
1 Aerator pipes with disc aerators 3 Pipe connections 2 Drainage connection
The drainage connection forms the end piece of an aerator group. Accordingly, all aera­tor lines must also be connected to it. The connection for the drainage line is also here. The drainage connection is installed on an aerator pipe in the same way as the “aerator pipe / aerator pipe” installation.
5.4.8. Securing the pipes
After the entire pipe system has been assembled, the aerator group can be afxed to the base supports.
Installation and operating instructions Wilo-Sevio AIR 61
English INSTALLATION
1. Check whether the aerator group is complete and resting horizontally on the base sup­ports. It may be necessary to adjust the height of some base supports.
2. Use the elastic bands to secure the aerator pipes to the base support. The elastic bands are hooked into the support using the eyelets.
Important: If the ambient temperature is below 15°C, it is recommended that the
elastic bands be placed in warm water before installation. This allows the elastic to
be more easily stretched and simplies installation.
3. Use the second pipe clamp to secure the air distributor. Fit this onto the anchor rod, put on a at washer, and screw on two hexagon nuts per anchor rod. The pipe clamp is se­cured using the bottom hexagon nut; the attachment is secured using the top hexagon nut (locknut).
5.4.9. Installation of the drainage line (supplied by the customer)
Fig. 10.: Connecting the drainage line
1 Connection for the drainage line
Once the aerator group has been completely installed, the drainage line needs to be connected. The drainage connection is located at the end of the pipe system, or, in case of aerator systems that are not connected, the drainage connection is located on the air distributor.
The drainage line must be attached outside of the basin and equipped with a valve.
5.4.10. Installing the disc aerators with customer-supplied aerator systems
If the aerator system has already been provided by the customer, only the disc aerators can be installed. To do this, it is only necessary to drill the connection holes into the existing pipe system. The corresponding drilling diagram can be found in the included drilling plan.
Fig. 11.: Installing the disc aerators
1. Clean the pipes.
2. Mark the boreholes according to the included drilling plan. The minimum distance be-
tween two connection holes may not be smaller than 800mm.
3. Drill the connection holes:
Size: 20mm; +5/-0mm
Horizontal tolerance: ±5°
Vertical tolerance: ±1°
4. Fit the disc aerator onto the pipe. Ensure that the connection of the disc aerator is com­pletely inserted into the connection hole.
62 WILO SE 11/2012 Ed.03 DIN A5
START-UP English
5. Place the slide closure laterally into the guide and slide it up in the direction of the arrow.
6. Start-up
The “Start-up” section contains all the important instructions for the operating person­nel for starting up and operating the product safely. The following conditions must be adhered to and monitored:
The compressor/blower has sufcient output for the required air supply.
The pressure in the intake line corresponds to the specication and remains constant.
The pipes are absolutely tight.
The drainage line is connected.
If the machine has not been operated for an extended period, also check these con-
ditions and rectify any identied faults.
Always keep this manual either by the product or in a place specially reserved for it, where it is accessible to all operating personnel. In order to prevent damage or serious injury when starting up the product, the following points must always be observed:
The product may only be started up by qualied, trained persons. The safety advice must be followed at all times.
All persons working on or with the product must have received, read and understood this operating and maintenance manual.
The product is suitable for use under the specied operating conditions.
The work area of the product is not a recreational area and is to be kept free of people!
No persons are allowed in the work area during start-up or operation.
During all work, a second person must be present. Adequate ventilation must be en­sured if there is danger of poisonous gases forming.
6.1. Initial start-up
The following points must be checked before the initial start-up:
Inspecting the installation as described in the “Installation” section.
Basic cleaning of the operating area.
Function test / clear water test
6.1.1. Inspecting the installation as described in the “Installation” section
Before a function test of the aerator system is conducted, the complete installation needs to be checked to ensure that it is correct (tightness, horizontal installation, base support securely anchored to the oor, etc.). Any defects must be rectied before a function test is conducted.
Installation and operating instructions Wilo-Sevio AIR 63
English START-UP
6.1.2. Basic cleaning of the operating area
The operating area can be heavily soiled during installation. This soiling can negatively inuence the air inclusion or damage the disc aerator. For this reason you should clean the entire operating area with clear water and remove soiling. Course soiling and foreign bodies must be removed by hand.
