White Rodgers 11B05 User Manual

WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
These controls have close-on-rise switch action and are designed for use on hot water heating installations. They prevent operation of the circulator or unit heater fan if the boiler water is not hot enough for proper heating.
Models are available with either horizontal or vertical well. Some of these models also have excess capillary stored within the enclosure, permitting them to be used with wells having either a standard or extended shank.
Another model, ideal for replacement purposes, has a slotted case and excess capillary stored within the enclo­sure. This control can be used with either a standard or extended shank well, on either horizontal or vertical well installations.
THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED INSTALLER.
Do not exceed the specification ratings. All wiring must conform to local and national electrical
codes and ordinances. This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to calibrate this control will void the White­Rodgers warranty.
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
11B05
HOT WATER CONTROL
Reverse Acting – Well-Immersion
Adjustable Differential
INSTALLATION INSTRUCTIONS
DESCRIPTION
PRECAUTIONS
CAUTION
Label all wires prior to disconnection when ser­vicing controls. Wiring errors can cause im­proper and dangerous operation.
Following installation or replacement, follow appliance manufacturer’s recommended instal­lation and/or service instructions to insure proper operation.
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system, at main fuse or circuit breaker box, until installation is complete.
Shut off main gas to heating system until instal­lation is complete.
Convertible controls have a Knockout Plate on back of
case (secured by Hex Nut on Horizontal models, and by Knockout Plug on Vertical models). To convert from Horizontal to Vertical:
1. Remove control cover. Then remove bottom knockout.
2. Remove Hex Nut (inside control) from Well Mounting Stem. (To loosen, hold Hex Nut inside while turning Hex Nut on back of control counterclockwise.)
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3 (905) 475-4653, FAX (905) 475-4625
Printed in U.S.A.
CONVERTIBLE CONTROLS
3. Pull Well Mounting Stem away from case and remove Knockout Plate.
4. Swing capillary down through slot into bottom knock­out.
5. Secure Knockout Plate to back of case by using Knockout Plug provided in envelope.
6. Insert Well Mounting Stem into bottom knockout and tighten Hex Nut (inside control) securely.
PART NO. 37-2070B
9546
CONVERTIBLE CONTROLS CONT.
NOTE
To convert from Vertical to Horizontal model, remove Knockout Plug and Plate. Remove Hex Nut (inside con­trol) and swing capillary upward into back knockout. Place Knockout Plate beneath Hex Nut on back of control and tighten Hex Nut (inside control). If bottom knockout is not used for wiring, insert Knockout Plug.
EXTENDING CAPILLARY
Some controls have excess stored capillary which may be extended for use with an extended shank well. Use reason­able care when straightening and forming the capillary.
INSTALLATION
If the manufacturer of the boiler recommends a control location, follow such recommendations.
If none are offered, locate the control at the top of the boiler near an outlet pipe or in the outlet pipe.
To remove the well from the control, loosen the set screw in the large nut, then slide the well off which exposes the bulb. Screw the well into the proper tapping. Slide the bulb
HEX NUT
MOUNTING STEM
CAPILLARY
BULB
Convertible Control converted to Vertical Model.
KNOCKOUT PLUG
KNOCKOUT PLATE
With the capillary fully extended, the bulb should slide all the way to the end of the well.
back into the well, making sure that the bulb enters the well as far as it will go and tighten the set screw.
CAUTION
Do not dent or bend the bulb as this will prevent it from fitting into the well properly.
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
If the boiler manufacturer recommends a wiring diagram, then follow such recommendations. If none is offered, these diagrams show suggested circuits.
LINE VOLTAGE
THEMOSTAT
HOT LINE
N
TYPE
11B05
FAN
MOTOR
Used as Hot Water Control to prevent unit heater fan from
HOT LINE
N
Used as Hot Water Control to start and stop the circulator.
TYPE
11B05
CIRCULATOR
MOTOR
operating until coils are warm.
SETTING THE CONTROL
CONTROLS WITH ADJUSTABLE DIFFERENTIAL
The movable indicator points to the temperature at which the contacts close. The fixed indicator points to the temperature at which the contacts open. The difference between these two indicators is the differential. To set the control:
1. Use a screwdriver in the adjusting slot (A) on the front of the control to turn the dial so that the fixed indicator (B) points to the temperature at which the contacts will open.
2. Turn the differential adjusting screw (C) until the movable indicator (D) points to the temperature at which the contacts will close.
“B” Fixed indicator
(cut-out point)
“C” Differential
adjusting screw “D” Movable indicator
(cut-in point)
“A” Adjusting
slot
2