WIKA SF6 User Manual

Operating Instructions GB
SF6 Gas Density Monitors with magnetic snap-action contacts
(Models 233.52.100, with gas or liquid filling as well as Model 212.22.100)
Examples:
3. Description, application
The built-in electric alarm contacts (magnetic snap-action) are auxiliary current switches which open and close the connected electrical circuits at the set points via the contact arm, which is driven by the main instrument pointer.
4. Mechanical connection
According to the general technical regulations for pressure gauges, respectively (i.e. EN 837-2). When screw-fitting the gauges the force required for this must not be applied through the case or terminal box but just through the spanner flats (with suitable tool) provided for this purpose.
Model 233.52.100, with external temperature sensor
Model 233.52.100
Contents
1. Safety instructions
2. General information
3. Description, application
4. Mechanical connection
5. Wiring details
6. To set desired value indicator
7. Ingress protection IP
9. Maintenance and servicing / cleaning
10. Power ratings
11. Overcurrent protection devices
12. Repairs / Complaints
1. Safety instructions
The appropriate national safety regulations (i.e. VDE 0100) must be observed when installing, putting into operation and running these
while under voltage. Serious injuries and/or damage can occur should the appropriate regulations not be observed. Only appropriately qualified persons should work on these instruments.
2. General information
Gas density monitors are modified pressure measuring instruments with electrical accessories. Gas density monitors combine both measuring and switching functions in one single instrument. Temperature influences that have an effect on the confined SF6 gas are com­pensated by means of a compensation system. Each density monitor is specially adapted to the specific application conditions of the switchgear it is intended for (pure SF6 gas, gas compounds, calibration pressure, switching points ...).
During transportation or storage gas density monitors might warm up or cool down. Temperatures that are different from the reference temperature (20 °C) lead to pointer deflections. This is absolutely normal, because the compensation system is working.
In order to ensure that the instruments have sufficiently adjusted to the ambient temperature, they have to be exposed to a temperature of 20 ±2 °C for at least 2 hours. Subsequently in an unpressurised condition the pointer will be within the tolerance bar.
instruments. Do not work on gauge
Installation with open-end wrench
5. Wiring details
The electrical connections should be made by qualified electricians. Connection details and switch functions are given on the instrument type plate. Connection terminals and ground terminal are appropriately marked. The main connection line to be provided must be dimensioned for maximum instrument power consumption and comply with IEC 227 or IEC 245. Power ratings and overcurrent protection devices see overleaf!
6. To set desired value indicator
As a standard the alarm contacts of SF6 gas density monitors are non-adjustable, i.e. they cannot be re-adjusted later on. Therefore the risk of unintentionally mis-adjusting the alarm contacts is eliminated.
Desired value indicators (red set pointer)
If on express request by the customer the contacts have to be adjustable, re-adjustments can be carried out as follows: The desired value can be set via the adjustment lock in the window by means of the re­adjustment key provided (at the terminal box of standard instruments).
7. Ingress protection IP
The type of enclosure to EN 60 529 for protection against external influences depends on the basic instrument and is found in the respective data sheet.
8. Admissible ambient temperatures
The permissible ambient temperatures for alarm contacts is -20 to +70 °C. Where this span exceeds the permissible temperature limits for the instrument to which the contacts are fitted, the limits for the instrument apply (see data sheet).
9. Maintenance and servicing / cleaning
The instruments require no maintenance or servicing. The instruments should be cleaned with a damp cloth moistened with soap solution. For cleaning inside the instrument the mains power supply should be disconnected by means of the plug box or plug connection. It must be ensured that all the parts are dry before the power is switched on again.
10. Power ratings
Table 1: Maximum contact rating
Maximum contact rating Magnetic snap-action contact model 821 with non-inductive
Gas filled gauges Liquid filled gauges
(ohmic) load
Maximum voltage (MSR) U
eff
Current ratings:
Make rating 1.0 A 1.0 A Break rating 1.0 A 1.0 A Continous load 0.6 A 0.6 A
Maximum load 30 W 50 VA 20 W 20 VA
Note: None of the limit values for voltage,
current and capacity are to be exceeded!
We recommend the following load values to ensure safe, continuous operation:
Table 2: Recommended contact ratings with different nominal voltages and instrument versions
250 V 250 V
Voltage Magnetic snap-action contact model 821
(DIN IEC 38) Gas filled gauges Liquid filled gauges DC / AC
ohmic load inductive ohmic load inductive
load load
DC AC cos ϕ >0.7 DC AC cos ϕ >0.7
VmAmAmAmAmAmA
230 100 120 65 65 90 40 110 200 240 130 130 180 85 48 300 450 200 190 330 130 24 400 600 250 250 450 150
The switching current must not be less than 20 mA with low voltages for switching reliability reasons.
For higher loads, and instruments with liquid-filled cases, we recommend the use of a separate relay, WIKA Models 905.1X.
11. Overcurrent protection devices
No overcurrent protection devices are installed in the instruments. Should overcurrent protection devices be required we recommend the following values in
12. Repairs / Complaints
Repairs are to be carried out by the manufacturer only. The instruments must not be opened, as this would result in indication and switching point errors.
accordance with EN 60 947-5-1.
In the case of complaints the manufacturing and Voltage 24 V: 2 A Voltage 250 V: 1 A
product identification numbers have to be
stated. The manufacturing number is indicated
on the dial, the product identification number on Data refers to miniature fuses M and a maximum short circuit current 100 A.
the type plate. When measuring, the
atmospheric pressure, the temperature during
measurement and the data of the reference
standard (model, class) always have to be
indicated.
The density monitors have to be exposed to a
specific temperature long enough (at least 2
hours) to ensure temperature equalisation.
WIKA Alexander Wiegand GmbH & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg Germany Phone (+49) 93 72/132-0 Fax (+49) 93 72/132-406 E-Mail SF6@wika.de
info@wika.de
www.wika.de
Technical alteration rights reserved.
9078061 01/2003 GB/D/F
Loading...