White Rodgers 176, 152, 196 User Manual

CAUTION
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
These room thermostats are especially designed for controlling heating equipment operating on line voltage with heavy electrical loads. They are suitable for opera­tion of unit heaters, boilers, furnaces, electric heaters, etc., or any similar application requiring a heavy duty room thermostat.
THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED INSTALLER.
Do not exceed the specification ratings. All wiring must conform to local and national electrical
codes and ordinances. This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to calibrate this control will void the White­Rodgers warranty.
The proper location of a heavy duty room thermostat is very important to assure good performance. The following general rules will help in determining the proper location:
1. Make sure that it is in a place where air circulates around it freely. This is important.
2. Never install it on or near an outside wall.
3. Keep it away from windows or doors.
4. Don’t locate it too close to a strong light or any other false source of heat such as direct sunlight, steam lines, etc.
5. Mount it on a post or a partitioning wall, but make sure that there are no pipes or duct work in that wall or directly behind it.
6. If the electrical conduit leads into a cooler or a warmer room, plug up the space around the wires in the conduit with rock wool.
TYPE 152, 176, 196
ROOM THERMOSTATS
Heating Service, External Dial
INSTALLATION INSTRUCTIONS
DESCRIPTION
W
H
I
T
E
-
R
S
O
R
D
E
G
90
70
80
50
60
40
PRECAUTIONS
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
INSTALLATION
CONCRETE
PLASTER
JUNCTION BOX
THERMOSTAT
CONDUIT
INSIDE WALL
CONDUIT ALONG WALL
WALL INSTALLATION
The mounting plate for this thermostat has two
5
/16”apart for attaching the control on a
holes 3 standard switch box.
Figure 1
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
PART NO. 37-1116B
Replaces 37-1116-1 & 37-9113
9550
INSTALLATION
If the thermostat is used with unit heaters, the following suggestions may help. (See Fig. 2).
1. Position “A” is good if it is sufficiently close to the unit heater so that the return air to the heater flows over the thermostat.
2. Position “B” is good if it is not necessary to make frequent adjustments of the dial setting.
3. Position “C” is all right if it is sufficiently far from the heater that air flowing over the thermostat is not much above the average room temperature.
4. In general, position “D” is not advisable because the post may prevent air from circulating over the thermo­stat.
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
CEILING
POST PARTITION
UNIT
B
D
C
RETURN AIR
FLOOR
WALL OR POST DIRECTLY BEHIND UNIT
A
Figure 2
SUPPLY
TYPE 11B09
Diagram showing a single room thermostat controlling several steam or hot water unit heaters. Any number of unit heaters can be operated from one thermostat pro­vided that the sum of the motor locked rotor currents or the sum of the full load currents does not exceed the electrical rating of the thermostat. The Type 11B09 Reverse-acting Surface Hot Water Control is used to prevent operation of the fans when the steam is off or when the water temperature is too low for proper heating.
The diagram at the right shows a heavy duty line voltage room thermostat controlling an electric heater.
TYPE 11B09
ROOM THERMOSTAT
ROOM THERMOSTAT
TYPE 11B09
RETURN
TO LINE SWITCH AND POWER SUPPLY
TO LINE SWITCH AND POWER SUPPLY
ELECTRIC HEATER
2