Wilo Control SC-Fire Electric Installation And Operating Instructions Manual

Pioneering for You
Wilo-Control SC-Fire Electric
de Einbau- und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service
2 541 365-Ed.01 / 2014-02-Wilo
nl Inbouw- en bedieningsvoorschriften
Fig. 1:
SPRINKLER PUMP MOTOR SUPPLY.
NOT TO BE SWICHED OFF
IN THE EVENT OF FIRE
I ON
0 OFF
1
2
**
3
1
6
7
5
4
Fig. 2:
2 31 54 6
7 8
10
9
English
Captions
Fig. 1 Switchgear set-up
1 Menu selection and parameter input
2 Main switch: for switching the switchgear
on/off
3 Fusible cut-outs
4 Transformer:
3-phase pump current measurement
5 Contactors/contactor combinations
6 Base board: printed circuit board with micro-
controller
7 Measurement board:
converting current and voltage values
** Note regarding the main switch:
Power supply for the sprinkler pump motor. DO NOT SWITCH OFF IN THE EVENT OF A FIRE!
Fig. 2 Switchgear display elements
1 LED (green): Operational standby
2 LED (green): Pump operation
3 LED (yellow): False start
4 LED (white): Sprinkler request
5 LED (white): Float switch request
6 LED (yellow): Collective fault
7 LED (green) and button: Manual start
8 LED (red) and button: Manual stop
9 Button: Lamp test
10 Button: Acknowledgement of error messages
26 WILO SE 01/2014
English
Installation and operating instructions
1 General
1.1 About this document
The language of the original operating instruc­tions is German. All other languages of these instructions are translations of the original oper­ating instructions. These installation and operating instructions are an integral part of the product. They must be kept readily available at the place where the product is installed. Strict adherence to these instructions is a precondition for the proper use and correct operation of the product. These installation and operating instructions cor­respond to the relevant version of the product and the underlying safety regulations and standards valid at the time of going to print. EC declaration of conformity: A copy of the EC declaration of conformity is a component of these operating instructions. If a technical modification is made on the designs
amed there without our agreement or the decla-
n rations made in the installation and instructions on product/personnel safety are not observed, this declaration loses its validity.
operating
2Safety
These operating instructions contain basic infor­mation which must be adhered to during installa­tion, operation and maintenance. For this reason, these operating instructions must, without fail, be read by the service technician and the responsible specialist/operator before installation and com­missioning. It is not only the general safety instructions listed under the main point “safety” that must be adhered to but also the special safety instructions with danger symbols included under the following main points.
2.1 Indication of instructions in the operating instructi
Symbols: General danger symbol
Danger due to electrical voltage
NOTE
Signal words: DANGER! Acutely dangerous situation. Non-observance results in death or the most serious of injuries. WARNING! The user can suffer (serious) injuries. ’Warning’ implies that (serious) injury to persons is proba­ble if this information is disregarded.
ons
CAUTION! There is a risk of damaging the pump/unit. tion’ implies that damage to the product is likely if this information is disregarded.
NOTE: Useful information on handling the product. It draws attention to possible problems.
Information that appears directly on the product, such as:
• Direction of rotation arrow,
• Identification for connections,
• Rating plate,
• Warning sticker, must be strictly complied with and kept in legible condition.
2.2 Personnel qualifications
The installation, operating and maintenance per­sonnel must have the appropriate qualifications
this work. Area of responsibility, terms of ref-
for erence and monitoring of the personnel are to be e
nsured by the operator. If the personnel are not in possession of the necessary knowledge, they are to be trained and instructed. This can be accom­plished if necessary by the manufacturer of the product at the request of the operator.
2.3 Danger in the event of non-observance of the safety instructions
Non-observance of the safety instructions can result in risk of injury to persons and damage to the environment and the product/unit. Non­observance of the safety instructions results in the loss of any claims to damages. In detail, non-observance can, for example, result in the following risks:
• Danger to persons from electrical, mechanical and bacteriological influences
• Damage to the environment due to leakage of hazardous materials
• Property damage
• Failure of important produc
• Failure of required maintenanc dures
2.4 Safety consciousness on the job
The safety instructions included in these installa­tion and operating instructions, the existing national regulations for accident prevention together with any internal working, operating and safety regulations of the operator are to be com­plied with.
