WIKA PSD-30 Data sheet

Electronic pressure switch with display Model PSD-30, standard version
Model PSD-31, with ush diaphragm
Applications
Machine tools
Hydraulics and pneumatics
Pumps and compressors
Machine building
Special features
Electronic pressure measurement
WIKA data sheet PE 81.67
nAvailable with single or dual NPN or PNP solid state
switches
nHigh visibility, rugged 14-segment red LED display
electronically rotates 180° for top-down installation
nIndependent rotation between the M12x1 electrical
connection and the display
nUser-friendly, intuitive 3-key operation nVersions with 4-20 mA or 0-10V analog output available nProgramming menu meets VDMA Standards for user
friendly navigation
Description
Award-winning in design and functionality
The successful design and the excellent functionality of the
WIKA switch family were already conrmed by winning the
“iF product design award 2009” for the PSD-30 pressure switch.
The robust 14 segment LED display has been designed using 0.35in (9 mm) high characters and with a slight incline in order to make reading the pressure as easy as possible from a distance.
The 3-key operation makes simple, intuitive menu navigation possible, with no need for additional assistance. The menu navigation conforms to the latest VDMA standard.
The VDMA standard for uid sensors (24574-1, part 1 -
pressure switches) has the aim of simplifying the use of pressure switches by standardising menu navigation and display.
The control keys have been designed as large as possible and are arranged ergonomically to ensure fast and easy adjustments. Operation without any additional assistance is made easier through the tactile feedback.
Electronic pressure switch, model PSD-30
Customised installation
The installation of the model PSD-30 and PSD-31 can be
exibly adapted to the individual mounting situation. Due to
the almost unlimited rotation of the display and case by more than 300°, the display can be adjusted independently of the electrical connection. The display can thus always be aligned to face the operator, and the M12 x 1 connection positioned to suit the desired cable routing.
High quality
During development of the WIKA switch family a high value was placed on a robust design and the selection of appropri­ate materials suited for machine-building applications. For this reason the case and the threaded connection of the electrical connector are made from stainless steel. Overwinding or
tearing o the connector is therefore virtually impossible.
IO-Link
With the optional output signal in accordance with the IO-Link communication standard, the PSD-30 and PSD-31 allow a fast integration into modern automation systems. IO-Link
oers an even faster installation, parameterisation and higher
functionality of the model PSD-30 and PSD-31.
Page 1 of 8WIKA data sheet PE 81.67 ∙ 02/2016
Data sheets showing similar products:
Electronic temperature switch with display; model TSD-30; see data sheet TE 67.03
Electronic level switch with display; model LSD-30; see data sheet LM 40.01
Measuring ranges
Gauge pressure
bar
psi
1)
0 ... 1
0 ... 40 0 ... 60 0 ... 100 0 ... 160 0 ... 250 0 ... 400 0 ... 600
1)
0 ... 15
0 ... 500 0 ... 1,000 0 ... 1,500 0 ... 2,000 0 ... 3,000 0 ... 5,000 0 ... 8,000
Absolute pressure
bar 0 ... 1
psi 0 ... 15
1)
1)
Vacuum and +/- measuring range
bar -1 ... 0
psi -14.5 ... 0
1) Not available for PSD-31.