The stream of water must not directly impact the membrane, since this can lead to damage.
6.1.3. Function test / clear water test
A function test is used to ensure that all components are tight and that the aerator groups are working awlessly. A function test is conducted with clear water. During the function test, people must be in the basin to inspect the aerator groups. Inspection from the corners or from outside of the operating area is not permitted.
Fig. 12.: Function test in three steps
12.1 Tightness test of the pipes and of the disc aerator
12.2 Function test of the membranes
12.3 Tightness test of the intake line
1. Before the water is introduced into the operating area for the function test, air must be introduced into the aerator system. This prevents water from penetrating into the aerator system if there are any leaks.
2. Once the air supply is ensured, the operating area is slowly ooded with clear water.
3. In the rst step, the water level must extend up to the halfway point of the threaded ring on the disc aerator. If air bubbles emerge, the corresponding location must be disassembled and the fault rectied. This can be caused by the following:
Incorrect installation of the pipe coupling
Defective sealing ring in the pipe coupling
Defective sealing ring on the connection of the disc aerator
Material fault
4. In the second step, the water level is increased to approx. 10cm above the membranes. With this water level, you can see whether all disc aerators are functioning awlessly. For this test, air pressurization of 1.5Nm³/h to 6Nm³/h must be present. If the pressur­ization is too low, the disc aerators do not operate awlessly. If there are defective disc aerators in the system, they need to be replaced. Before a replacement can be made, the water must be completely pumped out so that no water penetrates into the pipes. If several disc aerators within a line are operating erratically, it is likely that water has penetrated into the pipes. Open the drainage line to press out the water that has pene­trated into the pipes.
64 WILO SE 11/2012 Ed.03 DIN A5
START-UP English
5. In the third step, the water level must be increased to approx. 10cm above the ange connection of the air distributor / intake pipe. Check the air distributor as well as the intake connection for tightness. Leaky spots must be xed.
6. To complete the test, check the drainage line. To do this, open the valve on the drainage line. If the aerator system is tight, only air or an air/water mixture may escape.
7. After the test is complete, a retest must be conducted after 24 hours. The system can only be placed into operation if this test also results in no faults.
After the second function test is completed successfully, the operating area must be ooded. If it is not yet possible to place the system into operation, provision must be made
to ensure a water level >1m. In this way the disc aerators are protected from falling
objects and the membranes are protected from UV light.
Before the system is placed into operation at a later point in time, an additional function test must be conducted. The relevant maintenance measures in accordance with the “Maintenance” section must be taken into account starting at this point.
6.2. Before switching on
Check the operating area to ensure that it is completely ooded.
If the start-up procedure was not yet conducted in full, an additional function test must
be conducted.
6.3. Starting up the aeration
After the function test has been successfully conducted, the system can be placed into operation. For this the aeration is switched on using a separate, customer-provided control station. It is standard that a differentiation is only made between the operation­al states of On and Off.
Additional operational states such as intermittent operation or time-based control must be arranged on an individual basis.
6.4. After switching on
During operation, check the formation of air bubbles on the surface of the liquid on a regular basis. If individual aerators or entire aerator groups fail, you can recognize this from the appearance of the bubbles.
We also recommend checking the air inclusion into the aeration system using a ma­nometer in the intake line. The pressure in the intake line changes due to deposits (the pressure increases) or defects (the pressure falls).
Note that when there is a pressure increase of 20mbar, the maintenance measure “Cleaning the membrane surface” must be carried out. The highest permitted pressure increase in the system is 50mbar. Higher deviations can damage the disc aerators.
Installation and operating instructions Wilo-Sevio AIR 65
English SHUTDOWN/DISPOSAL
7. Shutdown/disposal
All work must be carried out with the greatest care.
Proper protective equipment must be worn.
When carrying out work in basins or containers, the local protection measures must be
observed in all cases.
During all work, a second person must be present.
Only hoisting gear that is in a technically perfect condition and load-carrying equipment
that has been ofcially approved may be used for lowering and raising the product.