2.5 Safety instructions for the operator
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervi­sion or instruction concerning use o by a person responsible for their safety. Children should be supervised to ens do not play with the appliance.
t/unit functions
e and repair proce-
f the appliance
’Cau-
ure that they
Installation and operating instructions Wilo SC-Fire Electric 27
English
If hot or cold components on the product/the unit lead to hazards, local measures must be taken to guard them against touching. Guards protecting against touching moving com­ponents (such as the coupling) must not be removed whilst the product is in operation. Leakages (e.g. from the shaft seals) of hazardous fluids (which are explosive, toxic or hot) must be led away so that no danger to persons or to the environment arises. National statutory provisions are to be complied with.
• Highly flammable materials are always to be kept at a safe distance from the product.
• Danger from electrical current must be eliminated. Local directives or general directives [e.g. IEC, VDE etc.] and instructions from local energy supply companies must be adhered to.
2.6 Safety instructions for installation and maintenance work
The operator must ensure that all installation and maintenance work is qualified personnel, who are sufficiently informed from their own detailed study of the operating instructions. Work on the product/unit must only be carried out when at a standstill. It is mandatory that the pro­cedure described in the installation and operating instructions for shutting down the product/unit be complied with. Immediately on conclusion of the work, all safety and protective devices must be put back in posi­tion and/or recommissioned.
carried out by authorised and
3 Transport and interim storage
Immediately after receiving the product:
• Check product for transport damage.
• In the event of damage in transit, take the neces­sary steps with the forwarding agent within the respective time limits.
CAUTION! Risk of property damage! Incorrect transport and interim storage can cause property damage.
• The switchgear is to be protected against mois­ture and mechanical damage.
• It must not be exposed to temperatures outside the range of -10°C to +50°C.
4 Application (intended use)
The SC Fire pump switchgear is used to control an individual electric pump in automatic sprinkler systems, in accordance with EN 12845. The device is used in residential and office ings, hospitals, hotels, administrative and indus­trial buildings. The pump is used in conjunction with suitable sig­nal transmitters and it is s the pressure or on and off according to the level. The intended use includes complying with these instructions. Any other use is considered to be outside the intended use.
witched on according to
build-
2.7 Unauthorised modification and manufacture of spare parts
Unauthorised modification and manufacture of spare parts will impair the safety of the product/ personnel and will make void the manufacturer’s declarations regarding safety. Modifications to the product are only permissible after consultation with the manufacturer. Original spare parts and accessories authorised by the manufacturer ensure safety. The use of other parts will absolve us of liability for consequential events.
2.8 Improper use
The operating safety of the supplied product is only guaranteed for conventional use in accord­ance with Section 4 of the operating The limit values must on no account fall under or exceed those specified in the catalogue/data sheet.
instructions.
28 WILO SE 01/2014
5Product information
5.1 Type key
Example:
W W = Wilo CTRL Control SC Smart Control = control unit F F = fire fighting purposes 1x Number of pumps
7.7 A Maximum rated motor current [A] T4 T = 3 phases; 4 = 400 V DOL SD FM BM ND3 ND4 E Switchgear for electric pump
Direct online (direct starting) Star delta (star-delta starting) Frame mounted (on a base frame) Base mounted (free-standing cabinet) New Design switchbox 400 x 1300 x 250 mm New Design switchbox 400 x 950 x 250 mm
English
5.2 Technical data (standard version)
Mains supply voltage [V]: 3~400 V (L1, L2, L3, PE) Frequency [Hz]: 50/60 Hz Control voltage [V]: 230 VAC; 24 VDC Max. current consumption [A]: See rating plate Protection class: IP 54 Max. fuse protection on mains side [A]: See wiring diagram Ambient temperature [°C]: 0 to +40°C Electrical safety: Degree of contamination II Alarm/signalling contact 250 VAC, 1 A
5.3 Scope of delivery
•Switchgear
•Wiring diagram
• Installation and operating instructions
• Test report acc. to EN 60204-1
5.4 Accessories
6 Description and function
6.1 Description of the product (Fig. 1)
6.1.1 Function description
The switchgear is used to control an individual elec
tric pump in sprinkler systems, in accordance with EN 12845. The pump can be switched on and off by the control depending on the pressure. The system’s operating statuses, such as standby, pump operation, fault etc., are displayed visually by LEDs on the door and operating parameters such as current or voltage values are shown on the display. The system is operated using the rotary knob and the buttons in the door. Potential-free contacts are available for forward­ing run or fault signals mes management system.
