WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
Contents
Contents
1.General information4
2.Safety5
3.Specications8
4.Design and function9
5.Transport, packaging and storage10
6.Commissioning, operation11
7.Maintenance and cleaning12
8.Faults13
9.Warranty14
GB
10. Dismounting, return and disposal14
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.023
1. General information
1. General information
■
GB
The mini limit switch described in the operating instructions has been manufactured
using state-of-the-art technology.
All components are subject to stringent quality and environmental criteria during
production. Our management systems are certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling the mini limit
switch. Working safely requires that all safety instructions and work instructions are
observed.
■
Observe the relevant local accident prevention regulations and general safety
regulations for the mini limit switch's range of use.
■
The operating instructions are part of the instrument and must be kept in the immediate
vicinity of the mini limit switch and readily accessible to skilled personnel at any time.
■
Skilled personnel must have carefully read and understood the operating instructions,
prior to beginning any work.
■
The manufacturer's liability is void in the case of any damage caused by using the
product contrary to its intended use, non-compliance with these operating instructions,
assignment of insuciently qualied skilled personnel or unauthorised modications to
the mini limit switch.
■
The general terms and conditions contained in the sales documentation, shall apply.
... indicates a potentially dangerous situation, which can result in serious
injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation, which can result in light injuries
or damage to equipment or the environment, if not avoided.
4WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
1. General information / 2. Safety
Information
... points out useful tips, recommendations and information for ecient and
trouble-free operation.
DANGER!
...identies hazards caused by electric power. Should the safety instructions
not be observed, there is a risk of serious or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result in burns, caused
by hot surfaces or liquids, if not avoided.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate
instrument has been selected in terms of measuring range, design and
specic measuring conditions.
Non-observance can result in serious injury and/or damage to equipment.
GB
Further important safety instructions can be found in the individual chapters of
these operating instructions.
2.1 Intended use
This instrument is designed to detect limit levels of liquids. The values given in chapter
"3. Specications" must not be exceeded. The mini limit switch is not suitable for milky,
turbid, outgassing, sticky and crystallising media.
The mini limit switch has been designed and built solely for the intended use described
here, and may only be used accordingly.
The technical specications contained in these operating instructions must be observed.
Improper handling or operation of the mini limit switch outside of its technical specications
requires the instrument to be shut down immediately and inspected by an authorised WIKA
service engineer.
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.025
2. Safety
The manufacturer shall not be liable for claims of any type based on operation contrary to
the intended use.
GB
2.2 Personnel qualication
WARNING!
Risk of injury should qualication be insucient!
Improper handling can result in considerable injury and damage to equipment.
■
The activities described in these operating instructions may only be carried
out by skilled personnel who have the qualications described below.
■
Keep unqualied personnel away from hazardous areas.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training,
knowledge of measurement and control technology and on their experience and
knowledge of country-specic regulations, current standards and directives, are capable of
carrying out the work described and independently recognising potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive
media.
2.3 Special hazards
WARNING!
For hazardous media such as oxygen, acetylene, ammable or toxic gases or
liquids, and refrigeration plants, compressors, etc., in addition to all standard regulations, the appropriate existing codes or regulations must also be
followed.
WARNING!
To ensure safe working on the instrument, the operating company must
ensure
■
that suitable rst-aid equipment is available and aid is provided whenever
required.
■
that the operating personnel are regularly instructed in all topics regarding
work safety, rst aid and environmental protection and knows the operating
instructions and, in particular, the safety instructions contained therein.
6WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
2. Safety
DANGER!
Danger of death caused by electric current
Upon contact with live parts, there is a direct danger of death.
■
Electrical instruments may only be installed and mounted by skilled electrical personnel.
■
Operation using a defective power supply unit (e.g. short circuit from the
mains voltage to the output voltage) may result in life-threatening voltages
on the instrument!
WARNING!
Residual media in dismounted instruments may result in a risk to people, the
environment and the system. Take sucient precautionary measures.
Do not use this instrument in safety or Emergency Stop devices. Incorrect use
of the instrument can result in injury.
Should a failure occur, aggressive media with extremely high temperature and
under high pressure or vacuum may be present at the instrument.