7.1. Temporary shutdown
With this type of shutdown, the product remains completely installed and is ready to operate at all times. While the system is shut down, a minimum water level of >1m must be maintained in the operating area. Also ensure that the temperature of the liquid and in the operating area does not fall below +3°C.
During down times, it is also necessary to ensure that a 10-minute function run is con­ducted on a weekly basis.
7.2. Shutdown for maintenance work or storage
Switch off the system and secure it against being switched on again without permis­sion. The operating area must be completely drained and cleaned. Work on removing the product and storage can then commence.
During basin drainage, we recommend that the aerator system be allowed to continue to run. This prevents deposits on the bottom of the basin and foul odors.
BEWARE of poisonous substances! During work in environments hazardous to health, such as waste water or sewage treatment plants, there is an increased hazard from bacteria and viruses. In order to counteract this elevated risk, please keep the following points in mind:
• Open wounds must be immediately cleaned and treated.
• Eating and drinking are strictly prohibited.
• Proper protective equipment must be worn!
• Upon leaving the system, disinfect persons and tools.
7.2.1. Removal
Removal takes place in the reverse order to installation:
1. Remove the drainage line
2. Remove the base support attachment
3. Remove the drainage connection
4. Remove the aeration pipes
5. Remove the air distributor
66 WILO SE 11/2012 Ed.03 DIN A5
SHUTDOWN/DISPOSAL English
7.2.2. Return delivery / storage
Return delivery
For shipping, the parts must be packed and sealed in sufciently large, non-tearing plastic sacks to prevent leakages. Shipping must be performed by carriers who have been briefed accordingly.
Please also refer to the “Transport and storage” section.
Storage
Thoroughly clean all components, decontaminating them if necessary.
Store them in a clean, dry place protected from frost.
Place them on a rm foundation and secure them against falling.
Protect components from direct sunshine to prevent the plastic parts from becoming
brittle.
Please also refer to the “Transport and storage” section.
7.3. Starting up again
Clean the product of dust and soiling before starting up again. During operation and storage, the membrane is subject to natural wear and thus must be checked for cracks and elasticity before it is installed. The product can then be installed in accordance with the Installation section. After it is installed, a function test in accordance with the “Start-up” section must be conducted.
7.4. Disposal
7.4.1. Protective clothing
Protective clothing worn for installation and dismantling as well as cleaning and mainte­nance work is to be disposed of in accordance with German Waste Code TA 524 02 and EC Directive 91/689/EEC.
7.4.2. Product
Proper disposal of this product avoids damage to the environment and risks to personal health.
Make use of the services or the advice of public or private waste disposal companies for the disposal of the product or parts of it.
More information about proper disposal can be obtained from the urban administra­tion, the waste disposal authorities or from the supplier from whom the product was purchased.
Installation and operating instructions Wilo-Sevio AIR 67
English MAINTENANCE
8. Maintenance
Maintenance or repair work must be carried out by an authorized service center, Wilo customer service or a qualied specialist.
Maintenance or repair work and/or constructional changes that are not listed in this operating and maintenance manual may only be carried out by the manufacturer or by authorized service centers.
Note the following:
This manual must be available to the maintenance personnel and its instructions must be followed.
All maintenance, inspection and cleaning work on the product and system may only be carried out by trained specialists exercising extreme care. Proper protective clothing is to be worn.
When carrying out work in basins or containers, the local protection measures must be observed in all cases. A second person must be present for safety reasons.
Only hoisting gear that is in a technically perfect condition and load-carrying equipment that has been ofcially approved may be used for lowering and raising the product. The maximum load-carrying capacity must never be exceeded.
Make sure that all fastening devices, ropes and safety devices of the hoisting gear are in a technically perfect condition. Work may only commence if the hoisting gear has been checked and found to be in perfect working order. If it is not inspected, fatal injuries may result.
Electrical work on the system must be carried out by an electrician.
When working with ammable solvents and cleaning agents, res, naked lights and
smoking are prohibited.
Products that operate in uids that are hazardous to your health must be decontami­nated. It must be ensured that no dangerous gases can form or are present.
BEWARE of poisonous substances! During work in environments hazardous to health, such as waste water or sewage treatment plants, there is an increased hazard from bacteria and viruses. In order to counteract this elevated risk, please keep the following points in mind:
• Open wounds must be immediately cleaned and treated.