sages to the building
6.1.2 Set-up of the switchgear (Fig. 1)
The set-up of the switchgear depends on capacity of the pump to be connected. It consists of the following main components:
• Main switch: Switches the switchgear on/off (Fig. 1, item 2)
• Human-machine interface (HMI): signal lamps or display for indicating the operating status (e.g. standby, fault, and rated pump current), rotary knob and buttons for menu selection, parameter input and operation (Fig. 1, item 1)
• Base board: printed circui troller (Fig. 1, item 6)
• Measurement board: conver age values (Fig. 1, item 7)
• Transformer: 3-phase pump current measure­ment (Fig. 1, item 4)
• Fuse protection for drives: fusing for the pump motor by means of fusible cut-outs (Fig. 1, item 3)
• Contactors/contactor combinations: contactors for switching on the pumps (Fig. 1, item 5)
the
t board with microcon-
ting current and volt-
Installation and operating instructions Wilo SC-Fire Electric 29
English
6.2 Function and operation DANGER! Risk of fatal injury! When working on the open switchgear, there’s a danger of electric shock from touching the live components. This work must only be carried out by qualified personnel!
NOTE: After connecting the switchgear to the supply voltage, as well as after every mains interruption, the switchgear returns to the operating mode set before the power interruption.
6.2.1 Switchgear operating modes (Fig. 2) Switching the switchgear on/off
After connection to the mains supply, the switch­gear can be switched on or off using the main switch. Once the main switch has been switched on, the system is ready for operation after a few seconds (the start phase). If the supply voltage is within the set parameters, standby is indicated by the signal lamp (Fig. 2, item 1) lighting up green.
Pump request
If the pressure drops below the set target pressure at leas
t one of the two pressure switches, the sig­nal lamp lights up (Fig. 2, item 4). After a configur­able delay period (see menu 1.2.5.1) (LED flashes), the connected pump is activated. The signal lamp (Fig. 2, item 2) lights up green, indicating that the pump is in operation. Once the pressure reaches or exceeds the target pressure, the signal lamp (Fig. 2, item 4) goes out again but the pump remains activated. The pump has to be switched off manually. The signal lamp (Fig. 2, item 2) then goes out.
Priming device
If the level of the pump priming tank falls below 2/3, the float switch closes and the signal lamp (Fig. 2, item 5) lights up white. After a configur­able delay time (see menu 1.2.5.2) (LED flashes), the pump activates and the signal lamp (Fig. 2, item 2) lights
up green. Once the pump priming tank is full and the float switch opens again, the signal lamp goes out (Fig. 2, item 5) and the pump eithe
r switches off again automatically or it has to be deactivated manually (see menu 5.2.2.0). The signal lamp (Fig. 2, item 2) then goes out.
Voltage monitoring
To improve operational reliability, the mains power supply is monitored continuously. To do this, the correct supply voltage has to be set in menu 1.2.1.1. The voltage is monitored individu­ally between all three live wires. If no pump is run­ning (standby), the voltage in the display switches alternately between all three conductors. When the supply voltage exceeds or drops below the configurable tolerances (see menu 5.4.1.0 and
5.4.2.0), the signal lamp (Fig. 2, item 1) goes out after a configurable delay (see menu 1.2.5.3) and the collective fault signal (Fig. 2, item 6) lights up
yellow. If a fault occurs, the pump nevertheless starts or continues running. Once the voltage is back within the tolerance range, the fault is self­acknowledging. The signal lamp (Fig. 2, item 6)
oes out and the signal lamp (Fig. 2, item 1) lights
g up green again.