2.4 Labelling / safety marks
GB
Product label
Model
Electrical connection diagram
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.027
3. Specications
3. Specications
General Data
GB
Measuring accuracy±0.5 mm
Ambient lightmax. 10,000 Lux (immersed)
Mounting positionany
Weight0.15 kg
Design Data
Medium temperature-30 ... +140 °C
Ambient temperature-25 ... +70 °C
Working pressure0 ... 5 MPa (0 ... 50 bar)
Measuring lengthsee drawing on page 9
Process connectionG ½ A, M16 x 1.5, ½ NPT etc. see drawing on page 9
Supply voltageDC 24 V -25 ... +30 %
Supply current max.40 mA
Power consumption1 W
Output
■
Voltage
■
Current
■
other
Switching current
(Tu = 70 °C)
Electrical connection
Ingress protection
■
With plug
■
With cable
For further specications see WIKA data sheet LM 31.01 and order documentation.
8WIKA operating instructions mini limit switch, model LSO.02
DC 24 V
0.5 A at Tu 70 °C
short-circuit protection, reverse voltage protection,
current, voltage and power limitation
0.5 A
■
PVC cable 3 x 0.14 mm²
■
Plug 4-pole series 713, M12
IP 65 per EN 60 529
IP 66 per EN 60 529
13334591.02 10/2010 GB/D/F/E
4. Design and function
4. Design and function
4.1 Description
Principle of operation
This instrument is designed to detect limit levels of
liquids. For this purpose the sensor is equipped with a
V-shaped glass-tip. The model is also ideally suited for
level control, particularly in applications requiring high
precision. The measurement principle is independent of
the colour, refractive index, density, conductance and
dielectric constant of the liquid.
Integrated electronics include limit sensing and selfcalibration. The output is an open-collector pnp-transistor.
Gas
Liquid
4.2 Instrument design
The sensor is a one-piece device consisting of a mechanical connection which depends
on the type of sensor, and integrated electronics built into a stainless steel housing. The
measuring length, ML, to the sealing face is always 24 mm.
Dimensions in mm
Model LSO.02 with cable connection
green
LED
Plug connection
GB
cable
length
3000
Selectable process connections
Process connection
Ø A
Spanner width
B
Sealing face
Ø C
M16 x 1.5SW24Ø 21
G ½ ASW30Ø 26
½ NPTSW24-
4.3 Scope of delivery
Cross-check scope of delivery with delivery note.
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.029
5. Transport, packaging, storage
5. Transport, packaging and storage
5.1 Transport
GB
Check instrument for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in
installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage:
■
Storage temperature: -25 ... +70 °C
■
Humidity: 35 ... 85 % relative humidity (no condensation)
Avoidance of exposure to the following factors:
■
Proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
Store the instrument in its original packaging in a location that fullls the conditions listed
above. If the original packaging is not available, package and store the instrument as
described below:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument, along with shock-absorbent material, in the packaging.
3. If stored for a prolonged period of time (more than 30 days), place a bag, containing a
desiccant, inside the packaging.
WARNING!
Before storing the instrument (following operation), remove any residual
media. This is of particular importance if the medium is hazardous to health,
e.g. caustic, toxic, carcinogenic, radioactive, etc.
10WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
6. Commissioning, operation
6. Commissioning, operation
When unpacking the mini limit switch check all items for external damage. A functional
test may be carried out prior to the installation. To do this, the device should be temporarily
connected and the sensor-tip immersed in and then withdrawn from a glass of water.
WARNING!
The electrical connection must only be carried out by qualied skilled
personnel. Observe the relevant VDE regulations.
6.1. Installation instructions
horizontal installation
tank or pipe wall
rubber or metal seal
welded adapter
vertical installation
ATTENTION!
In the case of
electropolished pipes
min. distance can be
much larger than 10 mm.
GB
inclined installation
13334591.02 10/2010 GB/D/F/E
high-temperature medium
long adapter
Insulation
WIKA operating instructions mini limit switch, model LSO.0211
6. Commissioning, operation / 7. Maintenance and cleaning
6.2 Mechanical installation of the Mini Limit Switch
Mount the mini limit switch, pressure tight, into the process connection. The distance
between sensor-tip and opposite surface of the pipe should be greater than 10 mm. If the
GB
pipe is electropolished, the distance should be increased accordingly.
6.3. Electrical connection of the mini limit switch
The sensor must be connected as shown in the connection diagram.
As a rule, the Mini Limit Switch is maintenance-free.
If the plant is subject to heavy contamination or scale, it is advisable to set up periodic
maintenance. This depends on the optical condition of the glass tip and the switch
operation.
Repairs must only be carried out by the manufacturer.
12WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
7. Maintenance, cleaning / 8. Faults
7.2 Cleaning
CAUTION!
■
Before cleaning, correctly disconnect the instrument from the pressure
supply, switch it o and disconnect it from the mains.
