FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
These water valves provide a low cost system of zoned temperature control wherever hot water is the heating medium. In
new construction, the heating piping system can be laid out to
produce any number of independent temperature controlled
zones by use of these valves.
In existing buildings, a variety of zone heating combinations can
be obtained, depending on the particular -piping lay-outs. Each
zone requires one water valve and one thermostat, but onlyone circulator is required for the entire system. New construction properly piped, will not require flow control valves,
since the water valve itself performs this function.
Existing construction, where flow control valves have been
installed, will operate quite satisfactorily without removing the
existing flow control valves.
TYPE 1361
HYDRONIC ZONE VALVES
(2 WIRE)
INST ALLA TION INSTRUCTIONS
DESCRIPTION
If in “Closed” position, valve may be opened by turning dial
clockwise with your thumb until word “Open” appears. When
power is resumed, valve will automatically return to command of
room thermostat.
This zone valve motor is intended for use with a low voltage
system; do not use this zone valve with a millivolt or line voltage
system. If in doubt about whether your wiring is millivolt, line or
low voltage, have it inspected by a qualified heating contractor
or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and
ordinances.
CAUTION
!
To prevent injuries from scalding always drain system
before unlatching valve assembly from body.
All guarantees are void if these specifications are exceeded.
Maximum water temperature: 240°F (115°C)
Maximum system pressure: 50 PSI
Differential across valve: 15 PSI
Electrical Rating:
Valve motor: .2 Amp. Max at 25 VAC
(.40 Amp.) when valve is in open position.
Auxiliary Contacts: Do not exceed 2.0 Amp. at
25 VAC (Terminals 2 and 3)
NOTE: The valve motor draws more than .2 Amp. while it is
opening. For this reason, do not use more than the
The zone valve is designed to turn in one direction, stopping
every 90° in either the open or closed position, depending on
thermostat demand. The motor position is controlled by a wafer
switch attached to the motor shaft.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, Fax (314) 577-1517
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
Do not use on circuits exceeding specified voltages.
Higher voltages will damage control and could cause
shock or fire hazard.
SPECIFICATIONS
recommended number of valves per transformer as
shown on pages 3 and 4.
Thermostat: Use two-wire thermostat with .2 Amp. anticipator
Timing: From full close to full open–Approx. 45 seconds
From full open to full close–Approx. 60 seconds
Friction loss equivalents:
3/4" valves – 2-1/2 ft. copper tubing
1" valves – 4 ft. copper tubing
1-1/4" valves – 7 ft. copper tubing
PRINCIPLE OF OPERATION
The contact arrangement of the switch is constructed so that
when the shaft of the motor revolves 90° a new set of stationary
and moving contacts makes, while the old set breaks. Fig.1.
The schematic shows the valve in the closed position. As the
PART NO. 37-5422B
Replaces 37-5422A
9812
PRINCIPLE OF OPERATION (CONT.)
thermostat calls for heat, the valve motor is energized by a
circuit made through side “A” of the motor switch to terminal “4”.
Fig. 2. (At the same time, a circuit is made through the warp
switch heater.) As the valve begins to open, side “A” of the motor
switch makes with a “holding” contact and then breaks from the
stationary contact wired to terminal “4”. The “holding” contact
provides a circuit which prevents the valve from stopping part
way through its cycle if the thermostat is changed to the satisfied
position. As the valve reaches the full open position, side “B” of
the motor switch closes, providing a low voltage auxiliary circuit
for starting the burner or circulator. At the same time side “A” of
the motor switch makes a circuit through the warp switch
contacts to terminal “2”. The valve does not continue to rotate
since the warp switch opened its contacts before the valve
reached the full open position. The warp switch heater remains
energized as long as the thermostat calls for heat.
WARP SWITCH
THERMOSTAT
HEAT
ANTICIPATOR
INTERNAL WIRING
EXTERNAL WIRING
TYPE 1E/F30
▼
SIDE “A” OF
MOTOR
SWITCH
HOLDING
CONTACT
CONTACTS
NORMALLY CLOSED
5
▼
SIDE “A”
4
WARP SWITCH HEATER
OPEN
POSITION
▼
▼
▼
MOTOR
Fig. 2
2
3
▼
▼
1
TO AUXILIARY CIRCUIT
(NOTE: IF SAME
TRANSFORMER POWERS BOTH THE AUXILIARY CIRCUIT AND THE
WATER VALVE, CONNECT AUXILIARY CIRCUIT TO TERMINALS 1
AND 3 INSTEAD OF 2
AND 3.)
OPEN POSITION
MOTOR SWITCH
SIDE “B”
SIDE “B” OF
TRANSFORMER
NOTE: INTERNAL PARTS AND
WIRING OF WATER VALVE.
STATIONARY CONTACTS
(TERMINALS 2 & COM.)
SWITCH CONTACTS)
JUMPER WIRES
(2 THRU WARP
▼
2
COMMON
▼
▼
▼
▼
▼
▼
▼
STATIONARY CONTACTS
(TERMINALS 2, 4 & COM.)
MOTOR SHAFT:
Revolves in 90° intervals
with each thermostat cycle.
▼
▼
▼
2
▼
▼
4
2
ROTATING BOARDS:
Each Board makes/breaks
1 set of contacts with each
90° revolution of motor
shaft on thermostat
demand.
(Valve is shown in the open position)
Fig. 1
When the thermostat is satisfied, the circuit through the warp
switch heater is broken, allowing the heater to cool. When the
warp switch contacts close, the valve motor is energized, and
drives the valve to the closed position. As the valve begins to
move to the closed position, side “A” of the motor switch makes
the holding circuit. Then side “B” of the motor switch breaks the
auxiliary circuit and side “A” of the motor switch makes contact
“4” then breaks the holding circuit stopping the valve (in a fully
LINE
closed position).