Current monitoring
The pump current is monitored while the pump is in operation. To do this, the correct rated current for the pump has to be set in menu 1.2.1.2. The current is monitored individually in all three con­ductors. If the pump is running, the pump current in the display switches alternately between all three conductors. The signal lamp (Fig. 2, item 2) lights up green once the pump current reaches a configurable minimum threshold (see menu
5.4.3.0). When the pump current exceeds or drops below the configurable tolerances (see menu
5.4.3.0 and 5.4.4.0), the signal lamp (Fig. 2, item 6) ghts up after a configurable delay (see menu
li
1.2.5.5). If a fault occurs, the pump nevertheless
starts or continues running. Once the pump cur­rent is back within the tolerance range, the fault can be
acknowledged. The signal lamp (Fig. 2,
item 6) goes out.
Monitoring hydraulic false start
Once the pump has started, the hydraulic output is monitored by a pressure switch on the pump. If the pump does not build up any pressure after the configurable period of time (see menu 1.2.2.2) and the pressure switch on the pump remains open, the signal lamps (Fig. 2, item 6) and (Fig. 2, item 3) light up. If the pump is running, the relevant pres­sure has been reached and the pump pressure switch is closed accordingly, the fault can be acknowledged. The signal lamps (Fig. 2, item 6) and (Fig. 2, item 3) go out and the signal lamp (Fig. 2, item 2) lights up green.
Monitoring electric false start
Once the pump has started
, the pump’s electric output is monitored for a configurable period of time after the start (see menu 1.2.2.1). To do this, the correct pump output has to be set in menu
1.2.1.3. If the configurable minimum threshold (see menu 5.4.5.0) is not reached within the monitoring period, the signal lamps (Fig. 2, item 6) and (Fig. 2, item
3) light up after a configurable delay period (see menu 1.2.5.4) plus the time for the star/delta changeover (see menu 1.2.5.6). If the pump is run­ning and the relevant pump output has been reached, the fault can be acknowledged. The signal lamps (Fig. 2, item 6) and (Fig. 2, item 3) go out and the signal lamp (Fig. 2, item 2) lights up green.
Logic reversal of the collective fault signal (SSM)
The required logic of the SSM can be set in menu
5.5.2.0. In this case, it is possible to select between negative logic (falling edge in case of a fault = “fall”) or positive logic (rising edge in case of a fault = “raise”).
30 WILO SE 01/2014
English
4
4
1
2
3
5
6.2.2 Operation of the switchgear Operating elements
Main switch on/off (lockable in “Off” position)
•The LCD shows the operating statuses of the
pump and the settings menu. The menu selection and parameter input are performed using the operating knob. Turn the knob to change values or to scroll through a menu level; press it in order to select and confirm:
The following graphic symbols are used:
Information appears on the display as shown in the sample illustration below:
Item Description
1 Menu number 2 Value display 3 Units display 4 Standard symbols 5 Graphic symbols
Symbol
Function/description Availability
Go back (brief press: one menu level; long press: main screen) all
EASY menu all
EXPERT menu all
Meaning: Service not logged in
all
Meaning: Display value – no entry possible
Service menu all
Parameter all
Information all
Fault all
Reset fault all
Installation and operating instructions Wilo SC-Fire Electric 31
Alarm settings all
English
Symbol
Function/description Availability
Pump all
Setpoints all
Actual value all
Sensor signal all
Sensor measurement range Electrical equipment
Delay time all
Operating mode/application all
Stand-by all
Operating data all
Switchgear data:
all
Controller type; ID number; software/firmware
Operating hours all
Pump’s operating hours all
Switchgear’s switching cycles all
Pump’s switching cycles all
Communication all
Output parameters all
SSM parameter all
Set motor speed Diesel
32 WILO SE 01/2014
English
Symbol
Function/description Availability
Starting time per start attempt Diesel
Pause between start attempts Diesel
Fuel Diesel
Battery A Diesel
Battery B Diesel
Sprinkler (pressure switch) all
Pump priming tank (float switch) all
Heating Diesel
Engine oil Diesel
Motor temperature thermostat Diesel
Cooling water (temperature) Diesel
Belt break Diesel
False start Electrical equipment
Pressure Electrical equipment
Mains power supply Electrical equipment
Voltmeter all
Ampere meter all
Star-delta switching Electrical equipment
Installation and operating instructions Wilo SC-Fire Electric 33
English
Symbol
Function/description Availability
Freely configurable fault signal all
Fault input all
Start attempts counter Diesel
Duration all
Power meter Electrical equipment
Communication parameters all
Modbus all
BACnet all
Factory setting all
Resetting the settings to the factory settings all
Alarm counter all
Maintenance interval all
Reset all
Motor speed Diesel
Set motor speed Diesel
Minimum speed for “motor in operation” Diesel
Reset starting counter Diesel
Menu structure: The menu structure of the control system has
4 levels.