• Eating and drinking are strictly prohibited.
• Proper protective equipment must be worn!
• Upon leaving the system, disinfect persons and tools.
If injuries involving hazardous liquids or gases occur, rst-aid measures
must be performed in accordance with the notices in the workplace and a doctor should be called immediately.
Ensure that all necessary tools and materials are available. Tidiness and cleanliness guarantee safe and trouble-free operation of the product. After working on the unit, all
68 WILO SE 11/2012 Ed.03 DIN A5
MAINTENANCE English
cleaning materials and tools should be removed from it. All materials and tools should be stored in an appropriate place.
Appropriate protective clothing must be worn for cleaning and maintenance jobs. This is to be disposed of in accordance with waste code TA 524 02 and EC Directive 91/689/ EEC.
Only use genuine parts made by the manufacturer.
8.1. Maintenance intervals
To ensure reliable operation, various maintenance tasks must be carried out regularly. The maintenance intervals should be decided according to the demands placed on the product. If strong vibrations occur during operation, the product or installation must be checked, regardless of the maintenance intervals.
8.1.1. Intervals for normal operating conditions
Weekly during a brief period of shutdown
Function run
Drainage of the aerator system
Weekly during regular operation
Cleaning the membrane surface
Annually during regular operation
Leak check of the aerator group(s)
Maintenance measures of the compressors/blower
Changing the lter
8.1.2. Intervals for difcult operating conditions
For difcult operating conditions, the maintenance intervals stated should be shortened accordingly. In this case, please contact Wilo customer service. If the products are to be used in difcult conditions, we also recommend that you take out a maintenance contract.
The following are considered difcult operating conditions:
Large quantities of brous materials or sand in the uid
Heavily corrosive liquids
Very aggressive liquids
For industrial applications
8.1.3. Measures recommended to ensure smooth operation
We recommend installation of a manometer in the intake line for the aerator group. The current pressure allows small defects to be immediately detected and rectied as necessary.
Installation and operating instructions Wilo-Sevio AIR 69
English MAINTENANCE
Deposits on the aerator membranes reduce the air inclusion into the liquid and increase the pressure in the aerator system. This reduces the efciency of the system. This becomes visible due to a changed appearance of the bubbles on the surface of the liquid. In this case, the maintenance measure “Cleaning the membrane surface” must be carried out.
If the aerator system is not tight or if a membrane cracks, the pressure drops in the aerator system. This leads to uncontrolled air inclusion and causes the efciency of the aeration to drop. This also becomes visible on the surface of the liquid, where large air bubbles will be escaping. In this case, the plant needs to be taken out of operation and a function test with clear water must be conducted in order to nd the leak.
Regular checks can therefore prevent greater damage from occurring later and reduce the risk of a total failure. For monitoring on a regular basis, we recommend remote mon­itoring of the air inclusion. Please contact Wilo customer service about this.
8.2. Maintenance tasks
8.2.1. Function run
To prevent damage to the membrane, a function run lasting 10 minutes must be con­ducted. Here it must be ensured that a minimum water level >1m exists in the operating area. The air inclusion must be between 1.5Nm³/h and 6Nm³/h.
8.2.2. Drainage of the aerator system
During the function run, open the valve of the drainage line. Supplying air into the aeration system causes any water/condensate that is present to be channeled through the drainage line.
8.2.3. Cleaning the membrane surface
During operation, the membrane surface can be clogged by deposits. This leads to reduced air inclusions into the uid and decreases the efciency of the aeration system. To counteract this, the membrane must be blown off in brief intervals under peak load in accordance with the maintenance intervals.
1. Increase the pressure in the system to the max. permitted value of 7.5Nm³/h for ve minutes.
2. Switch off the aeration for two minutes.
3. Repeat these steps 3 to 4 times.
The max. permitted value for pressurization of 7.5Nm³/h may not be exceeded.
Since this maintenance measure makes a major contribution to the functional safety and efciency of the system, we recommend that the maintenance interval be carried out automatically. This can be accomplished using a control station. Contact the manu­facturer of the control station in this regard.