1)
1)
Overpressure limit
2 times
1.7 times for the relative pressure measuring ranges 160 psi,
1,000 psi and 1,500 psi
1)
0 ... 1.6
1)
0 ... 25
1)
0 ... 1.6
1)
0 ... 25
-1 ... +0.6
-14.5 ... +15 1)-14.5 ... +30 -14.5 ... +50 -14.5 ... +100 -14.5 ... +160 -14.5 ... +200 -14.5 ... +300
0 ... 2.5 0 ... 4 0 ... 6 0 ... 10 0 ... 16 0 ... 25
1)
0 ... 30
0 ... 2.5 0 ... 4 0 ... 6 0 ... 10 0 ... 16 0 ... 25
1)
0 ... 30
1)
-1 ... +1.5 -1 ... +3 -1 ... +5 -1 ... +9 -1 ... +15 -1 ... +24
0 ... 50 0 ... 100 0 ... 160 0 ... 200 0 ... 300
0 ... 50 0 ... 100 0 ... 160 0 ... 200 0 ... 300
Display
14-segment LED, red, 4-digit, 9 mm (0.35 inch) character size Display can be turned electronically through 180° Update (adjustable): 100, 200, 500 or 1,000 ms
Output signals
Switching output Analogue signal
SP1 SP2
PNP - 4 ... 20 mA (3-wire) PNP - DC 0 ... 10 V (3-wire) PNP PNP ­PNP PNP 4 ... 20 mA (3-wire) PNP PNP DC 0 ... 10 V (3-wire)
Optionally also available with an NPN instead of a PNP switching output
IO-Link, revision 1.1 (option)
IO-Link is optionally available for all output signals. With the IO-Link option, switching output SP1 is always PNP
Zero oset adjustment
max. 3 % of span
Switching thresholds
Switch point 1 and switch point 2 are individually adjustable
Switching voltage
Power supply - 1 V
Switching current
without IO-Link: max. 250 mA
with IO-Link: SP1 max. 100 mA
SP2 max. 250 mA
Settling time
Analog signal: 3 ms Switching output: ≤ 10 ms (20 ms with IO-Link)
Load
Analog signal 4 ... 20 mA: ≤ 0.5 kΩ Analog signal DC 0 ... 10 V: > 10 kΩ
Service life
100 million switching cycles
Switching functions
Normally open, normally closed, window, hysteresis Freely adjustable
Page 2 of 8 WIKA data sheet PE 81.67 ∙ 02/2016
Voltage supply
Operating conditions
Power supply
DC 15 ... 35 V
Current consumption
Switching outputs with
Analog signal 4 ... 20 mA: 70 mA
Analog signal DC 0 ... 10 V: 45 mA
without analog signal: 45 mA
IO-Link option causes a deviating current consumption
Total current consumption
without IO-Link: max. 600 mA including switching current
with IO-Link: max. 450 mA including switching current
Accuracy specications
Accuracy, analog signal
≤ ±1.0 % of span
Including non-linearity, hysteresis, zero oset and end value
deviation (corresponds to measured error per IEC 61298-2). Calibrated in vertical mounting position with process connec­tion facing downwards.
Non-linearity: ≤ ±0.5 % of span (BFSL, IEC 61298-2) Long-term drift: ≤ ±0.2 % of span (IEC 61298-2)
Permissible temperature ranges
Medium: -4 ... +185 °F (-20 ... +85 °C) Ambient: -4 ... +176 °F (-20 ... +80 °C) Storage: -4 ... +176 °F (-20 ... +80 °C) Nominal temperature: 32 ... 176 °F (0 ... 80 °C)
Humidity
45 ... 75 % r. h.
Vibration resistance
10 g (IEC 60068-2-6, under resonance)
Shock resistance
50 g (IEC 60068-2-27, mechanical)
Service life, mechanics
100 million load cycles (10 million load cycles for measuring
ranges > 600 bar/7,500 psi)
Ingress protection
IP 65 and IP 67
The stated ingress protection (per IEC 60529) only applies when plugged in using mating connectors that have the appropriate ingress protection.