34 WILO SE 01/2014
Navigation in the individual menus as well as the parameter input are described in the following example (selecting the transformer):
English
Installation and operating instructions Wilo SC-Fire Electric 35
English
Refer to the following table for a description of the individual menu items:
Menu no./
Display Description Parameter range
Factory setting
The main screen shows the status of the system. The display continuously switches between the voltages of the live wires.
When the motor is running, the present pump cur­rent in all three live wires is shown alternately on the display.
The EASY menu allows you to make settings for the supply voltage, rated pump current and the pump’s performance.
The EXPERT menu contains other settings that can be used for a detailed setting of the switch­gear.
The parameter menu for all settings that influence operation.
The setting menu for the electrical parameters of the connected pump.
Setting the supply voltage. 400
36 WILO SE 01/2014
English
Menu no./
Display Description Parameter range
Factory setting
Setting the rated pump current. 0.1..7.8..5000
Setting the pump motor’s output. 1..4..250
The setting menu for the monitoring operations periods.
Setting the duration for monitoring of the pump’s
0..70..120
electric output (electric false start).
Setting the duration for monitoring of the pump’s
0..70..120
hydraulic output (hydraulic false start).
The setting menu for the delays.
Start delay when pressure switch trips 1..10
Start delay when float switch trips 1..10
Installation and operating instructions Wilo SC-Fire Electric 37
English
Menu no./
Display Description Parameter range
Factory setting
Delay in event of error message from voltage
0..1..10
monitoring
Delay for “electric false start” error message 0..1..20
Delay in event of error message from current
0..1..20
monitoring
Star-delta changeover time 0..5..60
Buffer time between deactivation of star contac-
0.00..0.05..1.0
tor and activation of delta contactor
Communication
Display of currently activated fieldbus OFF, Modbus, BAC-
net, GSM
Pump menu
38 WILO SE 01/2014
English
Menu no./
Display Description Parameter range
Factory setting
Drives on/off OFF, ON
Information
Current operating values
Voltage values
Voltage between conductors L1 and L2
Voltage between conductors L1 and L3
Voltage between conductors L2 and L3
Current values
Installation and operating instructions Wilo SC-Fire Electric 39
English
Menu no./
Display Description Parameter range
Factory setting
Pump current in L1
Pump current in L2
Pump current in L3
Output values
Pump output L1
Pump output L2
Pump output L3
Status information
40 WILO SE 01/2014
English
Menu no./
Display Description Parameter range
Factory setting
System status or readiness
Status of pressure switch
Status of float switch
Operating data
Total running time of the system
Total running time of pump
Unit switching cycles
Pump’s switching cycles
Installation and operating instructions Wilo SC-Fire Electric 41
English
Menu no./
Display Description Parameter range
Factory setting
System data
System type
Serial number as ticker format
Software version
Firmware version
Settings
Sensor settings
Transformer selection 30..1000
42 WILO SE 01/2014
English
Menu no./
Display Description Parameter range
Factory setting
Motor stop when started by float switch Manual, Auto
Limit values
Lower tolerance limit for supply voltage 0..10
Upper tolerance limit for supply voltage 0..10
Lower tolerance limit for rated pump current 0..10
Upper tolerance limit for rated pump current 0..10
Setting for minimum output necessary for detec-
0..80..100
tion that pump has started
Signal output parameters
Installation and operating instructions Wilo SC-Fire Electric 43
English
Menu no./
Display Description Parameter range
Factory setting
Characteristics of collective fault signal (SSM) Fall, Rise
Freely configurable fault signal
Acknowledgement process for fault signal Not store, ON store
Logic reversal of input signal Fall, Rise
Activation of configurable fault signal OFF, ON
Fault active:
Ever, Pump
Always Only when pump in operation
Response delay 0..60
Fault signals
44 WILO SE 01/2014
English
Menu
Display Description Parameter range
no./
6.1.0.1 to
6.1.1.6
Operation levels:
The parameterisation of the switchgear is divided into the menu areas EASY and EXPERT. For rapid commissioning using the factory presets, it is enough to set the speed values and the speed adjustment in the EASY area. The EXPERT area is provided in case other p ar am et e rs ne ed t o b e c ha ng ed , o r fo r r ea di ng ou t data from the device. Menu level 7.0.0.0 is reserved for Wilo customer service.