70 WILO SE 11/2012 Ed.03 DIN A5
MAINTENANCE English
8.2.4. Leak check of the aerator group(s)
Leaks become visible on the surface of the liquid through a change in the appearance of the bubbles. Check the operating area from all sides for unusual bubble formation. For this maintenance measure, we recommend carrying out a function test with clear water and an inspection of the operating area.
8.2.5. Maintenance measures of the compressors/blower
Carry out maintenance work according to the manufacturer’s specications for the devices.
8.2.6. Changing the lter
If lters are used in the air intake, they need to be cleaned or replaced on a regular basis. You can nd more information in the respective lter documentation.
8.3. Repairs
When carrying out repairs, you must:
Switch off the system and make sure it cannot be switched on accidentally.
Drain the operating area, thoroughly clean all components, and decontaminate them if
necessary.
Never use brute force during any of this work.
8.3.1. What repairs may be carried out?
Membrane replacement, including the non-return valve
Disc aerator replacement
8.3.2. Membrane replacement, including the non-return valve
1. Use the special key to loosen and unscrew the threaded ring on the disc aerator.
2. Remove the separation ring and membrane support.
3. Remove the non-return valve.
4. Pull off the membrane from the membrane support.
5. Attach a new membrane to the membrane support.
6. Attach a new non-return valve.
7. Fit the membrane support and separation ring.
8. Screw the threaded ring back on and tighten it securely using the special key.
Before the system is started up again, a function test must be conducted.
8.3.3. Disc aerator replacement
1. Use a rubber mallet to push down the slide closure on the underside of the disc aerator against the direction of the arrow.
2. Remove the disc aerator.
3. Fit the new disc aerator onto the connection hole in the aerator pipe.
Important The connection of the disc aerator must be completely on the connection hole and the O ring must seal the connection!
Installation and operating instructions Wilo-Sevio AIR 71
English MAINTENANCE
4. Slide the slide closure up in the direction of the arrow using a rubber mallet.
Before the system is started up again, a function test must be conducted.
72 WILO SE 11/2012 Ed.03 DIN A5
Wilo–International(Subsidiaries)
Argentina
WILO SALMSON Argentina S.A. C1295ABI Ciudad Autónoma de Buenos Aires T+ 54 11 4361 5929 info@salmson.com.ar
Australia
WILO Australia Pty Limited Murrarrie, Queensland, 4172 T +61 7 3907 6900 chris.dayton@wilo.com.au
Austria
WILO Pumpen Österreich GmbH 2351 Wiener Neudorf T +43 507 507-0 office@wilo.at
Azerbaijan
WILO Caspian LLC 1014 Baku T +994 12 5962372 info@wilo.az
Belar
us
ILO Bel OOO
W 220035 Minsk T +375 17 2535363 wilo@wilo.by
Belgium
WILO SA/NV 1083 Ganshoren T +32 2 4823333 info@wilo.be
Bulgaria
WILO Bulgaria Ltd. 1125 Sofia T +359 2 9701970 info@wilo.bg
Brazil
WILO Brasil Ltda Jundiaí – SP – CEP
13.201-005 T + 55 11 2817 0349 wilo@wilo-brasil.com.br
Canada
WILO Canada Inc. Calgary, Alberta T2A 5L4 T +1 403 2769456 bill.lowe@wilo-na.com
China
WILO China Ltd. 101300 Beijing T +86 10 58 w
041888
