White Rodgers 151 User Manual

CAUTION
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
These room thermostats have been designed for control­ling cooling equipment operating on line voltage with heavy electrical loads. They are suitable for operation of unit coolers, room coolers, etc., or any similar refrigera­tion application requiring a heavy duty room thermostat.
Models are available with various ranges for meeting the needs of almost any application.
THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED INSTALLER.
Do not exceed the specification ratings. All wiring must conform to local and national electrical
codes and ordinances. This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to calibrate this control will void the White­Rodgers warranty.
The proper location of a heavy duty room thermostat is very important to assure good performance. The following general rules will help in determining the proper location:
1. Make sure that it is in a place where air circulates around it freely. This is important.
2. Never install it on or near an outside wall.
3. Keep it away from windows or doors.
4. Don’t locate it too close to a strong light or any other false source of heat such as direct sunlight, steam lines, etc.
5. Mount it on a post or a partitioning wall, but make sure that there are no pipes or duct work in that wall or directly behind it.
6. If the electrical conduit leads into a cooler or a warmer room, plug up the space around the wires in the conduit with rock wool.
TYPE 151
ROOM THERMOSTAT
Cooling Service, External Dial
INSTALLATION INSTRUCTIONS
DESCRIPTION
W
H
I
T
E
-
R
S
O
R
D
E
G
90
70
80
50
60
40
PRECAUTIONS
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
WARNING
Do not use on circuits exceeding specified volt­ages. Higher voltages will damage control and could cause shock or fire hazard.
INSTALLATION
CONCRETE
PLASTER
JUNCTION BOX
THERMOSTAT
CONDUIT
INSIDE WALL
CONDUIT ALONG WALL
WALL INSTALLATION
The mounting plate for this thermostat has two
5
holes 3
/16”apart for attaching the control on a
standard switch box.
Figure 1
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
PART NO. 37-1118B
Replaces 37-1118
9548
INSTALLATION CONT.
70
60
80
INDICATING
LINE
IMPORTANT
When control is located where ambient temperature is below freezing, choose a control location far enough away from doors and windows so that moisture will not condense on control.
If the thermostat is used with unit coolers, the following suggestions may help. (See Fig. 2).
1. Position “A” is good if it is sufficiently close to the unit cooler so that the return air to the cooler flows over the thermostat.
2. Position “B” is good if it is not necessary to make frequent adjustments of the dial setting.
3. Position “C” is all right if it is sufficiently far from the cooler that air flowing over the thermostat is not much above the average room temperature.
4. In general, position “D” is not advisable because the post may prevent air from circulating over the thermo­stat.
CEILING
POST
UNIT
B
D
C
RETURN AIR
FLOOR
Figure 2
PARTITION WALL OR POST DIRECTLY BEHIND UNIT
A
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
If the manufacturer of the cooling equipment has supplied a wiring diagram, follow the manufacturer’s recommenda­tions. The following diagrams show the general use of these controls.
TEMPERATURE
CONTROL
TO LINE SWITCH
AND POWER SUPPLY
HOT GND
Circuit showing temperature control to open and close refrigerant valve. Suction pressure control starts and stops compressor through motor starter.
HIGH SIDE
PRESSURE CONTROL
(IF USED)
MOTOR
STARTER
Circuit showing temperature control con­trolling compressor directly.
TO LINE SWITCH
AND POWER SUPPLY
HIGH SIDE
PRESSURE
CONTROL
SUCTION
PRESSURE
CONTROL
TEMPERATURE
CONTROL
SOLENOID
REFRIGERANT
VALVE
SETTING THE DIAL
To set the dial, simply move it so that the indicating line on the case points to the temperature at which the contacts are to open as the temperature drops.
2
Loading...
+ 2 hidden pages