Manual start (Fig. 2, item 7) The pump is started
manually by pressing the button. The relevant sig­nal lamp (Fig. 2, item 7) lights up green when the button is pressed, indicating that the pump was started manually, not automatically. The pump can only be stopped manually. The signal lamp (Fig. 2, item 7) then also goes out.
Manual stop (Fig. 2, item 8) The pump is stopped
manually by pressing the button. The relevant signal lamp (Fig. 2, item 8) lights up red when the button is pressed, indicating that the pump was stopped manually. The pump can only be stopped using this button, except if the pump was started by the float switch and “auto” has been set in menu 5.2.2.0. The signal lamp (Fig. 2, item 8) goes out the next time the pump starts again or when the button (Fig. 2, item 10) is pressed.
Lamp test (Fig. 2, item 9) Pressing the button
switches on all the signal lamps (Fig. 2, items 1, 2, 3, 4, 5, 6, 7, 8) for as long as the button is pressed, in order to check that the lamps are working. When you release the button, the signal lamps go out again or only light up according to the func­tion.
Ack
nowledgement (Fig. 2, item 10) Pressing the
button resets all the error messages or signal lamps provided that the cause of the error no longer exists.
Resetting fault signals
Fault signal 1 to 16
6.2.3 Switchgear display elements
Factory setting
Operational standby
The signal lamp (Fig. 2, item 1) lights up green if the power
supply is connected, activated via the main switch and the power supply is within the configurable tolerance range (see menu 5.4.1.0 and 5.4.2.0).
Pump operation
The signal lamp (Fig. 2, item 2) lights up green if the pump is activated and the pump current is within the configurable tolerance range (see me nu
5.4.3.0 and 5.4.4.0).
False start
When the pump starts, it is monitored by means of two different parameters (hydraulic false start, electric false start). The signal lamp (Fig. 2, item 3) lights up yellow after the pump has started and the configurable minimum output (see menu 5.4.5.0) is not reached within a configurable period of time (see menu
1.2.2.1). The signal lamp (Fig. 2, item 3) lights up yellow
ter the pump has started and the pump pressure
af switch (option) does not close again (pump under pressure) after a configurable period of time (see menu 1.2.2.2).
Sprinkler request
The signal lamp (Fig. 2, item 4) lights up white if the pressure in the system falls below the set/ requested pressure and at least o
ne of the two pressure switches trips. If the pressure rises accordingly, the signal lamp (Fig. 2, item 4) goes out again.
Float switch request
The signal lamp (Fig. 2, item 5) lights up white when
the level in the pump priming tank falls to 2/ 3 and the float switch is triggered. If the level rises again accordingly, the signal lamp (Fig. 2, item 5) goes out.
Installation and operating instructions Wilo SC-Fire Electric 45
English
Collective fault
The signal lamp (Fig. 2, item 6) lights up yellow when a fault occurs. Faults include a fault in the supply network, over- or undercurrent, false pump start and a fault in the freely configurable fault signal. The signal lamp (Fig. 2, item 6) goes out again once the fault no longer exists and the fault has been acknowledged. If “Automatic off” is set in menu 3.1.0.0, the signal lamp (Fig. X, item 6) will flash yellow, because the automatic mode is disabled.
Manual pump start
The signal lamp (Fig. 2, item 7) lights up green when the pump is started manually using the but­ton (Fig. 2, item 7). It goes out again when the pump is stopped manually.
Manual pump stop
The signal lamp (Fig. 2, item 8) lights up red when the button ope been acknowledged.
