WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
These room thermostats are especially designed for
controlling heating equipment operating on line voltage
with heavy electrical loads. They are suitable for operation of unit heaters, boilers, furnaces, electric heaters,
etc., or any similar application requiring a heavy duty room
thermostat.
THESE CONTROLS MUST BE INSTALLED BY A
QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the WhiteRodgers warranty.
The proper location of a heavy duty room thermostat is
very important to assure good performance. The following
general rules will help in determining the proper location:
1. Make sure that it is in a place where air circulates
around it freely. This is important.
2. Never install it on or near an outside wall.
3. Keep it away from windows or doors.
4. Don’t locate it too close to a strong light or any other
false source of heat such as direct sunlight, steam
lines, etc.
5. Mount it on a post or a partitioning wall, but make sure
that there are no pipes or duct work in that wall or
directly behind it.
6. If the electrical conduit leads into a cooler or a warmer
room, plug up the space around the wires in the conduit
with rock wool.
TYPE 152, 176, 196
ROOM THERMOSTATS
Heating Service, External Dial
INSTALLATION INSTRUCTIONS
DESCRIPTION
W
H
I
T
E
-
R
S
O
R
D
E
G
90
70
80
50
60
40
PRECAUTIONS
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
WARNING
Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.
INSTALLATION
CONCRETE
PLASTER
JUNCTION BOX
THERMOSTAT
CONDUIT
INSIDE WALL
CONDUIT
ALONG WALL
WALL INSTALLATION
The mounting plate for this thermostat has two
5
/16”apart for attaching the control on a
holes 3
standard switch box.
Figure 1
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
PART NO. 37-1116B
Replaces 37-1116-1 & 37-9113
9550
INSTALLATION
If the thermostat is used with unit heaters, the following
suggestions may help. (See Fig. 2).
1. Position “A” is good if it is sufficiently close to the unit
heater so that the return air to the heater flows over the
thermostat.
2. Position “B” is good if it is not necessary to make
frequent adjustments of the dial setting.
3. Position “C” is all right if it is sufficiently far from the
heater that air flowing over the thermostat is not much
above the average room temperature.
4. In general, position “D” is not advisable because the
post may prevent air from circulating over the thermostat.
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
CEILING
POST PARTITION
UNIT
B
D
C
RETURN AIR
FLOOR
WALL OR POST
DIRECTLY BEHIND
UNIT
A
Figure 2
SUPPLY
TYPE
11B09
Diagram showing a single room thermostat controlling
several steam or hot water unit heaters. Any number of
unit heaters can be operated from one thermostat provided that the sum of the motor locked rotor currents or
the sum of the full load currents does not exceed the
electrical rating of the thermostat. The Type 11B09
Reverse-acting Surface Hot Water Control is used to
prevent operation of the fans when the steam is off or
when the water temperature is too low for proper heating.
The diagram at the right shows a heavy duty line voltage
room thermostat controlling an electric heater.
TYPE
11B09
ROOM
THERMOSTAT
ROOM
THERMOSTAT
TYPE
11B09
RETURN
TO LINE SWITCH
AND POWER SUPPLY
TO LINE SWITCH
AND POWER SUPPLY
ELECTRIC HEATER
2