Mounting position
as required
Accuracy, switching output
Switch point accuracy: ≤ ±1 % of span Adjustment accuracy: ≤ ±0.5 % of span
Display
≤ ±1.0 % of span ± 1 digit
Temperature error in rated temperature range
typical: ≤ ±1.0 % of span
maximum: ≤ ±2.5 % of span
Temperature coecients in rated temperature range
Mean TC zero point: ≤ ± 0.2 % of span/10 K (typical) Mean TC span: ≤ ± 0.1 % of span/10 K (typical)
Reference conditions
Temperature: 59 ... 77 °F (15 ... 25 °C) Atmospheric pressure: 13.78 ... 15.23 psi (950 ... 1,050 mbar) Humidity: 45 ... 75 % r. h. Nominal position: Process connection lower mount (LM) Power supply: DC 24 V Load: see output signals
Page 3 of 8WIKA data sheet PE 81.67 ∙ 02/2016
Materials
Wetted parts
Process connection: Stainless steel 316L Pressure sensor: < 150 psi (9.8 bar): Stainless steel 316L
≥ 150 psi (9.8 bar): Stainless steel 13-8 PH
Non-wetted parts
Case: Stainless steel 304 Keyboard: TPE-E Display window: PC Display head: PC+ABS-Blend
Options for specic media
Medium Option
Oil and grease free Residual hydrocarbon: < 1,000 mg/m Oxygen, oil and grease free
Residual hydrocarbon: < 200 mg/m
Packaging: Protection cap on the process connection
Maximum permissible temperature -4 ... +140 °F (-20 ... +60 °C)
Only available for PSD-30
Available measuring ranges: 0 ... 145 psi to 0 ... 5,800 psi gauge (- 0 ... 10 to 0 ... 400 bar gauge)
-14.5 ... 130 to -14.5 ... 350 psi compound (- -1 ... 9 to -1 ... 24 bar)
Factory supplied without sealing
2
2
Process connections
Available connections, model PSD-30
Standard Thread
DIN 3852-E G ¼ A
G ½ A
EN 837 G ¼ B
G ¼ female
G ½ B
ANSI/ASME B1.20.1 ¼ NPT
½ NPT ISO 7 R ¼ KS PT ¼
- G ¼ female (Ermeto compatible)
Other connections on request.
Available connections, model PSD-31
Standard Thread
- G ½ B with ush diaphragm
Sealings
Process connection per DIN 3852-E
Standard NBR
Option 1 without Option 2 FPM/FKM
Process connection per EN 837
Standard without
Option 1 Copper Option 2 Stainless steel
1) Process connections per EN 837 with female threads do not include any seal.
1)
Process connection G ½ B ush
Standard NBR
Option FPM/FKM
Page 4 of 8 WIKA data sheet PE 81.67 ∙ 02/2016
Electrical connections
4
3
1
2
CE conformity
Connections
Circular connector M12 x 1 (4-pin)
Circular connector M12 x 1 (5-pin)
1) Only for version with two switching outputs and additional analogue signal
1)
Electrical safety
Short-circuit resistance: S Reverse polarity protection: U
/ SP1 / SP2 vs. U
+
vs. U
-
+
Insulation voltage: DC 500 V Overvoltage protection: DC 40 V
Connection diagram
Circular connector M12 x 1 (4-pin)
U
+
U
-
S
+
SP1/C 4
SP2 2
1
3
2
Circular connector M12 x 1 (5-pin)
U
+
U
-
S
+
SP1/C 4
SP2 2
1
3
5
Pressure equipment directive
97/23/EC
EMC directive
2004/108/EC, EN 61326 emission (group 1, class B) and
interference immunity (industrial application)
-
Manufacturer's declaration
RoHS conformity
2011/65/EU
Approvals
cULus, safety (e.g. electr. safety, overpressure, ...), USA, Canada
EAC, import certicate, customs union Russia/Belarus/
Kazakhstan
CRN, safety (e.g. electr. safety, overpressure, ...), Canada
Approvals and certicates, see website
Legend:
Positive power supply
U
+
U
Reference potential
-
SP1 Switching output 1 SP2 Switching output 2 C Communication with IO-Link S
Analog output
+
Page 5 of 8WIKA data sheet PE 81.67 ∙ 02/2016
Dimensions in mm (inch)
Pressure switch with circular connector M12 x 1 (4-pin and 5-pin)
(1.38)
Weight: approx. 220 g (7.76 oz)
Process connections, model PSD-30
(1.50)
(1.16)
(1.42)(1.02)
(1.06)
(0.79) (2.83)
G L1
G ¼ A DIN 3852-E 12 (0.47) G ½ A DIN 3852-E 14 (0.55)
G L1
G ¼ B EN 837 13 (0.51) G ½ B EN 837 20 (0.79)
PSD-30
Female thread
G L1 L2 L3 D1
1)
G ¼
1) Ermeto compatible
2) Welding sockets recommended as dened counter-thread (see accessories)
20
(0.79)15(0.59)12(0.47)
∅ 25
( 0.98)
Female thread
G L1 L2 L3 D1
G ¼ EN 837
20
(0.79)13(0.51)10(0.39)
∅ 25
( 0.98)
G L1
¼ NPT 13 (0.51) ½ NPT 19 (0.75) R ¼ 13 (0.51) PT ¼ 13 (0.51)
Process connection, model PSD-31Process connections, model
Flush
G L1 L2 L3 D1
2)
G ½ B
23 (0.91)
20.5 (0.81)10(0.39)
∅ 18
( 0.71)
Page 6 of 8 WIKA data sheet PE 81.67 ∙ 02/2016
Accessories and spare parts
Welding socket
Description Order no.