(Fig. 2, item 8) is pressed to stop pump
ration. It goes out once the pump stop has
7 Installation and electrical connection
Installation and electrical connection must be carried out in accordance with local regulations and only by qualified personnel! WARNING! Risk of injury! The existing directives for accident prevention must be adhered to. Warning! Danger of electric shock! Danger from electrical current must be elimi­nated. Local directives or general directives [e.g. IEC] and instructions from local energy supply com­panies must be adhered to.
7.1 Installation
Install the switchgear/system at a dry location. Protect the place of installation from direct expo­sure to sunlight.
7.2 Electrical connection DANGER! Risk of fatal injury! Improper electrical connections can lead to fatal electric shocks.
• Have the electrical connection established by an electrician approved by the local electricity sup­plier only and in accordance with local regula­tions.
• Observe the installation and operating instruc­tions for the pumps and accessories!
• Disconnect the power supply before any work.
Warning! Danger of electric shock! There is a potentially fatal voltage on the supply side, even when the main switch is turned off.
• The type of mains, current and voltage of the mains connection must match the details on the rating plate of the control device.
NOTE:
• Fuse on mains side in acco mation in the wiring diagram
• Feed the ends of the mains cable through the threaded cable connections and cable inlets and wire them according to the markings on the ter­minal strips.
• Earth the pump/installation in accordance with the regulations. NOTE: In accordance with EN /IEC 61000-3-11 (see table below), the switchgear and pump with motor power of ... kW (column 1) are provided for opera­tion on a mains power supply with a system imped-
ance of Zmax at the building connection of max. ...
Ohm (column 2) for a maximum number of ... con­nections (column 3). If the mains impedance and the number of con­nections per hour are greater than the values given in the table, the switchgear with the pump may lead to temporary voltage drops and also to disturbing voltage fluctuations (flickering) due to the unfavourable mains conditions. Therefore, measures may be necessary before the switchgear at this connection. The necessary information must be obtained from the local electricity supply company and the manufacturer.
with pump can be operated as intended
rdance with the infor-
46 WILO SE 01/2014
English
3~400 V 2-pole Direct starting
3~400 V 2-pole S-D starting
Output [kW] (Column 1)
System impedance [Ω] (Column 2)
Connections per hour (Column 3)
2.2 0.257 12
2.2 0.212 18
2.2 0.186 24
2.2 0.167 30
3.0 0.204 6
3.0 0.148 12
3.0 0.122 18
3.0 0.107 24
4.0 0.130 6
4.0 0.094 12
4.0 0.077 18
5.5 0.115 6
5.5 0.083 12
5.5 0.069 18
7.5 0.059 6
7.5 0.042 12
9.0 – 11.0 0.037 6
9.0 – 11.0 0.027 12
15.0 0.024 6
15.0 0.017 12
5.5 0.252 18
5.5 0.220 24
5.5 0.198 30
7.5 0.217 6
7.5 0.157 12
7.5 0.130 18
7.5 0.113 24
9.0 – 11.0 0.136 6
9.0 – 11.0 0.098 12
9.0 – 11.0 0.081 18
9.0 – 11.0 0.071 24
Installation and operating instructions Wilo SC-Fire Electric 47
English
7.2.1 Power supply connection
Connect the on-site 4-wire cable (L1, L2, L3, PE) for the supplying network to the main switch, in accordance with the wiring diagram.
7.2.2 Fault signal/run signals connection
A signal can be taken from the terminal strip for the fault signal/run signal via a potential-free contact in order to indicate a fault/operation (see wiring diagram). Potential-free contacts, max. contact load 250 V~/1 A
Warning! Danger of electric shock! There is a potentially fatal voltage on these ter­minals, even when the main switch is turned off.
8 Commissioning
WARNING! Risk of fatal injury! Commissioning by qualified personnel only! Improper commissioning poses a risk of fatal i
njury. Have commissioning performed by quali-
fied personnel only.
DANGER! Risk of fatal injury! When working on the open switchgear, there’s a danger of electric shock from touching the live components. This work must only be carried out by qualified personnel!
We recommend that you have the switchgear commissioned by Wilo customer service. Before switching on for the first time, the on-site wiring must be checked, in particular the earthing.
Tighten all terminals prior to commissioning!
8.1 Switchgear settings
After switching on the main switch and expiration of the start sequence in the display and of the sig­nal lamps, the switchgear is ready for operat and factory preset. The factory settings can be rest tomer service. To ensure correct operation it is necessary to implement and/or check certain settings in the menu
Menu 1.2.1.1: Setting of the supply voltage in volts.