ilobj@wilo.com.cn
Croatia
WILO Hrvatska d.o.o. 10090 Zagreb T +38 51 3430914 wilo-hrvatska@wilo.hr
CzechRepublic
WILO Praha s.r.o. 25101 Cestlice T +420 234 098711 info@wilo.cz
Denmark
WILO Danmark A/S 2690 Karlslunde T +45 70 253312 wilo@wilo.dk
Estonia
WILO Eesti OÜ 12618 Tallinn T +372 6 509780 info@wilo.ee
Finland
WILO Finland OY 02330 Espoo T +358 207401540 wilo@wilo.fi
France
WILO S.A.S. 78390 Bois d'Arcy T +33
1
30050930
info@wilo.fr
GreatBritain
WILO (U.K.) Ltd. DE14 2WJ Burton­Upon-Trent T +44 1283 523000 sales@wilo.co.uk
Greece
WILO Hellas AG 14569 Anixi (Attika) T +302 10 6248300 wilo.info@wilo.gr
Hungary
WILO Magyarország Kft 2045 Törökbálint (Budapest) T +36 23 889500 wilo@wilo.hu
India
WILO India Mather and Platt Pumps Ltd. Pune 411019 T +91 20 27442100 service@ pun.matherplatt.co.in
Indonesia
WILO Pumps Indonesia Jakart
a S
elatan 12140 T +62 21 7247676 citrawilo@cbn.net.id
Ireland
WILO Ireland Limerick T +353 61 227566 sales@wilo.ie
Italy
WILO Italia s.r.l. 20068 Peschiera Borromeo (Milano) T +39 25538351 wilo.italia@wilo.it
Kazakhstan
WILO Central Asia 050002 Almaty T +7 727 2785961 info@wilo.kz
Korea
WILO Pumps Ltd. 621-807 Gimhae Gyeongnam T +82 55 3405890 wilo@wilo.co.kr
Latvia
WILO Baltic SIA 1019 Riga T +371 7 145229 mail@wilo.lv
Leb
anon
ILO SALMSON
W Lebanon 12022030 El Metn T +961 4 722280 wsl@cyberia.net.lb
Lithuania
WILO Lietuva UAB 03202 Vilnius T +370 5 2136495 mail@wilo.lt
Morocco
WILO Maroc SARLQUARTIER INDUSTRIEL AIN SEBAA 20250 CASABLANCA T +212 (0) 5 22 660 924 contact@wilo.ma
TheNetherlands
WILO Nederland b.v. 1551 NA Westzaan T +31 88 9456 000 info@wilo.nl
Norway
WILO Norge AS 0975 Oslo T +47 22 804570 wilo@wilo.no
Poland
WILO Polska Sp. 0
5-090 Raszyn T +48 22 7026161 wilo@wilo.pl
Portugal
Bombas Wilo-Salmson Portugal Lda. 4050-040 Porto T +351 22 2080350 bombas@wilo.pt
Romania
WILO Romania s.r.l. 077040 Com. Chiajna Jud. Ilfov T +40 21 3170164 wilo@wilo.ro
Russia
WILO Rus ooo 123592 Moscow T +7 495 7810690 wilo@wilo.ru
SaudiArabia
WILO ME - Riyadh Riyadh 11465 T +966 1 4624430 wshoula@wataniaind.com
SerbiaandMontenegro
WILO Beograd d.o.o. 11000 Be
+381 11 2851278
T office@wilo.co.yu
Slovakia
WILO Slovakia s.r.o. 83106 Bratislava T +421 2 33014511 wilo@wilo.sk
Slovenia
WILO Adriatic d.o.o. 1000 Ljubljana T +386 1 5838130 wilo.adriatic@wilo.si
z.o.o.
ograd
SouthAfrica
Salmson South Africa 1610 Edenvale T +27 11 6082780 errol.cornelius@ salmson.co.za
Spain
WILO Ibérica S.A. 28806 Alcalá de Henares (Madrid) T +34 91 8797100 wilo.iberica@wilo.es
Sweden
WILO Sverige AB 35246 Väx
T
+46 470 727600
wilo@wilo.se
Switzerland
EMB Pumpen AG 4310 Rheinfelden T +41 61 83680-20 info@emb-pumpen.ch
Taiwan
WILO-EMU Taiwan Co. Ltd. 110 Taipeh T +886 227 391655 nelson.wu@ wiloemutaiwan.com.tw
Turkey
WILO Pompa Sistemleri San. ve Tic. A.S¸. 34956 İstanbul T +90 216 2509400 wilo@wilo.com.tr
Ukraina
WILO Ukraina t.o.w. 01033 Kiew T +38 044 2011870 wilo@wilo.ua
UnitedArabEmirates
WILO Middle East FZE Jebel Ali F
- Dubai T +971 4 880 91 77 info@wilo.ae
USA
WILO USA LLC Rosemont, IL 60018 T +1 866 945 6872 info@wilo-usa.com
Vietnam
WILO Vietnam Co Ltd. Ho Chi Minh City, Vietnam T +84 8 38109975 nkminh@wilo.vn
e Zone - South
re
Loading...