G ½ B female, outer diameter 50 mm (2 in), material 1.4571 1192299
Sealings
Description Order no.
NBR prole sealing G ¼ A DIN 3852-E 1537857
FPM/FKM prole sealing G ¼ A DIN 3852-E 1576534
NBR prole sealing G ½ A DIN 3852-E 1039067
FPM/FKM prole sealing G ½ A DIN 3852-E 1039075
Copper G ¼ B EN 837 11250810
Stainless steel G ¼ B EN 837 11250844
Copper G ½ B EN 837 11250861
Stainless steel G ½ B EN 837 11251042
Connectors with moulded cable
Description Temperature range Cable diameter Order no.
Straight version, cut to length, 4-pin, 2 m (6.6 ft)
PUR cable, UL listed, IP 67
Straight version, cut to length, 4-pin, 5 m (16.4 ft)
PUR cable, UL listed, IP 67
Straight version, cut to length, 4-pin, 10 m (32.8 ft)
PUR cable, UL listed, IP 67
Straight version, cut to length, 5-pin, 2 m (6.6 ft)
PUR cable, UL listed, IP 67
Straight version, cut to length, 5-pin, 5 m (16.4 ft)
PUR cable, UL listed, IP 67
Straight version, cut to length, 5-pin, 10 m (32.8 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 4-pin, 2 m (6.6 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 4-pin, 5 m (16.4 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 4-pin, 10 m (32.8 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 5-pin, 2 m (6.6 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 5-pin, 5 m (16.4 ft)
PUR cable, UL listed, IP 67
Angled version, cut to length, 5-pin, 10 m (32.8 ft)
PUR cable, UL listed, IP 67
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
-20 ... +80 °C
(-4 ... 176 °F)
4.5 mm (0.18 in)
4.5 mm (0.18 in)
4.5 mm (0.18 in)
5.5 mm (0.22 in)
5.5 mm (0.22 in)
5.5 mm (0.22 in)
4.5 mm (0.18 in)
4.5 mm (0.18 in)
4.5 mm (0.18 in)
5.5 mm (0.22 in)
5.5 mm (0.22 in)
5.5 mm (0.22 in)
14086880
14086883
14086884
14086886
14086887
14086888
14086889
14086891
14086892
14086893
14086894
14086896
Cooling element for screwing G ½ female / G ½ male
(for instruments with process connection G ½ B)
Description Order no.
Max. medium temperature 150 °C (302 °F) at an ambient temperature of max. 30 °C (86 °F) Max. operating pressure 250 bar (3,626 psi)
Max. medium temperature 200 °C (392 °F) at an ambient temperature of max. 30 °C (86 °F) Max. operating pressure 250 bar (3,626 psi)
14055439
14055438
Page 7 of 8WIKA data sheet PE 81.67 ∙ 02/2016
Instrument mounting bracket
Description Order no.
Instrument mounting bracket for PSD-30, aluminium, wall mounting 11467887
Ordering information
Model / Measuring range / Output signal / Process connection / Accessories and spare parts
© 2011 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specications given in this document represent the state of engineering at the time of publishing. We reserve the right to make modications to the specications and materials.
Page 8 of 8 WIKA data sheet PE 81.67 ∙ 02/2016
WIKA Instrument Corporation
1000 Wiegand Boulevard Lawrenceville, GA 30043-5868 Tel: 888-WIKA-USA • 770-513-8200 Fax: 770-338-5118 E-Mail: info@wika.com www.wika.com
04/2015 EN
Loading...