Menu 1.2.1.2: Setting of the pump’s rated current. Information relating to the pump’s rated current is to be inferred from the pump’s rating plate.
ored by Wilo cus-
ion
Menu 1.2.1.3: Display of the pump’s capacity. The value used for the capacity results from the set values for voltage and current under menu 1.2.1.1. and menu 1.2.1.2.
Menu 5.2.1.0: Setting of the transformer type (primary current measuring range). Information relating to the transformer type can be found on the trans­former’s rating plate. NOTE: If the measuring line has not only been run through the transformer but also wrapped around it, the current value of the transformer is to be halved for each wrapping. Example: The measuring line has been wrapped twice around a 100/5A transformer. 1 wrapping = 50/5A transformer 2 wrappings = 25/5A transformer A 25/5A transformer should th menu.
Menu 3.1.0.0: Setting of the operating mode to “Automatic on” (automatic pump operation).
CAUTION! Risk of malfunctions!
If “Automatic off” is set, automatic mode is not possible. The pump can only be switched on man­ually.
8.2 Checking the motor direction of rotation
By briefly switching on the pump, check that the direction of rotation of the pump is correct. When the pump motor runs out, compare the direction of rotation of the fan wheel and the direction specified on the pump housing. If the direction of rotation of the pump is wrong, swap over any two phases of the power cable.
erefore be set in the
9Maintenance
Have maintenance and repair work carried out by qualified skilled personnel only! DANGER! Risk of fatal injury! There is a risk of fatal injury from electric shock when
working on electrical equipment.
• The switchgear should be electrically isolated and secured against unauthorised switch-on during any maintenance or repair work.
• Any damage to the connection cable should only ever be eradicated by a qualified electrician.
• The switchbox must be kept clean.
• Visual inspection of the electric system parts in the switchbox
48 WILO SE 01/2014
English
10 Faults, causes and remedies
DANGER! Risk of fatal injury! There is a risk of fatal injury from electric shock when working on electrical equipment. Have faults remedied by qualified skilled per­sonnel only! Follow the safety instructions in Section “2 Safety”. Before all work to remedy faults, disconnect the unit from the power supply, and make sure it cannot be switched back on by unauthorised persons.
10.2 History memory for faults
A history memory has been set up for the switch­gear and operates according to the FIFO principle (first-IN, first-OUT).
Code Fault description Causes Remedy
E54.0 No bus communication to
HMI board
Connection to HMI board inter­rupted
10.1 Fault indication
If a fault occurs, the relevant fault signal LED lights up, the collective fault signal and associated indi­vidual fault contact are activated and the fault is displayed on the LCD (fault code number). The fault can be acknowledged by pressing the acknowledgement button (Fig. 2, item 10) or in menu 6.1.0.0 by proceeding as follows:
The memory is configured for 16 faults. The fault memory can be called up using menus 6.1.0.1 –
6.1.1.6.
Check connection
Request customer service
E4.0 Undervoltage Supply voltage too low on mains
side
E5.0 Overvoltage Supply voltage too high on mains
side
E61.0 Hydraulic false start Pump pressure switch indicates
no pressure after pump start
E11.0 Electric false start Motor’s minimum electric output
not reached after pump start
E23.0 Excess current Excessive rated pump current
during operation
Exx.x Undercurrent Insufficient rated pump current
during operation
E109.0 Freely configurable fault Depending on the fault configu-
ration
If the fault cannot be remedied, please contact
ur nearest Wilo customer service point or rep-
yo resentative.
Check mains voltage/mains supply, check fuses Check mains voltage/mains supply Check pump/impeller, check pipes for leaks, check pump’s direction of rotation, check pressure switch setting Check settings, check pump/ impeller Pump blocked or stiff, check supply voltage Check settings, check pump/ impeller Depending on the fault config­uration
Installation and operating instructions Wilo SC-Fire Electric 49
Pioneering for You
WILO SE Nortkirchenstraße 100 D-44263 Dortmund Germany T +49(0)231 4102-0 F +49(0)231 4102-7363 wilo@wilo.com www.wilo.com
Loading...