STATIONARY CONTACTS
(TERMINALS 2 & 3)
▼
▼
3
PIPING
The two most commonly used piping systems are
shown below. Plan 1 is popular for new installations,
while plan 2 is frequently used when converting twopipe systems.
This valve does not seal completely. A small amount of
leakage through valve is permitted. The amount depends on valve size and pressure differential across
PLAN 1
Water valves installed at the boiler
header to provide a separate supply to each zone.
Fig. 3
closed valve. Do not use if your application requires
complete seal off. Maximum leakage at rated differen-
tial is two, four or six gal. per hour for 3/4", 1" or 1-1/4"
valves, respectively.
PLAN 2
A common main supplies all
zones, with a water valve installed
on the riser to each zone.
INSTALLATION
ALL GUARANTEES ARE VOID IF THE VALVE IS NOT ASSEMBLED ACCORDING TO THESE INSTRUCTIONS.
1. Remove body assembly only from shipping carton. Valve
head and stem should be left in carton at this time for
protective purposes. Do not assemble head to body before
attaching body into line.
2. Mount the valve body in the line in any desired position
except upside down. CAUTION: Provide the necessary
clearances for turning valve head sideways when assembling it to valve body (see fig. 5). Note that terminal end of
valve head requires more clearance.
CAUTION
!
Use only silicone grease, water, or soap suds on O-ring
or Valve Body to facilitate assembly. Use of vaseline or
any petroleum grease or oil will cause O-ring to deteriorate.
2
VALVE
HEAD
BODY
STEM
Fig. 5
2" MINIMUM
CLEARANCE
▼
2-3/4" MINIMUM
CLEARANCE
▼
Clearances required for
assembling valve head to
valve body.
▼
▼
729
Fig. 4
T2
T1-V1
V2-L1
Z-L2
CAUTION
CAUTION
!
!
Be sure that bayonet lock securely latches mounting
plate to body. Failure to do so could allow valve head
to separate from body and result in scalding injuries
and/or water damage.
3. Be sure that any excess solder, flux, or other foreign matter
is thoroughly removed from the valve bore.
4. With valve body mounted in the line, remove the head
assembly from the carton, and carefully wipe stem with a soft
cloth to remove any dust or grit.
All wiring should be done according to local and national electrical codes
For best connections, use #18 Thermostat wire. #16 will also
work satisfactorily.
Make connections to screw terminals according to wiring diagram.
NOTE: To check motor operation without thermostat con-
nected, jumper 2 and 4 to open valve; remove jumper
to close valve.
If the boiler manufacturer recommends a wiring diagram, follow
his instructions. If none are available, the following diagrams
show suggested circuits for Type 1361 Water Valves in conjunc-
to prevent injuries from scalding always drain
system before unlatching valve assembly from
body.
5. The valve head may now be assembled to the valve body.
With valve head positioned as shown in figure 5, insert valve
stem into valve bore, push downward, and turn valve head
until it locks to valve body.
6. Support piping with a pipe hanger on each side of valve. The
valve is now ready to be wired.
WIRING
CAUTION
!
Do not attempt to wire two or more zone valves in
parallel to operate from a single thermostat. (If valves
are wired in parallel, the motors may run continuously,
due to feedback between the motor holding circuits.)
tion with two-wire thermostat (.2 Amp. anticipator) and other
related controls.
A 40 VA transformer will handle up to four (4) water valves. A
20 VA transformer will handle a maximum of two (2) 1361 series
valves.
DIAGRAM FOR SYSTEMS WHERE BURNER AND
CIRCULATOR OPERATION IS INDEPENDENT OF
THERMOSTAT
Fig. 6 Using Type 1361 Zone Valve
123
452
ADDITIONAL
ZONES
123
452
452
123
HOT
LINE
N
123
TRANSFORMER
452
123
DIAGRAM FOR SYSTEMS WHERE INTERNAL TRANSFORMER OF RELAY CONTROL SUPPLIES POWER
FOR ZONE VALVES
Alternate Wiring for using
750 Mv. Gas Valve
BURNER CONTROL
IGNITION
TRANS.
ORANGE
WHITE
BURNER
MOTOR
N
LINE
HOT
Fig. 7 Diagram
for Oil-fired
System using
8A03A-2
WHITE
BLACK
TYPE 668 OIL
HIGH LIMIT
F
F
T
T
BLACK
TYPE 956
FLAME DETECTOR
TYPE 8A03A-2
RELAY CONTACTS
(24V OR 750 MV)
TRANSFORMER
RELAY
CONTACTS
(LINE
VOLTAGE)
ORANGE
CIRCULATOR MOTOR
TYPE 8A03A-2
V1
V2
1
2
3
RELAY COIL
V1
V2
1
2
3
HIGH LIMIT
MUST BE N.E.C.
CLASS 1 WIRING
750 MV
GAS VALVE
TH
PG
TH PG
1
TO ZONE VALVES
2
}
3
452
123
Fig. 7a Diagram for
Gas-Fired System
3
750 MV
POWER
GENERATOR
TO ZONE
VALVES
1
2
{
3
MUST BE N.E.C.
CLASS 1 WIRING
Alternate Connections
For Type 8A02A Relay
452
123
TYPE 8A02A-1
TO 24 VOLT
GAS VALVE
452
123
1
MUST BE N.E.C.
CLASS 1 WIRING
3
YELLOW
452
123
HIGH LIMIT
HIGH LIMIT
CIRCULATOR
MUST BE N.E.C.
CLASS 1 WIRING
HOT
LINE
N
MOTOR
GAS VALVE
24 VAC
452
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.