■
Clean the instrument with a moist cloth.
■
Electrical connections must not come into contact with moisture.
■
Wash or clean the dismounted instrument before returning it, in order to
protect sta and the environment from exposure to residual media.
■
Residual media in dismounted instruments can result in a risk to persons,
the environment and equipment. Take sucient precautionary measures.
For information on returning the instrument see chapter "10.2 Return".
8. Faults
FaultsPossible causesMeasures
No functionNo power supplyMeasure power supply, check
connection to cable or plug
No function in spite of
liquid level change
Sensor works to reverse
logic
Contamination or scale on
the glass-tip
SA instead of SE or SE
instead of SA specied
Clean glass-tip (set up periodic
maintenance)
Change sensor
GB
CAUTION!
If faults cannot be eliminated by means of the measures listed above, the
instrument must be shut down immediately, and it must be ensured that
pressure and/or signal are no longer present, and it must be prevented from
being inadvertently put back into service.
In this case, contact the manufacturer.
If a return is needed, please follow the instructions given in chapter
"10.2 Return".
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.0213
9. Warranty / 10. Dismounting, return and disposal
9. Warranty
The warranty period is 24 months.
GB
Under the condition that this Mini Limit Switch has been handled and operated in
accordance with these operating instructions. For consumable and spare parts the warranty
is restricted to faults in material or construction.
10. Dismounting, return and disposal
WARNING!
Residual media in dismounted instruments can result in a risk to persons, the
environment and equipment. Take sucient precautionary measures.
10.1 Dismounting
WARNING!
Risk of burns!
Let the instrument cool down suciently before dismounting it!
When dismounting it, there is a risk that dangerously hot pressure media may
escape.
Only disconnect the mini limit switch once the system has been depressurised!
10.2 Return
WARNING!
Absolutely observe when shipping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous
substances (acids, bases, solutions, etc.).
When returning the instrument, use the original packaging or a suitable transport package.
To avoid damage:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument, along with the shock-absorbent material, in the packaging.
Place shock-absorbent material evenly on all sides of the shipping box.
3. If possible, place a bag, containing a desiccant, inside the packaging.
4. Label the shipment as transport of a highly sensitive measuring instrument.
14WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
10. Dismounting, return and disposal
Enclose the completed return form with the instrument.
The return form is available on the internet:
www.wika.de / Service / Return
10.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally
compatible way and in accordance with the country-specic waste disposal regulations.
GB
13334591.02 10/2010 GB/D/F/E
WIKA operating instructions mini limit switch, model LSO.0215
GB
16WIKA operating instructions mini limit switch, model LSO.02
13334591.02 10/2010 GB/D/F/E
Inhalt
Inhalt
1.Allgemeines18
2.Sicherheit19
3.Technische Daten22
4.Aufbau und Funktion23
5.Transport, Verpackung und Lagerung24
6.Inbetriebnahme, Betrieb25
7.Wartung und Reinigung26
8.Störungen27
9.Garantie28
D
10. Demontage, Rücksendung und Entsorgung28
13334591.02 10/2010 GB/D/F/E
WIKA Betriebsanleitung Kleingrenzschalter, Typ LSO.0217
1. Allgemeines
1. Allgemeines
■
Der in der Betriebsanleitung beschriebene Kleingrenzschalter wird nach den neuesten
Erkenntnissen gefertigt.
Alle Komponenten unterliegen während der Fertigung strengen Qualitäts- und Umweltkriterien. Unsere Managementsysteme sind nach ISO 9001 und ISO 14001 zertiziert.
D
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Kleingrenzschalter. Voraussetzung für sicheres Arbeiten ist die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Kleingrenzschalters geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen Sicherheitsbestimmungen einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Kleingrenzschalters für das Fachpersonal jederzeit zugänglich aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig
durchgelesen und verstanden haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung, Einsatz ungenügend qualizierten
Fachpersonals sowie eigenmächtiger Veränderung am Kleingrenzschalter.
■
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
… weist auf eine möglicherweise gefährliche Situation hin, die zum Tod oder
zu schweren Verletzungen führen kann, wenn sie nicht gemieden wird.
VORSICHT!
… weist auf eine möglicherweise gefährliche Situation hin, die zu geringfügigen oder leichten Verletzungen bzw. Sach- und Umweltschäden führen
kann, wenn sie nicht gemieden wird.
WIKA Betriebsanleitung Kleingrenzschalter, Typ LSO.0218
13334591.02 10/2010 GB/D/F/E